You are on page 1of 10

Technical information

Commissioning instructions

TopTronic® E GLT module

TopTronic® E GLT

TopTronic® E control module

Hoval products may only be installed and com-


missioned by appropriately qualified experts.
These instructions are intended exclusively for the
specialist. Electrical installations may only be carried
out by a qualified electrician.

Subject to modifications | 4 212 585 / 00 - 08/15 EN


TABLE OF CONTENTS

1. Important notes........................................................................................................................................ 3

2. Addressing............................................................................................................................................... 4

3. 0-10V temperature request...................................................................................................................... 5


3.1 0-10V temperature heating...................................................................................................................................................5
3.2 0-10V hot water temperature................................................................................................................................................6

4. 0-10V output requirement........................................................................................................................ 7


4.1 0-10V output requirement heating.......................................................................................................................................7
4.2 0-10V output requirement domestic hot water....................................................................................................................8

5. Information............................................................................................................................................... 9

2 4 212 585 / 00
IMPORTANT NOTES

1. Important notes
All basic information about commissioning the base and
controller modules can be found in the commissioning
instructions for the base module heat exchanger. These
can be downloaded from the Hoval intranet/IDA if re-
quired (if you have questions, please contact Hoval cus-
tomer service).

These commissioning instructions contain further infor-


mation specifically for the GLT module 0-10V.

4 212 585 / 00 3
ADDRESSING

2. Addressing
All GLT modules 0-10V are delivered with
address 12!

DIP switch

Fig. 01

Addressing table for controller modules:

DIP switch Addr. Factory setting DIP switch Addr. Factory setting
4 3 2 1 4 3 2 1
Off 1 TTE-WEZ / TTE-FW Off 9 TTE-HK/WW
On (TTE-WEZ No. 1) On

4 3 2 1 4 3 2 1
Off 2 TTE-WEZ Off 10
On (TTE-WEZ No. 2) On

4 3 2 1 4 3 2 1
Off 3 TTE-WEZ Off 11
On (TTE-WEZ No. 3) On

4 3 2 1 4 3 2 1
Off 4 TTE-WEZ Off 12 TTE-GLT (0-10V)
On (TTE-WEZ No. 4) On

4 3 2 1 4 3 2 1
Off 5 TTE-WEZ Off 13 TTE-MWA (M-Bus)
On (TTE-WEZ No. 5) On

4 3 2 1 4 3 2 1
Off 6 TTE-WEZ Off 14
On (TTE-WEZ No. 6) On

4 3 2 1 4 3 2 1
Off 7 TTE-WEZ Off 15 TTE-PS
On (TTE-WEZ No. 7) On

4 3 2 1 4 3 2 1
Off 8 TTE-WEZ Off 16 TTE-SOL
On (TTE-WEZ No. 8) On

If there are several controller modules of the same type


in the bus system, the modules must have different ad-
dresses set for them. Use the available vacant addresses
for this.
Setting the addresses of the control modules is only pos-
sible after switching on and it determines the allocation
to the heat generators, heating and DHW circuits, etc. in
the system.

4 4 212 585 / 00
TEMPERATURE REQUEST

3. 0-10V temperature request


3.1 0-10V temperature heating

1. Select “Service” in the main menu 7. Set the parameter for “0-10V Temp.HZ”

1.

Fig. 05
Fig. 02
The following parameters can be set for the temperature
2. Select “TTE-GLT” request “0-10V Temp.HZ”:
3. Select “General” function group Example:
TTE-GLT (12)
General
0-10V temp. HT
07-002 28 °C Min. request heating
3. 07-008 95 °C Max. request heating
07-035 1=Heat generator Heating request type
30-063 4 Alloc. heating request input
06-113 0.5 V Characteristic curve X1
heating
06-111 5 °C Characteristic curve Y1
heating
2. 06-114 10 V Characteristic curve X2
heating
06-112 100 °C Characteristic curve Y2
Fig. 03
heating
4. Under “General”, select “General” again
5. Select “0-10V Temp.HZ”
Example temperature request heating from 28°C to
6. Select a parameter (e.g. Min. request heating)
max. 95°C:
°C

6. 100
2
(X2,Y2)
Max.

50

Fig. 04
Min.

1 (X1, Y1)
0 V
0 5 10

Fig. 06

4 212 585 / 00 5
TEMPERATURE REQUEST

Temperatur / temperature oder/or


Leistung / power 3.2 0-10V hot water temperature
TTE-GLT
(0-10V)
8. Perform 1.-4. from chapter 3.1
9. Select “0-10V Temp.WW”
10. Select a parameter (e.g. Min. request hot water)

TTE-
WEZ
Dies ist ein
unerlaubter Weg!
Gehen Sie einen
Schritt zurück oder
löschen Sie dieses
Shape!
Sie ...
haben
Möglichkeit
die
ein
neues Shape zu
nehmen!!!
hovhovalh
hovalhova
alhovalho
Fig. 08
11. Set the parameter for “0-10V Temp.WW”

Fig. 07

Notes:
Maximum temperatures can be limited by the H-Gen or
the automatic function.

The following statuses apply to control via 0-10V:


• at 0 - 0.5V = H-Gen OFF
• at 0.5 - 10V = control 5°C - 100°C (adjustable limits)

Fig. 09

The following parameters can be set for the temperature


request “0-10V Temp.WW”:
Example:
TTE-GLT (12)
General
0-10V temp. DHW.
36-004 5 °C Min. request hot water
05-057 100 °C Max. request hot water
05-087 1=Heat generator Hot water request type
30-065 0=OFF Alloc. hot water req. input
36-002 0.5 V Characteristic curve X1
hot water
36-000 5 °C Characteristic curve Y1
hot water
36-001 10 V Characteristic curve X2
hot water
36-003 100 °C Characteristic curve Y2
hot water

Each temperature request requires a sepa-


rated VE 10V input. If there is more than one
temperature request, a module expansion
must be used!

6 4 212 585 / 00
OUTPUT REQUIREMENT

4. 0-10V output requirement 7. Select “Parameters”

Before the output requirement heating or hot


water can be set, the “H-GEN target address”
parameter of the Cascade manager must be
deactivated.

1. Select “Service” in the main menu

7.

Fig. 13

8. Set “H-Gen target address” to 0 = deactivated

1.

Fig. 10

2. Select “TTE-WEZ”
3. Select “General” function group
8.

Fig. 14
3.
2.
4.1 0-10V output requirement heating

1. Select “Service” in the main menu

Fig. 11

4. Under “General”, select “General” again


5. Select “Cascade m.”
6. Select “Cascade m. 1”

1.

Fig. 15

Fig. 12

4 212 585 / 00 7
OUTPUT REQUIREMENT

2. Select “TTE-GLT” 4.2 0-10V output requirement domestic hot


3. Select “General” function group water

1. Perform 1.-4. from chapter 4.1


2. Select “0-10V Outp.WW”
3. Select a parameter (e.g. Allocation heat generator hot
3. water)

3.
2.

Fig. 16

4. Under “General”, select “General” again


5. Select “0-10V Outp.HZ” 2.
6. Select a parameter (e.g. Alloc. heat generator heat-
ing)
Fig. 18
4. Set the parameter for “0-10V Outp.WW”

The following parameters can be set for the output re-


quirement “0-10V Outp.WW”:
5. Example:
TTE-GLT (12)
General
0-10V outp. WW
20-018 0 Alloc. heat generator hot water
30-069 4 Alloc. outp. ref. value hot water
4. inp.

Fig. 17 Each output requirement requires a separat-


ed VE 10V input. If there is more than one
7. Set the parameter for “0-10V Outp.HZ” output requirement, a module expansion
must be used!
The following parameters can be set for the output re-
quirement “0-10V Outp.HZ”:
Example:
Example output requirement 0-100%:
TTE-GLT (12)
General
0-10V outp. Hz.
20-016 1 Alloc. heat generator heating
30-067 4 Alloc. outp. ref. value heating inp.
(4=VE10V)

Fig. 19

8 4 212 585 / 00
INFORMATION
Temperatur / temperature oder/or
Leistung / power
TTE-GLT 5. Information
(0-10V)
The info screen (1, Fig. 21) is used for a quick overview
of the plant.

TTE-
WEZ
Dies ist ein
unerlaubter Weg!
Gehen Sie einen
Schritt zurück oder
löschen Sie dieses
Shape!
Sie ...
haben
Möglichkeit
die
ein
neues Shape zu
nehmen!!!
hovhovalh
hovalhova
alhovalho
Fig. 21

A different number of information values are displayed


here depending on the user level. Statuses are displayed
in most of the functions.

Fig. 20

Notes:
Cascade manager must be deactivated with output
control.

The following statuses apply to control via 0-10V:


• at 0-1V heat generator off
• at 1-10V heat generator on, voltage produces refer-
ence output.

Fig. 22

4 212 585 / 00 9