Enquiry Number :
Date : March 14, 2024
Customer :
Project :
Page 1 of 2 The document becomes contractual only after HBL acceptance and acknowledgement of a purchase order
Version : Beta 3.0
Uncorrected Size (US) (8) 30.89 Ah x Design Margin (9) 1.00 x Aging Factor (10) 1.25 x Temperature factor (11) 1 x Spare
capacity factor (12) 1 / State of Charge Factor 1.00 = (13) 38.61 Ah
When the cell size (13) is greater than a standard cell size, the next larger cell is required.
Required cell size (14) 38.61 Ampere Hours. Therefore, cell (15) OPTI 42 is required