You are on page 1of 1

Version : Beta 3.

0 March 18, 2024

Datasheet of VRLA Battery


Enquiry Number : Project Ref. :
Customer Name : Revision : 0

S.No Parameters 110V - 200AH Battery Details

1 Battery Type Maintenance Free Valve Regulated Lead Acid Battery


2 Model Offered T-200 HP (Single cell)
3 Battery Rating 110V - 200Ah
4 No. of Cells 55 Cells of 200 Ah in 2V
5 Recommended max. Period of storage 6 months at 25°C
6 Capacity rated at 8 hour rate to 1.75 ECV at 25°C
7 Ah Efficiency Min 95%
8 Wh Efficiency Min 85%
9 Recommended charging for Float application Constant potential with minimum current 0.2 C8 Amps
Float charging: 2.23 ± 0.005V/Cell at 25°C
Boost charging: 2.32 ± 0.005V/Cell at 25°C
Recommended charging for Cyclic application Constant potential with current limited to 0.2 C8 Amps (Max.)
Float charging: 2.27 ± 0.005V/Cell at 25°C
Boost charging: 2.35 ± 0.005V/Cell at 25°C
10 Grid Alloy High corrosion resistant alloy
11 Plate type Flat pasted
12 Separator AGM (Absorbent Glass Mat)
13 Electrolyte Sulfuric acid, immobilized in Absorbent type Glass Mat
14 Container & Lid Material Polypropylene
15 Container to lid sealing method Heat Sealing Method
16 Safety vent Self resealing, Pressure Regulating Valve with Flame arrestor
17 Cell enclosure or Housing Steel enclosures with Powder Coated
18 Nuts, Bolts and Washers for Inter cell connectors Acid Resistant Stainless Steel
19 Termination Bolted type
20 Operating temperature range -20°C to 55°C
21 Self discharge < 2% per month at 25°C
22 Design float life 20 years at 25°C on float under recommended charging
23 Ventilation Natural ventilation is sufficient
24 Battery shipment condition Filled and charged. Ready to use
25 Applicable standards IEC 60896 – 21 & 22-2004