COMPARATIVE STATEMENT OF OFFERS FOR 110V SMF VRLA BATTERY AGAINST SPEC

NO.1223/RMLC/LRF-3/SMS-1/ELE-004
TECHNICAL AMARA RAJA POWER SYSTEMS CHLORIDE POWER SYSTEMS
LIVE LINE
PARAMETERS LIMITED AND SOLUTIONS LIMITED

Maintenance Free Valve Regulated Lead acid 110 Volts 100 AH battery type
1 Type VRLA
Acid (MF-VRLA) UPST VRLA

2 No of Cell 55 55 55

Cell dimensions
3 (198.4 x 321 x 46.1) mm Approx. Not Furnished Not Furnished
(LxDxH)
110V/25A FLOAT CUM
BOOST CHARGER
4 Battery Rating 110 V - 100 AH to 1.75 ECV @ C10 at 27°C 110 Volts 100AH VRLA battery
SUITABLE FOR 100AH VRLA
BATTERY

(i) IS15549:2005
Applicable (ii) IEEE1188 & 1189
5 Not Furnished Not Furnished
Standard (iii) BS-6290, PART-IV.
(iV) IEC 60896-21&22:2004, PART-II.
AH efficiency-Above 95%
6 Efficiency Not Furnished Not Furnished
WH efficiency-Above 85%
Battery bank
7 432 Kg. Approx Not Furnished Not Furnished
weight
Auto : 123.75 V (2.25V per
Float Charging Cell)
8 2.23-2.25Volts per cell @ 27 °C Not Furnished
Voltge Manual: 0 to 123.75 V (2.25V
per Cell)
Boost Charging
9 2.30-2.32 Volts per cell @ 27 °C Not Furnished 126.5V (2.3V per Cell)
Voltage
15A maximum including
10 Current Limit 10Amp minimum to 20Amp maximum Not Furnished
trickle charging current.

Not exceeding 3% rms at


Allowable voltage
11 <2% of the RMS. Value Not Furnished rated output
ripple voltage and current.

12 Type of connectors Lead coated heavy duty copper strips Not Furnished Not Furnished

4000 cycles at 20% Depth of


Cycle Life of Discharge(DOD) (or) 2000 cycles at 50%
13 Not Furnished Not Furnished
battery at 27°C DOD (or)
1200 cycles at 80% DOD
14 Cooling Natural Air Cooling Not Furnished Natural Cooling
Degree of
15 IP-42 Not Furnished IP-42
Protection
1.6mm for Non-load bearing sections and
16 Panel Thickness Not Furnished 1.6mm.
2.0mm for Load bearing sections.

17 DCDB Not furnished Not Furnished Not Furnished

Freestanding Cabinet; Floor Mounting Type, Free Standing Steel Cabinet,


Sheet Steel Construction; Easy for Easy for Accessing,
Installation and Maintenance; Components Installation and
18 Cabinet Features Not Furnished
are accessible from Front Commissioning and Cable
& Rear; Cable entry at Front Bottom of the Entry at
Cabinet bottom.

19 Mode of Operation Automatic & Manual Not Furnished Automatic / Manual

Input AC Power 415V AC ±10% (Three Phase, Three/Four 415V ±10% 3 Ф 4 Wires,
20 Not Furnished
Supply Wire) 50Hz ± 5% 50Hz ±5%
21 Output Current 20A DC Not Furnished 25A (max)

Load variation : 10-100% Not exceeding +/-1% for +/-


22 Output Regulation Line variation : ± 10% Not Furnished 10% supply fluctuation and
Frequency Variations : ± 5% 10 to 100% load variation
The following protections will be provided:
a. AC Input MCB
a) AC Input Circuit Breaker
b. DC Output MCB
b) Fast acting Semiconductor Fuses for SCR
c. Battery Input Fuses
Bridge
d. Fast acting Semiconductor
c) DC Over Voltage Cutback / Shut Down
Fuses for the Rectifier
23 PROTECTIONS d) DC Overload Not Furnished
Bridge
e) DC Output Circuit Breaker
e. Phase fail protection
f) Battery Input Fuses
f. Over Current Protection
g) Battery Current Limit
g. Charger Current Limit
h) Charger Current Limit
h. Blocking Diodes
i) Blocking Diode

a) Auto Phase Reversal Operation


b) Soft Start on DC side
c) Class-F Insulation with Class-F
Temperature Limits for all Magnetics
a. Soft start on DC side
d) Automatic Voltage Regulation using
b. Class-F insulation for all
Digital Control Logic
Magnetics
e) Filter Circuit to Limit Ripple
c. Automatic Voltage and
f) Charger Current Limiting
current Regulation
g) Battery Current Limiting
d. Filter Circuit to limit
h) Automatic Float to Boost changeover
Ripple
24 Special Features based on current drawn by Battery Not furnished
e. Charger Current Limiting
i) Automatic Boost to Float changeover
f. Automatic changeover from
based on Current or Voltage.
Float to Boost and vice
j) Anti-condensation Heater with
versa based on voltage /
Thermostat Control
current drawn by the
k) Blocking Diode Short Sensing
Battery.
l) RS-485, 4-Wire Communication with
MODBUS Protocol (communication cable
from Battery Charger System to user
equipment like SCADA is not in Amara Raja
scope)