Preliminary Thermal Analysis of


Typical Unitized Curtain Wall (Tinted Glass) for
BPO Tower

ONE AYALA AVENUE


Makati City

Document Reference No.


PTCC-1AYL-CS01-001NC
Revision 02

Prepared for:
Makati Development Corporation

Prepared by:
Professor Torsten Calvi Corporation
15 May 2017
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

Revision Status Summary


ONE AYALA AVENUE Thermal Performance Analysis
Makati City

Submittal Date Revision Notes Comments

15 May 2017 Revision 02 This thermal calculation set analyzed the thermal performance of grey-
Prepared by: tinted class with a single Low-E coating on the #2 surface for the BPO
tower.
JAJA
Checked by:
RLV/ADL

10 November 2016 Revision 01 This thermal calculation set analyzed the thermal performance of grey-
Prepared by: tinted glass with varying coatings on the #2 surface for the BPO tower.
JAJA
Checked by:
RLV/ADL

21 October 2016 Revision 00 This thermal calculation set analyzed three different candidate glass types
Prepared by: for the BPO tower.
JAJA
Checked by:
RLV/ADL
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

Table of Contents
Thermal Analysis for Typical Unitized Curtain Wall (Tinted Glass) System of
One Ayala Avenue, Makati City

Introduction / Executive Summary


Material Thermal Properties
Environmental Conditions (Solar Heat Gain Coefficient)
Environmental Conditions (U-Factor)
Glass Types and Properties

Area Elevation Drawing

CHAPTER 1: Thermal Performance Analysis (NFRC Summer Condition) Page I – 1


One Ayala Avenue, Makati City

Average Thermal Performance


Summary of Computations for Overall Solar Heat Gain Coefficient (SHGC) Page I – 2
for the Vision Panel of the Typical Unitized Curtain Wall System
Overall SHGC for Typical Fixed Curtain Wall System Page I – 3
Overall SHGC for Typical Operable Window System Page I – 5

1.1 Mullion at Vision Plan Thermal Performance


1.1.1 Isotherms for Mullion at Vision Plan Page I – 7
1.1.2 Colored Infrared for Mullion at Vision Plan Page I – 8
1.1.3 U-factor for Mullion at Vision Plan Page I – 9
1.1.4 Colored Heat Flux Diagram for Mullion at Vision Plan Page I – 9

1.2 Stack Joint at Vision-Spandrel Thermal Performance


1.2.1 Isotherms for Stack Joint at Vision-Spandrel Page I – 10
1.2.2 Colored Infrared for Stack Joint at Vision-Spandrel Page I – 11
1.2.3 U-factor for Stack Joint at Vision-Spandrel Page I – 12
1.2.4 Colored Heat Flux Diagram for Stack Joint at Vision-Spandrel Page I – 12

1.3 Intermediate Transom at Vision-Spandrel Thermal Performance


1.3.1 Isotherms for Intermediate Transom at Vision-Spandrel Page I – 13
1.3.2 Colored Infrared for Intermediate Transom at Vision-Spandrel Page I – 14
1.3.3 U-factor for Intermediate Transom at Vision-Spandrel Page I – 15
1.3.4 Colored Heat Flux Diagram for Intermediate Transom at Vision-Spandrel Page I – 15

1.4 Intermediate Operable Transom at Vision-Spandrel Thermal Performance


1.4.1 Isotherms for Intermediate OperableTransom at Vision-Spandrel Page I – 16
1.4.2 Colored Infrared for Intermediate Operable Transom at Vision-Spandrel Page I – 17
1.4.3 U-factor for Intermediate Operable Transom at Vision-Spandrel Page I – 18
1.4.4 Colored Heat Flux Diagram for Intermediate Operable Transom at Vision-Spandrel Page I – 18

1.5 Operable Stack Joint at Vision-Spandrel Thermal Performance


1.5.1 Isotherms for Operable Stack Joint at Vision-Spandrel Page I – 19
1.5.2 Colored Infrared for Operable Stack Joint at Vision-Spandrel Page I – 20
1.5.3 U-factor for Operable Stack Joint at Vision-Spandrel Page I – 21
1.5.4 Colored Heat Flux Diagram for Operable Stack Joint at Vision-Spandrel Page I – 21
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

CHAPTER 2: Thermal Performance Analysis (NFRC Winter Condition) Page II – 1


One Ayala Avenue, Makati City

Average Thermal Performance


Summary of Computations for U-Factor Page II – 2
U-Factor for the Typical Fixed Curtain Wall System Page II – 5
U-Factor for the Typical Operable Curtain Wall System Page II – 5
U-Factor for the Typical Spandrel Curtain Wall System Page II – 6
Overall U-Factor for the Low Zone Facade Module Page II – 6
Overall U-Factor for the Mid Zone Facade Module Page II – 6
Overall U-Factor for the High Zone Facade Module Page II – 6

2.1 Mullion at Spandrel Plan Thermal Performance


2.1.1 Isotherms for Mullion at Spandrel Plan Page II – 7
2.1.2 Colored Infrared for Mullion at Spandrel Plan Page II – 8
2.1.3 U-factor for Mullion at Spandrel Plan Page II – 9
2.1.4 Colored Heat Flux Diagram for Mullion at Spandrel Plan Page II – 9

2.2 Mullion at Vision Plan Thermal Performance


2.2.1 Isotherms for Mullion at Vision Plan Page II – 10
2.2.2 Colored Infrared for Mullion at Vision Plan Page II – 11
2.2.3 U-factor for Mullion at Vision Plan Page II – 12
2.2.4 Colored Heat Flux Diagram for Mullion at Vision Plan Page II – 12

2.3 Stack Joint at Vision-Spandrel Thermal Performance


2.3.1 Isotherms for Stack Joint at Vision-Spandrel Page II – 13
2.3.2 Colored Infrared for Stack Joint at Vision-Spandrel Page II – 14
2.3.3 U-factor for Stack Joint at Vision-Spandrel Page II – 15
2.3.4 Colored Heat Flux Diagram for Stack Joint at Vision-Spandrel Page II – 15

2.4 Intermediate Transom at Vision-Spandrel Thermal Performance


2.4.1 Isotherms for Intermediate Transom at Vision-Spandrel Page II – 16
2.4.2 Colored Infrared for Intermediate Transom at Vision-Spandrel Page II – 17
2.4.3 U-factor for Intermediate Transom at Vision-Spandrel Page II – 18
2.4.4 Colored Heat Flux Diagram for Intermediate Transom at Vision-Spandrel Page II – 18

2.5 Intermediate Operable Transom at Vision-Spandrel Thermal Performance


2.5.1 Isotherms for Intermediate OperableTransom at Vision-Spandrel Page II – 19
2.5.2 Colored Infrared for Intermediate Operable Transom at Vision-Spandrel Page II – 20
2.5.3 U-factor for Intermediate Operable Transom at Vision-Spandrel Page II – 21
2.5.4 Colored Heat Flux Diagram for Intermediate Operable Transom at Vision-Spandrel Page II – 21

2.6 Intermediate Transom at Spandrel-Spandrel Thermal Performance


2.6.1 Isotherms for Intermediate Transom at Spandrel-Spandrel Page II – 22
2.6.2 Colored Infrared for Intermediate Transom at Spandrel-Spandrel Page II – 23
2.6.3 U-factor for Intermediate Transom at Spandrel-Spandrel Page II – 24
2.6.4 Colored Heat Flux Diagram for Intermediate Transom at Spandrel-Spandrel Page II – 24

2.7 Operable Stack Joint at Vision-Spandrel Thermal Performance


2.7.1 Isotherms for Operable Stack Joint at Vision-Spandrel Page II – 25
2.7.2 Colored Infrared for Operable Stack Joint at Vision-Spandrel Page II – 26
2.7.3 U-factor for Operable Stack Joint at Vision-Spandrel Page II – 27
2.7.4 Colored Heat Flux Diagram for Operable Stack Joint at Vision-Spandrel Page II – 27

2.8 Stack Joint Section at Spandrel-Spandrel Thermal Performance


2.8.1 Isotherms for Stack Joint Section at Spandrel-Spandrel Page II – 28
2.8.2 Colored Infrared for Stack Joint Section at Spandrel-Spandrel Page II – 29
2.8.3 U-factor for Stack Joint Section at Spandrel-Spandrel Page II – 30
2.8.4 Colored Heat Flux Diagram for Stack Joint Section at Spandrel-Spandrel Page II – 30
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

INTRODUCTION

Preliminary Thermal Analysis of Typical Unitized Curtain Wall (Tinted Glass) System for BPO Tower
ONE AYALA AVENUE
Makati City, Philippines

· General

Professor Torsten Calvi Corporation was engaged by Makati Development Corporation to make a preliminary study of the
thermal performance of the unitized curtain wall system for the tower exterior facade of the BPO tower at One Ayala
Avenue, Makati City, Philippines. The typical framing members and glass options were analyzed using a finite element
computer model (THERM 7.4 version, developed at Lawrence Berkeley National Laboratory, USA) in order to predict the
thermal conductivity of the curtain wall system. An area averaging calculation, in accordance with the procedures set out
by the National Fenestration and Ratings Council (NFRC100: Procedure for Determining Fenestration Product U-Factors
and NFRC 200: Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at
Normal Incidence) was used to determine the over-all thermal conductivity of the curtain wall.

For the vision and operable window panels, the glass type considered in the study are an 8mm+12AS+8mm thick
insulating glass unit (IGU) with tinted outer pane and a Low-E coating on the #2 surface, and clear inner pane, and a
10mm thick monolithic spandrel pane.

The U-factor and SHGC for the 1800mm spandrel and 2200mm vision facade layout were obtained in the analysis. The
quantity of the fixed, operable window, and spandrel panels was also considered to determine the total U-factor and
SHGC of the panels in the low, mid, and high zone areas.

Environmental conditions and design assumptions are in accordance with NFRC 100-2010. Analysis was conducted
under the following temperature conditions:

SHGC: 32 °C exterior temperature, 24 °C interior temperature, and outside air velocity of 5.5 m/s.
U-Factor: -18 °C exterior temperature, 21 °C interior temperature, and outside air velocity of 5.5 m/s.

Each curtain wall type was able to meet the following specifications: U-value of 2.8 W/m²K and SHGC of 0.25.

The computer model predicts that the total U-value and SHGC of the curtain wall system, including glazing with frame,
are as follows:

Overall Values
Location Number of Floors U-Factor SHGC
Low Zone (L7 to L19) 13 2.533 0.201
Mid Zone (L20 to L23) 4 2.562 0.201
High Zone (L24 to L26) 3 2.572 0.201
Area-Weighted
2.545 0.201
Average

The overall U-Factor and SHGC of the building are 2.545 W/m2-K and 0.201, respectively.
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

· Material Thermal Properties

Material Conductivity Emissivity


(W/m-K)
Aluminum Alloy (Painted) 160.00 0.9
Silicone 0.35 0.9
Silica Gel (Dessicant) – Loose Fill 0.03 0.9
Steel – Galvanized Sheet (0.14%C) 62.00 0.2
Ethylene Propylene Diene Monomer (EPDM) 0.25 0.9
Insulation Fiberboard 0.05 0.9
Gypsum Board (12mm) 0.1512 0.9
Keff 1 2.8395 0.9
Keff 2 10.2300 0.9

· Environmental Conditions
One Ayala Avenue, Makati (SHGC)

A. U-Factor Inside
Inside Air Temperature 24.0 °C
Convection Model ASHRAE / NFRC Inside
Radiation Model ASHRAE / NFRC
Effective Room Temperature 24.0 °C
Effective Room Emissivity 1.0

B. U-Factor Outside
Outside Temperature 32.0 °C
Direct Solar Radiation 0.0 W/m2
Convection Model ASHRAE / NFRC Outside
Convection Coefficient 15.0 W/m2-K
Outside Wind Speed 2.75 m/s
Wind Direction Windward
Radiation Model ASHRAE / NFRC
Effective Sky Temperature 32.0 °C
Effective Sky Emissivity 1.0

C. SHGC Inside
Inside Air Temperature 24.0 °C
Convection Model ASHRAE / NFRC Inside
Radiation Model ASHRAE / NFRC
Effective Room Temperature 24.0 °C
Effective Room Emissivity 1.0

D. SHGC Outside
Outside Temperature 32.0 °C
Direct Solar Radiation 783.0 W/m2
Convection Model ASHRAE / NFRC Outside
Convection Coefficient 15.0 W/m2-K
Outside Wind Speed 2.75 m/s
Wind Direction Windward
Radiation Model ASHRAE / NFRC
Effective Sky Temperature 32.0 °C
Effective Sky Emissivity 1.0

· Environmental Conditions
One Ayala Avenue, Makati (U-Factor)

A. U-Factor Inside
Inside Air Temperature 21.0 °C
Convection Model ASHRAE / NFRC Inside
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

Radiation Model ASHRAE / NFRC


Effective Room Temperature 21.0 °C
Effective Room Emissivity 1.0

B. U-Factor Outside
Outside Temperature -18.0 °C
Direct Solar Radiation 0.0 W/m2
Convection Model ASHRAE / NFRC Outside
Convection Coefficient 26.0 W/m2-K
Outside Wind Speed 5.5 m/s
Wind Direction Windward
Radiation Model ASHRAE / NFRC
Effective Sky Temperature -18.0 °C
Effective Sky Emissivity 1.0

C. SHGC Inside
Inside Air Temperature 21.0 °C
Convection Model ASHRAE / NFRC Inside
Radiation Model ASHRAE / NFRC
Effective Room Temperature 21.0 °C
Effective Room Emissivity 1.0

D. SHGC Outside
Outside Temperature -18.0 °C
Direct Solar Radiation 0.0 W/m2
Convection Model ASHRAE / NFRC Outside
Convection Coefficient 26.0 W/m2-K
Outside Wind Speed 5.5 m/s
Wind Direction Windward
Radiation Model ASHRAE / NFRC
Effective Sky Temperature -18.0 °C
Effective Sky Emissivity 1.0

· Glass Types and Properties


Typical Curtain Wall
U-Factor

Vision Glass:
Outer Pane Glass Code: VE192m-8mm-LoE.VIR
Outer Pane Thickness: 8.0 mm
Cavity: Air
Cavity Thickness: 12.0 mm
Inner Pane Glass Code: CLR_8.AFG
Inner Pane Thickness: 7.9 mm
Tilt: 90.0o
U Value: 1.638 W/m2-k
SHGCc: N/A
SCc: N/A
Vtc: 0.383
RHG: N/A

Spandrel Glass:
Glass Code: 01_Clear_10.syp
Thickness: 10.0 mm
Tilt: 90.0o
U Value: 5.674 W/m2-k
SHGCc: N/A
SCc: N/A
Vtc: 0.878
RHG: N/A
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

Typical Curtain Wall


SHGC

Vision Glass:
Outer Pane Glass Code: VE192m-8mm-LoE.VIR
Outer Pane Thickness: 8.0 mm
Cavity: Air
Cavity Thickness: 12.0 mm
Inner Pane Glass Code: CLR_8.AFG
Inner Pane Thickness: 7.9 mm
Tilt: 90.0o
U Value: 1.583 W/m2-k
SHGCc: 0.220
SCc: 0.253
Vtc: 0.383
RHG: 172 W/m2

Spandrel Glass:
Glass Code: 01_Clear_10.syp
Thickness: 10.0 mm
Tilt: 90.0o
U Value: 5.128 W/m2-k
SHGCc: 0.803
SCc: 0.922
Vtc: 0.878
RHG: 622 W/m2
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

ONE AYALA AVENUE


Typical Unitized Curtain Wall (Tinted Glass) System
Ayala Avenue, Makati City

AREA ELEVATION DRAWING

A – MULLION AT SPANDREL PLAN


B – MULLION AT VISION-OPERABLE WINDOW PLAN
C – STACKJOINT AT VISION-SPANDREL SECTION
D – STACKJOINT AT VISION-OPERABLE WINDOW SECTION
E – STACKJOINT AT SPANDREL-SPANDREL SECTION
F – INTERMEDIATE TRANSOM AT SPANDREL-VISION SECTION
F – INTERMEDIATE TRANSOM AT SPANDREL-OPERABLE WINDOW SECTION
G – INTERMEDIATE TRANSOM AT SPANDREL-SPANDREL SECTION
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

CHAPTER 1

Thermal Performance Analysis for


ONE AYALA AVENUE
Ayala Avenue, Makati City
NFRC Summer Condition
(Exterior Temperature = -18 oC,
Interior Temperature = 21 oC)

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 1
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

Average Thermal Performance


ONE AYALA AVENUE, Ayala Avenue, Makati City, Typical Unitized Curtain Wall System
(NFRC Summer Condition: -18 oC exterior and 21 oC interior temperatures)

Summary of Computations for Overall Solar Heat Gain Coefficient (SHGC)


for the Vision Panel of the Typical Unitized Curtain Wall System

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 2
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

Frame Solar Heat Gain Coefficient

SHGC f = α x Uf x Af
Asurf x hout

where: α = Frame/divider absorptance (0.5 if glazed or sloped system, 0.3


otherwise)
Uf = Average winter night-time U-factor of opaque areas
Af = Sum of opaque areas
Asurf = Sum of opaque wetted areas
hout = Exterior Air Film Coefficient = 30 W/m2-K

SHGC of Product with Center-Of-Glazing SHGC = 0

SHGC 0 = (SHGC xAx) + (SHGC dAd) + (SHGC eAe) + (SHGC deAe) + (SHGC leAe) + (SHGC cAc)
Apf
SHGC of Product with Center-Of-Glazing SHGC = 1

SHGC 1 = (SHGC xAx) + (SHGC dAd) + (SHGC eAe) + (SHGC deAe) + (SHGC leAe) + (SHGC cAc)
Apf

where: SHGC x = Frame SHGC as determined by SHGC f


Ax = Sum of frame areas
SHGC d = Divider SHGC as determined by SHGC f
Ad = Sum of divider areas
SHGC e = Edge-of-glazing SHGC set to zero for SHGC 0 and one for SHGC 1
Ae = Sum of edge-of-glazing areas
SHGC de = Edge-of-divider SHGC set to zero for SHGC 0 and one for SHGC 1
Ade = Sum of edge-of-divider areas
SHGC le = Door-lite edge SHGC set to zero for SHGC 0 and one for SHGC 1
Ale = Sum of door-lite edge areas
SHGC c = Center of glazing SHGC set to zero for SHGC 0 and one for SHGC 1
Ac = Center of glazing area
Apf = Projected fenestration area

Overall Fenestration Solar Heat Gain Coefficient

SHGC = SHGC 0 + SHGC cc(SHGC 1 – SHGC 0)

where SHGC 0 = SHGC of Product with Center-Of-Glazing SHGC = 0


SHGC 1 = SHGC of Product with Center-Of-Glazing SHGC = 1
SHGC cc = Actual center-of-glazing SHGC

Overall SHGC for Typical Fixed Curtain Wall System


Environmental Condition: Summer Condition
Tilt: 90o
Width: 1500 mm
Height: 2200 mm
Area: 3.3 m2
U-FACTOR HEIGHT WIDTH U-VALUExWIDTHxHEIGHT
ELEMENT ELEMENT DESCRIPTION
(W/m2-K) (mm) (mm) (W/K)
5 Mullion F rame 15.4182 2200.00 46.50 1.58
6 Mullion F rame 15.4182 2200.00 46.50 1.58
8 Intermediate Transom 13.0929 47.50 1407.00 0.88
9 Stack Sill 9.5612 99.50 1407.00 1.34
Sum 5.37

Overall U-Factor (W/m2-K) 13.0475

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 3
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

Average winter night-time U-factor of opaque areas, Uf = 13.0475 W/m2-K


Actual SHGC of center-of-glazing, SHGC cc = 0.22
Frame/divider absorptance, α = 0.5
Sum of opaque areas, Af = 0.41 m2
Sum of opaque wetted areas, Asurf = 1.34 m2
Exterior Air Film Coefficient, hout = 30 W/m2-K

SHGC f = α Uf Af = 0.5 * 13.0475 * 0.41


Asurf hout 1.34 * 30

SHGC f = 0.067

HEIGHT WIDTH WETTED LENGTH WETTED AREA


ELEMENT ELEMENT DESCRIPTION AREA (m²)
(mm) (mm) (mm) (m²)
1 Center of vision glass 1926 1280 2.47 - -
Center of Glass Area (m²) = 2.47
2 Mullion Frame 2200.00 46.50 0.1 56.479 0.1243
3 Mullion Frame 2200.00 46.50 0.1 56.479 0.1243
4 Intermediate Transom Frame 47.50 1407.00 0.07 712.055 1.0019
5 Stack Joint Frame 99.50 1407.00 0.14 64.789 0.0912
Total Frame Area (m²) = 0.41 Wetted Area (m²) = 1.34
6 Edge of glass 2053.00 63.50 0.13 - -
7 Edge of glass 2053.00 63.50 0.13 - -
8 Edge of glass 63.50 1280.00 0.08 - -
9 Edge of glass 63.50 1280.00 0.08 - -
Total Edge of Glass Area (m²) = 0.42
Total Area (m²) = 3.3

Sum of frame areas, Ax = 0.41 m²


Sum of divider areas, Ad = 0
Sum of edge-of-glazing areas, Ae = 0.42 m²
Sum of edge-of-divider areas, Ade = 0
Sum of door-lite edge areas, Ale = 0
Center of glazing area, Ac = 2.47 m²
Projected fenestration area, Apf = 3.3 m²

SHGC 0 = (SHGC xAx) + (SHGCdAd) + (SHGC eAe) + (SHGC deAe) + (SHGC leAe) + (SHGC cAc)
Apf
= (0.067)(0.41) + (0)(0) + (0)(0.42) + (0)(0) + (0)(0) + (0)(2.47)
3.3
SHGC 0 = 0.008

SHGC 1 = (SHGC xAx) + (SHGCdAd) + (SHGC eAe) + (SHGC deAe) + (SHGC leAe) + (SHGC cAc)
Apf
= (0.067)(0.41) + (1)(0) + (1)(0.42) + (1)(0) + (1)(0) + (1)(2.47)
3.3
SHGC 1 = 0.884

Overall Fenestration Solar Heat Gain Coefficient


ONE AYALA AVENUE, Makati City (Summer Condition)

SHGC = SHGC 0 + SHGC cc(SHGC 1 – SHGC 0)

= 0.008 + 0.22 (0.884 – 0.008)

SHGC = 0.201

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 4
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

Overall SHGC for Typical Operable Curtain Wall System


Environmental Condition: Summer Condition
Tilt: 90o
Width: 1500 mm
Height: 2200 mm
Area: 3.3 m2

U-FACTOR HEIGHT WIDTH U-VALUExWIDTHxHEIGHT


ELEMENT ELEMENT DESCRIPTION
(W/m2-K) (mm) (mm) (W/K)
5 Mullion F rame 15.4182 2200.00 46.50 1.58
6 Mullion F rame 15.4182 2200.00 46.50 1.58
8 Intermediate Transom 14.7083 47.50 1407.00 0.98
9 Stack Sill 9.2712 99.50 1407.00 1.30
Sum 5.44

Overall U-Factor (W/m2-K) 13.2113

Average winter night-time U-factor of opaque areas, Uf =13.2113 W/m2-K


Actual SHGC of center-of-glazing, SHGC cc = 0.22
Frame/divider absorptance, α = 0.5
Sum of opaque areas, Af = 0.41 m2
Sum of opaque wetted areas, Asurf = 1.34 m2
Exterior Air Film Coefficient, hout = 30 W/m2-K

SHGC f = α Uf Af = 0.5 * 13.2113 * 0.41


Asurf hout 1.34 * 30

SHGC f = 0.067

HEIGHT WIDTH WETTED LENGTH WETTED AREA


ELEMENT ELEMENT DESCRIPTION AREA (m²)
(mm) (mm) (mm) (m²)
1 Center of vision glass 1926 1280 2.47 - -
Center of Glass Area (m²) = 2.47
2 Mullion Frame 2200.00 46.50 0.1 56.479 0.1243
3 Mullion Frame 2200.00 46.50 0.1 56.479 0.1243
4 Intermediate TransomFrame 47.50 1407.00 0.07 712.255 1.0021
5 Stack Joint Frame 99.50 1407.00 0.14 64.889 0.0913
Total Frame Area (m²) = 0.41 Wetted Area (m²) = 1.34
6 Edge of glass 2053.00 63.50 0.13 - -
7 Edge of glass 2053.00 63.50 0.13 - -
8 Edge of glass 63.50 1280.00 0.08 - -
9 Edge of glass 63.50 1280.00 0.08 - -
Total Edge of Glass Area (m²) = 0.42
Total Area (m²) = 3.3

Sum of frame areas, Ax = 0.41 m²


Sum of divider areas, Ad = 0
Sum of edge-of-glazing areas, Ae = 0.42 m²
Sum of edge-of-divider areas, Ade = 0
Sum of door-lite edge areas, Ale = 0
Center of glazing area, Ac = 2.47 m²
Projected fenestration area, Apf = 3.3 m²

SHGC 0 = (SHGC xAx) + (SHGCdAd) + (SHGC eAe) + (SHGC deAe) + (SHGC leAe) + (SHGC cAc)
Apf
= (0.067)(0.41) + (0)(0) + (0)(0.42) + (0)(0) + (0)(0) + (0)(2.47)
3.3
SHGC 0 = 0.008

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 5
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

SHGC 1 = (SHGC xAx) + (SHGCdAd) + (SHGC eAe) + (SHGC deAe) + (SHGC leAe) + (SHGC cAc)
Apf
= (0.067)(0.41) + (1)(0) + (1)(0.42) + (1)(0) + (1)(0) + (1)(2.47)
3.3
SHGC 1 = 0.884

Overall Fenestration Solar Heat Gain Coefficient


ONE AYALA AVENUE, Makati City (Summer Condition)

SHGC = SHGC 0 + SHGC cc(SHGC 1 – SHGC 0)

= 0.008 + 0.22 (0.884 – 0.008)

SHGC = 0.201

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 6
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

1.1 MULLION AT VISION PLAN THERMAL PERFORMANCE

(1.1.1) Isotherms for Mullion at Vision Plan

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 7
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(1.1.2) Colored Infrared for Mullion at Vision Plan

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 8
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(1.1.3) U Factors for Mullion at Vision Plan

(1.1.4) Colored Heat Flux Diagram for Mullion at Vision Plan

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 9
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

1.2. STACKJOINT SECTION AT VISION-SPANDREL THERMAL PERFORMANCE

(1.2.1) Isotherms for Stackjoint Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 10
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(1.2.2) Colored Infrared for Stackjoint Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 11
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(1.2.3) U Factors for Stackjoint Section at Vision-Spandrel

(1.2.4) Colored Heat Flux Diagram for Stackjoint Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 12
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

1.3 INTERMEDIATE TRANSOM SECTION AT VISION-SPANDREL THERMAL PERFORMANCE

(1.3.1) Isotherms for Intermediate Transom Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 13
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(1.3.2) Colored Infrared for Intermediate Transom Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 14
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(1.3.3) U Factors for Intermediate Transom Section at Vision-Spandrel

(1.3.4) Colored Heat Flux Diagram for Intermediate Transom Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 15
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

1.4 INTERMEDIATE OPERABLE TRANSOM SECTION AT VISION-SPANDREL THERMAL


PERFORMANCE

(1.4.1) Isotherms for Intermediate Operable Transom Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 16
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(1.4.2) Colored Infrared for Intermediate Operable Transom Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 17
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(1.4.3) U Factors for Intermediate Operable Transom Section at Vision-Spandrel

(1.4.4) Colored Heat Flux Diagram for Intermediate Operable Transom Section at Vision-
Spandrel

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 18
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

1.5. OPERABLE STACKJOINT SECTION AT VISION-SPANDREL THERMAL PERFORMANCE

(1.5.1) Isotherms for Operable Stackjoint Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 19
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(1.5.2) Colored Infrared for Operable Stackjoint Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 20
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(1.5.3) U Factors for Operable Stackjoint Section at Vision-Spandrel

(1.5.4) Colored Heat Flux Diagram for Operable Stackjoint Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Summer Condition)


Page I - 21
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

CHAPTER 2

Thermal Performance Analysis for


ONE AYALA AVENUE
Ayala Avenue, Makati City
NFRC Winter Condition
(Exterior Temperature = -18 oC,
Interior Temperature = 21 oC)

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 1
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

Average Thermal Performance


ONE AYALA AVENUE, Ayala Avenue, Makati City
(NFRC Winter Condition: -18oC exterior and 21oC interior temperatures)

Summary of Computations for U-Factor

Overall U-Factor = S(AreaixUi)


Areatotal

where: Areai = Area of the Element (ft2)


Ui = U-Factor Corresponding to the Element (Btu/h-ft²-F)
Areatotal = Total Study Area

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 2
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 3
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 4
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

U-Factor for the Typical Fixed Curtain Wall System


Environmental Condition: U-Factor Condition
Tilt: 90o
Width: 1500 mm
Height: 4000 mm [1800mm+2200mm]
Area: 6.0 m2
U-FACTOR HEIGHT WIDTH U-FACTORxWIDTHxHEIGHT
ELEMENT ELEMENT DESCRIPTION
(W/m2 -K) (mm) (mm) (W/K)
1 Center of Spandrel Glass 0.821 1564 1280 1.64
2 Center of Vision Glass 1.638 1926 1280 4.04
3 Mullion at Spandrel 11.955 1800 46.5 1.00
4 Mullion at Spandrel 11.955 1800 46.5 1.00
5 Mullion at Vision 15.418 2200 46.5 1.58
6 Mullion at Vision 15.418 2200 46.5 1.58
7 Stack Head 9.579 61.5 1407 0.83
8 Intermediate Transom 13.093 95 1407 1.75
9 Stack Sill 9.579 99.5 1407 1.34
10 Edge of Spandrel 1.110 1691 63.5 0.12
11 Edge of Spandrel 1.110 1691 63.5 0.12
12 Edge of Vision 1.986 2053 63.5 0.26
13 Edge of Vision 1.986 2053 63.5 0.26
14 Edge of Spandrel 0.860 63.5 1280 0.07
15 Edge of Spandrel 0.683 63.5 1280 0.06
16 Edge of Vision 2.130 63.5 1280 0.17
17 Edge of Vision 1.861 63.5 1280 0.15
Sum 15.96

Total U-Factor (W/m2-K) 2.6606

U-Factor for the Typical Operable Window System


Environmental Condition: U-Factor Condition
Tilt: 90o
Width: 1500 mm
Height: 4000 mm [1800mm+2200mm]
Area: 6.0 m2

U-FACTOR HEIGHT WIDTH U-FACTORxWIDTHxHEIGHT


ELEMENT ELEMENT DESCRIPTION
(W/m2-K) (mm) (mm) (W/K)
1 Center of Spandrel Glass 0.821 1564 1280 1.64
2 Center of Vision Glass 1.638 1926 1280 4.04
3 Mullion at Spandrel 11.955 1800 46.5 1.00
4 Mullion at Spandrel 11.955 1800 46.5 1.00
5 Mullion at Window 15.418 2200 46.5 1.58
6 Mullion at Window 15.418 2200 46.5 1.58
7 Stack Head 9.271 61.5 1407 0.80
8 Intermediate Transom 14.708 95 1407 1.97
9 Stack Sill 9.271 99.5 1407 1.30
10 Edge of Spandrel 1.110 1691 63.5 0.12
11 Edge of Spandrel 1.110 1691 63.5 0.12
12 Edge of Window 1.986 2053 63.5 0.26
13 Edge of Window 1.986 2053 63.5 0.26
14 Edge of Spandrel 0.844 63.5 1280 0.07
15 Edge of Spandrel 0.707 63.5 1280 0.06
16 Edge of Window 2.116 63.5 1280 0.17
17 Edge of Window 1.896 63.5 1280 0.15
Sum 16.11

Total U-Factor (W/m2-K) 2.6853

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 5
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

U-Factor for the Typical Spandrel Curtain Wall System


Environmental Condition: U-Factor Condition
Tilt: 90o
Width: 1500 mm
Height: 4000 mm [1800mm+2200mm]
Area: 6.0 m2
U-FACTOR HEIGHT WIDTH U-FACTORxWIDTHxHEIGHT
ELEMENT ELEMENT DESCRIPTION
(W/m2-K) (mm) (mm) (W/K)
1 Center of Spandrel Glass 0.821 1564 1280 1.64
2 Center of Spandrel Glass 0.821 1926 1280 2.02
3 Mullion at Spandrel 11.955 1800 46.5 1.00
4 Mullion at Spandrel 11.955 1800 46.5 1.00
5 Mullion at Spandrel 11.955 2200 46.5 1.22
6 Mullion at Spandrel 11.955 2200 46.5 1.22
7 Stack Head 8.253 61.5 1407 0.71
8 Intermediate Transom 10.911 95 1407 1.46
9 Stack Sill 8.253 99.5 1407 1.16
10 Edge of Spandrel 1.110 1691 63.5 0.12
11 Edge of Spandrel 1.110 1691 63.5 0.12
12 Edge of Spandrel 1.110 2053 63.5 0.14
13 Edge of Spandrel 1.110 2053 63.5 0.14
14 Edge of Spandrel 0.939 63.5 1280 0.08
15 Edge of Spandrel 0.821 63.5 1280 0.07
16 Edge of Spandrel 0.821 63.5 1280 0.07
17 Edge of Spandrel 0.939 63.5 1280 0.08
Sum 12.26

Total U-Factor (W/m2-K) 2.0428

Overall U-Factor for the Low Zone Facade Module (L7 to L19)
LOW ZONE FACADE U-FACTOR NUMBER OF TOTAL U-VALUE x NUMBER
ELEMENT
MODULE (W/m2-K) PANELS PANELS ÷ TOTAL (W/m2-K)
1 Fixed Panel 2.6606 102 291 0.93
2 Window Panel 2.6853 124 291 1.14
3 Spandrel Panel 2.0428 65 291 0.46

Overall U-Factor (W/m2-K) 2.5331

Overall U-Factor for the Mid Zone Facade Module (L20 to L23)
MID-ZONE FACADE U-FACTOR NUMBER OF TOTAL U-VALUE x NUMBER
ELEMENT
MODULE (W/m2-K) PANELS PANELS ÷ TOTAL (W/m2-K)
1 Fixed Panel 2.6606 81 199 1.08
2 Window Panel 2.6853 83 199 1.12
3 Spandrel Panel 2.0428 35 199 0.36

Overall U-Factor (W/m2-K) 2.5622

Overall U-Factor for the High Zone Facade Module (L24 to L26)
HIGH ZONE FACADE U-FACTOR NUMBER OF TOTAL U-VALUE x NUMBER
ELEMENT
MODULE (W/m2-K) PANELS PANELS ÷ TOTAL (W/m2-K)
1 Fixed Panel 2.6606 64 150 1.14
2 Window Panel 2.6853 62 150 1.11
3 Spandrel Panel 2.0428 24 150 0.33

Overall U-Factor (W/m2-K) 2.5720

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 6
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

2.1 MULLION AT SPANDREL PLAN THERMAL PERFORMANCE

(2.1.1) Isotherms for Mullion at Spandrel Plan

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 7
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.1.2) Colored Infrared for Mullion at Spandrel Plan

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 8
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.1.3) U Factors for Mullion at Spandrel Plan

(2.1.4) Colored Heat Flux Diagram for Mullion at Spandrel Plan

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 9
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

2.2 MULLION AT VISION PLAN THERMAL PERFORMANCE

(2.2.1) Isotherms for Mullion at Vision Plan

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 10
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.2.2) Colored Infrared for Mullion at Vision Plan

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 11
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.2.3) U Factors for Mullion at Vision Plan

(2.2.4) Colored Heat Flux Diagram for Mullion at Vision Plan

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 12
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

2.3. STACKJOINT SECTION AT VISION-SPANDREL THERMAL PERFORMANCE

(2.3.1) Isotherms for Stackjoint Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 13
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.3.2) Colored Infrared for Stackjoint Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 14
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.3.3) U Factors for Stackjoint Section at Vision-Spandrel

(2.3.4) Colored Heat Flux Diagram for Stackjoint Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 15
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

2.4 INTERMEDIATE TRANSOM SECTION AT VISION-SPANDREL THERMAL PERFORMANCE

(2.4.1) Isotherms for Intermediate Transom Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 16
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.4.2) Colored Infrared for Intermediate Transom Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 17
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.4.3) U Factors for Intermediate Transom Section at Vision-Spandrel

(2.4.4) Colored Heat Flux Diagram for Intermediate Transom Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 18
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

2.5 INTERMEDIATE OPERABLE TRANSOM SECTION AT VISION-SPANDREL THERMAL


PERFORMANCE

(2.5.1) Isotherms for Intermediate Operable Transom Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 19
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.5.2) Colored Infrared for Intermediate Operable Transom Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 20
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.5.3) U Factors for Intermediate Operable Transom Section at Vision-Spandrel

(2.5.4) Colored Heat Flux Diagram for Intermediate Operable Transom Section at Vision-
Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 21
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

2.6 INTERMEDIATE TRANSOM SECTION AT SPANDREL-SPANDREL THERMAL PERFORMANCE

(2.6.1) Isotherms for Intermediate Transom Section at Spandrel-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 22
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.6.2) Colored Infrared for Intermediate Transom Section at Spandrel-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 23
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.6.3) U Factors for Intermediate Transom Section at Spandrel-Spandrel

(2.6.4) Colored Heat Flux Diagram for Intermediate Transom Section at Spandrel-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 24
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

2.7 OPERABLE STACKJOINT SECTION AT VISION-SPANDREL THERMAL PERFORMANCE

(2.7.1) Isotherms for Operable Stackjoint Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 25
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.7.2) Colored Infrared for Operable Stackjoint Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 26
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.7.3) U Factors for Operable Stackjoint Section at Vision-Spandrel

(2.7.4) Colored Heat Flux Diagram for Operable Stackjoint Section at Vision-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 27
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

2.8 STACKJOINT SECTION AT SPANDREL-SPANDREL THERMAL PERFORMANCE

(2.8.1) Isotherms for Stackjoint Section at Spandrel-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 28
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.8.2) Colored Infrared for Stackjoint Section at Spandrel-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 29
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02

(2.8.3) U Factors for Stackjoint Section at Spandrel-Spandrel

(2.8.4) Colored Heat Flux Diagram for Stackjoint Section at Spandrel-Spandrel

Thermal Performance Analysis (NFRC Winter Condition)


Page II - 30