Prepared for:
Makati Development Corporation
Prepared by:
Professor Torsten Calvi Corporation
15 May 2017
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02
15 May 2017 Revision 02 This thermal calculation set analyzed the thermal performance of grey-
Prepared by: tinted class with a single Low-E coating on the #2 surface for the BPO
tower.
JAJA
Checked by:
RLV/ADL
10 November 2016 Revision 01 This thermal calculation set analyzed the thermal performance of grey-
Prepared by: tinted glass with varying coatings on the #2 surface for the BPO tower.
JAJA
Checked by:
RLV/ADL
21 October 2016 Revision 00 This thermal calculation set analyzed three different candidate glass types
Prepared by: for the BPO tower.
JAJA
Checked by:
RLV/ADL
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02
Table of Contents
Thermal Analysis for Typical Unitized Curtain Wall (Tinted Glass) System of
One Ayala Avenue, Makati City
INTRODUCTION
Preliminary Thermal Analysis of Typical Unitized Curtain Wall (Tinted Glass) System for BPO Tower
ONE AYALA AVENUE
Makati City, Philippines
· General
Professor Torsten Calvi Corporation was engaged by Makati Development Corporation to make a preliminary study of the
thermal performance of the unitized curtain wall system for the tower exterior facade of the BPO tower at One Ayala
Avenue, Makati City, Philippines. The typical framing members and glass options were analyzed using a finite element
computer model (THERM 7.4 version, developed at Lawrence Berkeley National Laboratory, USA) in order to predict the
thermal conductivity of the curtain wall system. An area averaging calculation, in accordance with the procedures set out
by the National Fenestration and Ratings Council (NFRC100: Procedure for Determining Fenestration Product U-Factors
and NFRC 200: Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at
Normal Incidence) was used to determine the over-all thermal conductivity of the curtain wall.
For the vision and operable window panels, the glass type considered in the study are an 8mm+12AS+8mm thick
insulating glass unit (IGU) with tinted outer pane and a Low-E coating on the #2 surface, and clear inner pane, and a
10mm thick monolithic spandrel pane.
The U-factor and SHGC for the 1800mm spandrel and 2200mm vision facade layout were obtained in the analysis. The
quantity of the fixed, operable window, and spandrel panels was also considered to determine the total U-factor and
SHGC of the panels in the low, mid, and high zone areas.
Environmental conditions and design assumptions are in accordance with NFRC 100-2010. Analysis was conducted
under the following temperature conditions:
SHGC: 32 °C exterior temperature, 24 °C interior temperature, and outside air velocity of 5.5 m/s.
U-Factor: -18 °C exterior temperature, 21 °C interior temperature, and outside air velocity of 5.5 m/s.
Each curtain wall type was able to meet the following specifications: U-value of 2.8 W/m²K and SHGC of 0.25.
The computer model predicts that the total U-value and SHGC of the curtain wall system, including glazing with frame,
are as follows:
Overall Values
Location Number of Floors U-Factor SHGC
Low Zone (L7 to L19) 13 2.533 0.201
Mid Zone (L20 to L23) 4 2.562 0.201
High Zone (L24 to L26) 3 2.572 0.201
Area-Weighted
2.545 0.201
Average
The overall U-Factor and SHGC of the building are 2.545 W/m2-K and 0.201, respectively.
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02
· Environmental Conditions
One Ayala Avenue, Makati (SHGC)
A. U-Factor Inside
Inside Air Temperature 24.0 °C
Convection Model ASHRAE / NFRC Inside
Radiation Model ASHRAE / NFRC
Effective Room Temperature 24.0 °C
Effective Room Emissivity 1.0
B. U-Factor Outside
Outside Temperature 32.0 °C
Direct Solar Radiation 0.0 W/m2
Convection Model ASHRAE / NFRC Outside
Convection Coefficient 15.0 W/m2-K
Outside Wind Speed 2.75 m/s
Wind Direction Windward
Radiation Model ASHRAE / NFRC
Effective Sky Temperature 32.0 °C
Effective Sky Emissivity 1.0
C. SHGC Inside
Inside Air Temperature 24.0 °C
Convection Model ASHRAE / NFRC Inside
Radiation Model ASHRAE / NFRC
Effective Room Temperature 24.0 °C
Effective Room Emissivity 1.0
D. SHGC Outside
Outside Temperature 32.0 °C
Direct Solar Radiation 783.0 W/m2
Convection Model ASHRAE / NFRC Outside
Convection Coefficient 15.0 W/m2-K
Outside Wind Speed 2.75 m/s
Wind Direction Windward
Radiation Model ASHRAE / NFRC
Effective Sky Temperature 32.0 °C
Effective Sky Emissivity 1.0
· Environmental Conditions
One Ayala Avenue, Makati (U-Factor)
A. U-Factor Inside
Inside Air Temperature 21.0 °C
Convection Model ASHRAE / NFRC Inside
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02
B. U-Factor Outside
Outside Temperature -18.0 °C
Direct Solar Radiation 0.0 W/m2
Convection Model ASHRAE / NFRC Outside
Convection Coefficient 26.0 W/m2-K
Outside Wind Speed 5.5 m/s
Wind Direction Windward
Radiation Model ASHRAE / NFRC
Effective Sky Temperature -18.0 °C
Effective Sky Emissivity 1.0
C. SHGC Inside
Inside Air Temperature 21.0 °C
Convection Model ASHRAE / NFRC Inside
Radiation Model ASHRAE / NFRC
Effective Room Temperature 21.0 °C
Effective Room Emissivity 1.0
D. SHGC Outside
Outside Temperature -18.0 °C
Direct Solar Radiation 0.0 W/m2
Convection Model ASHRAE / NFRC Outside
Convection Coefficient 26.0 W/m2-K
Outside Wind Speed 5.5 m/s
Wind Direction Windward
Radiation Model ASHRAE / NFRC
Effective Sky Temperature -18.0 °C
Effective Sky Emissivity 1.0
Vision Glass:
Outer Pane Glass Code: VE192m-8mm-LoE.VIR
Outer Pane Thickness: 8.0 mm
Cavity: Air
Cavity Thickness: 12.0 mm
Inner Pane Glass Code: CLR_8.AFG
Inner Pane Thickness: 7.9 mm
Tilt: 90.0o
U Value: 1.638 W/m2-k
SHGCc: N/A
SCc: N/A
Vtc: 0.383
RHG: N/A
Spandrel Glass:
Glass Code: 01_Clear_10.syp
Thickness: 10.0 mm
Tilt: 90.0o
U Value: 5.674 W/m2-k
SHGCc: N/A
SCc: N/A
Vtc: 0.878
RHG: N/A
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02
Vision Glass:
Outer Pane Glass Code: VE192m-8mm-LoE.VIR
Outer Pane Thickness: 8.0 mm
Cavity: Air
Cavity Thickness: 12.0 mm
Inner Pane Glass Code: CLR_8.AFG
Inner Pane Thickness: 7.9 mm
Tilt: 90.0o
U Value: 1.583 W/m2-k
SHGCc: 0.220
SCc: 0.253
Vtc: 0.383
RHG: 172 W/m2
Spandrel Glass:
Glass Code: 01_Clear_10.syp
Thickness: 10.0 mm
Tilt: 90.0o
U Value: 5.128 W/m2-k
SHGCc: 0.803
SCc: 0.922
Vtc: 0.878
RHG: 622 W/m2
PRELIMINARY THERMAL ANALYSIS OF THE TYPICAL UNITIZED CURTAIN WALL (TINTED GLASS) FOR THE BPO TOWER OF ONE AYALA AVENUE - Makati City
PTCC-1AYL-CS01-001NC REV02
CHAPTER 1
SHGC f = α x Uf x Af
Asurf x hout
SHGC 0 = (SHGC xAx) + (SHGC dAd) + (SHGC eAe) + (SHGC deAe) + (SHGC leAe) + (SHGC cAc)
Apf
SHGC of Product with Center-Of-Glazing SHGC = 1
SHGC 1 = (SHGC xAx) + (SHGC dAd) + (SHGC eAe) + (SHGC deAe) + (SHGC leAe) + (SHGC cAc)
Apf
SHGC f = 0.067
SHGC 0 = (SHGC xAx) + (SHGCdAd) + (SHGC eAe) + (SHGC deAe) + (SHGC leAe) + (SHGC cAc)
Apf
= (0.067)(0.41) + (0)(0) + (0)(0.42) + (0)(0) + (0)(0) + (0)(2.47)
3.3
SHGC 0 = 0.008
SHGC 1 = (SHGC xAx) + (SHGCdAd) + (SHGC eAe) + (SHGC deAe) + (SHGC leAe) + (SHGC cAc)
Apf
= (0.067)(0.41) + (1)(0) + (1)(0.42) + (1)(0) + (1)(0) + (1)(2.47)
3.3
SHGC 1 = 0.884
SHGC = 0.201
SHGC f = 0.067
SHGC 0 = (SHGC xAx) + (SHGCdAd) + (SHGC eAe) + (SHGC deAe) + (SHGC leAe) + (SHGC cAc)
Apf
= (0.067)(0.41) + (0)(0) + (0)(0.42) + (0)(0) + (0)(0) + (0)(2.47)
3.3
SHGC 0 = 0.008
SHGC 1 = (SHGC xAx) + (SHGCdAd) + (SHGC eAe) + (SHGC deAe) + (SHGC leAe) + (SHGC cAc)
Apf
= (0.067)(0.41) + (1)(0) + (1)(0.42) + (1)(0) + (1)(0) + (1)(2.47)
3.3
SHGC 1 = 0.884
SHGC = 0.201
(1.3.4) Colored Heat Flux Diagram for Intermediate Transom Section at Vision-Spandrel
(1.4.4) Colored Heat Flux Diagram for Intermediate Operable Transom Section at Vision-
Spandrel
(1.5.4) Colored Heat Flux Diagram for Operable Stackjoint Section at Vision-Spandrel
CHAPTER 2
Overall U-Factor for the Low Zone Facade Module (L7 to L19)
LOW ZONE FACADE U-FACTOR NUMBER OF TOTAL U-VALUE x NUMBER
ELEMENT
MODULE (W/m2-K) PANELS PANELS ÷ TOTAL (W/m2-K)
1 Fixed Panel 2.6606 102 291 0.93
2 Window Panel 2.6853 124 291 1.14
3 Spandrel Panel 2.0428 65 291 0.46
Overall U-Factor for the Mid Zone Facade Module (L20 to L23)
MID-ZONE FACADE U-FACTOR NUMBER OF TOTAL U-VALUE x NUMBER
ELEMENT
MODULE (W/m2-K) PANELS PANELS ÷ TOTAL (W/m2-K)
1 Fixed Panel 2.6606 81 199 1.08
2 Window Panel 2.6853 83 199 1.12
3 Spandrel Panel 2.0428 35 199 0.36
Overall U-Factor for the High Zone Facade Module (L24 to L26)
HIGH ZONE FACADE U-FACTOR NUMBER OF TOTAL U-VALUE x NUMBER
ELEMENT
MODULE (W/m2-K) PANELS PANELS ÷ TOTAL (W/m2-K)
1 Fixed Panel 2.6606 64 150 1.14
2 Window Panel 2.6853 62 150 1.11
3 Spandrel Panel 2.0428 24 150 0.33
(2.4.4) Colored Heat Flux Diagram for Intermediate Transom Section at Vision-Spandrel
(2.5.4) Colored Heat Flux Diagram for Intermediate Operable Transom Section at Vision-
Spandrel
(2.6.4) Colored Heat Flux Diagram for Intermediate Transom Section at Spandrel-Spandrel
(2.7.4) Colored Heat Flux Diagram for Operable Stackjoint Section at Vision-Spandrel