GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
1.1 Purpose
The proposed Solar PV power station will be completed and commissioned by year
2022. All common facilities at the power station will be built to cater for operation of the
plant.
Generated power will be exported via power station's switchyard through connection
at MERALCO's new Baras switching station. Connection to new substation Baras
switching station shall be via a single circuit 115 kV transmission line.
Auxiliary transformer will be provided for house load consumption.
Page | 2
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 3
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
The grounding system shall be designed in accordance with the applicable sections
of the latest revisions of the following standards:
The grounding system design calculation is based on the earthing system power station layout,
grounding details, soil resistivity test report and bare copper properties as shown in Annex B to
E.
3.2 MERALCO Available Short Circuit Current
In accordance with MERALCO’s available fault level in the area, the maximum fault current
of 11.35 kA when three-phase fault occurred within the substation and 12.03 kA at MVPS
station and typical value of X/R ratio of 30 will be used based on ANSI37.010. Refer to GBP-
PSS-EE-005 for the short circuit calculation report.
3.3 Soil Resistivity Results
The resistivity of the soil used in the design calculation is based on the Soil Resistivity Test
Results conducted by a Third Party as shown in Annex D.
Page | 4
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
The following computed values and assumed data shall be used in grounding system
design calculation for the substation:
Value
Symbol Description
calculated/defined
ρ Soil resistivity in Ω-m (average) 40.75
3.4.2 The following computed values and assumed data shall be used in grounding system
design calculation for the MV Power Station:
Value
Symbol Description
calculated/defined
ρ Soil resistivity in Ω-m (average) 40.75
Page | 5
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
The following computed values and assumed data shall be used in grounding system
design calculation for the Inverter/PV area:
Value
Symbol Description
calculated/defined
ρ Soil resistivity in Ω-m (average) 40.75
Based on the results as shown in Annex A-1, the required size for grounding
grid conductors for substation shall be 70 mm2 . However, considering future
expansion of MERALCO network, the grounding conductor shall be 95 mm 2
commercial hard drawn copper wire. The depth of the horizontal grounding grid
is 0.6 m and the grounding rod shall be 19 mm diameter, 3 m long, copper-clad
steel rod of 20% conductivity. There are 24 grounding rods located throughout
of the grounding layout.
Page | 6
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
For a person with a body weight of 50 kg, when the maximum fault duration is
1 sec, the tolerable touch and step voltages are 519.2 V and 1728.7 V
respectively, while the calculated touch and step voltages are 491.6 V and
544.3 V respectively which are 94.7% and 31.5% of tolerable touch and step
voltages respectively. Hence, initial design is safe.
The computed ground grid resistance of 0.434 Ω is lower than what is being
specified in the relevant standards.
5.2 MV Power Station
Based on the results as shown in Annex A-2, the required size for grounding
grid conductors for MVPS shall be 70 mm2 . However, considering safety
margin, the grounding conductor shall be 95 mm2 commercial hard drawn
copper wire. The depth of the horizontal grounding grid is 0.6 m and the
grounding rod shall be 19 mm diameter, 3 m long, copper-clad steel rod of 20%
conductivity. There are 30 grounding rods located throughout of the grounding
layout.
For a person with a body weight of 50 kg, when the maximum fault duration is
1 sec, the tolerable touch and step voltages are 519.2 V and 1728.7 V
respectively, while the calculated touch and step voltages are 502.1 V and
603.2 V respectively which are 96.7% and 34.9% of tolerable touch and step
voltages respectively. Hence, initial design is safe.
The computed ground grid resistance of 0.447 Ω is lower than what is being
specified in the relevant standards.
5.3 PV Area
Based on the results as shown in Annex A-3, the required size for grounding
grid conductors for substation shall be 95 mm2 copper-clad steel wire. The
depth of the horizontal grounding grid is 0.6 m and the grounding rod shall be
19 mm diameter, 3 m long, copper-clad steel rod of 20% conductivity. There
are 32 grounding rods located throughout of the grounding layout.
For a person with a body weight of 50 kg, when the maximum fault duration is
0.5 sec, the tolerable touch and step voltages are 734.2 V and 2444.8 V
respectively, while the calculated touch and step voltages are 59.2 V and 12.7
V respectively which are 8.1% and 0.5% of tolerable touch and step voltages
respectively. Hence, initial design is safe.
The computed ground grid resistance of 0.024 Ω is lower than what is being
specified in the relevant standards.
Page | 7
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Although the computed ground grid resistances are lower than what are being
specified in the relevant standards, to further reduce the grounding resistance,
it is recommended that gravel surface of at least 0.15 cm with a
resistivity of 3,000 Ω-m shall be added to the substation and other areas where
personnel are expected to work.
Further, if in case the actual grounding values on the actual installation will not
meet the the required value, additional grounding conductors and rods shall be
installed.
7.0 APPENDICES
ANNEX A – Calculation Results and Summary
ANNEX B – San Miguel Grounding System Layout
ANNEX C – Grounding System Details
ANNEX D – Soil Resistivity Test Report
ANNEX E – Bare Copper Properties
Page | 8
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
APPENDICES
Page | 9
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 10
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 11
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 12
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 13
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 14
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 15
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 16
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 17
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 18
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 19
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 20
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 21
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 22
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 23
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 24
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 25
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 26
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 27
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 28
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 29
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 30
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 31
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 32
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 33
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 34
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 35
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 36
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 37
GROUNDING SYSTEM CALCULATION
75 MWac PINUGAY SOLAR POWER PLANT PROJECT
Page | 38