Professional Documents
Culture Documents
Equipment / Matrerial
STEEL STRUCTURE, MECHANICAL AND PIPING
/ Service
2023.01.11
13:41:48
+07'00'
0 Issued for Construction 08-Jan-23 MDH WLF KEO
A Issued for Review 07-Jan-23 MDH WLF WLF
Rev Reason for Issue Date Author Checked Approver
Revision History
Amendment Revision Amender
Amendment
Date Number Name
07-Jan-23 A M. Danny H Issue for Review
08-Jan-23 0 M. Danny H Issue for Construction
Holds
Hold Section
Short description of hold
No Number
COMMENT SHEET
Date Rev. Page/Section Company Comment Contractor Response
Table of Contents
1 INTRODUCTION ................................................................................................................... 5
1.1 Project Background ............................................................................................... 5
1.2 Project Location .................................................................................................... 5
1.3 Purpose ................................................................................................................ 5
1.4 Scope.................................................................................................................... 6
2 INFORMATION PRIOR TESTING ............................................................................................ 6
2.1 Extent of Testing ................................................................................................... 6
2.2 Safety Precoution .................................................................................................. 6
3 PROCEDURE QUALIFICATION ............................................................................................... 6
3.1 High Voltage Spark ............................................................................................... 7
3.1.1 Equipment ......................................................................................................................... 7
3.1.2 Procedures for Use ........................................................................................................... 8
3.1.3 Verifying Sensitivity of Equipment .................................................................................... 9
3.1.4 Verifying Tester Calibration or Sensitivity ......................................................................... 9
4 ACCEPTANCE CRITERIA ........................................................................................................ 9
5 RECORDING INDICATION AND INTERPRETAION .................................................................... 9
5.1 Reporting .............................................................................................................. 9
6 TESTING OF REPAIRED AREA .............................................................................................. 10
List of Tables
Table 1 Minimum Testing Voltage for Various Coating Thickness ....................................7
List of Figures
Figure 1 Project Location ...........................................................................................5
1 INTRODUCTION
1.3 Purpose
This procedure of Discontinuity (Holiday) Test provides requirements guideline to conduct
discontinuity (holiday) examination in a coating film systems that are applied to conductive
substrates by electrical detection for salak brine heat recovery binary power plan project. This
procedure covers all work activities associated with piping Installation, fabrication, and Testing
to be performed by Baharu Penta Kencana (BPK).
1.4 Scope
This written procedure divided into 2 (two) main groups of test method and equipment; low voltage
wet sponge testing and high voltage spark testing Reference Document. Scope of this written
procedure is High Voltage Spark Test which will be used for Geothermal Salak Brine Heat
Recovery Binary Power Plan Project (SEGS-BHRBPP). The following documents shall be
referred and followed.
3 PROCEDURE QUALIFICATION
High voltage spark test equipment is generally used for determining the existences of
discontinuities in coating films having a total thickness of greater than 20 mils (0.5 mm). Unspecified
variables in this written procedure, will refer to coating, equipment and instrument manufacturer’s
design.
CAUTION: Coatings that are applied at a thickness of less than 20 mils (0.5 mm) may be
susceptible to damage if tested with high voltage spark testing equipment.
Table 1
3.1.1 Equipment
A high-voltage (in excess of 800V) spark tester is an electronic device used to locate
discontinuities in a nonconductive protective coating. It consists of an electrical energy source,
an exploring electrode, and a ground connection from the indicator signaling current flow
through a coating discontinuity to the substrate.
The exploring electrode shall be of the type capable of maintaining continuous contact with the
surface being inspected, including bolts, raised areas, etc. It shall be kept clean and free of
coating material.
A high-voltage spark tester can be identified as either a pulse type tester or a direct current
tester. A pulse type tester discharges a cycling, high-voltage pulse. A direct current tester
discharges continuous voltage.
The thickness of the coating shall be measured with a nondestructive dry film thickness gauge.
If the coating is less than 500 µm (20 mil), procedures for low-voltage testing should be
considered. Although the high-voltage spark tester is suitable for determining discontinuities in
coatings less than 500 µm (20 mil), the coating manufacturer should be consulted before using
this test. Certain coatings can be damaged if tested with this equipment.
The high-voltage spark tester shall be calibrated in accordance with Paragraph 2.1.4.
The high-voltage spark tester shall be adjusted to the proper voltage for the coating thickness
being tested. In selecting the inspection voltage, sufficient voltage shall be provided to break
the air gap that exists at the holiday. This air gap varies depending on the total applied film
thickness. Excessive voltage may produce a holiday in the coating. The maximum voltage for
the applied coating shall be obtained from the coating manufacturer. Table 1 contains
suggested voltages that may be used as guides.
The ground wire from the high-voltage spark tester ground output terminal shall be attached
to the conductive substrate, and positive electrical contact shall be ensured. When testing
concrete surfaces, the ground wire shall be attached to the rebars. If the rebars are not visible,
the ground wire shall be placed directly against the bare concrete surface and weighted with
a damp cloth or wet-sand-filled paper bag.
Contact shall be made with the exploring electrode on the conductive substrate to verify that
the tester is properly grounded. This test shall be conducted periodically during the testing of
the coating.
The exploring electrode shall be moved over the surface of the dry coating at a rate of
approximately 0.3 m/s (1 ft/s) using a single pass. Moisture on the coating surface can cause
erroneous indications. If moisture exists, it shall be removed or allowed to dry before the test
is conducted.
Discontinuities that require repair shall be identified with a marker that is compatible with the
repair coating or one that is easily removable.
Test the energy source (battery) for proper voltage output according to the
manufacturer’s instructions.
Connect the exploring electrode and grounding cable to the terminals of the tester.
Touch the exploring electrode to the ground cable alligator clip. The tester signal should
actuate in accordance with the manufacturer’s operating instructions.
Connect a high-voltage voltmeter between the probe and the ground lead.
Switch the tester to the “on” position.
Compare the voltage of the voltmeter with the output voltage of the tester. Depending
on the type of tester, adjust to the specified voltage (±5%) using either the variable
regulator or predetermined selector switch.
Switch the tester to the “off” position.
Disconnect the voltmeter.
4 ACCEPTANCE CRITERIA
Discontinuity is normally not permitted on any coating. If found retest on those areas that have
been repaired following the procedure as previously outlined. All discontinuity (holiday) testing
results shall be recorded in the applicable forms.
5.1 Reporting
Discontinuity (Holiday) Testing Report (Attachment)
NOTE : All repairs should be made within the recoat window of the coating—generally 18 hours.
Repairs made outside of the recoat window require abrading and cleaning the coating surface per
manufacturers recommendations. All debris, amine blush or other contaminates need to be
removed from the coating surface before any repairs are made.
Project Title : Salak Brine Heat Recovery Binary Power Plant Project Report No. : 9773-BPK-A2B (HDR)-001
Job No. : 9773 Line No. :
Company : Star Energy Geothermal Salak.Ltd Report Date : 01-Aug-23
Contractor : PT. Tripatra-ORMAT Consortium Page : of
SubContractor : PT. Baharu Penta Kencana
Visual Inspection Holiday Test
Rev. Wide/
No. Item Name / Drawing Coating Test Remark
Sheet Length/Joint Status Date Result
Condition Voltage
Testing Specific :
1. Testing Object : Piping Underground DFT : 1.224 mm
2. Holiday Test Equipment : - Brand : PCWI Digital Series : DC30
- Serial Number : 13109-3 Volt Range : 1-30KV
- Cal. Date : 04 Jan 2023
Wahyu L. Fais
NAME DATE NAME DATE NAME DATE