Professional Documents
Culture Documents
This experiment studied the three-phase generator and the relationships between the
voltages that it is able to supply. The four-wire three-phase generator, offers two types
of voltages; phase voltage, and line voltage. Each type of voltage can be set up three
different ways, each supplies the required signal with a certain phase shift for each
signal. During the experiment two phase voltage signals were measured using the
oscilloscope, also the rms phase voltage and rms line voltage was measured. Results
show that each voltage signal has a certain phase shift, and that the ratio between the
phase and line is constant. These results show the many properties of the
three-phase generator
Introduction
Theory
The three-phase generator has three induction coils, each isapart, and since the
induction coils have the same number of turns and they rotate with the same velocity,
the voltage induced across each coil will have the same peak value and frequency [1].
The phase voltage (subscript) is the voltage across any of the lines (or) and the
neutral line (). Figure 1 shows the all three phase voltages that the three-phase
generator can supply. As can be seen there is a phase shift of between each of the
lines.
Aims:
• Measure the angle of phase shift between the voltages and explain the
measurements.
Equipment
• Universal panel.
• Digital multimeter.
Procedure
• Trace what is seen on the screen of the oscilloscope on a graph as shown in Fig.
3
Fig 3: The oscilloscope display of the two measured phase voltages.
• Disconnect the oscilloscope, and connect the multimeter to measure the phase
voltage.
• Find the ratio between the measured line voltage and the measured phase
voltage.
fig5
The multimeter readings for the phase voltage and line voltage.
fig6
oscilloscope (XSC2) was used to draw two of the phase voltage signal
Conclusion:
• The 120° phase shift between waveforms and the similarities in appearance of the
three sinusoidal functions.
• at any instant of time, the algebraic sum of the three phase voltages of a
three-phase generator is zero
• The off-load voltage exceed the values quoted for the generator nominal values of
voltage.
References
[1] Robert L. Boylestad, Introductory Circuit Analysis, Prentice Hall, 11th ed., 2006, pp.
1029-1034.