PJT NAME : GUAM CCPP PJT (5-5-2, 180MW) Revision : 0 Currency : USD or Korean Won
Total Price
구 분 Item Description Q'ty Unit Unit Pirce Remark
based on FOB
115kV AIS Substation
115kV AIR INSULATED SWITCHGEAR
- 40kA (3-SECOND) SYMMETRICAL SHORT CKT CURRENT, 50 HZ,
1
3-PHASE, 2000A- Double bus configuration with single breaker
scheme. with BCU control panel
115kV Circuit Breaker (Outdoor), GCB TYPE, Dead Tank type
1.1 - 115kV, 60HZ, 3PH,2000A, 40kA(3sec.) inculding current 11 SETS
transformer(At a minimum, multi-ratio Class 400)
Disconnector Switch w/2ES with supporting structure
- 115kV, 60Hz, 40kA(3-Seconds), 3PH, 2000A, Three-pole, single-
1.3 throw, gang-operated, air break, manually operated, rated for 22 SETS
outdoor service on a 60 Hz, 3-phase, system. with single or double
earthing swtich
Coupling Capacitor Transformer(3PH) with supporting structure
1.5 Bidder shall provide as per
- Line side : 115kV/√3/(110V/√3)/(110V/√3), 200VA 3 SETS
GPA standards
Bidder shall provide as per
- Bus side : 115kV/√3/(110V/√3)/(110V/√3), 200VA 2 SETS
GPA standards
Lightning Arrester(3PH) with supporting structure
1.6 3 SETS Metal-oxide station class.
- Single phase Surge Arrester 420kV, 20kA
Bidder can change quantity
1.8 Post Insulator (1-PH/ea) with supporting structure 24 SETS
as bidder design
1.9 Line Trap (1-PH/ea) with supporting structure 3 SETS
Bidder shall provide as per
2 Tariff metering System 1 LOT
GPA standards
Minimum condition
OWS : 1 set, EWS : 1set
3 RTU & SAS Equipment/System 1 LOT Including GPS set
Bidder shall provide as per
GPA standards
Bidder shall provide same
4 Protection Panel 1 LOT
type(SEL Relay)
Bidder shall provide same
type(Tesla 4000 Power
Base 5 Fault & event reacorder with Computer 1 LOT
System Monitoring
Recorder)
6 Interface Marshalling Kiosk 1 LOT
7 Gantry steel structure and support 1 LOT
Rigid buses : Aluminum
tubular bus conductor AA
Conductor, insulator, bushing and hardware for AIS conductors Schedule 40 pipe (standard
8 1 LOT
including overhead conductor from P/P pipe
size), ASTM B429, 6063-T6
alloy.
9 Annunciator panel 1 LOT
10 Accessories for 115kV AIS 1 LOT
11 Synchronization device(Check panel) 1 LOT
12 All Cable and accessary 1 LOT Power/Control/Fiber optic
13 Cable tray and accessary 1 LOT
14 Coduit and accessary 1 LOT
15 Earting & Lightning material 1 LOT
16 Lighting & small power system 1 LOT
17 Fire stop material 1 LOT
18 SF6 Gas Treatment Plant and accessories 1 SETS
19 dew point meter 1 SETS
20 device for measuring the purity of SF6 GAS 1 SETS
21 GAS leak detector 1 SETS
22 AC Auxiliary power system(480V LV SWGR/MCC/120V AC DB) 1 LOT
23 125/48VDC system(including Battery) 1 LOT Back up time : 1Hours
24 130V UPS system 1 LOT Back up time : 1Hours
Spare Part and consumables for Start-up, Pre-Commissioning,
25 1 LOT
Commissioning
26 Special Tools 1 LOT
Sub-Total
Recommanded Spare parts for 2 years operation
1 1 LOT
(2 Years Spare Parts from Final Acceptance)
All Test and Commissioning work for Substation Specify All test for
2 1 LOT
(Performing) Substation
5 Supervisory service
6-1 Installation 1 MD
7 Trainging service
8 Mechnical system
Sub-Total
Total
Page 1 of 2
PJT : Mae Moh
Appendix 2
PJT NAME : GUAM CCPP PJT (5-5-2, 180MW) Revision : 0 Currency : USD or Korean Won
Total Price
구 분 Item Description Q'ty Unit Unit Pirce Remark
based on FOB
115kV AIS Substation
115kV AIR INSULATED SWITCHGEAR
1 - 40kA (3-SECOND) SYMMETRICAL SHORT CKT CURRENT, 50 HZ,
3-PHASE, 2000A with BCU control panel
115kV Circuit Breaker (Outdoor), GCB TYPE, Dead Tank type Refer Attachment Drawing
1.1 - 115kV, 60HZ, 3PH,2000A, 40kA(3sec.) inculding current 1 SETS Bidder shall apply to same
transformer. type CT with existing CT
Disconnector Switch w/2ES with supporting structure
- 115kV, 60Hz, 40kA(3-Seconds), 3PH, 2000A, Three-pole, single-
1.2 throw, gang-operated, air break, manually operated, rated for 2 SETS
outdoor service on a 60 Hz, 3-phase, system. with single or double
earthing swtich
Potential Transformer(3PH) with supporting structure
1.3 Bidder shall provide as per
- Line side : 115kV/√3/(110V/√3)/(110V/√3), 200VA 6 SETS
GPA standards
Lightning Arrester(3PH) with supporting structure
1.4 3 SETS
- Single phase Surge Arrester 96kV, 10kA
Bidder can modify quantity
1.5 Post Insulator (1-PH/ea) with supporting structure 6 SETS
as per Attachment Drawing
Sub-Total
Recommanded Spare parts for 2 years operation
1 1 LOT
(2 Years Spare Parts from Final Acceptance)
All Test and Commissioning work for Substation Specify All test for
2 1 LOT
(Performing) Substation
5 Supervisory service
6-1 Installation 1 MD
7 Trainging service
Sub-Total
Total