Volume 2
MlSSlON STATEMENTS
As the Nation’s principal conservation agency, the Department of the Interior has responsibility
for most of our nationally owned public lands and natural resources. This includes fostering
sound use of our land and water resources; protecting our fish, wildlife, and biological diversity;
preserving the environmental and cultural values of our national parks and historical places;
and providing for the enjoyment of life through outdoor recreation. The Department assesses
our energy and mineral resources and works to ensure that their development is in the best
interests of all our people by encouraging stewardship and citizen participation in their care.
The Department also has a major responsibility for American Indian reservation communities
and for people who live in island territories under U.S. Administration.
The mission of the Bureau of l3cclamation is to manage, develop, and protect water and
related resources in an environmentally and economically sound manner in the interest of the
American public.
Any use of trade names and trademarks in this publication is for descriptive purposes only and does not
constitute endorsement by the Bureau of Reclamation.
The information contained In this report regarding commercial products or firms may not be used for advertising
or promotional purposes and is not to be construed as an endorsement of any product or firm by the Bureau of
Reclamation.
PREIFACE
Canal automation is a proven method of providing automation technology. The manual is an attempt
cost-effective solutions to improve canal operations to bring together the various technologies into a
and conserve water. This manual has been single resource for the canal operator, manager,
prepared as a technical reference to provide and designer. A single gate structure could be
specific tools for the design of an automated canal. automated by an individual using this manual and
Since the publication of volume 1 of the Canal off-the-shelf components. However, the
Systems Automation Manual in 1991, the Bureau of complexities of a centralized control system would
Reclamation has received numerous requests for require a team with varied technical expertise. The
volume 2. Reorganization, retirements of key manual provides important considerations to aid in
personnel, and budget, personnel, and program the technical design of an automated canal. In
cutbacks have resulted in delays in the completion volume 2, the authors have documented
of volume 2 until 1995. institutional knowledge that should help canal
operators and designers with practical applications
Volume 1 of the Canal Systems Automation Manual of canal automation.
discusses the fundamentals of canal operation and
automation. Volume 2 gives the reader more Principal Bureau of Reclamation contributors are
specific information for designing an automated listed below.
canal or to retrofit automation to an existing canal.
Chapter 5 deals with canal design and automation Authors: David Ehler, Henry Falvey,
requirements. In chapter 6, the reader is provided David Rogers, Edward Serfozo,
with a brief review of canal hydraulics and a Rodney Johansen, Peter Voorheis,
discussion of numerical solutions to the hydraulic Ronald Arrington, Larry Rossi
equations used in canal applications. Chapter 7 is
a discussion of control theory and application. Project management: David King
Chapter 8 examines communication systems and
their application to data telemetry and control. In Editors: David King, Tom Hovland
chapter 9, the reader can learn about various types
of measurement instrumentation. Chapter 10 Occasional references to proprietary materials or
discusses the mechanical features of an automated products exist in this publication, but these
canal system. The last chapter, chapter 11, deals references should not be construed in any way as
with the electronic components used to control a an endorsement. The Bureau of Reclamation
canal, either onsite or remotely. cannot endorse proprietary products or processes
of manufacturers or the services of commercial
The Bureau of Reclamation’s canal automation firms for advertising, publicity, sales, or other
team is a multidisciplinary team that has been purposes.
actively involved in practical application of canal
.. .
III
CONTENTS
Page
...
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . III
V
CONTENTS
Page
vi
CONTENTS
Page
vii
CONTENTS
Page
Glossary . ... .... .. ..... .. ..... ... ..... .... .... ... ..... .. ..... ... ..... ....... G-l
Nomenclature .... ... .... .... .... ... ..... ... .... .... .... .... .... .. ...... ...... N-l
TABLES
NO. Page
FIGURES
No. Page
VIII
CONTENTS
FIGURES-Continued
No. Page
5-11 Upstream supply oriented segment, reservoir, and downstream demand oriented segment ... 5-26
5-12 In-line reservoir .......................................................... 5-27
5-13 Off-line reservoir ......................................................... 5-27
5-14 Canal pumping plants ..................................................... 5-29
5-l 5 On-off pumping plant control ................................................ 5-30
5-l 6 Control levels for reduced pump cycling ........................................ 5-31
5-17 Control levels for different-sized pumps ........................................ 5-31
5-18 Forebay and afterbay reservoir levels .......................................... 5-32
5-l 9 Stilling well for water level measurement ....................................... 5-32
5-20 Parshall flume.. ......................................................... 5-33
5-21 Rampflume ............................................................ 5-35
6-1 View of hydraulic laboratory canal radial gate model showing manometer and stilling
well boards used to measure water pressure at selected points ...................... 6-2
6-2 Canal model ............................................................ 6-4
6-3 Control panels, flumes, and side-spill weirs of canal model .......................... 6-5
6-4 Laboratory test facility used for the ELFLO plus RESET controller ..................... 6-6
6-5 Electrical analog of a canal ................................................. 6-7
6-6 Characteristic lines ....................................................... 6-12
6-7 Grid of characteristics ..................................................... 6-l 3
6-8 Specified time interval grid .................................................. 6-13
6-9 Finite difference grid ...................................................... 6-14
6-10 Cross section of canal ..................................................... 6-l 6
7-l Block diagram ........................................................... 7-3
7-2 Multiple sensors in a pool .................................................. 7-3
7-3 ELFLO plus RESET controller ............................................... 7-4
7-4 Control components of ELFLO plus RESET ..................................... 7-5
7-5 Three-position control function ............................................... 7-8
7-6 Frequency of limit cycle for three-position controller ............................... 7-9
7-7 Proportional control example ................................................ 7-9
7-8 Variation of proportional constant with discharge .................................. 7-10
7-9 Complex-domain specifications .............................................. 7-l 3
7-10 Time-domain specifications ................................................. 7-14
7-l 1 Little-Man controller action .................................................. 7-16
7-12 Colvin controller SOTNRT mode of control ...................................... 7-17
7-13 Colvin controller response and recovery characteristics ............................. 7-18
7-14 Colvin control of a diversion dam gate ......................................... 7-20
7-15 ELFLO controller typical response and recovery characteristics for automatic
downstream control ...................................................... 7-22
7-l 6 Percent of critical damping versus the ratio of two successive discharges, Q/Q, ........... 7-24
7-17 ELFLO plus RESET controller typical response and characteristics .................... 7-26
7-18 Response characteristics of ELFLO controller with and without RESET ................. 7-28
7-19 P+PR controller schematic diagram for upstream control ............................ 7-31
7-20 P+PR response and recovery characteristics .................................... 7-32
7-21 Bypass Drain response characteristics with the P+PR automatic upstream
control system ......................................................... 7-33
7-22 Local automatic Q-Controller ................................................ 7-34
ix
CONTENTS
FIGURES-Continued
No. Page
7-23 Q-Controller applying the discharge algorithm’s typical response and recovery
characteristics .......................................................... 7-35
7-24 Differential head algorithms-Q-Controller procedure .............................. 7-36
7-25 Big Horn Canal Headworks Q-plus error controller differential head algorithms ............ 7-40
7-26 Big Horn Canal Headworks Q-plus error controller typical response and recovery
characteristics .......................................................... 7-41
7-27 Gate motions with gate stroking .............................................. 7-42
8-l Atypicalfigure8cable .................................................... 8-5
8-2 A typical air core direct buried cable ........................................... 8-7
8-3 A typical filled direct buried cable ............................................. 8-7
8-4 A typical satellite data collection system ........................................ 8-15
8-5 Diagram of a remote data collection platform .................................... 8-17
8-6 Meteor burst communication technique ......................................... 8-17
8-7 A typical power line protection circuit .......................................... 8-23
9-l Float, pulley, and counterweight .............................................. 9-4
9-2 Modified Leupold Stevens Chart Recorder ...................................... 9-5
9-3 Submersible pressure transmitter ............................................. 9-5
9-4 Capacitance probe ....................................................... 9-6
9-5 Acoustic level encoder. .................................................... 9-6
9-6 Ultrasonic flow meter ...................................................... 9-8
9-7 Parshall flume.. ......................................................... 9-9
9-8(a) Ramp flume ............................................................ 9-l 1
9-8(b) Ramp flume schematic .................................................... 9-12
9-9 Weir .................................................................. 9-13
9-10 Radial gate hoist with sensor ................................................ 9-15
9-11 Slidegate hoist .......................................................... 9-16
9-12 B&W water level alarms ................................................... 9-l 9
9-13 (a) Potentiometer and (b) digital encoder ....................................... 9-21
9-14 Inclinometer ............................................................ 9-22
9-15 Syncro ................................................................ 9-22
9-16 Pressure transducer ...................................................... 9-23
9-17 Weather station and satellite platform .......................................... 9-24
9-l 8 Analog output ........................................................... 9-26
9-19 Digital representation ...................................................... 9-27
10-l Radial gate structure ...................................................... 1 o-2
1o-2 Typical radial gate hoist .................................................... 1 o-3
1o-3 Slide gate motor-operated lift ................................................ 1 o-5
1o-4 AMILgate .............................................................. 1o-7
1o-5 Obermeyergate ......................................................... 1O-8
1O-6 Vertical pumping unit in open sump ........................................... 1o-9
1o-7 Hydraulic cylinder protective enclosure ......................................... lo-16
1O-8 Gate pushbutton controls ................................................... lo-16
1o-9 Small box attached over pushbuttons .......................................... lo-16
10-10 Canister locked over assembly ............................................... 10-17
10-11 Hydraulic trash rake ...................................................... 10-17
11-l Dual redundant computer system ............................................. 11-12
11-2 Dual redundant computer configuration with front-end processors ..................... 11-13
11-3 Distributive processing computer configuration ................................... 11-13
X
CANAL SYSTEMS AUTOMATION MANUAL
A Bureau of Reclamation Technical Publication
Volume 2
BY
D.C. Rogers
D.G. Ehler
H.T. Falvey
E.A. Serfozo
P. Voorheis
R.P. Johansen
R.M. Arrington
L.J. Rossi
Project Management by
D.L. King
In theory, designing a new canal system has the Armed with a preliminary operation scheme, an
advantage over modification of an existing canal engineer can design the canal system’s structural
because the designer can choose from all components. This step involves civil engineering
possibilities to yield the optimum system design. design in a more traditional sense, specifying
Structural features and control system design can conveyance channel properties, check structure
be tailored to each other to produce the best and location and details, turnout structures, storage
most economical overall system. Coordinating the facilities, siphons, drops, wasteways, and any other
structural and control system design allows greater structural details. Structural design details can be
optimization, but designing a new automated canal found in other texts such as the Bureau of
can be much more difficult than upgrading an Reclamation’s (Reclamation) Design of Small Canal
existing canal because the design choices appear Structures [l].’ Chapter 5 does not provide a
to be infinite. A designer can never be sure when thorough discussion of canal design.
the best design has been achieved.
Here, design considerations specifically associated Operation, control, and automation are interrelated
with automated canals are emphasized. and order dependent. New canal design should
start with a thorough study of unsteady-flow
Finally, control system components can be scenarios and evaluation of various operational
designed, beginning with the selection of a control alternatives. After the method of operation is
concept and control method. Control logic must be known, specific control methods can be studied and
developed and coded into software. Then, selected. Then, automatic control logic and
specifications can be written for mechanical, equipment can be designed.
electrical, and communication equipment. The
discussion of control system design in this chapter When determining control system complexity, the
concerns important considerations in the design objective is to serve the needs of water users
process. Control equipment details are provided in efficiently and economically. Underdesign will lead
chapters 8 through 11. to inefficiencies and problems with operation and
maintenance; overdesign can yield an overly
Modern canal design must thoroughly consider expensive or complex system. Using automation
operation and control. Unfortunately, designing an does not necessarily result in a “gold plated”
automated canal system is not a “cookbook” project. On the other hand, the best design may
process-no design code exists. However, this not incorporate a large, complex control system. A
chapter presents procedures and criteria that simpler system often works better. The minimum
should help designers make good engineering system which satisfies users’ requirements is
decisions. preferable to an overdesigned system.
5-2. Operation, Control, and Automation Automated canal system design is a relatively new
science and, consequently, the best procedure is
Historically, canal operation and control has been not yet defined clearly. A natural starting point is to
an afterthought to canal design. The physical organize the design process so that a designer can
features of a canal system were designed for the step through the process in a logical and efficient
maximum steady-state flow, incorporating freeboard order. The axiom “first things first” applies to the
and wasteways to prevent damage during design process. The wrong order of design will
emergency conditions. Although operating criteria result in a poor design which, in turn, will lead to
were provided, operation was the responsibility of poor canal operations.
operators, not designers. Conventional operation
evolved as a practical method of satisfying irrigation In the early stages of project design, the choices
needs within traditional canal system limitations. appear to be unlimited. A process of elimination is
Local manual control was the only control method needed to reduce alternatives to a workable
available. number. Elimination is easier in the beginning,
when some alternatives are obviously better than
Design of automated canals should follow a others. One of the designer’s first jobs is to identify
nontraditional approach to optimize the potential known or “given” parameters. Design parameters
advantages of automatic control. The realm of that are not subject to variation can be separated
possibilities for operating canals has been greatly from variables to limit the number of choices as
expanded by recent advancements in monitoring early in the process as possible.
and control systems. Designers must now consider
many more operation alternatives before designing Successive elimination of alternatives should
the structural features of a canal system. If a canal proceed as far as possible based on experience
is designed based on steady-state assumptions and and judgment. Decisions will require a more
conventional operations, the best operation detailed level of study as the process of elimination
alternatives may be eliminated by structural proceeds. Selection of the best alternative will be
constraints. Canal design should be based on based on engineering and economic factors. To
realistic operations that include the types of flow evaluate these factors, studies and preliminary
changes and delivery flexibility that are feasible in a
modern canal.
5-2
Designof AutomatedCanalSystems
designs must be prepared. A workable number of An automatic control system is designed near the
alternatives should be proposed for detailed end of the process even though approximate
analysis. capabilities of the control system must be
anticipated earlier. Control software often remains
Typically, designing a new automated canal is an uncompleted until after the canal is put into service;
iterative process; a designer may need to only then will operators know the exact project
repeatedly loop back to earlier steps to evaluate needs and water use patterns. The most
design alternatives or changes. For example, a successful existing automated canal projects have
preliminary canal design must be proposed before control details that were developed dynamically
canal operations can be studied. Results of (over a period of time) based on actual project
operation studies may suggest changes to canal operations.
layout, capacity, freeboard, or control structures.
Designers must then loop back to create a new The following pages discuss the design process,
design before proceeding. The design process including all of the various design tasks in the
includes successive stages of trial and evaluation recommended order of completion.
before selection of a final design.
5-3
Canal Systems Automation Manual
greatly affects operational flexibility; increasing b. Control structures .-The location and type of
canal cross-sectional area increases capability to control structures in a canal system have a major
make flow changes. impact on operations. The distance between
control structures such as check structures and
When a flow change occurs, acceleration of the pumping plants affects the canal system’s response
water causes depth fluctuations. The larger the to flow changes. Large distances require slow flow
canal, the smaller these fluctuations will be. A changes to avoid rapid depth fluctuations. With
larger canal will also provide additional volume in some methods of operation, structure spacing has
which to store extra water. This in-channel storage a significant effect on the volume of water required
provides a buffer for absorbing flow changes to change to a new water surface profile, and,
because flow imbalances can be accommodated by therefore, on the time required to achieve a new
adding or draining water from storage. flow rate (see chapter 2).
To illustrate the effects of channel size on water Pumps create additional operational problems
level fluctuations, consider the following example which must be accommodated during design.
canal: Without variable-speed motor controllers, pumps
can be controlled only in large steps of flow
Bottom width = 6 meters (m) (20 feet [ft]) change. In canal systems with pumps, supply will
Side slope = 2:l (horizontal to vertical) seldom match demand exactly. Some type of
Manning’s n = 0.013 regulatory storage is needed to absorb the flow
Bottom slope = 0.0001 mismatches. Additionally, pump power failures and
Pool length = 2,500 m (8,200 ft) limitations on the pump on-off cycling frequency
Initial flow = 18.4 cubic meters per can have a major impact on canal operations.
second (m”/s) (650 cubic feet per Advanced control system capabilities are more
second [ft3/s]) important where pumps are involved.
Normal depth = 2 m (6.5 ft)
Initial depth = 2 m (6.5 ft) c. Regulatory storage.-Storage capacity outside of
the conveyance channel can create a buffer which
If the flow at the downstream end of this canal pool insulates canal operations on one side of the
is suddenly reduced by 2.8 m3/s (100 fi?‘/s), the storage facility from the other side. Storage
accompanying sudden depth increase will equal facilities can be in line with the canal or off-channel.
about 70 millimeters (mm) (0.23 ft). If pool inflow Commonly, reservoirs, ponds, and tanks are used
remains at the initial flow for 1 hour after this to provide this storage. These facilities allow a
outflow reduction, the average pool water level will mismatch in the flow to exist without wasting water
rise 320 mm (1.05 ft). or changing the depth in the canal. Flow changes
which occur upstream from the storage facility do
If the bottom width is doubled to 12 m (40 ft), not have to be matched on the downstream side,
keeping all other dimensions the same, the same and vice versa. For example, a change in turnout
flow reduction would cause a sudden depth demands can be fed from storage without changing
increase of about 40 mm (0.13 ft), and the 2.8-m3/s inflow to the canal at the headworks.
(lOO-ft3/s) flow mismatch for 1 hour would cause
the average pool level to rise 200 mm (0.66 ft). d. Spill flows.-Canal flow fluctuations can also be
Therefore, increasing channel size reduces both the reduced by spilling, or wasting, water from the
short-term and long-term effects of a flow change. canal. When canal flow rate exceeds demand for
Furthermore, normal depth in the widened channel that water, the excess supply can be spilled
is only 1.4 m (4.7 ft) for the initial flow rate in this through wasteways. This excess may be caused
example. Pool water level could be raised and by an inflow increase such as storm runoff entering
lowered between this normal depth and higher the canal or by outflow changes such as turnout
operating levels, as needed, to use in-channel flow reductions, power failures, pump shutoff, gate
operational storage. closings, or flow obstruction.
Canal automation facilitates the use of in-channel Building a canal with wasteways generally is less
storage. Supervisory control systems in particular expensive than providing supplemental storage, but
allow a canal operation to take advantage of extra wasteways offer fewer advantages. Unlike storage,
storage within the canal prism. wasteways will not supply flow shortages caused by
5-4
Desienof AutomatedCanalSvstems
inflow decreases or outflow increases. Usually, for the canal. Therefore, design data should
spilled water is not recoverable like stored water. include expected delivery flow patterns.
In some canals, wasteways may be designed for
use only during emergency conditions. Final design requires more comprehensive and
detailed studies. When decisions become difficult,
An automated control system will significantly more sophisticated analyses must be used to
reduce spills in most cases. Canals without determine the best alternatives. Automated canal
wasteways need a dependable control system. system design studies are rooted in hydraulic
analysis, ranging from simple steady-state hydraulic
computations to complete unsteady-state analysis.
S-5. Technical Studies Hydraulic analysis can begin as soon as a
preliminary design of the physical system is
To evaluate alternatives accurately, a canal available. Canal layout, dimensions, hydraulic
designer must perform studies. Studies vary from properties, and control structure data are needed
brief investigations using simple deductions to as input to hydraulic studies. Study results may
detailed and highly technical analyses. Regardless show a need to change preliminary physical
of scope or level of sophistication, study results properties to improve system performance or
should provide the designer with specific decrease project cost.
information for making design decisions. Typically,
studies are required at various stages in the design b. Steady-state hydraulic studies.-Hydraulic
process. analysis should begin with steady-state hydraulics.
Steady, gradually varied flow water surface
a. Preliminary studies.-Planning studies determine profiles-or backwater curves-will yield important
the water requirements to predict required flow design information. Ignoring transient effects, a
capacities and delivery point locations. Studies designer can estimate changes in storage volumes
may begin during canal system layout, helping the and water levels for different methods of pool
engineer locate main features such as reservoirs, operation. This estimate, in turn, leads to
pumping plants, branch canals, check structures, approximate times required to perform various
tunnels, siphons, and wasteways. Preliminary operations, assuming accurate control.
design studies also may be required to produce
initial designs for structural features such as canal Generally, steady-state hydraulic analysis will
prism size and shape, lining material, bank height, suffice for selecting a method of operation. For a
and control structure type and location. particular method of operation, steady-state flow
profiles should be calculated to produce data
Preliminary design studies can be quite simple, relating to water volume changes, depth variations,
using experience and deduction to choose between freeboard requirements, delivety water levels, and
alternatives. Preliminary decisions may require preliminary design of wasteways and check
only simple calculations and cost estimates-just structures.
enough detail to eliminate obviously inferior
alternatives. Designers should not lose sight of the Costs of different methods of operation can be
purpose, information needed, or decision to be estimated by looking at full-flow and zero-flow
made. Analysis results are only as good as the steady-state water surface profiles. As shown on
assumptions on which they are based. A study’s figure 5-1, these profiles show required bank height
complexity and accuracy should match the and maximum depth variations.
accuracy of the input data and the accuracy of the
answers required. By predicting maximum possible flow changes for a
specified time span and comparing water surface
Good data collection is essential. Conventional profiles, designers can estimate short-term depth
design data may include information such as variations and select preliminary check structure
topography and required delivery capacities. Data spacing. Section 5-16a discusses check structure
on flow changes are of particular importance for spacing.
automated canals. To develop operating strategies
and design a control system, designers must know c. Unsteady-state hydraulic studies.-Unsteady-
the magnitude and rate of flow changes expected’ state hydraulic studies should be performed as
canal system design progresses. System response
5-5
I
Canal Systems Automation Manual
,-Check 1
TOP of lanai bank, J
Max. wove height
‘-Max. wafer
t level fluctuafiOfl
//// ,,,,,
Drowdown from
cc
Design of Automated Canal Systems
5-7
Canal Systems Automation Manual
Project objectives will affect design decisions a. Service areas .-Land areas to be irrigated should
concerning operation, control, and automation. be mapped, showing location and size of each
Operational concept and method of operation will area. Then, irrigated lands can be grouped into
be chosen by balancing project requirements with service areas that each represent a single delivery
economic constraints. For example, extra expense point from the canal. Other major delivery points,
to design the canal and control system for on- such as municipal turnouts, should be included. A
demand operation may be warranted in a project map of proposed service areas will serve as a
where delivery flexibility is extremely important. guide for selecting the canal alignment. The canal
However, a minimum-cost canal design may be a should follow an efficient path from the supply
better alternative if canal water can be spilled easily source(s) to the service areas.
with little negative consequence.
b. Topography.-The canal network alignment
Future needs of both water users and canal depends on existing topography, especially natural
operators must be thoroughly considered before features that prevent the canal from following
making design decisions. Communication is the constant elevation contours. Rivers, lakes, steep
key to establishing project objectives. The client slopes, and cross-drainage channels can present
must be informed of the consequences and costs of obstacles to the canal alignment. Designers must
different alternatives. Water users will want to estimate the economic and operating conse-
quences of crossing or avoiding topographical
5-a
Design of Automated Canal Systems
features. Land acquisition (right-of-way), design because the proper flow capacity can be
environmental concerns, and proximity to populated achieved with many different combinations of
areas may also influence canal alignment. hydraulic properties. Lining type, head losses,
available head, and cut/fill balance will influence the
C. Delivery capacity.-Initially, a delivery canal’s design choice (section 5-15 presents more details
size can be estimated from the accumulated water on designing the conveyance channel).
needs of service areas. Once individual users’
water allotments have been determined, the total of f. Conveyance structures.-A canal system may
all allotments will yield a total quantity of water that include numerous structures to convey water over,
the project must deliver over the course of a under, around, or through topographical features or
season. Project seasonal storage must be existing infrastructure. Tunnels, bridges, inverted
adequate to supply the total quantity. However, the siphons, drop structures, pumping plants, cross-
maximum water delivery rate during the peak water drainage structures, fish screens and ladders,
use period is more important for predicting delivery energy dissipation structures, and elevated flumes
capacity. are examples of expensive structures sometimes
required in canal systems. Usually, minimizing the
For a given service area, the types of crops to, be need for and cost of these structures will influence
grown and the anticipated application efficiency of canal alignment and design.
water to crops will provide input to the calculation of
required delivery capacity [4,5]. Records of actual g. Control structures.-Preliminary control structure
water use under similar conditions will help locations should be based on terrain, turnout or
estimate water requirements per hectare (or acre) branch canal locations, and location of conveyance
for a project. structures that require flow or depth control.
Generally, these factors will override operational
Capacity requirements for collector or connector considerations. Additional check gate structures
canals will be based on supply flow estimates. should be designed and located to fulfill operational
requirements, as described later in this chapter.
d. Turnouts .-Many canals deliver water through a Initial check structure spacing can be estimated
limited number of major turnouts into secondary from experience or rules of thumb. For example,
canal or pipeline systems. A single turnout may checks might be spaced so that the elevation drop
supply an entire service area or even multiple between checks equals the allowable water level
service areas. Location, type, and capacity of fluctuation from expected flow changes.
major turnouts will help define conveyance channel
requirements. Minor turnouts should be estimated
or lumped together to produce approximate location 5-9. Water Delivery
and capacity information for use in designing the
canal. When designing a structure, engineers work with
maximum load combinations to ensure that the
e. Canal hydraulic design.-Minimum canal size will structure is strong enough to hold all design loads.
be determined from the required maximum In designing a canal, the design loads consist of
conveyance capacity. For delivery systems, a first the maximum anticipated flow changes. The canal
estimate of channel conveyance capacity-or should have the capability to handle all flow
design flow rate-is the aggregate of all turnout changes without exceeding operating criteria.
flows. Inflow requirements will determine the Therefore, designers must establish the most
design flow for collector and connector canals. severe flow changes that can occur early in the
Canal design flow also should consider hydraulic design process.
efficiency, accounting for evaporation and seepage
losses. The term delivery refers to release of water through
turnouts from the canal system to water users.
Using steady flow at the design flow rate, initial Canal system design depends on water delivery
hydraulic design of the canal prism will yield canal characteristics because delivery flows create flow
hydraulic properties such as channel slope, bottom changes in the canal. Water use patterns and
width, side slope, and depth. Numerous factors delivery flexibility help define the flow changes for
must be weighed to select the most economical which a canal system must be designed. The rate
5-9
Canal Systems Automation Manual
and amount of delivery flow change must be For some types of turnouts, delivery flexibility is a
predicted to predict flow changes in the canal requirement. The canal design may have to
system. accommodate uncontrolled situations. For
example, pumped turnouts may shut down upon
a. Water use patterns.-Water users, project power failure. Drain inlets, which can produce
personnel, and designers should predict the uncontrolled inflow to the canal, may also cause
frequency, rate, and duration of water use problems.
throughout the project area. Usually, municipal and
industrial water use patterns are predictable from
historical records, which contain daily, weekly, and 5-10. Operating Criteria
seasonal water use data. Agricultural water use is
more difficult to predict. As stated previously (section 59), a canal must be
designed to accommodate expected flow changes
Maximum agricultural water use during the peak of without exceeding operating criteria. Therefore, the
the irrigation season defines the canal’s maximum next logical step is to establish these criteria.
delivery requirement, but delivery flow frequency Some important operating criteria are discussed in
and duration will depend on crop patterns, water the following subsections.
application methods, soil conditions, weather, and
water users’ habits. The canal will not experience a. Depth fluctuations--Water surface fluctuations
many short-term flow changes if most turnouts should be limited to prevent canal lining damage
maintain constant delivery flow. For example, and undesirable turnout flow changes. General
larger farms may take a constant flow from the fluctuation limits can be used for design purposes,
canal and rotate irrigation among different land although acceptable rate and amount of water level
areas within the farm boundaries. Conversely, variation should be determined for each particular
canal flow may change drastically twice a day if canal through operating experience.
many water users begin taking water at daybreak
and quit taking water at dark. Another cause of Water surface rise usually is limited to 0.15 m
large flow change might be many irrigators growing (6 inches [in]) in any 1 hour to prevent undesirable
the same crop; they may all take water at the same changes in turnout discharge. A faster rate of rise
times during peak crop demand periods and stop may be acceptable for canals without gravity
irrigating at the same time to harvest. turnouts (e.g., all turnout flow goes through canal-
side pumping plants). Experience has shown that
b. Delivery flexibility.-As discussed in chapter 2, the rate of water surface rise during canal filling
delivery flexibility depends largely on the canal should not exceed 0.45 m (18 in) in any 24-hour
system’s delivery concept, i.e., rotation, schedule, period.
or demand. Delivery flow changes-and, therefore,
canal flow changes-vary dramatically among the Water surface drawdown limitations prevent
different delivery concepts. undesirable changes in turnout flows, protect
concrete and membrane lining from damage by
The level of delivery flexibility should be external hydrostatic pressures, and prevent eatth-
established, either project-wide or for individual lined sections from sloughing. The acceptable rate
turnouts. Usually, delivery flexibility depends on of depth reduction varies with the strength and
convenience and economics. Water users benefit weight of the lining material, drainage behind the
from unrestricted delivery. Studies have shown that lining, and shape of the canal prism. For design
increased delivery flexibility can greatly increase the purposes, drawdown should not exceed 0.15 m
value of water to irrigators [6]. In addition to (6 in) in any 1-hour period, 0.30 m (12 in) in any
growing more crops with less water, farmers can 2-hour period, and 0.45 m (18 in) in any 24-hour
enjoy the convenience of irrigating when they want period. Exceptions to these drawdown rates, either
to instead of when the water arrives. However, the increases or decreases, should be based on
price of flexible delivery is increased canal flow specific design conditions for each particular canal.
variation. Water users’ desires for fewer delivery Impervious or poorly drained soil may require
restrictions must be weighed against the system- slower drawdown rates. Conversely, reinforced
wide costs and required capabilities. canal lining or good drainage behind the lining may
allow faster drawdown.
5-l 0
Design of Automated Canal Svstems
b. Spills.-Most canals have wasteways for spilling The power required for motor startup usually
excess water. (The terms spill and waste are constitutes the maximum power requirement.
interchangeable.) Criteria for spilling water can
vary widely. Spills may have few negative Power cost can vary between peak use and off-
consequences in some canals, so criteria for peak use time periods. Therefore, criteria should
spilling water can be quite liberal. Other canal be established for on-peak and off-peak pumping.
systems may not tolerate spilling. These criteria may influence the design of major
structural features such as regulating reservoirs.
Many canals that are supplied by gravity from a Designers need to scrutinize the consequences of
river follow a path more or less parallel to the river, power outages, which can cause extreme
but at a higher elevation. Excess water in the disruptions to operations. Pump shutdown criteria
canal can be returned to the river by way of gravity should address valve closures, check gate
wasteways. Spilling canal water through closures, and wasteway operation. Criteria are also
wasteways may be an acceptable and routine required for unexpected power loss at motorized
procedure during normal canal operation. check gates. That is, should gates automatically
Operators of these canals prefer the term spill to close or maintain their position following a power
waste because little water is actually lost. Excess outage?
flow is sometimes intentionally diverted through
canal headworks to assure an adequate supply to The need for and cost of backup power for
all users. Reasonable criteria in this type of monitoring and control equipment should be
operation might involve limiting spill flows to considered, and criteria should be established to
10 percent of total canal flow. itemize which monitoring and control functions are
to remain operational through loss of primary
Spills are highly undesirable in most new canals. power. Generally, data collection and
Water availability, cost, or environmental concerns communication equipment should be backed up
have resulted in canal systems that are designed with battery power to allow continuous system
for minimal waste. Usually, spills are unacceptable monitoring through power outages. Usually,
when spilled water cannot be recovered and reused backup power for gate motors and pump motors is
or when the water has been pumped. Spilling not feasible for canal systems.
pumped water wastes the energy that was used for
pumping. Sometimes, acceptable wasteway d. Pump operation.-Criteria for pump operation
locations and drainage channels are not available. include minimum run and rest times, number of
Therefore, modern spill criteria may be prohibitive. pump starts per day, size of flow change
increments, and requirements for distribution of run
Canal and control system design must be based on time among pump units. Minimum run times and
appropriate spill criteria. Examples of criteria to be rest times ensure proper cooling of pump motors
established prior to design include: before successive motor starts. Table 5-1 shows
minimum run times for pumps of different sizes
l Quantity of water that can be spilled from (horsepower[hp]) and speeds (revolutions per
the canal (percent of total delivery quantity) minute [r/min]).
l Wasteway locations
. Maximum spill flow rate at each location A pump motor that has been on for the minimum
l Threshold canal water levels and/or flows run time can be restarted if stopped for at least
that trigger spills 5 minutes. If the pump is shut off before the
. Allowable spill frequency minimum run time, an off time equal to three times
l Operating conditions during which spills are the minimum run time is required before restarting
allowed the motor. Motors rated 200 hp and larger should
not average more than eight starts per day.
c. Power limitations.-Power requirements and
restrictions influence the design of control Sequencing and rotation of pump unit operation
structures and equipment. A first criterion is power may be important to avoid uneven wear of different
availability for gate motors, pump motors, pumps within a pumping plant. Pump operation
monitoring, communication, and control hardware. may be scheduled to intentionally promote uneven
Maximum power demand will establish transmission wear so that all pumps will not need maintenance
and onsite electrical equipment design capacities. at the same time. Example criteria might include:
5-11
Canal Systems Automation Manual
Minimum run time 1,800 dmin 1,200 dmin 900 r/min 720 r/min
(minutes) (horsepower) (horsepower) (horsepower) (horsepower)
5 O-50 O-25 - -
. First on, first off-whichever unit has been l Whether automatic control response to
running longest is the first unit to shut off, emergencies should be programmed or if
and the unit that has been off longest is manual override is sufficient
turned on first. . Extent of the alarm system
. Small units cycle before large units-
smaller pumps are always turned on and The response time used for canal design will
off before larger pumps to minimize starts depend on control method. When local manual
of large motors. control is the only method available to move gates
. Scheduled rotation of unit designation- during power outages, a delay of several hours
unit designations (No. 1, No. 2, No. 3, etc.) may exist before ditchriders can reach every control
are periodically changed among the pumps; structure. However, the delay may last only a few
No. 1 is always first on and first off, No. 2 minutes if backup power is available. The
is second, etc. appropriate delay should be used to predict depth
and flow changes during critical operations and to
Criteria for the maximum size of flow change design canal sections, check structures, and
increments will influence pumping plant design. wasteways accordingly.
Large, fixed-speed pumps may be unacceptable
because of the large flow mismatches they cause in f. Hazards.-Operating criteria definition also must
the canal system. Smaller, fixed- or variable-speed take hazards into account. A finite level of risk
pumps may be required if a small flow change always will exist, so the risk and consequences of
increment is needed. failure must be evaluated to establish acceptable
criteria.
e. Response time.-System response time criteria
will influence structural component design and Statistical information can help predict severe
control system capabilities. Severity of emergency natural conditions such as floods. The designs of
conditions and consequences of slow response will drain inlets, cross-drainage structures, canal
determine the length of delay that can be tolerated embankment, bypass weirs, and wasteways
in responding to emergencies. Quick response depend on predicted floodflows. Similarly, control
may be unnecessary in a gravity system with system design should be based on naturally
wasteways but essential for a canal with in-line occurring severe conditions. Designers must weigh
pumping plants and no wasteways. Some frequency of occurrence versus cost to prevent
examples of design decisions based on response damage from such events.
time criteria are:
For example, canal structures might be designed
l Whether local manual control can be used for a 25year flood if the consequences of failure
as a backup to automatic control during are not too severe. Repairing damage every
power outage or if backup power is needed 25 years may be cheaper than preventing the
. Whether operations staff are required on damage. In cities or environmentally sensitive
duty 24 hours a day areas, design might be based on a loo-year flood.
Similarly, a canal control system might be designed
to prevent overtopping the canal lining or exceeding
5-12
Design of Automated Canal Systems
drawdown criteria for an event that occurs several Primarily, designing canal operations involves
times per year but not for events that occur once studying and selecting an operational concept and
every 5 years. Capability should be provided to a method of operation (see chapter 2). Normal,
ensure that a 25year event does not overtop the abnormal, and emergency operating conditions
canal bank. must be considered, including procedures for filling
and draining canals, early and late season
g. Miscellaneous criteria.-Additional operating operations, and, in some cases, winter operations.
criteria are listed below:
513
Canal Systems Automation Manual
Abnormal or emergency operations may operational concept. This combination yields good
necessitate temporary changes in the primary response and recovery characteristics because
concept. For example, an irrigation canal that downstream flow changes cause favorable depth
normally operates with a downstream concept may changes in canal pools (figure 2-19). Recovery is
need to convert to the upstream concept to pass smooth, but slow, for large flow changes because
flood inflows during a rainstorm. In this case, pool volume change is needed to achieve new
temporary inefficient operations are acceptable. steady-state profiles. The constant upstream depth
Some canals change operational concept method should never be used with supply oriented
seasonally to accommodate different summer and operation because an overly expensive canal with
winter needs. For example, a canal which makes poor response and recovery characteristics would
irrigation deliveries during the summer may switch result.
to an upstream concept to deliver water to a
reservoir in winter. The main disadvantage to the constant upstream
depth method of operation is construction of a level
bank canal. With concrete-lined canals, level bank
S-13. Method of Operation construction cost may be prohibitive in some cases.
Unlined or earth-lined canals may minimize the
Canal designers must choose a method of additional cost of a level bank.
operation before designing structural components.
Structure height, freeboard, and pool length all Depending on the lining height, pool length,
depend on the method chosen because different channel slope, and maximum flow rate, constant
methods of operation result in different water upstream depth operation sometimes can be used
surface profiles. Method of operation should be within a conventional prismatic channel. Usually,
compatible with operational concept and should additional freeboard is available at low flows, so a
have appropriate response and recovery level bank operation could be used even though
characteristics. Four methods of pool operation are the canal bank is parallel to the invert. A canal can
described in chapter 2 and depicted on figure 2-14: be designed for constant upstream depth operation
at low flows, allowing on-demand delivery, and for
1. Constant downstream depth conventional operation with scheduled delivery at
2. Constant upstream depth high flows.
3. Constant volume
4. Controlled volume The constant volume method can be applied with
either upstream or downstream operational
The constant downstream depth method is concepts (figure 2-20). Rapid response and
compatible with the upstream (supply oriented) recovery can be achieved using a simultaneous
operational concept. When flow changes originate check gate operating technique. Flow in the entire
at a canal’s upstream end, the canal responds canal system can be changed quickly with excellent
quickly and recovers smoothly to a new steady recovery characteristics. Unlike the previous
state (figure 2-16). Recovery may be slow for a methods, in-channel storage volume need not
large flow change-as pool storage volumes adjust change significantly to achieve a new steady-state
to new steady-state flow profiles-but canal pools flow. Additionally, the constant volume method can
should recover easily. The constant downstream adapt easily to changes in operational concept.
depth method is less compatible with demand
oriented operation. Downstream flow changes For constant volume operation, canal design must
cause unfavorable depth changes in canal pools. provide a raised canal bank at the downstream end
Response and recovery characteristics are poor of each pool to accommodate the level water
because of the overcompensation required. Flow surface at zero flow. Although less expensive than
changes which originate downstream must be a level bank canal, a canal designed for constant
relatively small and gradual to avoid excessive volume operation will be more expensive than a
depth fluctuations. Therefore, the constant conventional canal. (Additional bank and lining is
downstream depth method of operation should be about 25 percent of that required for level bank
paired with the upstream operational concept. operation.) Cost depends on lining type, pool
length, and channel slope.
The constant upstream depth method should be
used with the downstream (demand oriented)
5-l 4
Design of Automated Canal Systems
Simultaneous adjustment at all control structures measured data such as water level, gate position,
requires a supervisory control system. Data or flow velocity. Although pool volume change can
monitoring should include water levels at both ends be calculated from pool inflow and outflow totals,
of each canal pool. Although complex supervisory water level must always be monitored to keep
control software is used on some projects, constant depths and drawdown rates within limits.
volume operation can be implemented effectively
with supervisory manual control. Designers should Another means of accomplishing controlled volume
account for control system cost when choosing a operation involves directly controlling water level
method of operation. If supervisory control is and varying the target water level to create the
planned regardless of the method of operation desired pool volume changes. Different target
selected, additional cost to implement constant water levels are prescribed at different flow rates.
volume operation may be minor. Local controllers can be used if supervisory setpoint
variation or some other form of supervisory override
The controlled volume method can be combined is provided.
effectively with either operational concept. The
volume of water in each canal pool can be The possibilities for implementing controlled volume
managed to satisfy priorities from either upstream operation are practically limitless. Potentially, canal
or downstream, although only one operational operation can be extremely flexible and responsive.
concept should be used at a time (figure 2-21). Presently, however, details must be worked out for
each canal system individually; no “cookbook”
Potentially, controlled volume operation has all the solution exists. Producing comprehensive control
advantages of the other methods of operation. software to accommodate all situations is a
Designers should consider using the controlled substantial design task. The California Aqueduct
volume method to store or spill excess water for [7], Canal de Provence [8], and Central Arizona
canals having limited capacity that are prone to Project [9,10] have implemented controlled volume
sudden flow changes or large flow mismatches. operation successfully using supervisory control.
This method is most applicable for canals with Another controlled volume scheme that uses
complex operational needs such as: variable setpoint local controllers was developed for
the Canal de Cartagena, Spain [l 11.
. Large daily fluctuations in delivery flows
. Demand delivery concept
. Large canal-side pumping plants DESIGN OF STRUCTURAL
. In-line (relift) pumping plants COMPONENTS
. Pumping schedule restraints (e.g., off-peak
w-wing) 5-14. Structural Considerations
. Storm runoff inflows
l No wasteways An automated canal’s structural design differs little
. No off-channel storage from that of a conventional canal. The bulk of the
civil engineering work to design canals and related
Controlled volume operation is the most difficult structures remains virtually unchanged. However,
method to implement. Its complexity makes local designing structural components for an automated
manual control infeasible; a supervisory control canal system requires decisions based on
system and complex software (customized) is knowledge of operations. A designer should
required. Consequently, control system cost will be anticipate different operating conditions-normal,
expensive. abnormal, and emergency-for the method of pool
operation chosen. Many assumptions and rules of
The controlled volume method of operation can be thumb used to design conventionally operated
accomplished in a number of ways. Pool volume canals are not valid or prudent in an automated
can be used as the controlled quantity by canal design. Results of design studies-uniquely
comparing the calculated volume of water in each determined for each canal-should be used to
pool to a target volume. Then, a control algorithm make design decisions.
adjusts inflows and/or outflows to correct pool
volume errors. Target volumes are established at Without attempting to provide structural design
the master station to satisfy system-wide water details, the following sections address design
needs, and actual pool volumes are calculated from
5-15
Canal Systems Automation Manual
considerations which are especially important for known from projected delivery flows and water use
automated canals. Structural components patterns predicted during project definition.
discussed include: Channel slope, size, shape, and friction interrelate
to produce the desired flow capacity, as calculated
. Conveyance channel using the Manning equation or another uniform flow
. Check structures equation [2].
. Turnouts
. Wasteways A canal’s longitudinal slope is influenced by the
. Siphons and drops canal alignment, existing ground surface, available
. Regulating reservoirs head, elevation of delivery points, allowable flow
. Pumping plants velocities, and lining type. Minimal available head
. Cross drainage may require a large canal with a mild slope.
. Water measurement structures Conversely, a smaller canal with a steeper slope
may be preferable when elevation head is
available. Allowable flow velocities will limit
5-15. Conveyance Channel channel slope. Design velocity should remain
within 0.3 to 1 meter per second (m/s) (1 to 3.5 feet
Usually, conveyance channel design begins with per second [ft/s]) for earth- and membrane-lined
selection of a channel cross-section shape and canals and within 0.6 to 1.5 m/s (2 to 5 ft/s) for
lining type. Most canals are trapezoidal, although concrete-lined canals. Higher velocities may be
semicircular and rectangular channels are used in acceptable in concrete canals with special design
some instances. Typical lining materials include considerations.
compacted earth, concrete, masonry, and plastic
membranes. Trapezoidal canal side slope varies Designing the size and shape of a canal section
with lining type and canal size. Typical side slopes combines hydraulic and construction consider-
are lM:l (horizontal:vertical) for concrete lining, 2:l ations. The channel should provide the required
for earth lining, and 2X:1 or 3:l for membrane flow capacity and minimize frictional losses yet be
lining. Side slopes may be steeper in small canals practical and economical to construct and maintain.
and less steep in very large canals. For trapezoidal canals, bottom width can be
estimated using the curves shown on
Canal lining material and method of operation are figure 5-4.
interrelated. Constant upstream depth or controlled
volume operation may be more feasible for earth- To maximize hydraulic efficiency, the channel width
lined canals than for concrete- or membrane-lined to depth ratio should result in a maximum hydraulic
canals. Therefore, lining material and method of radius (area divided by wetted perimeter). The
operation should be selected concurrently, based bottom width to depth ( b/d) ratio for trapezoidal
on the economics of both. canals typically is between 1 and 3 for concrete
lining and between 2 and 8 for earth and
Lining thickness, strength, and underdrains should membrane lining. Figure 5-5 shows minimum
be designed using predicted canal depth recommended b/d ratio versus flow for trapezoidal
fluctuations and ground-water conditions. canals.
Recommended minimum lining thicknesses for
compacted earth lining and for concrete lining are The graphs on figures 5-4 and 5-5 provide initial
shown on figure 5-3. Anticipated rapid depth design estimates, not strict rules to follow.
drawdown or high ground water will require Designers should consider site-specific conditions
stronger lining or underdrainage. Concrete lining and canal operations before finalizing canal
can be thickened or reinforced to provide additional dimensions. For example, a deeper, narrower
strength against hydraulic back pressures. channel may be cheaper where canal right-of-way
Underdrains may be required to reduce ground is expensive to purchase or where the canal is to
water and may also allow more rapid drawdown in be cut below existing ground surface. Conversely,
the canal for all lining types. wide, shallow canals can have operational
advantages. For a given depth change, a wide
Initially, canal hydraulic properties should be canal section will have more storage than a narrow
calculated based on steady, uniform flow section. A wider canal will experience less depth
assumptions. Maximum flow capacity should be fluctuation during a flow change.
5-16
Design of Automated Canal Systems
t7
2.4 c
I I (0
:~ 9c
,
J 6
ff
II III 2
-1
0.45
0.3 I 1
0 0
0 0.6 1.2 1.8 6.0
NORMAL DEPTH (meters)
t I= Vertical thickness of earth lining at invert.
t2 = Horizontol thickness of eorth lining along side slopes.
175
102
78
65
5-17
Canal Systems Automation Manual
1.2
0.6
.l 1 4 10 30 100 500
5
I111111 I CANAI ,A 1 , 1 1
b/d
4
5-18
Design of Automated Canal Systems
Initial estimates for canal lining and bank height change. For example, with constant upstream
using steady flow profiles must take into account depth (level bank) operation, freeboard can be
the selected method of pool operation. Constant minimized. Freeboard may need only
upstream depth and constant volume methods accommodate wind waves because maximum
require additional lining and canal bank to contain steady-state depths occur at zero flow. Conversely,
the horizontal water surface at zero flow. During canals with storm drain inlets or in-line pumping
controlled volume operation, lining and bank height may require a large amount of freeboard. Waves
depends on maximum pool volumes planned. from sudden flow changes should remain within the
lining, so freeboard design requires unsteady-flow
After determining maximum steady-state water analysis.
levels for the given method of operation, the
designer should add freeboard to increase canal Design of Small Canal Structures [l] contains
lining and embankment height. Freeboard allows additional information on channel design, lining
for wind waves, flow change surges, excess friction, materials, drainage, and other design details.
storm runoff entering the canal, sedimentation, and
operation errors. Generally, canal lining freeboard
ranges from 150 mm (6 in) for small canals to 1 m 5-16. Check Structures
(3 ft) or more for large canals. Canal bank
freeboard ranges from 0.35 m (1.2 ft) to more than Canal system operation depends on check
2 m (6 ft). Suggested freeboard for conventionally structures for depth and flow management.
operated canals is shown on figure 5-6. Designers should select check structure type and
location to satisfy system-wide operational needs.
Although the curves on figure 5-6 are valuable as Traditionally, check structures have been used to
an initial freeboard estimate, canal lining and bank regulate the canal water surface upstream from the
heights in’the final design should be based on structure to maintain the water surface elevation
method of operation and anticipated rate of flow required for upstream deliveries. For a new canal,
.3 1 10 100 600
DESIGN FL0 W (ems)
5-19
F
Canal Systems Automation Manual
Figure 5-7.-Water level fluctuation upstream from a drop with and without a check structure.
checks should be designed to enable operation of changing flow without causing large depth
the chosen scheme. Check structures may be fluctuations will be difficult. Depth fluctuation
used to regulate depths, to measure and control between the full flow profile and the zero flow
flow, and to increase and regulate in-channel profile will be proportional to the invert elevation
storage volumes. Chapter 2 discusses the need for drop from one check to the next, as shown on
check structures and their importance to canal figure 5-8.
operations.
5-20
Design of Automated Canal Systems
end. With level bank operation, maximum water As discussed in chapter 2, check structure spacing
level fluctuation would occur at the downstream influences canal system response because of
end. Absolute criteria do not exist for check storage considerations. In most canals, check
structure spacing, but an initial estimate might be spacing has a significant effect on the volume of
achieved by spacing check structures so the water required to change to a new water surface
vertical drop between them equals the maximum profile. Increasing the number of check structures
allowable water level fluctuation: will reduce the volume change needed to establish
a new steady-state flow. Therefore, flow changes
can be accomplished more quickly when check
,A structure spacing is reduced.
S
Unsteady-flow considerations and automatic control
where: response may also affect check spacing. Most
automatic control schemes will work better when
I = pool length (distance between checks) check spacing is reduced, and many schemes will
cfy = maximum allowable water level not work with too few check structures in the canal.
fluctuation
S = pool invert slope Naturally, designers must consider economics when
deciding on check structure spacing. Increasing
The above spacing permits flow change from the number of checks in a canal increases initial
maximum to zero, or vice versa, without exceeding costs and forces canal operators to manage more
the allowable water level fluctuation. This criterion control structures. However, additional check
may be overly conservative for many canals where structures usually improve canal operations and
such a severe flow change never occurs. reduce long-term maintenance costs. Canals with
Therefore, the designer should evaluate the largest too few check structures usually experience
realistic flow change for the time period to which operating problems.
water level fluctuation limits apply and increase
check structure spacing accordingly. b. Automated checks.-Gates must be motorized in
most automated canal check structures. (An
For example, steady-state profiles for 100 percent exception is float- and counterweight-driven gates
and 75 percent of design flow can be calculated if such as the NEYRTEC automatic gates [12].)
the canal shown on figure 5-9 will never experience Either radial gates or vertical slide gates may be
a flow change greater than 25 percent of design used, but radial gates are preferable for automated
flow in any 12-hour period. Check spacing is structures. Slide gates are less expensive initially
acceptable for steady-state conditions when the but have more operation and maintenance
maximum water level difference between these two problems. Radial gates are more durable, pass
profiles is less than the allowable fluctuation for a trash better, can be adjusted more accurately, and
12-hour period. This logic can be applied using perform better in applications that require frequent
any time period for which flow change and water gate movements. Reclamation designs generally
level fluctuation data are known. use radial gates when the design flow exceeds
6 m% (200 e/s), or for gates wider than 1.8 m
(6 ft). Designers should also consider radial gates
Maximum check spocin for the smaller automated checks to attain long-
t- 1 term dependability and cost savings.
5-21
Canal Systems Automation Manual
should have a high duty cycle to accommodate a Check structures often include a combination of
large number of gate movements per day. gates and weirs. Bypass weirs (overflow walls) are
Mechanical equipment is discussed in more detail constructed on either side of the gates to pass
in chapter 10. excess flow in emergencies and to prevent
excessive canal depths. Bypass weir capacity
In designing automated canal systems, engineers equals the canal maximum flow rate in case gates
should consider alternatives for gate operation accidentally close when the canal is flowing full.
during abnormal and emergency conditions. Designers may choose to allow water to overtop
the canal lining in this case but should ensure that
. What should the gates do if communication the canal bank is not overtopped.
or power to the check structure is lost?
. Is backup power required? In conventionally operated canals, bypass weir
. During a power failure, should gates close crest elevation usually is about 60 mm (0.2 ft)
automatically or remain stationary? above the normal water surface elevation on the
upstream side of the check. However, if an
The answers depend on site-specific conditions; alternate method of operation is to be used, bypass
anticipated frequency, duration, and severity of weirs must be raised or eliminated so the canal
abnormal conditions; and manual backup capability. water surface upstream from the check can be
raised above normal depth. Bypass weirs must be
For most canals, local manual control of structures higher than the zero-flow depth at the downstream
during abnormal operating conditions is the most end of the pool when using the constant upstream
feasible backup method. During communication, depth (level bank) and constant volume methods of
power, or equipment failures, operation and operation.
maintenance personnel have to travel to check
sites and manually adjust gates. Although canal As discussed in chapter 2, a check gate can
operations may suffer during local manual control, operate under either free or submerged conditions
the canal system usually can be protected from on the downstream face of the gate. Flow will be
damage until normal operation resumes. Design free when downstream water level is low and
provisions should allow manual gate adjustment at submerged when downstream water level is high.
check structures, either with handwheels or In the transition zone between free and submerged
portable generators to power gate motors. Check flow levels, flow through the gate may be either free
gates should be designed to maintain position upon or submerged. Operating a gate in the transition
power or communication loss to minimize canal zone can have unpredictable results. Avoiding
flow disturbance. transitional gate flow is particularly important under
automatic control. Control instability may develop if
Local manual control cannot always provide flow in the transition zone oscillates between free
satisfactory backup to automatic gate control. More and submerged flow. Check structures should be
extensive backup systems should be designed designed so that gate flow is either always
when travel time to check sites is too long or when submerged or always free during normal operation.
severe consequences can develop rapidly during a
failure of the primary control system. For example,
in a canal with a headworks pumping plant, the S-17. Turnouts
upstream pools can dewater rapidly following power
failure if check gates remain open after the supply The type and location of canal-side turnouts must
pumps shut off. Automatic gate closure should be be compatible with canal system operations.
specified if an operator cannot reach these check Turnout locations should be identified early in the
sites quickly. Backup power to close gates can design process to establish check structure
come from batteries or from pressure stored in a locations and method of pool operation.
hydraulic accumulator. Automatic closure should
be delayed 5 or 10 minutes after primary bower is Gravity turnouts require a relatively constant canal
lost to prevent unnecessary canal flow disturbance water level so turnout flow is steady. Canal flow
during short-term outages. A motor generator set change will cause water level fluctuations that
with automatic start may be desirable at check disturb turnout service, especially if turnouts are
structures that require continuous gate operation located throughout canal pools. Therefore, most
through loss of primary power. canals with gravity turnouts must maintain a steady
5-22
Design of Automated Canal Systems
flow to provide good service to water users. This spilling any excess back to the river. Wasteways
constraint severely limits delivery flexibility, so a are particularly important if uncontrolled inflow such
designer may wish to change the type, number, or as rainfall runoff enters the canal by way of drain
location of turnouts. For example, delivery flows inlets.
can be lumped together at a single turnout instead
of at many individual turnouts from the main canal. a. Determining need.-Wasteways may not always
The single turnout-to serve a secondary be needed or desirable in new canals. Wasteways
distribution system (lateral)-should be located can be eliminated from the design through good
where pool water level remains fairly constant. control over water in a canal and effective use of
in-channel storage. As with most engineering
Pipeline distribution systems provide superior design, the designer should weigh safety and
delivery flexibility for water users. Either gravity economics. The water’s value will have a direct
flow or canal-side pumps can supply pipe laterals, impact on the decision to either spill or store
and delivery flow can be controlled at each water excess water. In systems which pump water from
user’s valve. Canal water level fluctuations may a source to higher elevations, the cost of the power
have little or no effect on delivery flows. Therefore, used to pump water will be sacrificed whenever
pipe delivery can tolerate head variation in the main water is wasted. A good location to spill water
canal without affecting service. Pipe turnouts can cannot always be found.
be located anywhere along the canal as long as a
minimum canal water level is maintained to supply The need for wasteways depends on canal size
the turnout. and cross-drainage design. Wasteways may not be
needed if cross-drainage structures are provided to
The best turnout locations depend on the method prevent storm runoff from entering the canal or if
of pool .operation. With the constant downstream the canal prism is enlarged to contain all inflows.
depth method of operation, gravity turnouts should Alternative methods to prevent damage from storm
be located near the downstream end of canal runoff should be studied for economic feasibility.
pools-where water depth is maximum and When designing an automated canal, one should
relatively constant-to avoid water delivery explore operation and control alternatives before
problems caused by low or fluctuating canal water deciding on wasteways. The type, size, and
depths. With the constant upstream depth method, location of wasteways depend on canal operations.
turnouts can be located anywhere within a pool
because the canal water depth should always at b. Selecting wasteway type.-Wasteways often
least equal the design flow normal depth. include a gravity overflow structure. Typically, the
However, turnouts should be located near the overflow crest is slightly above the maximum
upstream ends of canal pools if a constant head is normal operating water level, so water will be
required. spilled automatically whenever the canal water level
exceeds the overflow crest level. When properly
Constant flow turnout structures-developed in designed, overflow wasteways provide excellent
France-are gravity turnouts that maintain relatively protection against excessive water depths in the
constant delivery flow through a limited range of canal. However, they may prevent using the upper
upstream head variation [12]. portion of the canal prism for storage. Uncontrolled
overflow wasteways should be avoided when the
canal is being designed for a method of operation
5-18. Wasteways that intentionally creates greater than normal water
levels.
In conventional canal design, wasteways provide
important protection from disasters and sometimes Gated wasteways impose less operational
are useful to release normal excess flows. constraint because outflow from the canal is
Wasteways can be quite practical in canals where controllable. Spilling through gates is less depth
waste flows can easily return to a river through dependent than spilling through uncontrolled
natural drainage channels. These canal systems overflow wasteways. Wasteway gates can remain
can be simple to operate by supplying a large closed to allow intentionally high water levels and
steady flow through the canal headworks and open to pass high flows when spilling is necessary.
5-23
Canal Systems Automation Manual
Wasteway gates also can be used to sluice critical when using other methods of pool operation.
sediment and other submerged debris from the The combination of location and crest elevation
canal if the gate sill is low enough. However, gated must be designed to protect the canal without
wasteways do not provide the level of protection spilling water during normal operations.
provided by overflow wasteways because a gate
must open to protect the canal. Designers must A designer should combine the above priorities to
evaluate risk of failure and assure the wasteway find optimum wasteway locations throughout a
can always do its job when needed. Redundant canal system. The canal may need to be enlarged
control equipment, backup power, and alarms can to carry excess flow to a suitable wasteway location
provide additional safety. Local manual control when canal features do not coincide with natural
may be necessary during emergencies. terrain.
A canal’s structural features may influence One design alternative involves reinforcing the
wasteway location. Wasteways often are located canal lining upstream from siphons or drops so the
just upstream from transitions to a smaller canal canal can withstand large depth fluctuations. This
size to prevent exceeding the capacity of the option may be feasible for a short pool.
smaller channel downstream. Wasteways also
might be placed just upstream from pumping plants Siphons with check inlets may present control
or powerplants where a power failure or load complications because the check’s downstream
rejection can suddenly decrease flow. water level can be unpredictable. Water level
between the check gate(s) and siphon entrance will
Method of pool operation will determine the best fluctuate more than usual and may not maintain
wasteway location within a canal pool. Generally, submerged gate flow. Siphons are designed to
wasteways should be located at the water surface convey full flow with a prescribed head loss.
pivot point for best operation. Wasteways should Usually, the siphon entrance will be submerged at
be located at the downstream ends of pools when full flow, resulting in submerged gate flow.
using the constant downstream depth method of However, smaller head loss through the siphon at
operation. Wasteway location within a pool is less low flows may create free gate flow and
5-24
Design of Automated Canal Systems
supercritical flow entering the siphon, preventing 2. Separation of two canal system parts with
accurate prediction of siphon head loss, water level different operating periods
on the downstream side of gates, and check 3. Separation by operation priority (supply
structure flow. Control at the check structure will oriented or demand oriented)
be erratic when gate flow fluctuates between free 4. Buffer between steady flow on one side
and submerged conditions. Potential problems and unsteady flow on the other
include excessive gate movements and instability. 5. Separation between a gravity system and a
pumped system
Designers should analyze hydraulics at various flow 6. Automatic control regulation
rates when designing a check inlet structure.
Changes to structure design should be considered The operating period for a canal’s source of supply
if control problems are envisioned. For example, sometimes will differ from the operating period for
the check invert and siphon inlet can be lowered to deliveries. For example, many pumping plants in
increase submergence. Brazil must shut down for 4 hours in the evening
during peak power demand. Canal systems
supplied by pumps have a 20-hour supply period
5-20. Regulating Reservoirs and a 24-hour delivery period, so an intermediate
reservoir is required to supply deliveries while the
The benefits of automation will be limited in a canal pumps are off.
that lacks operational storage. Regulating
reservoirs provide additional water storage in canal As another example, farmers may want to irrigate
systems to improve operations. Reservoir storage only during daylight-perhaps 16 hours a day-
can supply water to points downstream or provide a but supply flow is constant 24 hours a day.
place to put excess water from upstream. The term With an intermediate reservoir, as shown on
reregulating reservoir sometimes is used to figure 5-10, maximum supply flow will be only two-
describe a reservoir located in the middle of a thirds of the maximum delivery flow rate, allowing
canal system because it regulates canal flow for a smaller, less expensive conveyance structures
second time (after primary regulation at the upstream from the reservoir.
headworks).
Irrigation canals are usually demand oriented;
Dictionaries define regulate as: i.e., operated to satisfy downstream delivery needs.
However, controlling a long canal based on
to bring order, method, or uniformity to; to fix or downstream conditions is difficult, requires a flexible
adjust the time, amount, degree, or rate of. flow source, and may create undesirable depth and
flow fluctuations throughout the canal length.
Consistent with these definitions, a regulating Supply oriented canals are much easier to operate
reservoir brings order and uniformity to canal because excess flows can be passed downstream.
operations. Reservoirs simplify and stabilize Combining a supply oriented segment with a
operations by adjusting the time, amount, and rate demand oriented segment requires a regulating
of flow changes in the canal. The main purpose of reservoir to separate the two segments. Canal
a regulating reservoir is to provide hydraulic inflow can be passed through the upstream
separation between two parts of a system. segment to the reservoir using supply oriented
Reservoir storage is used to accommodate flow operation, and outflow from the reservoir can be
mismatches between the canal segment upstream based on downstream demand, as shown on
from the reservoir and the canal downstream from figure 5-11. Reservoir storage will absorb flow
the reservoir. mismatches between the two segments.
Several reasons exist for flow mismatches. The The preceding examples involve situations where
following are specific applications of reservoirs in flow is relatively steady on one side of a regulating
canal systems: reservoir and unsteady on the other side. The
reservoir insulates one segment from flow changes
1. Supplemental storage where downstream in the other segment. Canals having fluctuating
demand may exceed upstream supply flow require complex control methods, but simple
capacity
5-25
Canal Systems Automation Manual
Connector System
Pumping commonly causes flow changes and
Operating period
system flow mismatches. Pumping plants with
Desi’gn Q = 67% Q,,,,, fixed speed pumps can only produce flow changes
in increments equal to pump unit capacity, so a
balanced flow condition (inflow = outflow) rarely
exists. Regulating reservoirs often are used
Minimum active
storage volum =
adjacent to pumping plants to offset flow
mismatches. In addition, a reservoir provides a
i 67)iQ,,,)i8 hours)
convenient and effective location to measure water
level for automatic pumping plant control. Pumps
are turned on and off to automatically maintain the
Distribution System reservoir level within a prescribed range.
Operating period
= 16 hours Regulating reservoir design should be based on
Design Q = Q,,, site conditions and anticipated canal system
operations. Reservoir type, size, and structural
design will vary with different applications.
5-26
Design of Automated Canal Svstems
ggqi?+I. &
In-line Reservoir
Off-line reservoirs are located alongside the canal example is a forebay reservoir for a canal-side
so that water can be turned out from the canal into pumping plant. The forebay reservoir can be
the reservoir, or from the reservoir back into the supplied from a canal turnout with less disruption to
canal, as shown on figure 5-13. Water usually canal operations from pump starts and stops.
flows by gravity in one direction and is pumped in
the other direction. An off-line reservoir can be b. Sizing.-The required size of a regulating
used for pumped storage with sufficient flow and reservoir is based on storage volume and depth
when enough elevation difference exists between fluctuation limits. The active or working storage
the reservoir and the canal. Pump-turbine units volume in the reservoir should equal or exceed the
pump water in one direction and generate power maximum canal flow mismatch times the duration of
(usually to meet peak power demands) when water the mismatch:
flows in the opposite direction.
INFLOW
SOURCE y-1 --L
Off-line Resevoir
!5-27
Canal Systems Automation Manual
or drawdown that exceeds the maximum allowable Operations may be unstable if the volume between
drawdown rate. Unless space is limited, larger control points is too small; the water level may
surface area usually is more economical than high “hunt” up and down while pumps cycle on and off.
embankments. Additionally, hydraulic head may Large pumps require minimum run and rest times
not be available for a large range of water levels. to prevent motor overheating. Therefore, sufficient
reservoir volume must be provided between on and
When designing a storage reservoir or tank, surface off control levels to satisfy minimum pump
area versus height decisions may affect the operating times. Regulating reservoirs must be
pumping head required, power consumption, and sized to meet these criteria.
pump efficiency. Also, the range of water level
fluctuations will influence the design of gravity
turnouts, wasteways, and the pumping plant 5-21. Pumping Plants
structure.
Many canal systems include pumping plants, as
Reservoirs in which different water levels are used shown on figure 5-14. Pumping plants can be
to control pumps, turbines, or gates require a located in-line with the canal (figure 5-14a)or can
minimum elevation difference between control function as a turnout from the canal (figure 5-14b).
levels. The minimum vertical distance between In either case, pumping plants usually will create
control levels should be about 0.15 to 0.3 m (0.5 to the largest sudden flow changes in a canal system.
1 .o ft). Some pumps have variable speed motors, which
allow gradual flow change, but most pumps start
Minimum distance between control levels is and stop flow in discrete increments. Therefore,
affected by depth measurement precision, control even normal pump operations cause sudden flow
deadbands, wind wave action, and transient waves. changes. Flow mismatches are typical because
Control points must be at least twice as far apart as canal supply and demand flows seldom match
the depth measurement accuracy. Wind waves will pump flows exactly. Power failures are a major
be important in large reservoirs; control levels must concern in canal systems that include pumps.
be spaced far enough apart to prevent wind waves Sudden flow rejection from power failure is the
from causing false pump starts and stops. most severe operating condition.
Hydraulic transients will be more important in small
reservoirs or tanks. If control levels are too close Canal design must accommodate all of the
together, transient waves from a pump starting or operating conditions caused by pumps. Hydraulic
stopping may trigger an immediate and undesirable transient analysis should be used to predict
operation of another pump. This problem can be maximum wave heights, and lining and
avoided with built-in time delays or control embankment freeboard should be designed
deadbands. Hydraulic transient analysis may be accordingly. Increased lining height, an enlarged
necessary to determine reservoir size and control canal section, or a forebay reservoir may be
levels. warranted upstream from a pumping plant.
Storage volume between successive control points Canal dewatering may be a concern downstream
is also important. Volume between control levels from an in-line pumping plant. Whether through
should be a function of reservoir surface area and structural features or control system capabilities,
the elevation between levels: the design should include methods to prevent or
withstand channel dewatering. In an automated
canal, check structures downstream from a
AV > AY x A 5.3 pumping plant should be able to close gates quickly
following power failure. Backup power, pressure
where: accumulators, and clutch mechanisms can be
designed to close gates after loss of primary power,
dV = storage volume between successive but local manual control may be adequate backup if
control levels operations personnel can reach the site quickly.
zlY = elevation difference between levels
A = reservoir surface area Limits on the frequency of pump starts and
stops-because of minimum run time and rest time
criteria-may impact the design of a canal system’s
5-28
Design of Automated Canal Systems
a.
b.
5-29
Canal Svstems Automation Manual
5-30
Design of Automated Canal Systems
5-31
Canal Systems Automation Manual
5-32
Design of Automated Canal Systems
Several devices to “measure” canal flow are calculate a value for weir discharge. Disad-
discussed briefly in the following paragraphs. More vantages include high head loss and potential
detailed information can be found in references 1, problems with trash.
13, 14, 15, and 16.
The Parshall flume is a specially shaped open
Weirs are simple and reliable flow measurement channel structure designed to measure flow, as
structures consisting of an overflow crest or notch. shown on figure 5-20. Water enters the flume
Weirs can have rectangular, trapezoidal, or through a converging section into a narrow,
triangular openings. Preferably, weirs should be downward-sloping throat and then exits through an
used where sufficient head is available for free flow upward-sloping diverging section. The flume’s
over theiweir crest. Then, weir flow can be constricted throat produces a differential head that
computed as a function of upstream water level and can be related to flow rate.
weir structure dimensions. The basic equation for
free weir flow is:
Q = C L H312 5.4
where:
Q = discharge
C = a weir flow coefficient (dependent on
type of weir)
L = weir crest length (sometimes adjusted
for end contraction)
H = head on weir crest (upstream water
level minus crest level) t-M-+-----B v--G1
For example, a Cipolletti weir has a trapezoidal
opening such that the sloping sides of the opening
negate flow area contraction from the weir sides.
The equation to calculate flow through a Cipolletti
weir is:
Sectional View
Q = 3.367 L H” 5.5
Advantages to using weirs for flow measurement Advantages of Parshall flumes include the
include ease of construction, low cost, simple flow following:
calculation, and minimal input data required. For
automatic flow monitoring, data from a water level . Accurate and reliable flow measurement
sensor can be entered into the above formula to (typically within 2 to 5 percent accuracy for
free flow, less accurate for submerged flow)
5-33
Canal Systems Automation Manual
l Small head loss that has advantages over Parshall flumes and
l Operating range from free flow to a high weirs. As shown on figure 5-21, the ramp flume is
degree of submergence constructed in the canal prism and consists of a 3:l
l Self-cleaning approach ramp to a horizontal broad crest, followed
l Unaffected by velocity of approach, which by a vertical drop to the canal invert. Discharge
is often a problem with weirs and orifices rate is calculated from a single water level
. Easy maintenance measured just upstream from the approach ramp.
l Tamper-proof
l Commercial availability and easy Ramp flumes can predict discharge rate accurately
installation of prefabricated flumes through a wide range of submergence. Depending
on calibration and depth measurement accuracy,
Disadvantages include: flow can be calculated within 1 to 5 percent
accuracy [17]. Ramp flumes with a vertical drop at
. Expensive construction of large flumes the end of the crest have a submergence depth
. Field calibration required for large flumes limit of 85 percent. (Submergence is H, on
. High degree of precision required for figure 5-21.) Submergence as high as 92 percent
construction is acceptable with a 6:l downward-sloping ramp at
l Cannot be located close to other structures the end of the crest. These high submergence
that can disturb uniform inflow to the limits allow ramp flumes to operate with low head
Parshall flume loss.
l Settling of flumes over time, which requires
recalibration Unlike Parshall flumes, ramp flumes do not require
precise construction for accurate flow
Calculating Parshall flume flow is a little more measurement. Ramp flumes can be computer
complicated than weir flow but easily programmed calibrated using dimensions measured after
into an automated system. For example, free flow construction. A computer program has been
through flumes with throats from 0.3 to 2.4 m (1 to developed to calibrate ramp flumes and, after
8 ft) wide follows the equation: calibration, generate rating curve data (head versus
flow) [14]. Another advantage to ramp flumes is
the relative ease with which they can be installed in
5.6 existing canals. One disadvantage is the potential
for problems with sediment buildup.
5-34
Designof AutomatedCanalSystems
The general form of the orifice equation is: The constant-head orifice (CHO) structure uses
submerged orifice flow calculation to both regulate
and measure flow. Usually used for turnout
Q = C, G, B &@i 5.7 structures, CHO’s use two gates in series. The first
gate regulates or measures flow, and the second
gate is used to maintain a constant head across the
first gate [l].
where:
Canal radial gate check structures can be
Q = discharge calibrated to estimate flow within 2 to 5 percent
Cd = coefficient of discharge accuracy. Discharge algorithms were developed for
G, = gate opening height radial gates through an extensive Reclamation
B = orifice (gate) width research program [18]. A computer program uses
g = gravitational constant these algorithms to generate rating tables or
h = differential head across the orifice calculate gate flow for combinations of upstream
(upstream water level minus and downstream depths and gate positions.
downstream water level) Additionally, flow or gate position can be calculated
in a real-time mode as a flow (C?)controller.
For a square-edged orifice, approximate results
may be obtained using C, equals 0.6. However, Using check structures to measure and control
C,, must be calibrated as a function of water levels discharge has many advantages. Control already
and gate opening to improve accuracy. Also, the requires check structures, so using them to
definition of the head term, h, often is modified to measure flow saves the additional expense and
avoid problems when differential head is very small. head losses of separate flow measurement
The orifice equation can be applied to check structures. Frequently, depth and gate position
structures or turnouts with vertical slide gates with
moderate calibration.
5-35
Canal Systems Automation Manual
monitoring is required for other reasons, so using In canal application, velocity measurement is only
these data to calculate flow makes sense. valuable if velocity can be converted to flow
accurately. Flow calculations require accurate
Local flow control can be a powerful addition to knowledge of flow, water level, and channel cross-
supervisory control systems, simplifying centralized section dimensions. Water level measurement
decisions and calculation. Operators can think in accuracy and changing channel dimensions
terms of flow, which facilitates balancing and (e.g., caused by sediment deposition) will affect
adjusting of system flows to match total turnout flow calculation accuracy. Therefore, flow
demands. Supervisory control software can adjust measurement accuracy may be significantly less
canal pool volumes by incrementing structure flows, than velocity measurement accuracy.
leaving individual gate adjustment to the local flow
controllers. Accurate velocity measurement requires initial
calibration and periodic adjustment. Velocity
The radial gate flow algorithms’ complexity is the measurement errors are difficult to detect because
main disadvantage of check structure flow velocity cannot be checked with observations of
measurement. The logic is much more complicated physical parameters such as water level and gate
than most local control algorithms. Despite this positions.
complexity, real-time application is quite feasible
using computers. AVM accuracy depends on equipment limitations,
acoustic-path length and angle measurements,
Flow rate in canals and pipes can be calculated water quality, and the stability of the mean velocity
using current meters and acoustic velocity to acoustic path velocity relationship. Typical
meters. Current meters have a propeller or a cup velocity error in AVM systems ranges from about
wheel that rotates to indicate flow velocity at a *l millimeter per second (kO.003 ft/s) for a 200-m
single point. Different types of current meters and (700-ft) path length to *lo millimeters per second
their use are described in the Water Measurement (kO.03 ft/s) for a 20-m (70-ft) path length.
Manual [13]. Acoustic velocity meters (AVM’s) yield
average flow velocity through a section by Designers must evaluate system-wide flow
measuring travel time of a sonic signal, which measurement requirements-considering the total
travels faster downstream than upstream [19,20]. control scheme-to design the type of
When combined with a stage-area relationship, measurement structures, number and location of
measured velocities are used to determine a measurement sites, and accuracy required.
discharge. AVM’s also can be used to measure Nontechnical considerations may impact decisions.
depth. For example, some States require the use of
Parshall flumes for water rights accounting even
Current meters and AVM’s should be located in though other methods of flow measurement may
cross sections of stable flow and uniform velocity have technical and economic advantages.
distribution. Velocity measurement should take
place far away from checks, turnouts, or other
structures that can disturb the uniform flow pattern.
Both types of meters operate without head loss,
and current meters can be used as a portable flow
measurement tool.
5-36
Design of Automated Canal Svstems
BIBLIOGRAPHY
[1] Aisenbrey, A.J., R.B. Hayes, H.J. Warren, [9] Becker, L., A.L. Graves, and W.W-G. Yeh,
D.L. Winsett, and R.B. Young, Design of “Central Arizona Project Operation,”
Small Canal Structures, Bureau of Proceedings of the International
Reclamation, rev. reprint, 435 pp., Denver, Symposium on Rainfall-Runoff Modeling,
Colorado, 1978. Water Resources Publications, Littleton,
Colorado, 1981.
[2] Chow, V.T., Open-Channel Hydraulics,
McGraw-Hill Book Company, New York, [lo] Gooch, R.S., and A.L. Graves, “Central
1959. Arizona Project Supervisory Control
System,” Proceedings of Computerized
[3] Chaudhry, M.H., Applied Hydraulic Transients, Decision Support Systems for Water
Van Nostrand Reinhold Company, Resource Managers: Case Studies of
New York, 1987. Large Systems, ASCE Spring Convention,
Denver, Colorado, 1985.
[4] Savage, M.T., and E.L. Johns, “U.S. Bureau of
Reclamation: How irrigation Projects are [11] Rogers, D.C., “Automation of the Canal
Sized,” Irrigation Systems for the 21st de Cartagena, Spain,” Water and
Century, ASCE, edited by L.G. James and Wastewater International, vol. 5, Issue 2,
M.J. English, pp. 201-208, New York, pp. 35-40, Houston, Texas, April 1990.
1987.
[12] Goussard, J., “NEYRTEC Automatic
[5] Tod, l.c., D W. Henderson, and J.J. DeVries, Equipment for Irrigation Canals,” Planning,
“Considerations for Sizing Water Delivery Operation, Rehabilitation, and Automation
Systems,” irrigation Systems for the 27st of Irrigation Water Delivery Systems, ASCE,
Century, ASCE, edited by L.G. James and Edited by D.D. Zimbelman, pp. 121-132,
M.J. English, pp. 217-224, New York, New York, 1987.
1987.
[I 31 Bureau of Reclamation, Water Measurement
[6] Merriam, J.L., “Six Seasons of Demand Manual, 327 pp., Denver, Colorado, 1984.
Schedule Irrigation for Improved Water
Management in Sri Lanka,” a paper [14] Replogle, J.A., “Compensating for
presented at the USCID Tenth Conference, Construction Errors in Critical-flow Flumes
Reno, Nevada, November 1985. and Broad-crested Weirs,” National Bureau
of Standards Special Publication 484,
[7] Dewey, H.G., and W.B. Madsen, “Flow Control Proceedings of the Symposium on Flow in
and Transients in the California Aqueduct,” Open Channels and Closed Conduits,
Journal of the Irrigation and Drainage pp. 201-218, Gaithersburg, Maryland,
Division, ASCE, vol. 102, No. IR3, October 1977.
pp. 335-348, September 1976.
[15] Replogle, J.A., “Flumes and Broadcrested
[8] Rogier, D., C. Coeuret, and J. Bremond, Weirs Mathematical Modeling and
“Dynamic Regulation on the Canal Laboratory Ratings,” Flow Measurement of
de Provence,” Planning, Operation, Fluids, H.H. Dijstelbergen, E.A. Spencer
Rehabilitation, and Automation of Irrigation (eds.), North-Holland Publishing Company,
Water Delivery Systems, ASCE, edited by 1978.
D.D. Zimbelman, pp. 180-200, New York,
1987.
5-37
Canal Systems Automation Manual
[16] Bos, M.G., J.A. Replogle, and [I91 Laenen, A., “Acoustic Velocity Meter
A.J. Clemmens, Flow Measuring Flumes for Systems,” U.S. Geological Survey
Open Channel Systems, John Wiley and Techniques of Water Resources
Sons, Inc., New York, 1984. Investigations, book 3, chapter A17, 38 pp~
[17] Dodge, R.A., “Ramp Flume Model Study- [20] Laenen, A., and R.E. Curtis, “Accuracy of
Progress Summary,” Bureau of Acoustic Velocity Metering Systems for
Reclamation Report No. GR-82-14, 29 pp., Measurement of Low Velocity in Open
Denver, Colorado, March 1983. Channels,” U.S. Geological Survey, Water
Resources Investigations Repoti 89-4090,
[18] Buyalski, C.P., “Discharge Algorithms for 15 pp., 1989.
Canal Radial Gates,” Bureau of
Reclamation Repori No. REC-ERC-83-9,
232 pp., Denver, Colorado, December
1983.
5-38
CHAPTER 6
a--e-v-. -w--- AND
SlM U LA’I’WN ANALYSIS
Figure 6-1.-View of hydraulic laboratory canal radial gate model showing manometer
and stilling well boards used to measure water pressure at selected points.
6-2
Physical analogs have been used to develop Electrical to hydraulic analogs can be formulated in
control schemes and to obtain data to verify several ways. One method was proposed by
mathematical analogs. For example, one analog of Braunagel [6], in which hydraulic quantities in the
this type was constructed in the Bureau of equation of motion are simulated by electrical
Reclamation’s (Reclamation) Hydraulics Laboratory quantities. These quantities are shown in the
as shown on figures 6-2 and 6-3 [4]. This model following table.
consisted of three pools having a total length of
335 meters (m) (1,100 feet [ft]). The canal prism
was rectangular in cross section with a bottom Electrical analog quantities
width of 360 millimeters (mm) (14 inches [in]) and a
maximum flow depth of 360 mm (14 in). The Hydraulic quantity Electrical quantity
maximum flow rate in the facility was 0.03 cubic Force acting on the cross- Voltage
meter per second (m%) (1 cubic foot per second sectional area of the canal
[ft3/s]). Four motorized radial gates were installed prism
to control water levels within the pools. Numerous
types of controllers could be investigated by routing Water velocity Current
all electrical leads into one control console
Mass of the water prism Inductance
(figure 6-3). This type of facility has the advantage
that surges in the canal and interaction between Water storage capacity of Capacitance
pools could be simulated. the canal pool
Water motion in a canal prism also has been Force due to wall shear per Resistance
simulated by flow into and out of a tank as shown unit of average velocity
on figure 6-4 [5]. The purpose of this study was to (equivalent to energy loss)
simulate water level fluctuations in a canal that had
Acceleration Time rate of
been predicted using a numerical analog. In
change of
essence, this procedure simulates full-scale
current
operation. Usually, operation of this type of analog
is termed hybrid operation because the input Total volume of water Electrical charge
variables to the physical analog are determined displaced
from a numerical analog.
The main limitation of physical analogs is the Figure 6-5 is an example electrical analog for a
difficulty encountered in modeling an entire canal canal reach consisting of:
system. And because each canal system is
unique, a new physical model is required for each . A reservoir
canal system. l Three pools
l A gated turnout
l A pumped turnout
6-3. Electrical Analog l A downstream weir
An electrical analog uses components such as Electrical analogs can be used to investigate the
resistors, capacitors, inductors, transformers, etc., effect of variations in one or more parameters
to simulate appropriate features in a canal system. about a steady-state condition. Initial conditions of
By choosing appropriate values for the components the electrical analog represent known steady-state
and connecting them systematically, a canal system hydraulic conditions. A perturbation is input into the
can be simulated. Usually, assembly of electrical analog computer, and effects of the perturbation
components is performed on a device known as an are observed. For instance, the effect of a
analog computer. The analog computer incor- sinusoidal variation in depth is simulated by
porates switches, contacts, meters, and various replacing the appropriate constant-voltage source at
types of signal sources into one console. Analog the equivalent location in the electrical analog with
computers integrate instantaneously but can only a varying sinusoidal source. In this manner, the
integrate linearized differential equations. propagation of disturbances through a canal system
caused by fluctuation at a specific location can be
investigated.
6-3
Canal Systems Automation Manual
6-4
Simulation and Analysis
6-5
Canal Systems Automation Manual
Figure 6-4.-Laboratory test facility used for the ELFLO plus RESET controller.
Electrical analogs are especially useful to simulate connecting control structures. Solutions to the
canal-system stability. Studies of feedback equations result in an approximation of the canal's
controllers have shown that some canal designs water surface level and flow as a function of time
are easily automated; other designs are almost and space.
impossible. For those problem cases, small
disturbances tend to amplify rather than decay. By The set of equations is an approximation of the
input of sinusoidal disturbances at various locations physical conditions. The equations can accurately
in an electrical analog, engineers can investigate a simulate natural conditions if enough mathematical
canal's sensitivity and identify the elements causing
terms are included in the equations and if the
problems. coefficients of these terms are properly selected. In
some cases, essential hydraulic behavior can be
Analog computers have been used primarily for
simulated using only a few terms. However, as the
flood routing, ground-water, and estuarine
complexity of flow increases, more terms must be
simulations. Although electrical analog techniques
included in the equations. For example, the
can be applied to studies of canal systems, digital
computers are much easier to use and are now fast simulation of steady-state flow in one pool of a
enough to eliminate the advantage once held by trapezoidal channel can be achieved using a simple
equation having only two terms. However,
analog computers.
satisfactory simulation of unsteady flow may require
up to five terms in the equations.
6-4. Numerical Analog
Equations that describe flow in canal systems are
A numerical analog of a canal system consists of a nonlinear; therefore, a closed form solution of the
set of equations that describes significant hydraulic equations cannot be obtained. Instead, approx-
relationships in each canal pool and in their imate solutions are obtained using numerical
integration techniques. Various solution methods
6-6
b. Electrical Schema f ic
3
L, = L2 = p (*z + *J ,, II i
2 ” .= Pg(Az+ A,) (hz + ht)
2
2
($q?j Es=( v)(ht - h.)
pg A4
Ed= y(hJ - hd) (SJ = (iz) E7 =F (hl-hr)
I
--R3 _ -hr z
R4 0 hs
EI,AkA6 2 -(h6-h,) pg AT
Eli= y(hs- h7)
Lr = b = P&d*, + As)
13
2 c3=pg(AiCA:)(hr+hs)
2 2
pg Ar hs
E,J= E,r= El,= --
2
6-7
Canal Systems Automation Manual
have been developed because the equations can Notice that these assumptions introduce
be integrated numerically in several different ways. approximations into a simulation. That is, velocity
As the number of terms in the equations increases, is not truly uniform throughout the cross section of
the solution techniques become more and more a constructed canal. The assumption of small
complicated. The art of numerical simulation is in streamline curvatures means no sudden
knowing different solution techniques and being expansions of the flow and no vertical accelerations
able to select the method that produces the best exist. The first condition is violated at control
solution with a minimum of computational effort. structures, and the second condition is violated at
sudden changes of invert slope.
Chapter 2 included a brief discussion of basic canal
hydraulics. The following examines numerical
Two formulations of the Saint-Venant equations are
techniques used to simulate different types of canal possible: (1) an integral form and (2) a differential
flow and to delineate some of the preferred
form [7]. The integral form is more general, and
methods used in solving the applicable
from it the differential form can be derived. The
mathematical equations.
integral form.does not require the functions to be
a. Basic equations.-Unsteady flow in open continuous. Therefore, it can be used to simulate
channels is governed by the principles of problems where water surface variation is
conservation of mass and momentum. The discontinuous-as with a hydraulic jump or bore
equation of water continuity expresses conservation wave. However, in practice, differential equations
of mass, and the equation of motion (dynamic are used most frequently for numerical analog
equilibrium) describes the momentum balance. formulation.
Commonly, these two unsteady-flow equations are
called the Saint-Venant equations. The Saint- By making simplifications to the complete
Venant equations assume the following [7]: differential equations, equations having application
to a specific type of flow can be generated. Each
. Flow is one-dimensional, and velocity is flow type is denoted by a unique name. Delinea-
uniform over the cross section. tion of the flow types can be understood by
l Streamline curvature is small. referring to the dimensionless form of the full
. Effects of boundary friction and turbulence differential equations of conservation for momentum
can be accounted for by the resistance and mass. The differential equations are defined in
laws of steady-state flow. dimensionless terms, respectively, as:
. Channel slope is small enough so that the
cosine of the angle between the invert and
horizontal can be replaced with unity.
Term:
6.1
and
", ay' + -+
ayf A’ av' = 1 6.2
ax' at' T/m z q'
6-8
where: l The steady dynamic wave model adds the
convective acceleration effect (term II) to
A = cross-sectional area the diffusion wave model.
V = flow velocity
V, = flow velocity at normal depth b. Numerical methods of solution.-In general,
A, = cross-sectional area at normal depth several numerical techniques are available to solve
A’ = A, / Y,‘, dimensionless area each of the simplified equations previously
F, = V, / (gAO/ TO)“, Froude number discussed. The goal of each technique is to obtain
g = gravitational acceleration solutions quickly and accurately. Solutions must be
L, = distance for change in elevation of stable from a computational point of view.
energy grade line to equal flow depth Consequently, understanding the advantages and
at normal depth limitations of each technique is imperative.
q = lateral inflow
q’ = q / (V,,Y,), dimensionless lateral inflow Numerical methods have been developed to solve
S = slope of energy grade line both steady and unsteady flow problems. A
so = sine of bottom slope of channel numerical method determines an approximation to
S’ = S/S,, dimensionless slope the true solution of the differential and integral
T = top width of water surface equations at discrete locations or points in time.
TO = top width of water surface at normal For specific types of problems, several popular
depth techniques encountered in water systems
T’ = T / TO,dimensionless top width automation are discussed below.
t = time
t’ . = tV,/&, dimensionless time c. Steady-state analysis.-Steady state means that
v’= V / V,, dimensionless velocity only spatial variations in the water surface exist;
X = horizontal distance along canal conditions remain constant with respect to time. In
x’ = X/L,, dimensionless distance this case, equations 6.1 and 6.2 can be combined
Y = depth of flow into one total differential equation given by:
Y’ = Y / Y,, dimensionless flow depth
Equations 6.1 and 6.2 are referred to as the dY’ = 1 - (S/S,) _ (F2,/ So) (V’q’/A’) (1 + T') 6 3
dxl 1-F I-F
dimensionless, one-dimensional shallow-water
wave equations, or as the dynamic wave model.
Equation 6.1 is frequently simplified as follows: where:
. For furrow irrigation, water enters at the F = V/(gA/ T)%= local Froude number
upstream end of a furrow and advances.
down a dry channel. The Froude number
is small in comparison to the other terms. Equation 6.3 can be solved using any of the
Therefore, only terms IV and V are numerical methods developed for solving first order
significant in equation 6.1. Solutions using nonlinear differential equations. Two traditional
only term V or terms IV and V are called methods are the step method and the standard-
kinematic approximations. Flood routing step method [a].
problems also are frequently solved using
the kinematic approximation. (1) Step method.-In the step method, equation 6.3
0 For rapidly varying flow in power and is written as:
pumping canals, frictional and lateral inflow
or outflow effects are minimal. In this case, Y, - Y, + v,2 / 2g v: / 2g
terms I, II, and III are the only ones used. AX= 6.4
s, - s
Solutions using these terms are referred to
as gravity wave approximations.
l Other combinations of terms are possible.
For instance, the inclusion of pressure and where:
frictional effects (terms I and V)-ignoring
inertial and inflow effects (terms II, III, and subscripts 1 and 2 refer to upstream and
IV)-results in the diffusion wave model. downstream conditions, respectively
6-9
Canal Svstems Automation Manual
The solution of the equation, AX, is the distance distance is fixed, the Y, depth and the corres-
between locations 1 and 2 (from the point where ponding velocity head and energy slope must be
depth equals Y, to the point where depth equals determined by trial and error. Equation 6.3 can be
Y,). programmed for solution on a computer using
Newton’s method of finding roots of an equation.
To solve the equation, a value of Y, slightly To use Newton’s method, equation 6.3 is rewritten
different from Y, is assumed. Values of velocity as:
head and energy slope are calculated for the depth
Y,. The energy gradient is calculated from:
” = cf Rl 6.5
243 where:
f = the Darcy-Weisbach friction factor Equations 6.7 through 6.9 are iterated until the new
depth, Y,, is within some predetermined tolerance
of the old depth.
In equation 6.4, the energy gradient is the
arithmetic average of the values at Y, and V,. (3) Direct integration.-Equation 6.3 can be
Studies by Laurenson [9] show that the arithmetic integrated directly if the following simplified
average is the single best method of averaging. assumptions are made [lo]:
Computations progress upstream if the flow depth
is greater than critical depth and downstream if the . Friction slope at depth Y and discharge Q
flow depth is less than critical. Because the is the same in nonuniform flow as in
solution is asymptotic to normal depth, this uniform flow
procedure minimizes error growth in the l Chezy coefficient is constant
computations. When computations progress away . Channel is rectangular
from normal depth, the solution may be incorrect . Hydraulic radius is equal to the flow depth
because the starting depth is imprecise.
(infinitely wide canal)
(2) Standard-step method.-This method uses a
The solution of equation 6.3 is:
prescribed distance increment rather than a
prescribed depth. Equation 6.3 is solved for a
constant value of AX. Because the incremental
6.10
6-10
Simulation and Analysis
6-11
Canal Systems Automation Manual
four total differential equations called characteristic of the characteristic lines (point p). The four
equations. The four characteristic equations are characteristic equations can be integrated as
given as follows: follows:
Positive characteristic:
6.20
--g dY + g + g(s - So) +ipq=o 6.16
I
xT Ydx=;(Y, + 2Y, + 2Y* + . + 2Y”.! + Y,)
C dt
where:
and
h = dx =X,-X,
dx
-=v+c 6.17
dt For the trapezoidal rule, -1.
Negative characteristic:
and
dx
-=v-c
dt
where:
Distance (X)
6-12
Simulation and Analysis
Distance (X)
a. Subcritical flow
b. Supercritical flow
P P
“.‘-’
c+ C-
-I!!
A C 5
R
S
ch
L
Distance (X) Distance (X)
6-13
Canal Systems Automation Manual
To ensure accuracy of specified time interval example, the partial derivative of velocity with
computations, the relationship between time distance might be approximated for a constant
increment and distance increment must obey the value of time by:
Courant condition. This condition is:
6.22
1
6.21
3 /VI +c
6-14
With the implicit scheme, finite difference Small wave numbers correspond to slow variations
approximations are expressed in terms of unknown in the water surface or discharge. Large time steps
variables. A set of algebraic equations is written for can be used for small wave numbers. The flood
the entire system using present time values. All of wave is an example of a shallow water wave that
the equations are solved simultaneously to evaluate can be simulated with large time steps. Usually,
every point at a single time step, and the unknowns normal canal operating conditions can be
appear implicitly. The implicit scheme is not limited accurately simulated with large time steps, offering
by the Courant condition; it is unconditionally stable great improvements in computational speed.
for all time steps. However, using a time step that
is too large may produce unsatisfactory results. Large wave numbers correspond to rapid
fluctuations in water level and flow. If the problem
The time step used with the implicit scheme should has large wave numbers, then the Courant
be short relative to the time required for a condition should be observed. Emergency
significant flow change. If flow can change rapidly, conditions in a canal must be simulated with small
a short time step should be used; if flow changes time steps. Generally, simulations of flows
are gradual, a long time step is adequate. One associated with water systems automation should
measure of the time-step size is the wave number. be studied with methods that obey the Courant
The wave number, o, is defined as: criterion.
6.25
and
6.26
where:
6-l 5
r--I’
Canal Svstems Automation Manual
where:
11
+gAtAX
2
8 [ (- /* + AS, - AS,),“” + (- I2 + AS, - AS,),:;’ 1
and
AX
2 (A;*’ + A;;‘) - w!$ (A,” + A;” )
6.28
Q/Y;' - Q,“+l) + (1 - 0) (Q,“+’ - Qjn) ] = 0
where:
6-l 6
Simulation and Analysis
Because I,, 1,, and S, are functions of Q and A, Input data may be entered interactively or from a
equations 6.27 and 6.28 are nonlinear. Generally, file in either International System of Units or inch-
the discretization given by equations 6.27 and 6.28 pound units.
is not used in computer programs because of the
increased computational effort required with this Output data can be sent to a printer or displayed
formulation. However, if the purpose of the graphically on the terminal screen, a printer, or a
simulation is to reproduce the steep wave fronts plotter.
found with bore waves, this formulation is the
correct one to use. Either Manning’s n or rugosity may be specified to
describe conduit friction.
e. Software .-Generally,numerical analogs are
applied through computer programs. Hydraulic (2) Unsteady-state analysis.-Reclamation has
analysis computer programs have been developed developed and used several unsteady-state
and used by government agencies, universities, analysis programs. Programs AQMAIN, CORNING,
and industry. Several computer programs have and CBACCH are different versions of a program
been developed and tested by the Bureau of that were developed under contract. Each program
Reclamation. Some of these programs are is a modification for a specific purpose. These
summarized below. programs are based upon the method of
characteristics, using a specified time interval with
(1) Steady-state analysis.-Numerous steady-state interpolation along the distance line. Program
drawdown and backwater programs are available. coding includes logic for upstream Proportional Plus
One of the most comprehensive programs available Reset (P+PR), ELFLO, ELFLO plus RESET, and
in the public domain is WS77 [15]. The program is Colvin controllers (vol. 1, chapter 3). The
available on diskettes and will run on IBM PC programs gave good results [6] when verified with
compatible computers. field results. However, using these programs is
discouraged because each program’s source code
Program WS77 uses the standard-step method and must be modified to make it compatible with the
can compute: specific canal and controller being analyzed. Also,
flow parameters must be artificially adjusted to
l Supercritical or subcritical flow in open compensate for interpolation errors that cause the
channels canal to appear to be “leaky” near steady state.
l Supercritical or subcritical in free-flowing
closed conduits For unsteady-state analysis, USM [16,17] is the
most general program developed by Reclamation.
The program has capability to calculate: This program uses the method of characteristics,
either with specified time intervals or with the grid
l Air entrainment of characteristics. The specified time interval
l Cavitation potential solution executes more quickly, but the grid of
l Turbulence characteristics characteristics significantly improves conservation
of mass. A large number of typical boundary
Open-channel cross sections may be: conditions can be simulated, including:
l Triangular Gates
. Rectangular Siphons
l Trapezoidal Gates with siphons
Weirs
Closed-conduit cross sections may be: Gates with weirs
Transitions
. Rectangular Turnouts
l Circular Pumps
6-17
Canal Systems Automation Manual
Gates may be controlled with either upstream or have the characteristic that small errors amplify with
downstream local controllers. These controller time. It is difficult to distinguish between
types include: instabilities that arise from the flow conditions and
those that are caused by improper approximations.
. Little-Man Fortunately, most of the typical errors caused by
. P+PR poor approximations have been studied. However,
. ELFLO plus RESET a novice programmer may generate poorly formed
. Colvin discretizations.
The canal sections that can be simulated include: Fourth, the analog should closely represent the
simulated field conditions. One of the most difficult
. Rectangular conditions to simulate properly is the boundary
. Trapezoidal friction characteristic. Often, Manning’s equation is
. Triangular used as the analog. Manning’s equation is a poor
. Circular choice because the coefficient is a function of depth
. Horseshoe and discharge. The Colebrook-White equation
overcomes some of the weaknesses of the
Program USM has a modular format which Manning equation, but even the Colebrook-White
facilitates the addition of other canal cross sections equation does not represent channel friction
or controllers into the computer code. USM is perfectly. Rouse [20] showed that a Froude
available for IBM PC compatible computers. number must be included in the resistance equation
for unsteady flow.
For gate stroking, the Gate Stroking Model (GSM)
[18,19] is used. GSM will determine a series of Numerical analysis is a new field, and many
continuous or discontinuous gate motions that computer programs are becoming available. Users
produce a desired water surface profile in a canal. are often unaware of programming techniques and
GSM uses the grid of characteristics solution inherent limitations of the programs. Therefore,
method. Available pool cross-section shapes and users frequently lose track of the approximate
structure types (boundary conditions) are the same nature of the numerical solution. The tendency to
as in USM. User-entered depth and flow schedules resolutely accept the computer output as being the
are employed to calculate gate movements and true solution must be resisted. The results of even
pump discharges. GSM is available for IBM PC the most sophisticated and user-friendly computer
compatible computers. program should be treated with skepticism and
thoroughly checked for correctness. If possible,
f. Practical considerations.-The choice of a results should be verified with field data or, at least,
numerical analog must always satisfy several with carefully formulated test problems.
requirements. First, the solution should conserve
mass. Within reasonable limits, the solution should
not gain or lose water. Mass conservation can be ANALYSIS
tested by observing the solution’s behavior at
steady state. As mentioned above, some of the 6-5. Analysis
interpolation techniques will cause a solution to
gradually depart from the steady-state solution. The purpose of the analogs discussed in this
chapter is to simulate canal system behavior given
Second, the numerical solution obtained with large certain design and operational parameters. The
time intervals and incremental distances should goal of the simulation is to develop improved
converge to the solution obtained if the time and designs and operational methods. This goal can
incremental distance was allowed to approach zero. be realized only if the proper analog is chosen and
Errors always will be introduced when using finite the proper analysis is performed.
increments rather than exact integrals. The errors
may be large where the solution varies rapidly. Before the analysis can begin, preliminary studies
Third, the numerical solution should be stable. must be completed. The primary purpose of these
Some methods used to approximate differentials studies is to establish both the operation concept
6-l 8
Simulation and Analysis
and the method of operation. Additionally, a ensure against canal dewatering and structure
preliminary canal system design should be overtopping, but unsteady flow is not analyzed.
developed, including the following items: This technique may lead to designs that are difficult
or impossible to operate.
l Establish the plan and profile
l Estimate inflow and delivery requirements To investigate the effect of canal geometry and
. Identify inflow and outflow locations along operations, both normal and emergency conditions
the canal system need to be investigated.
. Detail environmental, political and
operational constraints (1) Normal condition studies.-Normal conditions
are situations expected to occur frequently during
The importance of carefully conducting preliminary project operation. A canal should be designed to
studies is emphasized. Too often, analytic studies accommodate normal operating conditions without
commence with little or no consideration of the causing any damage or exceeding design criteria.
appropriate operation concept that should be Studies of normal conditions include investigations
applied to the system. Neglecting to perform using appropriate discharge variations in canal
preliminary studies can lead to systems that are inflow and turnout deliveries (within design flow
difficult or impossible to operate. criteria). These studies begin with a pre-
established method of operation.
Analysis requires using analogs that simulate
unsteady flow. Often, unsteady-flow simulation is For instance, with a constant volume method of
referred to as hydraulic transient studies. Transient operation, typical water-surface fluctuation rate is
studies consist of two broad classifications: design studied and compared with drawdown criteria.
and operational. Design studies are used to Additionally, the magnitude of water-surface
determine how to build a canal system. Opera- fluctuation is checked against freeboard allowance.
tional studies are used to determine how to operate If either drawdown or freeboard criteria are
the system. Although separated into these two exceeded, the canal system design or the method
classifications, the investigation is often one of operation will be revised until water-surface
interrelated process. fluctuation is within allowable limits.
6-l 9
Canal Systems Automation Manual
The Narmada Main Canal reach: used. For instance, the changes in flow rate could
progress as: 240, 100, 50, 30, and 6 m3/s (8,500,
. Cross section is trapezoidal with side 3,500, 1,750, 1,050, 200 ft3/s) at 5-hour intervals.
slopes of 2:l (horizontakvertical).
. Canal bottom width varies from 73 m The exponentially decreasing flow increment
(240 ft) at the diversion structure to 60 m schedule would establish design flow in a
(196 ft) at the Mahi Crossing. satisfactory manner without exceeding drawdown or
l Normal depth is 7.60 m (24.9 ft). canal freeboard design limitations.
. Bottom slope is 0.00008 with a Manning’s n
of 0.018. (2) Normal operation (decreasing discharge).-To
. Check gate structures total 9. decrease the discharge from the design flow, a
. Gate structure includes a 0.5-m (1.6-ft) rise constant increment of 90 m3/s (3,160 ft3/s) every
in invert from the upstream canal to the 5 hours was investigated. This schedule did not
gate section and a 0.59-m (1.9-ft) drop on produce any adverse flow conditions.
the downstream side of the gate.
. Average pool length is 18.6 kilometers (km) (3) Emergency flow stoppage.-Preliminar
(11.5 miles [mi]), with the exception of the investigations using the gate stroking algorithm
first pool. yielded a procedure to stop the canal flow as
. First pool has a length of about 9.3 km quickly as possible. While keeping the water level
(5.8 mi). upstream from each gate at a depth of 7.6 m
. Design discharge is 1150 m3/s (24.9 ft), flow was shut down from maximum to
(40,000 ft3/s). zero without generating waves that exceeded the
freeboard. Flow in the entire canal could be
The purpose of the simulations was to verify that stopped in 15 hours using a complicated sequence
the canal can operate satisfactorily at its design of gate opening and closing movements.
discharge. A downstream operation concept
(demand oriented) was to be used for this section If a uniform gate closure was used instead of the
of the canal with a constant water surface elevation complex gate adjustment pattern dictated by gate
upstream from every check gate. This method of stroking, flow could be stopped in 13.5 hours.
operation provides a predictable flow rate into the However, water level would exceed the freeboard in
major secondary canals that branch off the main the most downstream pool.
canal.
Computer simulations showed that adding three
(1) Normal operation (increasing discharge).-The check gate structures would permit a total
flow was increased from 54 percent of design shutdown from maximum flow in only 8 hours
discharge to the design discharge at the Mahi without overtopping the lining in any pools.
crossing in 19 hours. The flow was increased by Additionally, maximum flow at the Mahi crossing
90 m3/s (3,160 ff/s) every 5 hours for the first could be stopped in only 1 hour if upstream
15 hours and by 76.1 m% (2,670 f?/s) during the diversions were not turned off. Because of these
last 4 hours. This discharge schedule caused the significant reductions in shutdown time, the decision
water surface upstream from the third check gate was made to add the three additional check gate
structure to overtop the canal lining. Therefore, this structures.
operating schedule could not be used without
redesigning the canal. Two design changes were The preceding example points out that the method
considered. First, the drop across the second and of operation and the design are interrelated.
third gate structures could be increased. The Physical properties impose constraints on the
second possibility would be to change the normal capability to operate a canal at the design
depth in the first and second pools; however, this discharge. The example shows how a change in
change would require changes to the bottom width the number of check-gate structures or in the
or side slopes in these two pools. gate(s) operating sequence may significantly
improve response to emergencies. Successful
As an alternative, when flow increases, a decreas- canal system design requires analysis of unsteady-
ing discharge increment operating schedule could flow conditions using analogs to simulate the
be adopted. To minimize disturbances, an important physical properties and flow schedule.
exponentially decreasing rate of change could be
6-20
c. Operational studies.-Operational studies are l Filling the canal system
conducted to determine how the canal system will l Taking parts of the system out of service
be operated during its development from startup to for testing or maintenance
full capacity. Historically, canal system operations
have not been addressed until the canal is built and These studies define the best control response for
ready to use. This procedure has been particularly each of the anticipated abnormal operating
true with conventional canals controlled by situations.
ditchriders. Operations must be thoroughly
analyzed in advance with automated canals. (3) Emergency operation studies.-Emergency
Operational studies are concerned with ensuring studies are used to predict the optimum response
acceptable operations under a wide range of to the most severe operating conditions
conditions. The primary goals are to: conceivable. Emergencies are defined as
conditions that would cause severe damage to the
l Determine the control concept and control system if specific actions are not undertaken to
method-if this determination was not mitigate the situation. Usually, damage is the result
made during the design studies of excessive water levels or the effect of rapid
l Select algorithms for automatic controllers variation in the water level. Simulation results will
. Determine parameters for the automatic indicate the best operating strategy for different
controllers emergencies. These strategies can be performed
l Specify operational strategies that allow by the watermaster at the time of the emergency or
continued operation during periods of minor preprogrammed into a supervisory control system.
equipment failure
l Specify operational procedures to be d. Operational studies example.-Studies were
followed during emergencies made of R&lamation’s Garrison Diversion Unit in
North Dakota. The unit consists of three
Three types of conditions need to be investigated: conveyance canals connected in series (McClusky,
Sykeston, and New Rockford Canals).
. Normal
l Abnormal l The combined length of canals is 230 km
. Emergency (140 mi).
l The maximum discharge ranges from
(1) Normal operation studies.-A control system 45.3 m3/s (1,600 e/s) at the upstream end
must perform smoothly during typical daily canal to 24.8 m3/s (870 v/s) at the downstream
operation. Normal operation studies are used to end.
select the most appropriate type of controller. The l The canal bottom width ranges from 7.6 to
studies determine controller parameters that will 13.4 m (25 to 44 ft).
result in stable and responsive control action over l The average flow depth is 3.2 m (10.5 ft).
both the design and low flow rates. Low flow rates
may occur during the irrigation off-season or during Originally, McClusky and New Rockford Canals
the irrigation system’s initial development period. were to be connected by a regulating reservoir.
Normal operation studies permit quantitative For environmental reasons, the reservoir was
evaluation of tradeoffs. Tradeoffs may include: eliminated, and Sykeston Canal was needed to
connect the other two canals. Before producing the
. Flexibility in deliveries final design of Sykeston Canal, designers needed
l Allowable canal level fluctuations an operation plan for the entire canal system.
l Maintenance of delivery flow rates Preliminary operational studies were required to
l Operational costs develop methods of operation and control which
would satisfy delivery, environmental, and design
(2) Abnormal operation studies.-Abnormal studies constraints.
are performed to determine how flow will be
delivered when an abnormal or unusual Delivery to water users was to be unscheduled.
event occurs. Abnormal events include: Therefore, a demand oriented operation concept
was established. Because the canal is a
l Minor equipment failure combination delivery and connector system, water
l Draining the canal level was allowed to fluctuate within narrow limits.
C-21
Canal Systems Automation Manual
The constant volume method of operation, in which assumed to be a large, sudden rainstorm over a
the water level in each pool pivots about a point majority of the irrigation area, causing most of the
near its mid-pool, was selected. This method turnout deliveries to be turned off in a short period
requires simultaneous operation of all check gates; of time. This emergency event was simulated by
therefore, a supervisory control method is required. totally shutting down the system from design flow to
zero flow in 2 hours.
To study normal operations, typical day-to-day
conditions in the aqueduct system were predicted. Simulation results showed that simultaneous
Depths and flow variations in the canal system and operation of the gates would create unacceptably
typical turnout flow changes were used as program large fluctuations in the water levels. Additional
input to the numerical analog. The simulation analysis indicated large fluctuations could be
showed that water level fluctuations in the entire controlled by using a sequential check gate
canal system did not exceed the drawdown criteria. operation technique and by allowing pool storage to
Therefore, for normal operation, the supervisory increase during the shutdown period.
control system is satisfactory.
The Sykeston Canal study illustrates that different
Emergency operation studies were deemed to be methods of operation may be needed for normal
critical because of environmental constraints. versus emergency operations to accommodate
International requirements dictated that water could design constraints. In this case, two methods were
not be wasted from the Missouri River watershed necessary, but both could be implemented with
into the Red River watershed that passes into supervisory control.
Canada. The extreme emergency condition was
6-22
BIBLIOGRAPHY
[l] Schuster, J.C., ed., Hydraulic Laboratory [lo] Bress, J.A., “Cours de mechanique
Techniques, Bureau of Reclamation, applique,” 2e partie, Hydraulique,
208 pp., Denver, Colorado, 1980. Mallet-Bachelier, Paris, 1860.
[2] Simmons, W.P., “Hydraulic Design of [l l] Prasad, R., “Numerical Method of Computing
Transitions for Small Canals,” Engineering Flow Profiles,” ASCE, Journal of Hydraulic
Monograph No. 33, Bureau of Reclamation, Engineering, HYl, pp. 75-86, January
39 pp., Denver, Colorado, 1964. 1970.
[3] Buyalski, C.P., Discharge Algorithms for Canal See also discussions by:
Radial Gates, Bureau of Reclamation
Report No. REC-ERC-83-9,232 pp., Rao, S.S., and K. Rubramanya, HY6,
Denver, Colorado, December 1983. pp. 1759-l 760, August 1970.
[4] Schuster, J.C., and P.F. Enger, Laboratory Aplet, C., HYlO, pp. 2134-2135,
Facilities for Research and Development of October 1970.
Water Systems Control Automation, Bureau
of Reclamation Report No. GR-5-77, Prasad, R., HYll, pp. 2389-2392,
24 pp., Denver, Colorado, April 1977. November 1970.
[5] Buyalski, C.P., Electronic Filter Level Offset Prasad, R., HY6, pp. 861-864, June 1971.
(EL-FLO) Plus Reset Equipment for
Automatic Control of Canals, Bureau of [12] Levy, H. Baggott, Numerical Solutions of
Reclamation Report No. REC-ERG79-3, Differential Equations, Dover Publications,
145 pp., Denver, Colorado, June 1979. 1950.
[6] Braunagel, M.V., Electrical Analogue for [13] Liggett, J.A., and J.A. Cunge, “Chap-
Open Canals, Report to the Power and ter 4, Numerical Methods of Solution of the
Pumping Plant Design Section, Electrical Unsteady Flow Equations,” Unsteady Flow
Branch, Bureau of Reclamation, Denver, in Open Channels, vol. 1, Mahmood, I.K.,
Colorado, August 1968. Yevjevich, V., eds., Water Resources
Publications, pp. 89-l 82, Lakewood,
[7] Cunge, J.A., F.M. Holly, Jr., and Colorado, 1975.
A. Verwey, Practical Aspects of
Computational River Hydraulics, Pitman [14] Colin, E., and R. Pochat, “One-dimensional
Press, 1980. Open Channel Flows,” paper presented at
International Symposium on Unsteady Flow
[8] Posey, C.J., “Gradually Varied Channel in Open Channels, Newcastle-upon-Tyne,
Flow,” Engineering Hydraulics, H. Rouse England, pp. A4-39-52, 1976.
ed., John Wiley, 1950.
[15] Falvey, H.T., “Cavitation in Chutes and
[9] Laurenson, E.M., “Friction Slope Spillways,” Engineering Monograph
Averaging in Backwater Calculations,” No. 42, Bureau of Reclamation, Denver,
ASCE, Journal of Hydraulic Engineering, Colorado, 1990.
vol. 112, No. 12, pp. 1151-1163,
December 1986.
Canal Systems Automation Manual
[16] McGarry, E.G., “User’s Manual, Usteady McCann, G.D., and C.H. Wilts, “Application of
Model (USM),” Water Conveyance Branch Electric-Analog Computers to Heat-Transfer
Report, Bureau of Reclamation, 44 pp., and Fluid-Flow Problems,” American Society of
Denver, Colorado, 1990. Mechanical Engineers, Journal of Applied
Mechanics, pp- 247-258, September 1949.
[17] Rogers, D.C., and G.P. Merkley,
“Description and Evaluation of Program: Shen, J., “Use of Analog Models in the
USM,” Proceedings of the ASCE National Analysis of Flood Runoff,” U.S. Geological
Conference on Irrigation and Drainage Survey Professional Paper 506-A, 23 pp.,
Engineering, pp. 425-431, July 1991, 1965.
Honolulu, Hawaii.
Harder, J.A., “Analog Models for Flood Nwaogazie, I.L., “WICFEM - A FORTRAN
Program for the Solutions of Saint-Venant
Control Structures,” American Society of Civil
Streamflow Equations,” Advanced Engineering
Engineers, Journal of the Hydraulics Division,
Software, vol. 7, No. 4, pp. 182-198, 1985.
vol. 88, HY 2, pp. 63-74, 1962.
6-24
Simulation and Analysis
Hromadka, T.V., and C.C. Yen, “A Diffusion Stephenson, D., “Depiction of Friction
Hydrodynamic Model (DHM),” Advancements in Damping in Numerical Flow Modelling,”
Water Resources, vol. 9, pp. 118-170, Advanced Engineering Software, vol. 8, No. 4,
September 1986. pp. 211-216, 1986.
6-25
CHAPTER 7
CONTROL THEORY AND APPLICATION
As discussed in volume 1 (section 3-2, page 57), Local-automatic and supervisory-automatic control
control systems can be classified as either open are examples of closed-loop systems which employ
loop or closed loop. In an open-loop system, the feedback. The simplest control action is a three-
control action is independent of actual or desired position mode of control; that is, the correction has
conditions (output). The electrical switch example three discrete values: no correction, increase in
is an open-\oop system. The action of pressing the correction, and decrease in correction. The
switch is completely independent of whether or not Little-Man controller is a simple, closed-loop control
Canal Systems Automation Manual
system that uses a three-position mode of control. that all initial conditions are equal to zero. In block
Other types of closed-loop controllers use more diagrams, the operation of addition and subtraction
complicated control modes, which include is a summing point. The output of the summing
proportional, integral, and derivative functions. point is equal to the algebraic sum of the inputs to
Modes of control were introduced in volume 1 the point.
(section 3-6, page 60). A detailed discussion of
the logic used in these modes is described in In the following sections, elements in the feed
section 7-6, Controller Components. forward path are noted by a G, and those in the
feedback path by an H, . The feed forward path is
The control action affects the response and stability the transmission path from the actuating or error
characteristics of the system. Responsiveness is signal to the controlled output. The feedback path
the time in which the control system corrects errors. is the transmission path from the output to the
Stability is the ability to return to equilibrium after primary feedback signal. The primary feedback
initiating a change [14]. In a stable system, signal is the signal that is summed with the
disturbances decay with time. If the disturbances reference signal or input to obtain the actuating
oscillate or fluctuate at a constant amplitude or if signal. The subscript x is a function identifier.
they increase in amplitude, the system is unstable.
As noted in volume 1 (section 3-5, page 59), the
designer has to balance responsiveness and 7-2. Input and Output Variables
stability.
In canals, discharge is normally the parameter that
The advantages of a properly designed feedback is to be controlled, although discharge is not a
control action: quantity which can readily be determined. Instead,
some other quantity must be measured; then,
. Provides stability to the system being discharge is related to that quantity through
controlled algorithms. In canals, the parameter most
. Minimizes variations in the output frequently used is water surface elevation or the
. Reduces the effects of nonlinearities difference in water surface elevation between two
. Increases range of frequencies over which points. Unless otherwise noted, water surface
the system will function properly elevation is the controlled parameter (input) in the
. Provides responsiveness following discussion.
The disadvantage of feedback is an increase in the The location and number of sensors used as output
tendency for the system to oscillate and become depend on the objectives of the conveyance system
unstable. (see volume 1, section 4-2, page 84). Only one
water level sensor per reach is used if the canal is
In analyzing a system for stability, a time history a delivery system consisting of gravity turnouts.
analysis of the disturbances is often unnecessary. Usually, the location of the sensor is near the
Predicting the behavior of the oscillations with time downstream end of a canal reach near the
may be sufficient. This prediction can be done by turnouts. Thus, the water level at the turnout is
analyzing the characteristics of the Laplace relatively constant as the flow rate in the main
transform of the system [15]. The analysis is canal varies. Similarly, a pumping plant is usually
simplified by representing the system as a block controlled with only one water level sensor. If the
diagram. pumping plant is used in a collector system, the
sensor is located on the suction side of the
A block diagram is the pictorial representation of pumping plant. With a delivery system, the sensor
the relation between the input and output of is located on the delivery side of the pumping plant.
elements of a control system as shown on
figure 7-l. Block diagrams show the logic of the Multiple sensors in a canal pool are used to
interrelations between various elements of a control implement various control methods. Figure 7-2
system. Each block represents a transfer function shows the use of two sensors in a canal to control
of an element of the system. A transfer function is the location of the pivot point [14, 151. In this case,
the ratio of the Laplace transform of the input to the the sensors are located at each end of the pool.
Laplace transform of the output of a block. They are connected to a proportional controller
Transfer functions are written with the assumption which prorates the contribution of each sensor.
7-2
ControlTheoryandApplication
Feedback Controller
Response of
Water Level Movement
- To Gate - With Dead
Movement
G6
Upstream
Motion of
u Gs Disturbances
L3 in Canal
Downstream
Motion of :
Depth at Y,
Depth at 5 Disturbances c
in Canal
Disturbance Disturbance
Coused by Caused by
Pump Turnout or
Operation or Downstream
Upstream Gate Movement
Turnout
‘7-3
Canal Svstems Automation Manual
Proportional Controller
GP=Kl(M-YF)
,//
Comporotor y
m ?AG=GP+GR-GA_+ DB
v \/
Receiver
Reset Controller YF
Reset
GR=K2/;‘(GPfRDB)dt
t
& Actuator
I I
Water
YF
Level
downstream end. The mechanical equipment that The components of an ELFLO plus RESET
implements the control action is the gate at the controller are shotin on figure 7-4. As noted
pool’s upstream end. The controller includes all of earlier, all transforms noted with a G are located on
the electrical and electronic equipment between the the feed forward path. All transforms noted with an
input sensor and the gate, including: H are located on the feedback path. This controller
uses two feedback paths. One is located in the
l Control element gate-position loop, and the other consists of the
. Comparator sensor transform. Also, the diagram has three
l Gate movement actuator summing points. At these points, signals are either
l Gate position indicator added or subtracted to initiate a primary feedback
signal. A block diagram reduces the complicated
The following items will affect water levels interrelations of the canal and feedback
throughout the prism: components to a “black box” describing the system
and its feedback path.
. Variation of flow rate in pools upstream
from the upstream gate The goal of the controller in this example is to
. Movements of the upstream gate maintain the downstream-pool water level as
. Turnouts within the prism constant as possible by controlling the motion of
. Movement of the downstream gate the upstream gate. A rapid response to
l Changes in discharge in the disturbances is desirable (responsiveness).
downstream pools However, the gate motion must not be too large or
fast because an overreaction to the disturbance can
7-4
Control Theory and Application
7-5
Canal Systems Automation Manual
T=tc where:
L
13 = width of gate
C, = discharge coefficient based upon
where: upstream depth
G, = vertical distance between invert and
g = gravitational acceleration bottom of gate
k = hydraulic exponent g = gravitational acceleration
So = bottom slope Y, = depth upstream from gate
t = time
V,, = average velocity at normal depth The values of the discharge coefficient have been
determined for typical types of gates. These
For the complex domain, the Saint-Venant equation coefficients are functions of the gate opening and
is linearized and written in terms of small deviations the upstream and downstream depths. For radial
[14]. The transform of the linearized partial gates, the coefficients are also a function of the
differential equation, written in nondimensional radius of curvature of the upstream face of the gate
units, leads to the following ordinary differential and the height of the pinion above the canal invert.
equation:
The complex-domain expression for the discharge
response was derived by Hancu et al. [15], who
R2 g - (2FS + I’) z - S(S + p) v(s) = 0 7.5
assumed that the discharge through a gate could
be written as:
T = 0, Y = 0, dY(s)/dr =0
where:
The general solution of the differential equation is:
C’, = discharge coefficient based upon depth
differential across gate
V(S) = C, ealx + C, ealx 7.6 Y, = depth downstream from gate
7-6
Control Theory and Application
For this derivation, the change in head across the L = pool length
gate is assumed to be small enough so that the n = truncated value of G, /d (an integer)
discharge coefficient can be considered constant. 0, = delivery discharge
T, = average top width of water surface in
pool
7-6. Controller Components
The first term on the right side of the equation
The controller components are conceptually consists only of the canal parameters. Figure 7-6
described in volume 1 (sections 3-3 through 3-8, shows the variation of the second term as a
pages 57 to 62). Some controllers may only have function of frequency. Frequency is defined as the
one component. Other controllers may have number of times a periodic fluctuation repeats itself
several components connected either in parallel or per unit time, or as the reciprocal of the time
in series. The control element component of a interval, T, . The maximum possible frequency of
controller processes the control algorithms. The oscillation, fm , is given by:
control element may use one or more modes of
control. The modes of control (also called
KI Q,
functions) discussed below are three position: fm = 7.12
8 L T, G,
proportional, integral, and derivative. In addition,
the controller may include a linear function with
time, a filter, a deadband function, or an antihunt Many controllers contain a deadband function, For
function. Sections 7-10 through 7-19 describe instance, the controller shown on figure 7-3 uses a
details of specific controllers used on Reclamation deadband function in the comparator block for the
projects. gate position.
7-7
Canal Systems Automation Manual
Input x = X SIN wt
SUM of controller and gate
position indicator signals
Switch-On
Point -
Switch-Off Poinf
\ /-
/’ - d.-h
AQ = AY TJV + C) 7.15
7-8
Control Theory and Application
2
AG = fK,AY
3 0. 70
k
2s 0.08
E
0.06
n
0.2 0.4 0.6 0.8 1.0
For cases where the upstream depth, Y, , is held
d/A o constant, the AY, / I’, ratio is equal to zero.
where:
7-9
r
Canal Systems Automation Manual
G, = K2j-=)lY dt 7.20
where:
where:
Go = gate opening
Cd = discharge coefficient of gate based K2 = integration constant
upon upstream depth t = time
Y” = flow depth upstream from gate
The complex domain expression for the integral
The variation of the proportional constant with element is given by:
discharge for a typical canal pool using upstream
control is shown on figure 7-8.
7.21
7-10
Control Theory and Application
Y, = K4 Y [ 1 - e-(f’Td ]
f. Linear functions with time.-The motion of a
gate being driven by a constant-speed motor is an
example of a linear function with time. The time:
domain expression is given by:
where:
Hancu and Rus [14] have shown that the system 7-7. Objectives
can always be made stable by proper selection of
the time constant, T, . The analysis objectives are to investigate:
7-l 1
Canal Systems Automation Manual
l Speed of response
7-8. Methodology . Relative stability
. System accuracy or allowable error
Conventionally, two types of studies are used in the
analysis of the controllers for an automated canal a. Complex-domain specifications.-The frequency
system: stability methods and time-domain characteristics of a system consist of amplitude and
simulation methods. The stability methods use phase descriptions of the open- or closed-loop
linearized equations to describe small perturbations response characteristics over a specified range of
in the canal flow and of the control elements. frequencies. The complex-domain specifications
Although the linearized equations are simplifications define pertinent qualities of these characteristics.
of the true nonlinear equations, they are sufficiently The most common specifications are:
accurate to determine approximate values for the
control parameters. In addition, the computational . Resonant peak amplitude
effort to analyze the linear equations is much less . Resonant frequency
than is required for the exact nonlinear equations. . Bandwidth
The stability methods can be imagined as a . Cutoff frequency
screening method to determine values of the . Cutoff rate
control parameters that will yield a stable system. l Gain margin
The stable control parameters then must be l Gain crossover frequency
investigated with time-domain simulation methods . Phase margin
to determine the optimum values of the control . Delay time
parameters.
These specifications are described below and are
The time-domain simulation methods use the illustrated on figure 7-9.
nonlinear equations for modeling flow in the canal
and for simulating the control elements. The time- Resonant peak amplitude, Mr , is the maximum
domain simulation accurately reproduces the value of the magnitude of the closed-loop frequency
characteristics that will be observed in the field. response.
The computational effort for these studies is much
greater than that required for the stability studies. Resonant frequency, f, , is the frequency at which
Experience in both computer simulation and the resonant peak amplitude occurs.
operation of canal systems is necessary to properly
conduct the time-domain simulations. Bandwidth, f3, , is the range of frequencies of
input over which the peak amplitude does not differ
Reclamation has developed computer programs to by more than -3 decibels (db) from its value at a
investigate only the time-domain simulations. One specified frequency. A db is defined by:
of these programs, which includes several types of
controllers and is available for use on a personal db = 20 log,,(magnitude ratio)
computer, is called USM [17]. Hancir et al. [15],
describe methods of performing the complex- The magnitude ratio is defined as the ratio of the
domain simulations for stability analysis. input to the output, or the ratio of the actual value
to the setpoint value.
7-12
Control Theory and Application
fl f7T
FREQUENCY FREQUENCY
7-13
Canal Systems Automation Manual
where:
7-14
Control Theory and Application
minimum value as the control parameter is varied. setting. Of the four performance indexes, the
Each performance index produces a different integral-of-time-multiplied absolute-error is the
controller characteristic. most applicable to automatic controllers.
7-15
Canal Systems Automation Manual
/fIP--r Deadband
Anfihunt
turned on
7-16
ControlTheoryandApplication
7-17
Canal Systems Automation Manual
‘heck Gate
I Check Gote
(ft.)
0.40-
? 0.35- ft -- 0.
GA=O.235
$ 030-
-- 0. 08
?o 0.25-
TIME ~ MINUTES
ift-) Cm)
is 4.30
5 4.25 Anfihunt “UN” 1 30
kQI 4.20 1 28
2 4.15 1 26
2 4.10 Canal Water Depth, YC
5 1.24
R 4.05
s 4.00 7.22
$ 3.95
0 50 100 150 200 250 300 350 400
TIME - MINUTES
7-18
ControlTheoryandApplication
(ft %) Cm%)
-0.45
Q= 1 I ft 2 (0.31m 2)
A A
.- 0.25
.- 0.20
.- 0. 15
-- 0. 10
-- 0.05
0 50 100 150 200 250 300I 350I 0.00
400
TIME - MINUTES
(ft %) Cm%)
Q=ll ft~(O.31m~) -0.45
TIME - MINUTES
4.55ft
(1.39m)
Q=ll ft z’ ‘- -
LGA=O. 22 ft (0.067m)
f. Canal Water Surface Profile TIME 400 Minutes
7-19
F
Canal Systems Automation Manual
As shown on figure 7-6, the proportional gain provide stability for the control loop when the
should be varied to maintain flow continuity. setpoint is located at the downstream end of a pool.
Controllers with SOT/SRT or SOTNRT mode of The magnitude of the filter time constant depends
control do not have the capability to vary the upon the surge wave amplitude attenuation and its
proportional gain as a function of change in canal travel time in the canal pool.
flow demand. Therefore, the degree of control by
Little-Man and Colvin controllers, even with the In addition to the filter and proportional control
addition of multiple-stage and antihunt features, is elements, a third element is used to eliminate the
limited to control at a diversion dam or at a single residual offset of the proportional control mode.
check gate flow control application because they do The third element consists of an integral control
not have the elements to provide compensation. mode called RESET. Stable control action of the
feedback controller requires the careful selection of
the three-control elements.
CLOSED-LOOP CONTROL OF
CANAL SYSTEM The local automatic controllers used by
Reclamation to control an entire canal system are
7-13. Controller Requirements known as Hydraulic Filter Level Offset (HyFLO),
ELFLO, ELFLO plus RESET, and Proportional plus
The controllers discussed in the previous section Proportional Reset (P+P/?). The choice of the
are not intended to control an entire canal system specific control elements used with each controller
or even several pools in series. Lag or inertia determines the acronym used to define the
introduced by a canal pool requires a compensation controller. The HyFLO, ELFLO, and ELFLO plus
element in the feed-forward path. The basic RESET controllers are primarily used for
element of a controller that is required to control an downstream control applications. The P+PR
entire canal system is a proportional control mode. controller is used for upstream control applications.
The proportional element moves the control gate in
response to variations in the sensed water level.
The gate opening is based upon a discharge equal 7-14. HyFLO Controller
to the change in discharge that caused the water
level variation. The design of the hydraulic filter in the HyFLO
controller is based upon the analogy to an electrical
In addition to the proportional control mode, a filter resistor-capacitor (RC) circuit [18]. The laminar
as shown on figures 7-1 and 7-3 is often used to flow in a small capillary tube is analogous to an
7-20
ControlTheoryandApplication
electrical resistance. The volume of the well is l The offset, Y, - y , is determined and
analogous to the electrical capacitance. The multiplied by the proportional gain constant,
hydraulic filter was designed because the 4.
equipment required to obtain the long time
constants needed for canal control was impractical The characteristic response and recovery of a canal
in the late 1960’s. The hydraulic filter proved to be pool is illustrated on figure 7-15. The schematic on
impractical. in the field because debris would plug figure 7-15a shows the canal system and water-
the small capillary tube [6]. surface profile at time zero.
The filter time constant is determined by: Figure 7-15d shows the discharge through the
upstream controlled gate. The ratio of two
T,=RC 7.38 successive discharge maxima, $ and G, , can be
used to determine the degree of damping, or
attenuation, of the initial disturbance [19]. At time
where: 60 minutes, the first amplitude, Q,, measured from
the final steady-state condition of 0.31 m3/s
C = capacitance (11 ft3/s) is 0.0536 d/s (1.9 ti /s). The second
R = resistance amplitude, Q,, is measured at time 200 minutes
T = filter time constant and is 0.00566 m3/s (0.2 v/s). Therefore, the
logarithmic decrement is:
A filter also can be simulated with microprocessor
based equipment.
7-21
Canal Systems Automation Manual
’ Turnout, Q=O
-- 0. IO
-- 0.08
-- 0.06
-- 0.04
-- 0.02
0.00’ 4 I / I I I I I r 0.00
0 50 100 150 200 250 500 350 400
TIME - MINUTES
~~~~~I ::I:
Q 0 50 100 150 200 250 300 350 400
TIME - MINUTES
Figure 7-15.-ELFLO controller typical response and recovery characteristics for automatic downstream control.
7-22
Control Theory and Application
TIME - MINUTES
d. Upstream Discharge at Section @
Q 0’ ’ I I 1
0 50 100 150 200 250 300 350 400’
TIME - MINUTES
w
Upstream Check Gate
GA=O.29 ft (O.OSSm)
Turnout,Q=ll ftt(O.37mz)
Figure 7-15.-ELFLO controller typical response and recovery characteristics for automatic downstream control-continued.
7-23
Canal Systems Automation Manual
2.8
2.6
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1. 1
N I I I
0.8
0.6 ,,
\
0.4
\,
0.2 .
\ ij
0.0
10 2 3 456 810 2 3 456 810 2 3 45c^8 10
Figure 7-l 6.-Percent of critical damping versus the ratio of two successive discharges, Q/Q,.
. The gain, K,, was selected as 3.0 m/m. . The maximum designed discharge of the
. The target elevation is set to 1.28 m canal pool cannot be achieved; i.e., the
(4.20 ft). canal prism was designed to flow at the
. At time 275 minutes, the steady-state water maximum rate at the target depth, Y, , of
level was 1.25 m (4.103 ft). 1.28 m (4.20 ft).
. The residual offset may interfere with
Therefore, offset is 0.030 m (0.097 ft), and proper delivery to the canal-side turnouts.
computed gate opening, G, equals Gd, is 0.088 m
(0.29 ft). A controller with only the proportional function
introduces an offset in the water level as flow
The upstream controlled gate inflow was matched demand increases. Limited operation is required
to the downstream canal-side turnout flow change. unless adjustments to the target depth are made.
The water surface profile at the new steady state is One way to eliminate the restrictions is to raise the
shown on figure 7-15f. The new steady state was target to a higher depth. However, most canal
developed at time 120 minutes, or about 2 hours pools are not designed to operate at depths within
after the demand occurred. The response and the canal freeboard. Another way to eliminate the
recovery is typical of the ELFLO controller. imposed restrictions is to have the ditchrider
change the target depth as the base flow of the
The offset of the proportional mode of control canal delivery changes during the irrigation season.
imposes two restrictions on the canal pool However, this operation negates some of the
operation: benefits of local-automatic downstream control.
7-24
Control Theory and Application
The outputs of the proportional and reset control The magnitude of the logarithmic decrement
elements, GPand G,, are summed and then input decreases as the flow change progresses upstream
into the comparator element. through each controlled check gate structure to the
canal headworks. Therefore, flow change at the
l The two inputs are summed to determine canal headworks could have the following
the desired gate opening, G,. consequences:
l The desired gate opening is compared to
the measured gate opening, G,, to . Exceed the flow capacity
determine the error, *AG. l Require additional storage
. If the error, *AG, is greater than the gate . Require additional pump units to satisfy the
deadband, Dg (typically 0.03 m [O.lO ft]), overshoot of the controller’s recovery to a
the actuator element is energized to raise new steady state
or lower the gate depending on the polarity
of the error, *AG. An overshoot is necessary to recover the water
l The gate continues to move in the proper level to the target when flow demand increases.
direction until the error returns to zero. When flow demand decreases, the overshoot is
negative and usually does not present operational
The response and recovery characteristics of the problems. Overshoot is directly related to the
ELFLO plus RESET controller are illustrated on selection of the integral gain constant, K2.
figure 7-17. The canal pool and flow demand are
the same as those used on figure 7-17. Figure 7-16 is a composite of figures 7-15 and
7-17. It compares the response and recovery
l The recovery of the downstream water characteristics with and without the reset controller.
level, Y,, to the target, y, occurs at The elimination of the residual proportional mode
140 minutes (figure 7-17~). offset can be observed on figure 7-18~. The initial
l The desired gate opening, G,, represents water level drawdown is the same for both control
the sum of the ELFLO and RESET methods until the surge arrives at the downstream
controller outputs, GPand G,, respectively. sensor and the reset output, G,, begins to have
l G,, G,,, and G, are plotted separately as an effect on the upstream controlled-gate
shown on figure 7-17b. discharge. The upstream gate opening with reset
7-25
Canal Systems Automation Manual
’ Turnout, Q=O
: $2 0.04
) ‘: 6 rEL-FL0 Computed
,/ii< Gafe Opening, GP . . 0.02
, , I 022m)
I I ,~ 0.00
0 50 100 150 200 250 300 350 400
TIME ~ MINUTES
(ft.) Cm)
JTarget, YT=4.20ft(l.Z8m) , OR
Area=8 42 ft min
TIME - MINUTES
7-26
Control Theory and Application
(ft %) Cm%)
Q=ll ft~(O.31m~) -0.45
-- 0.40
-- 0.35
-- 0.30
-- 0.25
-. 0.20
-- 0. 75
-- 0.10
-- 0.05
I I I _ 0.00
0 50 100 150 200 250 300 350 400
TIME - MINUTES
(ft 79 _ 1 A r, ?/ /n
V=I I rr;S(u.31mg)T
Cm%)
14r T 0.40
0.30
0.25
0.20
0.15
0. IO
0.05
,u---.--I 0.00
0 50 100 150 200 250 300 350 400
TIME - MINUTES
0 1
Upstrec.. 7m Check
_. _ Gate
Target, M=4.20ft(l.Z8m)
tream Check Gote
-.-I-
-
Q=ll
7-27
Canal Systems Automation Manual
(ft.)
0 45
r 0. 12
0.40-
EL-FL0 Plus
2 0.35- ESET Method 0.10
cu 0.30-
% 0.25- 0.08
k
3 0.20- 0.06
TIME ~ MINUTES
1.27
7.26
7.25
L EL-FL0 Method
06 ’ 1 1 1 1 1 1 , ?.?a
0 50 100 150 200 250 300 350 400
TIME - MINUTES
7-28
ControlTheoryandApplication
i i’/, I ;I:I_; , , E
0 50 100 150 200 250 300 350 400
TIME - MINUTES
TIME - MINUTES
0I
rget, YT=4.2Oft( 1.28m)
stream Check Gate
EL-FL0 Meth
Turnout, Q= 17 it 2 (0.31m s)
7-29
r-'"
Canal Systems Automation Manual
(figure 7-18b) is much larger at time 80 minutes to for the upstream-control concept application. The
supply the overshoot flow and to return the time for the surge wave to travel between the
downstream water level to the target. At the new sensor and the controlled gate is short. Therefore,
steady-state flow condition (figure 7-l 8f), the water a filter element is not required to provide control
surface profile is higher with reset. This higher stability because the system has a fast response
profile decreases the head differential across the time.
gate structure. The decreased head differential
requires a slightly larger gate opening with reset to The P+PR automatic upstream controller uses the
produce the same flow at the new steady state. proportional and integral elements of control.
The mode of control is identical to the ELFLO
The control parameters, filter 7, , water level offset, plus RESET automatic downstream controller
and the controller gains K, and 4 must be carefully (figure 7-3). However, two major differences exist
selected. They are selected to give the quickest with an upstream control concept. First, the sign of
response and recovery without creating an the offset is reversed; i.e., offset equals Y,-V, .
excessive overshoot or causing instabilities. The Second, the input to the P and PR control elements
controller must function over a wide range of flow is the water sensor output, whereas the ELFLO
demand changes. The filter time constant, T, , has plus RESET includes a filter in the control path.
a significant effect on stability. The magnitudes of With these two exceptions, the elements in the
the offset and the K, and 4 gains determine the control path of the P+PR controller (figure 7-19) are
response and recovery characteristics [6,19,18,20]. the same as the ELFLO plus RESET controller
shown on figure 7-3.
The control parameters are interdependent. They
can be determined (approximately) using the The hypothetical response and recovery
stability analysis of Hancu et al. [15] (discussed in characteristics of the P+PR controller are illustrated
section 7-9), or through trial and error using on figure 7-20. A sudden increase of flow from
mathematical model simulation of the canal and upstream (figure 7-20a) arrives at the sensor
control system [5,20]. As a first approximation, the location (figure 7-20b). The water level rise
filter time constant, T,, is set equal to the travel produces a positive offset above the target depth,
time of the surge wave for the length of the canal Y, . The downstream controlled gate opens
pool. Initial values of the proportional gain can be (figure 7-20~) to release flow downstream
estimated using the procedure discussed in (figure 7-20d).
section 7-6. The approximation for the integral gain
is set initially to 0.01 per minute. The P+PR local automatic upstream controller was
applied to the Bypass Drain for the Yuma Desalting
Plant, located near Yuma, Arizona [7]. A simulation
7-17. P+PR Controller of the Bypass Drain Check Gate No. 1 is shown on
figure 7-21. Starting with an initial steady-state
The P+PR controller is identical to the ELFLO plus flow of 0.28 m3/s (10 f?/s), a step increase of
RESET controller except for the lack of a filter 0.51 m3/s (18 v/s) was made from the plant
control element in the control path. Some P+PR 3.2 kilometers (km) (2.0 miles [mi]) upstream at
controllers contain a high frequency cutoff filter time zero. The increased flow change arrived at
element. The only purpose of a high frequency check No. 1 at time 18 minutes. The check No. 1
cutoff filter is to dampen the effect of wind waves or gate opened its first increment 0.03 m (0.1 ft) at
other local disturbances. This filter is considered to time 20 minutes to begin transferring the increased
be a part of the signal conditioning and not a part flow downstream.
of the control action. A filter time constant of
100 seconds is usually adequate to filter out Figure 7-21 illustrates the controller performance
unwanted local disturbances. while transferring the sudden increase of flow
through check No. 1. The maximum rise of the
The P+PR controller’s purpose is to achieve local- water level at the check structure was about 0.3 m
automatic upstream control of the check gate of a (1 .O ft) and was within reasonable limits for a
canal system. The elements of the control path temporary emergency condition. The water level
and their arrangement are shown on figure 7-19. returned to the target, and a new steady-state flow
The first element, the sensor, is located a short condition was reached within a reasonable period.
distance upstream from the controlled check gate
7-30
Control Theory and Application
Target Level, YT
I The .Yystem
7-31
Canal Systems Automation Manual
Flow Upstream
- Offset = (YF-M)
- PR - Controller output, GR
- P - Controller output, GP
\
*Time
(C/J
F/o w Downstream
*Time
Transient Steady (D)
State 4 State
7-32
ControlTheoryandApplication
6.2 ,80
6. 1
Discharge , U/S
------1 _
z
5.6
Timse - Minutes
Figure 7-21 .-Bypass Drain response characteristics with the P+PR automatic upstream control system.
entered manually by the ditchrider or by a Periodic update procedures are incorporated at the
supervisory control system.The application of Q- master station to eliminate measurement and
Controllers at all the check gate structures of a calculation errors. The update procedure provides
canal system that is operated by the local-manual minor adjustments to the target flow to maintain
method is not recommended. The ditchrider would water levels within acceptable limits. Immediate
have difficulty obtaining the correct target flow and corrections for emergencies or abnormal operations
adjusting each check gate structure, including the can be accomplished by resetting the target.
correction for errors, on an hourly basis. However,
Q-Controllers can be successfully applied to: Generally, flow in an open channel can be
measured by calibrating gates or using weirs and
l Canal headworks structures flumes. Radial gate algorithms and differential
l Canal-side turnouts with appropriate gates head algorithms are discussed below. In addition,
or valves other technology such as ultrasonic flow
. Entire canals with supervisory automatic measurement may be used to monitor flow. In-line
control Q-Controllers for pipe delivery turnouts are
commercially available.
The application of the Q-Controller has its greatest
potential when the canal system is operated by the a. Radial gate algorithms.-A series of empirical
supervisory automatic method. The flow for the equations, referred to as algorithms, has been
entire canal system can be balanced on an hourly developed to accurately measure the flow through
basis. At the master station, a steady-state canal radial check gate structures [9]. The
mathematical model of the canal system is used to algorithms apply only to canal radial gates that are
determine the desired target flow for each check geometrically equal to those for which the
gate structure. A communication system transmits algorithms were developed. These discharge
the target flows to the remote terminal units (RTU’s) algorithms can be applied as a local-automatic Q-
located at each check gate structure. The RTU Controller for canal system check gate structures
maintains the required gate opening by local- as shown on figure 7-22. A microcomputer-based
automatic control. controller is needed at the site to continuously
7-33
r-
Canal Systems Automation Manual
COMPARATOR
_+AG=GD-GA _+ GDB
The System
calculate the required radial gate opening for the are complex. The controller needs sufficient
desired target flow. The calculation is based upon memory and an arithmetic coprocessor to obtain
the measurements of upstream water level, the solutions on a real-time basis.
downstream water level, and gate
openings-including gate geometry. The response and recovery of the Q-Controller
discharge algorithm technique application is
The comparator element determines if the gate(s) illustrated on figure 7-23. The flow arriving from
should operate (raise or lower) whenever the upstream at check gate No. 2 was scheduled to
desired gate opening, G, , differs from the actual change from 0 to 30.5 m3/s (100 f?/s) at time
gate(s) opening, G, , by more than the prescribed 0.5 hour. Therefore, the master station scheduled
deadband, D,,. Radial gate discharge algorithms the RTU’s target to change by the same amount.
7-34
Control Theory and Application
1 8.0
.- 6.0
0.0
1.0 1.5 2:o 2:5 3:o
Time - Hours
Figure 7-23.-CbController applying the discharge algorithm’s typical response and recovery characteristics.
As illustrated, the gate opened at time 0.5 hour and established as shown on figure 7-24a. For
increased downstream flow to 30.5 m%. The example, the calibration could represent a Parshall
upstream water deviation was insignificant; i.e., the flume, a weir, or a river gaging station.
scheduled arrival and gate operation times and the
magnitude of the changes were compatible. Next, the upstream controlled gate calibration (flow
versus gate opening) is determined. If the water
b. Differential-head algorithms.-The Q-Controller level upstream from the controlled gate is not
radial gate discharge algorithm technique is unique constant (e.g., at a reservoir), the upstream water
to canal-check radial gate structures. On many elevation should be included as illustrated on
canal systems, flow measurement facilities such as figure 7-24b. Usually, the calibration can be
the Parshall flume are used. A water depth determined from field data. However, the gate
measurement is used as a calibration of the rating curves can be developed theoretically by:
discharge rating. Employing the head versus flow
calibration uses the calibrated water level as the . Following the procedures developed by
target input. The Q-Controller is based upon a Shand [19,20]
unique algorithm which describes the head versus l Applying the radial gate discharge
flow calibration. algorithms [9]
The basic procedure to develop algorithms based The Q-Controller using the head versus flow
upon the head versus flow technique is as follows: technique employs the proportional mode of control.
Therefore, the proportional gain can be expressed
First, the calibration of the flow measurement as:
facility-water level versus flow-must be
7-35
Canal Systems Automation Manual
Upstream Depth
ERR0
Gate Opening
7-36
Control Theory and Application
where:
K, = +
t
B = intercept for figure 7-24~
B, = intercept of the intercept lines,
figure 7-24d
where: B, = intercept of the slope lines,
figure 7-24d
K, = proportional gain M = slope for figure 7-24~
G, = desired gate opening for the selected Mb = slope of the intercept lines,
flow, Q (figure 7-24b) figure 7-24d
Y, = water level of the flow measurement MS = slope of the slope lines, figure 7-24d
facility for the same discharge, Q
(figure 7-24a) For the family of curves shown on figure 7-24c, the
calibration of the proportional gain, K,, and the
Proportional gain, K,, equation 7.40, is plotted on desired gate opening, G,, may not be as linear as
figure 7-24~ as a function of gate opening. If the shown. It may be necessary to plot the data on
controlled gate upstream water level varies log-log paper to obtain the proper relationship.
significantly, then the results must include various Thus, equations 7.41, 7.42, and 7.43 would have to
selected upstream elevations, H, . Usually, one be expressed as a logarithmic function to achieve a
best-fit straight line through all the data points is not better best-fit representation.
sufficient to represent K, versus G, with reasonable
accuracy. Therefore, a family of best-fit straight The RTU solves equations 7.13, 7.41, 7.42, and
lines is needed for each selected upstream water 7.43 in reverse order as follows:
elevation, H, , as shown on figure 7-24~. The
proportional gain can be expressed as: M = H, M, + B, 7.44
K, = G, M + B 7.41 B = H, Mb + B, 7.45
where: K, = G, M + B 7.46
K, = proportional gain
G, = desired upstream controlled gate G, = K, V, 7.47
opening
M= slope of the best-fit straight line
B = intercept of the best-fit straight line when Equations 7.44 through 7.47 are only executed
the gate opening, G, , is zero when a new target, Y, , is desired. The 4 is based
upon the existing gate opening, G, . Therefore,
The values of the best-fit straight lines for equation 7.47 provides an estimate of the new
the slope, M, and the offset, B (derived from required gate opening, G,, and remains at this
figure 7-24c), are then plotted on figure 7-24d. A value until the next flow change; i.e., a new target,
best-fit straight line can now be determined for the I’, , is made.
slope and offset data as a function of the upstream
elevation, H, , as: Computation of the new gate opening (equa-
tion 7.47) could be in error because of:
M = H, M, + B, 7.42 l Errors in calibration
. Deviations from the best-fit algorithms
l Change of the upstream water elevation, H,
B = H, Mb + B, 7.43
To account for these errors, a correction algorithm
is used. The purpose of the correction algorithm is
to convert the water portion of the flow
7-37
Canal Systems Automation Manual
KS = G, 1’4. + B, 7.49
7-38
ControlTheorvandAmlication
Figure 7-26 shows the mathematical model a. Gate stroking.-Gate stroking is a technique
simulation of the system and for a step change in used to control transients in a canal subjected to
the target. The model included an interpolation variations in discharge or water level [12]. The
scheme to obtain the target in terms of the water term comes from a similar procedure used in
level, Y, , from a table developed by the Water closed conduits known as valve stroking. Although
Resources Division of the U.S. Geological Survey the term “stroking” as used in this context cannot
based upon a series of current meter measur- be found in the dictionary, its definition can be
ements. Periodically, the rating table was updated implied from the several meanings commonly listed.
to provide a correction to account for changes in For example, stroking is defined as: “any of a
the canal prism rating station. series of continuous or discontinuous efforts to do,
produce, or accomplish something, especially a
At time 10 minutes, the target flow was increased successful result.” Based on its technical usage
from 11.3 to 13.6 m% (400 to 480 ft3/.s). The and the general meaning of stroking, gate stroking
interpolation of the rating table increased the can be defined as: a continuous or series of
target, Y,, from 1.46 to 1.62 m (4.80 to 5.30 ft). At discontinuous gate motions that produce a
e-minute intervals, the Q-Controller calculates predetermined variation in discharge or water level
the desired gate opening, G, . The response in a canal.
and recovery of the water level and the gate
flow approaches the new steady state at time Gate stroking allows the rapid startup or shutdown
50 minutes40 minutes later. The step change of a canal without creating large disturbances in the
(increase) caused a large overshoot at 20 minutes.
Subsequent mathematical model runs indicated the
7-39
Canal Systems Automation Manual
COMPARATOR
DCGATE=CGATEE..,+CGCOR,,,,
CGA TEA = /-(CC{ 1) + CG(2 )7/Z. 0
YRES YCAN
L I I 1
v ( Max. WS -
I hrBi#
i. J..
I Controlled Gate/c
The System
Figure 7-25.-Big Horn Canal Headworks Q-plus controller differential head algorithms.
7-40
Control Theory and Application
(M) (Ft.1
1.8
1
0.0’ 0.0~~200
0 10 20 30 40 50 60 70 sb
Time - Minutes
Figure 7-26.-Big Horn Canal Headworks Q-plus errolr controller typical response and recovery characteristics.
water level. With gate stroking, a flow change can downstream end of the canal reach.
be made about 20 to 30 times faster than with Usually, the depth is held constant, but this
conventional manual operation techniques. Gate is not a requirement.
stroking also can be used to develop procedures 2. The depth is specified, as a function of
for rapid shutdown of canal systems during time, at the downstream end of each pool
emergencies. comprising the reach. In most studies,
these depths also are held constant.
The technique requires the solution of the unsteady 3. If turnout flows occur along the canal, their
equations of motion and continuity. Any compu- variation with time is also specified.
tational scheme which accurately calculates the 4. With given initial conditions and the
unsteady water surface profiles can be used. temporal variations specified above, the
Reclamation has chosen the method of unsteady-flow equations are solved for all
characteristics using a characteristic grid. The locations in each pool. Either steady or
advantage of the grid is that it is adaptive. That is, unsteady flows can be specified as initial
it adjusts itself to be closely spaced where the conditions.
water level varies rapidly and coarsely spaced 5. Finally, using the computed depths and
where the water level changes slowly. This method discharges at the ends of each pool, the
requires time-line interpolation at boundaries. variation of the gate openings between the
pools is computed as a function of time.
The method of solution is as follows:
The gate motions determined by this method are
1. The depth and discharge are specified, those required to produce the specified variations in
as functions of time, at the most depth along the canal reach.
7-41
-.
Canal Systems Automation Manual
Computer simulations have shown that the initiation . Minimize the input while a preassigned
of the gate motion is sequential, beginning with the output is achieved.
most downstream gate. The timing of the initiation . Maximize the output while a preassigned
of the gate motion corresponds to the wave travel input is achieved.
time in the canal. In general, initial motion of an . Maximize some functions of input and
individual gate is quite rapid with considerable output values, such as their difference
overshoot as shown on figure 7-27. Then, the gate (profit) or their ratio (return on investment).
motion becomes slower, gradually converging to
the final gate position. Variable-speed or Operational cost of a canal system supplied by
multispeed motors are required to accurately follow pumps can be large. For large power users, power
the irregular motion dictated by gate stroking. can be purchased at bulk rates during periods of
low demand. Costs can be reduced significantly if
For increases in flow, the characteristic of most of the pumping can be done during periods
overshooting and then settling on the desired final when low-priced rates are available. Pumping
gate opening is called creating push wafer. Studies during the low-rate periods is known as off-peak
of the Phellps Canal in Nebraska showed that the pumping. Conversely, pumping during periods of
time to increase the canal flow from zero flow to the high demand is known as on-peak pumping.
design discharge could be decreased from 3 days
for manual operation to about 3 hours using gate The objective of linear programming on a canal
stroking. system supplied by pumps is to satisfy scheduled
demands with minimum on-peak pumping. Thus,
b. Linear programming.-Linear programming is a on a canal system, input is minimized while a
standard technique of operations research. The preassigned output is achieved. This objective
purpose of linear programming is to obtain one of must be achieved within the physical constraints of
the following objectives: the canal. The constraints include:
18.0
T-Upstream Depth
16.0
74.0
3
k
z
12.0
1 i i i^._
i i i i i i i i i iii i i i
10.0
8.0
6.0
0.0 40.0 80.0 120.0 160.0 zoo. 0 240.0
T (Min.)
7-42
Control Theory and Application
. Drawdown criteria pool are straight lines. That is, backwater effects
. Minimum pool levels in each pump do not exist with the linear assumption. A change
forebay in discharge consists of a translation of the water
. Minimum pool levels at canal turnouts surface parallel to the original water surface level
. Maximum pool levels and a fluctuation of the water surface level about
. Positive heads at gates the center of the pool. In this manner, linear
. Maximum pump capacities relationships between the discharge and water
. Pump cycling criteria (number of starts in levels in each pool can be derived.
a given time period)
The procedure followed in the computations is to
As implemented by Reclamation, linear determine pump and gate discharge schedules that
programming is used to determine gate and satisfy demand and simultaneously minimize on-
pumping schedules in such a manner that peak pumping. Then, using linear discharge versus
operating costs are minimized [6]. For example, water level relationships, water level(s) schedules
linear programming predicts how on-line pumps are at each end of the pool are determined. From the
to be operated to minimize on-peak pumping costs. discharge and water levels, gate opening schedules
between pools are calculated.
With linear programming, hydraulic transients are
not considered. However, after gate and pump For the Granite Reef Aqueduct, Central Arizona
schedules are determined by linear programming, Project, gate opening schedules developed by
the amplitude of the resultant hydraulic transients linear programming did not produce large transients
can be examined to determine if they are [19]. The smooth operation can be attributed to
excessive. two factors: (1) only gradual changes in discharge
were allowed (hourly flow changes of less than
The methodology of linear programming was 15 percent of the design flow per pool) and
developed with the assumption that all of the (2) strict drawdown criteria (hourly water level
variables can be expressed as first degree changes of less than 3 percent of the design depth
equations or inequalities. The implication of this per pool).
assumption is that the water level profiles in each
7,-43
Canal Systems Automation Manual
BIBLIOGRAPHY
[l] Bureau of Reclamation, “A Summary Report on [9] Buyalski, C.P., “Discharge Algorithms for
Research and Development of a Canal Radial Gates,” Bureau of
Nonelectrical Gate Control,” Pacific Reclamation Report No. REC-ERC-83-9,
Northwest Regional Office, Boise, Idaho, Engineering and Research Center, Denver,
April 1977. Colorado, December 1983.
7-44
Control Theory and Application
1181 Schuster, J.C., and E.A. Serfozo, “Study [20] Shand, M.J., “Automatic Downstream
of Hydraulic Filter Level Offset (HyFLO) Control Systems for Irrigation Canals,” Final
Equipment for Automatic Downstream Technical Report HEL-8-4, Selection of
Control of Canals,” Bureau of Reclamation Control Parameters for the Hydraulic Filter
Report No. REC-ERG72-3, January Level Offset (HyFLO) Method, Hydraulic
1972. Engineering Laboratory, University of
California at Berkeley, August 1971.
[19] Shand, M.J., “Final Report-The
Hydraulic Filter Level Offset Method for the 1211 Yeh, W. W-G., L. Becker, D. Toy,
Feedback Control of Canal Checks,” and A.L. Graves, “Central Arizona Project:
Technical Report No. HEL-8-3, Computer Operations Model,” Proceedings of the
Program for System Simulation, Hydraulic American Society of Civil Engineers,
Engineering Laboratory, University of Journal of the Water Resources Planning
California at Berkeley, June 1968. and Management Division, vol. 106,
No. WR2, pp. 521-540, July 1980.
7-45
CHAPTER 8
COMMUNICATION SYSTEMS
COMMUNICATION SYSTEMS DESIGN and control are combined over the same
communication system, the overall system is
8-l. Purpose of Communication Systems usually referred to as a supervisory control and
data acquisition (SCADA) communication system.
Communication systems serve canal operations The SCADA type communication system provides
and maintenance by providing voice, alarm, the watermaster with the most flexibility in operating
telemetry, and control capabilities. These a canal system. The SCADA type communication
capabilities are essential for efficient and safe system provides alarm information, equipment
operation of a canal system. status information, and actual values for gate
positions, water levels, and flows throughout the
The voice communication system allows the entire canal system. With this information, the
watermaster to give instructions to ditchriders entire canal system operation can be automated,
related to adjustments of proper gate openings and creating more efficient use of the canal system and
water levels. The system also allows the ditchrider allowing maximum response to abnormal canal flow
to report operating conditions and canal system conditions.
abnormalities to the watermaster.
communication requirement will be discussed, as communication systems that are not suitable for the
well as how each layout can serve the canal particular canal system location can be eliminated
automation criteria in the most efficient manner. from the evaluation process.
Each type of layout will be discussed along with
selection criteria to be used when applied to canal Each of these criteria must be evaluated before the
automation. appropriate communication system can be selected
for the canal system automation. After the
Next, the types of communication channels will be selection of the proper type of communication
described, and how they are used for canal system, the design, installation, and quality of
automation projects will be described. The maintenance will determine the overall success of
information (voice or data) carried on a the communication system.
communication system is divided into channels.
Various types of communication channel The types of communication systems that are most
arrangements can be configured depending on the practical for canal system automation projects are:
requirements of the canal system operation.
. Metallic cable
Finally, important information will be presented to . Fiber optic cable
allow selection of the most reliable communication . Ultra-high frequency/very high frequency
system for the application. The information will (UHF/VHF) radio
include methods of protecting the communication . Microwave
system equipment from various electrical and
environmental hazards. Because the communi- The Bureau of Reclamation (Reclamation) has used
cation system is the major link between the canal these types of communication systems in canal
system and the operational headquarters, it must automation projects, and they have proven to be
be designed to provide reliable service to the the most economical and reliable. Although not
project. A communication system used to provide used by Reclamation to date, cellular phone
the important control and data acquisition technology appears to have some application in
information for the canal automation project must SCADA systems.
be extremely reliable. Because the canal
operations directly depend upon the ability of the Other types of communication systems sometimes
automatic control system to determine the actual used for canal system automation under certain
canal condition at any time, loss of communications circumstances are:
will result in serious degradation of the automatic
control system. . Leased line
. Satellite
. Meteor burst
8-3. Selection Factors
8-2
Communications System Design
the metallic cable path. The discussion that follows cable damage or setting up data levels. Buried
deals with the most basic use of metallic cable cabte system cable-loading techniques, which are
used for transmitting unmultiplexed voice frequency described in the following section on system
signals. design, should resemble those used for overhead
cable.
On new installations where trenching is a viable
option, serious consideration should be given to
using buried cable for the transmission of voice and 8-S. System Design
data communication. Reclamation communication
designers prefer buried cable when communication The twisted pair metallic communication cable uses
security is important or where a series-type multiple pairs of copper wires to carry electrical
communication system is required. signals (voice or data) from one place to another.
The number of wires in a cable varies from a single
For example, if a remote check structure needs to pair (two wires) to hundreds of wire pairs. The
communicate with an adjacent check structure, then cable pairs are bundled into a compact cable used
buried cable would be ideal; i.e., a series circuit. for either overhead or buried installation.
However, if the remote needs to communicate
with a central computer 48 or 84 kilometers (km) The practical transmission length of metallic twisted
(30 or 40 miles [mi]) away, then radio would be a pair communication cable depends upon the
better choice (i.e., a hub or spoke type of electrical signal attenuation characteristics of the
communication circuit configuration). cable. The transmission distance is 24 to 32 km
(15 to 20 mi) based on a 20-decibel margin
Rights-of-way must be obtained and cleared prior to between the transmitted and received signal. The
considering buried cable. Trenching is expensive; transmission distance can be improved by applying
therefore, buried cable should be used primarily for signal conditioning equipment to each twisted pair.
new installations (i.e., along canals or siphons) The addition of signal conditioning equipment will
where the government owns or has right-of-way improve the frequency response of the cable.
privileges. Applying signal conditioning frequency compen-
sation to a twisted pair cable system is called
Because the lifetime of buried cable is estimated loading.
around 20 years, the cost per year becomes
attractive when compared to radio systems, which Loaded metallic twisted pair communication cable is
have an equipment lifetime of some 8 to 8 years. used when longer transmission distances are
required. Loading coils are connected in each
Care should be used in the placement of the cable twisted pair, and the loading coils are designed for
in the trench and the splicing techniques used certain load coil spacing. The standard load coil
because water leakage and cable damage by spacings are 914, 1,372, and 1,829 meters (m)
rodents can become a problem with buried cable. (3,000, 4,500, and 8,000 feet [ft]). The loading
systems carry designations of B for 914-m
Cable splices should be raised above ground using (3,000-ft) spacing, D for 1,372-m (4,500-ft) spacing,
pedestals, and the cable should be protected from and H for 1,829-m (S,OOO-ft)spacing. The loading
damage, heavy equipment, large rocks, etc., during system designation is followed by a number that
the final filling of the trench. Protective cable designates the inductance of the loading coil in
coverings might be required when communication millihenries. A number preceding the loading
cable is buried in rodent-infested areas. system designation indicates the gauge of the
twisted pair wire. Therefore, a designation of
Be sure to leave some extra unused cable pairs for 19-H-88 loading system indicates the loading is for
expansion and replacement. Four-wire circuits No. 19 American Wire Gauge (AWG) wire size at
should be used for the same reasons as discussed 1,829-m (8,000-ft) spacing using loading coils with
in the “Four-Wire Versus Two-Wire System” 88 millihenries of inductance. The loading coils are
section. The cable should be frequency manufactured in 44-, 88-, and 88-millihenry sizes.
compensated for the highest data bit rate to be
used on the cable. A couple of pairs for an An H-88 loaded metallic twisted pair cable can
operation and maintenance channel will be helpful handle voice communications for 32 to 97 km (20
when maintenance personnel are checking for to 60 mi), depending upon which AWG wire gauge
8-3
Canal Systems Operations Manual
is used. Data communications using audio tones Tables 8-l and 8-2 illustrate the characteristics of
can be transmitted a distance of 13 to 40 km (8 to nonloaded and loaded cable pairs. The column
25 mi) over the same loaded twisted pair cable. headed distortion penalty has been developed by
measurement and experience and represents the
Loading the twisted pair cable will approximately signal distortion for factors that influence the signal
triple the transmission distance over the same integrity. The 1,OOO-hertz signal attenuation caused
unloaded twisted pair cable. Additional by the cable impedance represents the largest
transmission distances are achieved using signal distortion factor. The distortion penalty is
amplifiers to boost the signal strength when the almost insignificant when loading is applied to the
decibel loss reaches about 24 decibels for voice cable and the signal distortion is caused almost
communications and 10 decibels for data entirely by the wire pair attenuation.
communications.
Note: uF = microfarad, dB/mi = decibels per mile, kHz = kilohertz, res = resistance, Nkm = ohms per kilometer,
dB/km = decibels per kilometer.
Capacitance
Wire per cutoff Z, at Distortion
Loading size 2 frequency 1 kHz penalty
method AWG W-W (Q dB/km (dB/km)
8-4
Communications System Design
The H-88 loading system provides the best overall the B-88 loading system is a distinct disadvantage.
frequency response and attenuation improvement The cutoff frequency is about 5,000 hertz, and coils
when the required number of loading coil locations are required every 914 m (3,000 ft) * 2 percent.
and costs are considered. The H-88 loading The H-44 loading system may be desirable in
system requires 88-millihenry coils located every special cases where lower impedance and relatively
1,829 m (6,000 ft) f 2 percent. The cutoff high cutoff frequency are needed for impedance
frequency is about 3,500 hertz, and this loading matching purposes to other transmission systems.
method is used primarily for loops and trunk circuits This loading method requires 44-millihenry coils
having a total distance greater than 5,486 km located every 1,829 m (6,000 ft) f 2 percent. The
(18,000 ft). cutoff frequency is about 5,000 hertz. It is used for
loops having a total length greater than 3,658 m
The D-88 loading system has essentially the same (12,000 ft).
attenuation and impedance characteristics in the
lOOO-hertz range as the H-88 loading system. Each end section of a metallic twisted pair
D-88 loading is desirable on twisted pair cables communication circuit needs to have loading coil
having a high mutual capacitance (about spacing equal to one-half of the required distance
0.09 microfarad per mile or higher). This loading for the loading method used. For example, an
provides an impedance characteristic nearly H-88 system should consist of 914 m (3,000 ft) of
identical to that of the low capacitance cables cable from the start of the communication circuit to
loaded using the H-88 system. the first loading coil location and 1,829-m
(6,000-ft) spacing between loading coils thereafter.
The D-66 loading system requires 66-millihenry
coils located every 1,372 m (4,500 ft) rt2 percent.
The cutoff frequency is about 4,500 hertz, and this 8-6. Overhead Installations
wider frequency range allows higher data rates to
be transmitted over the cable. It is used for loops a. Cable type+-Two types of construction are
and trunk circuits having a total distance greater used for overhead cable systems. One requires
than 4,115 m (13,500 ft). that the cable be attached to a support strand
strung between the poles. The other is a self-
The B-88 loading system is justifiable for use, supporting construction that is sometimes called
based on the number of loading coils required and “figure 8” cable. A typical figure 8 cable is shown
cost, only when the objective of the loading system on figure 8-1. The Rural Utilities Services (RUS)
is to obtain a lower attenuation than is practical with has developed specifications that classify overhead
the H-88 or D-88 loading systems and where a cable types that are suitable to either installation
substantially higher cutoff frequency is also
required. The higher characteristic impedance of
rJACKET
High Moiecular Weight Polyethylene
MESSENGER
/ /- 7 Strand Extra Hiah Strenath
Galvanized Steel _ 2
INSULATION
SHIELD
Aluminum Tape
CORE WRAP
Non-Hydroscopic Dielectric Tape
I I
Canal Systems Operations Manual
method. The cable manufacturers supply cable exceed 300 volts root mean square (rms). The
that is constructed in accordance with the RUS grounding intervals will vary according to the power
specifications. line voltage. The grounding hardware should be
installed at the pole locations. Ground rods will
The overhead cable that requires a separate have to be driven into the ground using sufficient
supporting wire or messenger is covered by RUS numbers of ground rods to achieve a ground
Specification PE-22. This cable core can be resistance of 5 ohms or less. Coordination of cable
furnished in twisted pair configurations from 6 to installation with the local power line utility is also
900 pairs. The cable is constructed using 19, 22, recommended because the utility company can
24, or 26 AWG size wires to make up the core. The mitigate induced voltages.
size of the wires determines the number of pairs
that are assembled into one cable. c. Splicing and splicing closures.-The use of
splices in communication cable systems should be
The figure 8 type of overhead cable construction is kept to a minimum. The cable should be
covered by RUS Specification PE-38. This cable purchased in the longest reel lengths possible. The
core can be furnished in twisted pairs from 6 to splices should be made on the poles to allow
300 pairs. The cable is constructed using 19, 22, access to the cable splice closure. The splice
or 24 AWG size wires to make up the core. joints should be covered with insulation equal to
Smaller sizes are not used in this type of cable that on the conductors, and the integrity of the
design because of the tensile strength required for cable messenger should be maintained. Splice
installation. closures should not allow water to enter into the
splice, and the closures should be of the re-
Both cable types are constructed with an armor enterable type.
shield to protect the cable core from induced
electromagnetic and electrostatic fields. The shield
construction is either plastic-covered aluminum or 8-7. Direct Buried Installations
fully annealed solid copper that is corrugated and
applied longitudinally over the core covering. a. Cable types.-The construction of the direct
buried cable differs significantly from the overhead
No. 19 AWG is the recommended wire gauge for cable type. The cable construction must allow
overhead cable. This gauge provides the desirable protection from moisture entry into the conductors,
mechanical strength and sufficient cable pairs for and it must allow protection against rodent damage.
canal automation communication systems. The RUS has developed specifications that classify
direct buried cable into types that are suitable for
b. Installation methods.-The overhead cable is various installation methods. The cable
attached to the poles using an independent manufacturers supply cable that is constructed to
messenger cable. The messenger cable can be the various RUS specifications.
installed on the poles first, and the twisted pair
overhead cable can be laced to the messenger The major differences in direct buried cable
using steel lacing wire. The messenger is construction are the gauge of outer shielding used,
supported at each pole using clamps, and the cable number of jackets, gauge of armor shield, and the
is supported by the lacing wire. The figure 8 cable use of a filling compound. The direct buried cable
is installed by attaching clamps to the integral is susceptible to rodent damage, installation
messenger cable at each pole. damage, moisture penetration, and abrasion. To
protect against these hazards to the cable, special
The figure 8 cable installation requires only one construction is used for direct buried cables. Direct
pass to install the cable on the poles. Using a buried cable is constructed with and without a filling
separate messenger requires two passes to install compound. Figure 8-2 shows the construction of a
the cable on the poles. typical air core direct buried cable. Figure 8-3
shows the construction of a typical filled direct
Special grounding precautions must be taken when buried cable.
the communication cable is installed on poles that
carry power lines. The communication cable shield The direct buried cable construction shown on
should be grounded at regular intervals to prevent figure 8-2 is a double-jacketed type. This
induced power line voltage from becoming too high construction conforms to the requirements of RUS
on the communication cable. The induced voltage specification PE-23. The corrugated metal shield
developed on the communication cable should not thickness determines whether the cable is
8-6
Communications
SystemDesign
OUTER JACKET
High Molecular Weight
Polyethylene, Surface-Marked
INNER JACKET
Hi’gh Molecular Weight Polyethylene
/
INSULATION
High Density Polyethylene
SHIELD / / \
Corrugated Metal Tape --/
CONDUCTORS
CORE WRAP Solid Annealed Copper
Non-Hydroscopic Dielectric Tape
OUTER JACKf T
High Molecular Weight
Polyethylene. Surface-Marked
INNER JACKET
High Molecular Weight Polyethylene
i / 7 FILLING COMPOUND
susceptible to damage by gnawing rodents. The to prevent any moisture and water entry into the
shield must be corrugated to enhance cable cable core and to prevent any moisture that enters
flexibility and to minimize shield metal fatigue. The the cable from migrating along the core length.
inner jacket provides additional mechanical The filling compound is petroleum jelly based and
protection, dielectric strength, and water ingress completely fills the cable core space between
protection in case of outer jacket damage. insulated conductors and between the core and the
core wrap, including the core wrap tape overlap.
The direct buried cable construction shown on The armor shield protects the cable core from
figure 8-3 is a double-jacketed filled type. This induced electromagnetic and electrostatic fields.
construction conforms to the requirements of RUS This shield also protects the cable from damage
specification PE-39. The double jackets and armor caused by gnawing rodents and cable installation
shield provide the same characteristics as they do hazards. To provide adequate protection from
for the air core cable. The filling compound is used rodents, the metal shield must be 0.25millimeter-
8-7
Canal Systems Operations Manual
(mm) (O.Ol-inch- [in]) thick fully annealed solid Cable should be handled carefully at all times to
copper, or 0.15mm- (0.006-in-) thick bimetal avoid damage and should not be dragged across
(copper/iron/copper, copper/stainless steel). Other the ground. The ends of the cable should be
types of armor shields are also used to provide the sealed with manufacturer recommended caps to
same protection, but the copper and bimetal are prevent moisture penetration. The ends of the
the most commonly used materials. cable should be terminated or sealed immediately
after cutting the cable if a splice is not made at that
The type of cable construction used for a canal time. The minimum bending radius of the particular
communication system will depend on the soil in cable should not be exceeded.
which the cable is being buried. A desert or dry
location would indicate the use of the air core c. Splicing and splicing closures.-The use of
cable. The filled cable should be used whenever splices in communication cable systems should be
wet soil is anticipated at the depth of the cable kept to a minimum. The cable should be
installation. The recommended wire gauge for the purchased in the longest reel lengths possible. The
buried cable is No. 19 AWG. This gauge provides direct buried cable should be spliced only in above-
the desired mechanical strength and electrical ground splice enclosures or buried splice vaults
properties for buried cable communication systems with manhole covers. The splice joints should be
used for canal automation systems. covered with insulation equal to that on the
conductors, and the integrity of filled cable should
b. Installation methods.-The installation method be maintained. Splice enclosures should not allow
used to bury the communication cable is important water to enter into the splice, and the enclosures
to the success of the entire buried cable should be of a re-enterable design.
communication system. Early failure and cable
outages will certainly occur if the cable is not d. Metallic cable testing.-Metallic cable
installed properly. Two methods are popular for communication systems should be thoroughly
installing multipair cable systems. tested before and after installation. The methods
used to install metallic cable communication
One method involves the use of a special plow to systems expose the cable to potential damage,
install the cable without any excavation. The reel resulting in poor communication signal
of cable is pulled behind a plow that cuts the earth, transmission. The cable jacket can be damaged,
lays the cable, and returns the earth over the cut. causing the twisted pairs inside to be disturbed.
Using this method, cables can be installed at Overtensioning the cable can cause failures in the
depths of 0.6 to 0.9 m (2 to 3 ft). The other twisted pairs. Bending the cable too sharply can
method is to dig a trench and lay the cable in the cause twisted pair failures. The splicing process
trench. The cable is covered with a sand cushion, can cause pair mismatch and failures. These types
and the trench is then backfilled. This method can of cable failures can occur during both overhead
be used to install cables at depths of 1.5 m (5 ft) or and buried types of installations.
less.
The best method to detect and eliminate problems
The best technique for installing the cable in the with metallic cable communication systems is to
trench is to use a crawler tractor with a side boom test the twisted pairs before and after installation.
on which the reel is mounted. The cable feeds off The results of these tests can be compared, and
the top of the reel directly into the center of the any differences can be investigated to determine
trench without contacting the side walls or being the exact location and cause of the problem.
dragged along the bottom. The cable should
always be removed from the reel by turning the
mounted reel and not by pulling the cable off the 8-8. Applications
reel. The cable should be snaked into the trench
with sufficient slack to allow for ground settling and Metallic cable is probably the most preferred
shifting during the life of the cable installation. At communication system for systems using real-time
least 0.6 m (24 in) of slack should be left whenever or remote control, telemetry, and alarms. Because
a buried cable enters or exits a conduit. The metallic cable provides the versatility of separate
additional slack will reduce the strain on the cable circuits for alarms and data, it can easily be used in
during backfilling. a party line or radial configuration.
8-8
Communications
SystemDesign
8-9. Advantages and Disadvantages Reclamation designers normally consider fiber optic
cable when items such as large bandwidths, low
Advantages: noise, electrical isolation, greater unrepeatered
spans, lighter cable, and better electrical isolation
User owned; user has complete control. are important.
No Federal Communications Commission
(FCC) licensing required. Very basic fiber optic cable systems have a
Suitable for radial or party line practical span length of 914 m (3,000 ft) for step-
communications. index type fibers and 7,315 m (24,000 ft) for graded
Medium speed data rates and bandwidth index types.
available to 1,200 bits per second.
Long life-20 to 30 years. Telecommunication systems normally use a graded
System can be designed for expansion at index type cable because of its greater data
low cost by installing additional future pairs. handling capacity over very long lines. Step-index
Additional pairs allow for easy channel fibers can be used for data links equal to or less
expansion capability. than 914 m (3,000 ft).
A pair can be used for voice
communications.
In general, the major loss occurs in the actual
Suitable for continuous data scanning
supervisory control and data acquisition splicing of the fibers. Three splicing methods are
systems. currently being used:
. Mechanical
Disadvantages:
l Glued
Significant initial installation costs. l Fused or welded connections
Expensive to locate and repair cable faults.
Cable is susceptible to vandalism, weather, Mechanical connections have from 1 decibel to
and excavation. 2 decibels of loss per connection; epoxy or glued
Lightning protection for each pair is connections have from 0.5 decibel to 1.5 decibels
required. of loss per connection; and fused connections run
Cable shielding and special grounding is 0.1 to 0.4 decibel per splice. This additional loss
required to prevent interference or must, of course, be added to the loss per unit
personnel injury from electromagnetic length of the basic cable.
fields.
Special design and filtering is required to Fiber optic communication links are normally
reduce crosstalk between cable pairs. designed by: (1) considering the system bandwidth
Multipair cable requires special splicing requirements (i.e., number of channels and
enclosures; splicing the cable is time bandwidth of each subchannel); (2) the
consuming for high pair count cables. signal-to-noise ratio (i.e., maximum data speed
High pair count cables can only be required); and (3) the distance between the
purchased in short lengths (because of size endpoints of the circuit or channel. The optical
limitation of reels), so more splices are transmitter power required is determined by
required.
considering the bit-error rate (or signal-to-noise
ratio).
FIBER OPTIC CABLE Plastic fibers are used for spans of 91 m (300 ft) or
so at data rates of 6 megabits per second or less.
8-10. Background
Plastic-clad glass fibers are used for communi-
cation links of 27 to 457 m (90 to 1,500 ft).
Fiber optic cable systems are well suited to
Low-loss fibers are used for links up to about
applications requiring large bandwidth, low noise,
7,315 m (24,000 ft), and bandwidths of
high immunity to electromagnetic and electrostatic
500 megahertz are common for standard 91Gmeter
interference, and high speed or data rates. Fiber
(3,000-ft) sections or spans.
optic cable is appropriate for applications with an
unusually high data rate or where required to
overcome the problems as noted above.
6-9
Canal Systems Operations Manual
Full duplex repeaters can be used every 914 m Because of the present cost and complexity of fiber
(3,000 ft) or so to maintain the 56-kilobit-per- optic cable, fewer suitable applications exist
second to 2-megabit-per-second spectrum. The compared to metallic cable. However, if the past is
repeaters can adjust for up to 28 decibels of link any indication, the cost of fiber systems will
loss. continue to drop with fiber possibly replacing many
metallic wire installations at a lower cost. At
Some typical applications of fiber optics would be: present, a good fiber application might be the link
control of valves and relays at remote installations between the control console and the master station
from a central point; 9,600-baud computer-to- where the master control console is not colocated
computer links; transmittal of data through hostile with the master station computer and master to
environments of hydroelectric dams, switchyards, remote communications.
etc.; 3,600-baud peripheral-to-central-computer
links, and to fill communication link requirements
through explosive or corrosive environments. 8-13. Advantages and Disadvantages
8-10
Communications
SystemDesign
l User has complete control over do not use equipment classified in the strictest
communication system. sense as UHF. UHF radio systems are line of site
l High security against undesired monitoring and have a range of 32 to 48 km (20 to 30 mi) on
of communications. flat terrain. Licensing can become difficult for more
densely populated locations and for frequencies in
Disadvantages: conflict with local military and commercial needs.
Range and signal quality may be improved by
. High initial cost of installation. specifying higher-powered transmitters, directional
. Repeaters require power, may be antennas, and/or antennas located at higher
incorporated in cables; power requirement physical elevations such as on top of buildings,
reduces immunity to lightning, particularly steel towers, or mountains. The legal requirements
when incorporated in cables. of staying within the allowable transmitter,
. Electronic equipment is required to convert government licensing restraints, and the availability
electrical signals to light and back to and cost of good antenna locations should also be
electrical signals. considered.
. Special equipment is required for testing
and maintenance. Additional radio range and mountainous coverage
. Repair from excavation damage more may be obtained by the use of repeaters.
complicated. However, repeater installation cost may be
. Special termination and connector excessive or prohibitive in cases where potential
equipment required at termination points.
repeater sites are privately owned, costly, or
unavailable; sites are located in geographically
UHF/VHF RADIO challenging terrain with no existing roads or
commercially available power; and access during
winter months can be accomplished only by aircraft
g-14. Background
or snowmobile. To be reliable, repeater sites
UHF/VHF radio systems are well suited to should also be furnished with hot standby repeater
applications requiring smaller bandwidths and lower units and backup power in case of primary.power
data rates. UHF/VHF radio systems can be used failure.
to carry voice frequency communications and data.
In general, this type of communication system is Repeaters are licensed in frequency pairs rather
the most economical of all systems, especially than a single frequency because repeaters operate
when no or very few repeaters are required, and in the full duplex mode, receiving on one frequency
frequency licensing is readily available. The final and simultaneously retransmitting on a different
system end user should be considered at the time frequency. Repeaters also require additional
of licensing to avoid unnecessary cost and antenna equipment, such as duplexers, which
aggravation. For instance, in some cases, a prevent transmitter signals from feeding back into
Federal agency will procure licensing, furnish and and overloading the receiver connected to the
install the system, and upon completion, turn the same antenna. Circulators are also required to
system over to a private water district as the prevent the active transmitter signals from feeding
permanent system owner and operator. Because back into and overloading an idle hot standby
the Federal agency no longer owns the radio transmitter which, when present, is connected to
system, the water district will, in some cases, be the same antenna.
required to relicense the system, causing
interruption of system operations, or even worse, a When designing the system, consideration should
total shutdown of the radio system. be given to dual use of the assigned frequency for
both voice and data. The data transmissions are
limited to 3 to 5 seconds per minute, allowing voice
S-15. System Design communications between mobile radio units during
the remaining time. The optimal situation for this
type of system would involve infrequent and
UHF/VHF radio systems span the frequency range
minimal data transmittal. Major reporting from
from 30 to 300 megahertz (VHF) ahd 300 to
remotes could be scheduled for night or idle voice
3,000 megahertz (UHF). UHF frequencies above traffic times.
1,000 megahertz overlap the microwave band and
8-11
r-”
Canal Systems ODerations Manual
Lower cost UHF equipment in the 850-megahertz . Licensing may be difficult, costly, and
and above band could allow more dedicated lengthy.
channels and possibly higher data rates. These . Repeater site installation may be difficult
higher frequency systems are even more directional and costly.
than the 390- to 470-megahertz UHF bands. This
equipment can also link a remote location control
site to a cluster of hard-wired controllers. MICROWAVE
8-12
Communications
SystemDesign
physically separate radio wave signal paths, dual . Immunity to electromagnetic and
frequencies, and backup power in case of primary electrostatic fields.
power failure. l High bandwidth or data rate capability.
l Suitable for continuous scanning of
New microwave installations are of the digital type, supervisory control and data acquisition
in line with an overall industry trend toward all systems.
digital; older analog systems are being phased out l Can handle multiple voice and data
as they become inoperable or obsolete. Digital channels at the same time.
microwave has the added advantage that time . Large expansion capability.
division multiplexed systems (like Tl and T3) can . 20- to 30-year life, comparable to metallic
be interfaced directly to the digital microwave with cable.
no digital to analog modems required. The 9 User has complete control over
compatibility with digital communications industry communication system.
standards allows dynamic bandwidth, dynamic . Higher security against undesired
routing, and mixed analog and digital source media monitoring of communications when
to be transmitted digitally through a single compared to UHF/VHF radio.
communication path. Off-the-shelf digital
microwave is available to link computer local area Disadvantages:
networks (LAN’s) easily with no repeaters if LAN’s
are located within line of sight. This link can be High initial cost of installation when
accomplished sometimes at a considerable savings compared to UHF/VHF radio.
compared to telephone company wideband leased Licensing may be difficult, costly, and
lines. lengthy.
Repeater site installation may be difficult,
costly, and lengthy.
8-20. Applications Maintaining radio signal reliability requires
more care in design and installation.
Microwave systems are used in applications that Structures (such as high rise office
require large bandwidths and high data rates. buildings, etc.) erected in signal path after
Such applications might be between a master microwave antenna installation may cause
station and powerplant or pumping plant where system to become inoperable.
large amounts of data are transmitted on a frequent Not cost justifiable for small bandwidths
basis. Another application would be as a part of a and data rates.
redundant data signal path from remote sites back
to the master station simultaneously transmitting
large numbers of both voice and data channels. LEASED
For smaller bandwidths and data rates, microwave
is not cost effective, and UHF/VHF radio or other 8-22. Background
communication systems should be considered.
Virtually any communication system can be leased.
Perhaps the most common commercial leased
8-21. Advantages and Disadvantages system is known as a Bell Telephone Type 3002
circuit, which is a customer-dedicated private line.
Advantages: This service is available with a one-time installation
charge and a monthly charge per circuit. Some
. Installation time is small compared to cable. installations may also require a construction charge.
l System not susceptible to interruptions A Type 3002 circuit can be either an unconditioned
caused by cable faults and breeches. or a conditioned circuit. The type and speed of the
l System expansion achievable at a transmitted data will determine the degree of
minimum cost compared to cable. conditioning involved.
l System spare capacity can be coshared,
and the cost can be shared with other
agencies
8-13
Canal Systems Operations Manual
8-14
Communications
SystemDesign
Three modes of operation are currently available: The user is responsible for purchasing and
maintaining the remote data platform, which must
l Interrogated be type-approved by NOAA. The system is
l Self-timed designed to operate with earth-based transmitters
. Emergency (i.e., threshold detection) having effective radiated powers (ERP) of
50 decibels (maximum).
Bit-error rates of 1 x 10e5can be expected using
this satellite, and the data must be limited to status The spacecraft’s transponder can handle as many
because no command or control signals can be as 10,000 transmissions each hour if they are
initiated by the ground stations to the remote data limited to 30 seconds each. Domestic users have
platforms. access to 200 channels, and 33 channels are
available for international users. Data bit rates
The GOES system currently has five satellites in must be held to 100 bits per second or less.
earth-synchronous orbit. The satellites are
located at longitudes of 90.5” west, 112.5” west, Data recovered from the remote data plat-
130” west, 135” west, and 178” west. forms can either be received directly by a
1,894.45-megahertz receiver and demodulator (at a
level of -169 *lo decibels) or can be obtained from
The satellite system provides the following services: control centers located in California, Missouri,
Maryland, or Florida using either a full-time
l Returns both visible and infrared pictures of dedicated circuit, a dial-up 1,200-baud line, or a
the earth’s surface dial-up 11O-baud line. The direct dedicated line
. Receives and retransmits weather handles data at a nominal 2,400-baud rate, full or
information half duplex, ASCII, odd parity, and is
nontransparent.
. Measures the energy and trajectory of
incident space particles
. The 1,200-baud dial-up circuit operates at
Receives and retransmits data from data
120 characters per second, half duplex,
collection platforms located throughout the
asynchronous ASCII, even parity, and must have
United States
the following modem options:
Requests for use of the satellites are made to . “Auto-answer” line discipline
National Oceanic and Atmospheric Administration . “Answer-back” memory
(NOAA) and are coordinated by Reclamation’s
l Bell 202C modem or equivalent
Infrastructure Services in Denver, Colorado.
8-15
Canal Systems Operations Manual
The 1 IO-baud dial-up circuit operates at communication uses the packet format for
10 characters per second, half duplex, communications. Figure 8-5 is a diagram of a
asynchronous ASCII, and has even parity. remote data collection platform.
8-16
Communications System Design
Sensors J Signal
Modu laf ion Input
Meteor burst takes advantage of the fact that radio fast data rate either upon request or based on a
waves are reflected off of the ionization trails of time schedule. The receiving station (remote or
meteors which enter the Earth’s atmosphere. master) then verifies the data using the verification
Because of the relatively short time the data in the packet and responds with a confirmation
communication path is established and randomness or re-requests the information. Other stations
of those paths, the messages must be very short. ignore the message unless they are in the routing.
Packet communication techniques are used with This extensive “hand shaking” can cause delays in
meteor burst to provide the required short communications and is not appropriate for real-time
messages. The data are placed in a “packet” or remote control of irrigation facilities. Meteor burst is
data package along with routing and verification appropriate for a system where the canal-side
data. The data are then transmitted repeatedly at a
81-17
Canal Systems Operations Manual
controllers are downloaded with the required control data acquisition system are two typical examples.
parameters and are able to maintain control Both of these systems are comprised of over
independent of the communications link. 100 remote stations with periodic reporting
Meteor burst can provide message communication requirements of about 2 hours or greater. No
in addition to telemetry and limited control. A meteor burst applications exist on canal systems.
keyboard-entered message and routing information
are entered into the master or remote computer.
The message is formulated into one or more 8-33. Advantages and Disadvantages
packets and then handled by the system like a data
packet. The system software analyzes the packets Advantages:
and formats the messages, data, and system
information for use by the users. . Relatively easy to install.
. No repeater sites required.
. User owned.
S-31. System Design . Best suited for data acquisition and
downloaded control data for canal-side
A meteor burst system is comprised of one or more controllers and telemetry.
master stations and a multitude of RTU’s. Each . Single frequency required (party line).
site master or remote is comprised of a transmitter, l Specific sites can be addressed.
receiver, power supply, antenna system, and a . Provides limited text communications via an
microcomputer. The RTU’s can be battery/solar ASCII terminal.
operated because they only transmit for very short
periods of time. Only one frequency allocation is Disadvantages:
required for the system because the master
maintains network control and the frequency is . Licensing from FCC required.
time-shared. The microcomputer is required to . Complex equipment requiring skilled
handle the message formatting, system protocol, maintenance and repair.
data checking, and communications with the . Not suitable for continuous-scan SCADA
controller or operator terminal. The system can use systems.
both line-of-sight and meteor burst as determined . Extremely slow data response time-not
by the network geography. The master station also suitable for real-time remote control.
includes the man-machine interface (display and . Not suitable for voice, but teletype
software) to provide the data collected, usually in conversation is possible.
engineering units. The RTU’s also include the
various components to collect data such as water
level, temperature, and wind speed. CONFIGURATIONS
The meteor burst portion of the system is usually 8-34. Configuration Types
bought as a package, which includes the necessary
radio equipment, packet processor, and data The two general types of communication
handling processor. Other equipment includes configurations or networks are:
power supplies, antennas, various transducers, and
wiring. l The party line system, in which a single
channel serves all the RTU’s. In the party
line system, each RTU has a specific
8-32. Applications address. The party line system requires
communications overhead to handle remote
Meteor burst is a logical choice for the collection of addressing and can only service one RTU
water levels, rain, or snow data, and simple on-off at time. A party line does allow direct
control. The snow telemetry (SNOTEL) systems in communication between RTU’s for systems
Washington-Oregon and the Egyptian Nile River that require it.
8-18
Communications System Design
8-19
Canal Systems Operations Manual
full-duplex type systems. On larger multipoint . If two or more channels are carrying the
circuits (i.e., greater than six points), four-wire same information, then the power of each
channels are required to prevent “singing” or channel must be reduced by a factor of l/n
oscillations and high-level echoes. to reduce crosstalk between the channels.
That is, if redundant data channels are
Four-wire channels can be used to advantage on used (to improve reliability), then the power
multipoint polling systems when the RTU’s do not in each channel must be cut in half; i.e., by
need to communicate with each other. Some of 3 decibels. In fact, the equation -10 log
these advantages include faster turnaround times of 10 (n) decibels can be used to calculate the
the data, more possible points, and a prevention of reduction in per channel power for any
false RTU startups caused by crosstalk. Most value of subchannels.
Reclamation microwave channels are designed to
accommodate four-wire ear and mouth (E&M) type Each microwave channel will require a total of six
circus’; or channels. wires to interface; i.e., two wires for the transmit
signal, two wires for the receive signal, and one
Normally, two-wire channels are used for telephone wire each for the E lead and the M lead. The
voice channels and data circuits (half/duplex) using signaling leads are referenced to circuit ground for
acoustic coupled modems. Echoes on two-wire the return paths.
channels may cause intersymbol interference to
data streams or false startup of the FiTU’s, thus All circuits should be protected by using 3-mil gaps
limiting the data bit rate of the proposed control (or equivalent) between each conductor and
system. ground. The protectors should operate at 350 volts
rms or 500 volts peak.
Data systems that use a central computer facility
transmitting to two or more remote terminals (the The mainframe terminal levels for the four-wire
RTU’s do not transmit back to the computer) could circuits should be set at a level of +7 decibels on
use a two-wire simplex channel. A four-wire the transmit pair and -16 decibels on the receive
channel is required when a control system uses the pair. The mainframe terminal levels for the
so-called “slave” configuration (where the computer two-wire circuits should be set at -16 decibels.
talks, to all of the remote units at one time, and the
RTU’s talk only to the central computer). b. Pulse code modulation.-Pulse code modulation
(PCM) techniques are used where noise or
The inherent stability problems of two-wire signal/noise ratios are not satisfactory using the
multipoint (i.e., 20 drops or more) systems limit the more common frequency division multiplexer (FDM)
usefulness of such circuits for larger systems. schemes. Because of the increased bandwidth
Four-wire circuits should be used for proposed requirements of PCM (i.e., 56 kilohertz for a single
multidrop installations. voice channel compared to 4 kilohertz for a single
FDM voice channel), PCM is used primarily on
Here are some design constraints placed on both Reclamation hard-wire systems or on special
two- and four-wire interfaces to the commercial commercial wide-band telephone channels.
telephone system:
Data bit rates of 1.544 megabits can be achieved
l The input impedance of the modems must using commercially available Tl carrier equipment.
be 600 ohms *lo percent balanced and
resistive in nature across the entire Communication engineers do not place PCM and
bandwidth of 300 to 3,000 hertz. FDM in the same cable sheath. The reason, of
l The combined transmitted voice power course, is that the signal level of the PCM system
(3-second average) should not exceed is so high that indiscriminate mixing of the two
-6 decibels for four-wire circuits and systems could result in either partial or total
-12 decibels for two-wire circuits. The destruction of the FDM information. On the other
power per circuit for a multicircuit channel hand, PCM information will hardly, if ever, be
should not exceed 10 log 10 (n), where n is affected by the presence of FDM information.
the number of circuits on each channel.
8-20
Communications System Design
The planner or project manager who wishes to added in series. The maximum number of
gradually phase out FDM systems and phase in repeaters used should be limited to 200 series
PCM systems should adhere to the following repeaters. Once again, the number of repeaters
ground rules: used in the series circuit is not necessarily
governed by the circuit distance, but rather by the
l The highest frequency slot in the FDM combined jitter of the repeaters. Conservatively,
system will always be the one of most 60 km (50 mi) is a good maximum limit. However,
concern. This slot will be vulnerable to lengths of 322 to 463 km (200 to 300 mi) can be
PCM interference. obtained. The potential user of voice-grade cables
l The higher frequency FDM slots should be should first test the cable system with a PCM test
phased out first and be replaced with PCM set to determine its ability to handle PCM signals.
high-frequency slots. Because the power
spectrum of a PCM signal drops quickly PCM requires that cables be able to transmit
below 96.5 kilohertz, interference to signals out to 2.5 megahertz, where normal voice
channels below 96.5 kilohertz is usually cables are only required to handle 4-kilohertz
negligible. The point of maximum power signals. More care must be used with wire
in a PCM spectrum occurs around and cables when using PCM than when
710 kilohertz (i.e., the greatest amount of transmitting voice or slow-speed data.
interference to an FDM channel located in
this vicinity). The use of Reclamation microwave systems to
l The crosstalk coupling loss between two transmit PCM data is not recommended at the
cable pairs increases with the number of present time because of the large bandwidths
cable pairs in the cable. This characteristic required for PCM systems. PCM systems
is caused by the increased physical should be limited to wire or cable systems.
separation of the pairs in a larger cable.
Therefore, the larger the number of pairs in
a cable, the less the interference. The RADIO CIRCUIT RELIABILITY
actual value of crosstalk loss between the CONSIDERATIONS
pairs depends upon the splicing methods
used, the splicing groups selected, the Radio circuit path reliabilities are closely associated
gage of the cable, and the dielectric with a term called “fade margin.” Fade margin is
material. defined as the excess path gain above the
. FDM channels in baseband slots at or minimum signal level required to produce a
adjacent to multiples of 96.5 kilohertz demodulated signal-to-noise ratio of at least
should be avoided. 30 decibels.
Loading coils and line buildout networks must be For single-channel VHF applications, the designer
removed from wire lines if any carrier system above should supply at least 25 decibels of excess path
4 kilohertz is to be used. The loading coils should gain to obtain a path reliability of 90 percent and
be replaced with PCM type repeaters because the should provide a 40-decibel fade margin for
repeaters are designed to reproduce PCM signals Reclamation data circuits, which require
when placed at 6,000-ft intervals and used with 99.9-percent reliability.
No. 22 gauge wire having 0.063 microfarad of
capacitance. A go-percent path reliability means the radio path
will be unusable for 0.1 x 6,700 hours, or 870 hours
The advantage of a PCM system is that for every per year, which averages to roughly 3 days per
2 cable pairs used to accommodate 2 voice month! Each individual outage will be of short-term
channels using FDM, the same 2 cable pairs can duration (i.e., I1 minute), and the total accumulated
accommodate 24 two-way voice channels using outage time will be statistical in nature (based on
PCM. experiments by Raleigh and upon the observed
performance of 150-megahertz radio systems).
In theory, any number of repeaters can be placed Naturally, such designs would be limited to two-way
on the system; however, in actual practice, timing radio usage where information can be repeated if
jitter limits the number of repeaters that can be necessary (maintenance radio systems, for
example).
8.,21
Canal Systems Operations Manual
8-22
Communications System Design
the a-c power line, telephone or hard wire, antenna, transducer signals from passing through a
and transducer inputs. All equipment must be circuit. These devices are effective against
grounded and bonded together. lightning and also provide protection from
motor and switching transients.
S-37. Equipment for Lightning Protection Figure 8-7 shows a typical power line protection
circuit. It is comprised of a fuse, MOV network,
Several important components commonly used for and an RFI filter. For higher current equipment
lightning protection are: ratings, increase fuse size and corresponding filter
rating accordingly. This circuit is usually adequate
. Fuses-A fuse limits the amount of current where transients associated with power outages
to a device. It can be used alone or can be tolerated.
preferably in conjunction with other devices.
l Metal oxide varistor (MOV)-A MOV is Severe cases may require other techniques. These
installed across the a-c line, a-c line to techniques include opto-isolators and isolation
ground, and after the fuses. The MOV amplifiers. New controllers using microcomputers
safely conducts overvoltage on the a-c should incorporate opto-isolators in the control and
line to ground and causes the fuses to blow digital inputs and outputs.
and, thus, protects the equipment from the
lightning.
l Gas discharge tubes-A device usually S-38. Grounding
used for communications circuits that
conducts lightning-induced transients to Grounding is also essential for proper protection
ground. from lightning. All of the components of the
l Spark gaps-A spark gap is a device with automation system must be bonded together and
an air gap set to break down and conduct securely grounded. This arrangement is important
when a certain voltage potential is to provide a solid path for the lightning to ground
exceeded across the gap. Spark gap and to prevent large voltage potentials from
devices are often used for protection of developing between the various components of the
antenna leads. system. Grounding is accomplished by connecting
. Radio frequency interference (RFI) filters- a heavy conductor between all the metallic
RFI or transient filters. RFI filters are enclosures and chassis and connecting the
resistor, capacitor, and inductor devices conductor to the site ground mat or an array of
used to prevent high frequency transients, ground rods.
such as a-c power, telephone, or
Corcom
General Electric Series K (3VK)
3 Amp Power line filter
Metal Oxide Varistors
Fuses
n Vl5OLA2 I---- --&---- -1
8-23
r-”
Canal Systems OperationsManual
8-39. Power Failure The gate hoists must be operated where gate
control is required. This operation requires an
Lightning and other phenomena also cause power alternative source of a-c power such as a gas-
outages. If these outages cannot be tolerated in operated motor generator with auto-start or a
the control system, other protective systems must separate a-c line. Only battery backup operation
be considered. These systems fall into two need be provided when telemetry only is required.
categories: (1) telemetry and gate control are
required and (2) only telemetry is required.
8-24
CHAPTER 9
INSTRUMENTATION FOR PHYSICAL MEASUREMENT
I II
Canal Systems Automation Manual
9-2
Instrumentation for Phvsical Measurement
absolute shaft encoder attached to the pulley shaft The Leupold Stevens, Inc., Telemark and Type P
or gear assembly shaft of the recorder using a synchro systems, and other manufacturers’ encoder
flexible coupling. The encoder can also be coupled systems, can be used with float-driven water level
using chain drive. and sprockets. Absolute recorders. A modified Leupold Stevens Chart
encoders, as opposed to incremental or single-turn Recorder is shown on figure 9-2.
encoders, are used to assure that turn information
is not lost because of power outages and system The float system should be incorporated in an
resets. These encoders provide an output that can enclosed stilling well to prevent the effect of wind
be scaled and offset to provide a representation or waves, tampering, environmental damage, and
display analogous to the actual water level. vandalism. The system is subject to error from
objects or animals falling on the float.
A typical system is an adaptation of the Leupold
Stevens Type A5 water level chart recorder to drive b. Pressure method .-Pressure transducers provide
a multiple-turn potentiometer. The installation the basis for two additional methods: the bubbler
includes a float pulley 0.5 meter (m) (18 inches [in]) gage and submersible transducer methods.
in circumference directly connected to a lo-turn Numerous types of pressure transducers are
potentiometer. This combination will provide water available to accommodate many ranges of
measurement over a 5.0-m (15-foot [ft]) range. measurement, environments, and desired outputs.
Other combinations of pulleys, gears, and
potentiometers provide different ranges. The The bubbler gage is an adaptation of the
conversion relation is: manometer servo system. The bubbler gage
provides an analog output from a pressure
transducer. Bubbler gages use compressed
R=PC*GR*PT 9.1 nitrogen or air, a flow regulator, pressure
transducer, and a long tube that goes from the
where: instrument to fixed point in the canal below the
lowest depth of water expected. Nitrogen is
R = range released at a very slow rate through the tube and
PC = pulley circumference bubbler orifice anchored at the low point under the
GR = gear ratio water. The changing head over the orifice causes
PT = potentiometer turns a corresponding change in the pressure at the
orifice. Corresponding pressure is transmitted
By using gear assemblies and different multiple-turn through the tube back to the regulator and pressure
potentiometers or encoders, the system can transducer. The pressure transducer converts the
accommodate a large range of water levels. A pressure to an analog electrical output. The depth
2-to-1 gear assembly can be added to the above of water over the reference point at the end of the
example to provide a 2.5-m (8-ft) range, or by tube can then be converted to a digital
reversing the gearing, a 10-m (33-ft) range. representation and, subsequently, to feet or meters
Similarly, the encoder turns can be changed to of water depth by the RTU or controller. The
adjust the required range. bubbler gage allows the transducer to be located
remotely from the measuring point by using the gas
These systems are reliable, easy to verify, and to transfer the pressure to the transducer.
easy to repair. System errors are predictable and
consistent. The errors include float lag, line shift, System accuracy depends on proper installation,
and counterweight submersion. Mechanical operation, and the accuracy and stability of the
accuracy is 0.1 percent or better. A 15-m (50-ft) pressure transducer.
encoder system using a 300-millimeter (mm) (12-in)
float results in an error of 0.01 m (0.04 ft) or Bubbler gages require maintenance to replenish the
0.08 percent in the mechanical system. A compressed gas, inspection of the bubbler tube and
O-l-percent linear potentiometer results in an orifice, and periodic calibration and verification of
additional 0.1 percent, resulting in a 0.20-percent the transducer. The bubbler tube and outlet
system error. A typical float installation is shown orifice are subject to damage or clogging.
on figure 9-1.
Canal Systems Automation Manual
Some bubbler systems are available with a small above the transducer, the same as the bubbler
air compressor instead of the nitrogen or air gage does for head above the bubbler gage.
cylinder to supply the gas to be released into the 'Pressure transducers designed for this application
water . with a 4.0- to 20.0-milliampere output are often
referred to as pressure transmitters, as shown on
A second pressure transducer method has become figure 9-3.
feasible with improved submersible transducer
design. Pressure transducers are submerged and The conversion relation is:
attached below the minimum water level.
Submersible transducers do away with the
D=(K1xPxCFJ+CF2 9.2
regulator, compressed gas, and tube, therefore
eliminating the maintenance for compressed gas where:
and bubbler tube. These transducers are supplied
with a small vent tube to equalize the pressure on D = depth in feet
the back of the diaphragm to the atmosphere. K1 = calibration constant
However, submersible transducers are subject to p = pressure
damage from freezing and must be removed to a CF 1 = scaling correction factor
dry location when freezing conditions exist. The CF2 = offset correction factor
transducer output is converted directly to head
9-4
Illstrumentation for Physical Measurement
9-5
Canal Systems Automation Manual
9-6
Instrumentation for Physical Measurement
9-7
Canal Systems Automation Manual
9-8
Instrumentation for Physical Measurement
9-9
Canal Systems Automation Manual
3. It can make good measurements with no Six disadvantages of Parshall flumes are:
submergence, moderate submergence, or
considerable submergence downstream. 1. They cannot be used in close-coupled
4. Its flow velocity is sufficiently high to combination structures consisting of
virtually eliminate sediment deposition turnout, control, or measuring device.
within the structure during operation. 2. They are more expensive than weirs or
submerged orifices.
The equation for flow, Q, takes the form: 3. They require a solid, watertight foundation.
4. They require accurate workmanship for
Q=KH” 9.5 satisfactory construction and performance.
5. They require upstream and downstream
where: water levels if submerged.
6. Large flumes can settle and deform over
Q = discharge time, requiring recalibration.
H = head (upstream)
K = constant dependent on flume geometry Parshall flume sizes are designated by the throat
and material width, and dimensions are available for flumes from
n = constant dependent on flume geometry the 25mm (l-in) size for discharges as small as
and material (2 c n < 3). 28.3 liters per second (0.01 second-foot), up to the
15-m (50-ft) size for discharges as large as
Discharge through a Parshall flume can occur for 85 cubic meters per second (m3/s) (3,000 second-
two conditions of flow. The first, free flow, occurs feet). The flumes may be built of wood, concrete,
when backwater depth is insufficient to reduce the galvanized sheet metal, plastic, or other desired
discharge rate. The second, submerged flow, materials. Usually, large flumes are constructed on
occurs when the water surface downstream from the site. Smaller flumes may be purchased as
the flume is far enough above the elevation of the prefabricated structures to be installed in one piece.
flume crest to reduce the discharge (submerged Some flumes are available as lightweight shells,
flow). For free flow, only the head, Ha, at the which are made rigid and immobile by placing
upstream staff gage is needed to determine the concrete outside of the walls and beneath the
discharge from a standard table. The free-flow bottom.
range includes some of the range which might
ordinarily be considered submerged flow because The addition of an accurate water level encoder to
Parshall flumes tolerate 50 to 80 percent a properly installed Parshall flume provides an
submergence before the free-flow rate is excellent flow measuring device for a controller or
measurably reduced. For submerged flows (when RTU. The controller can convert the water level to
submergence is greater than 50 to 80 percent, a flow or use the water level directly. Accuracy of
depending upon flume size), both the upstream and flows from 3.0 to 5.0 percent can be expected in
downstream heads are needed to determine the nonsubmerged applications.
discharge.
d. Ramp flumes.-A ramp flume consists of a 3:l
A distinct advantage of the Parshall flume is its approach ramp up to a horizontal broad sill or crest
ability to function as a flowmeter over a wide with a vertical downstream drop back to the canal
operating range with minimum loss of head while invert. Ramp flumes are simple to form and
requiring but a single head measurement for each construct. Also, ramp flumes are easy to install in
discharge. The head loss is only about one-fourth existing canals. A typical installation is shown on
of that needed to operate a weir having the same figure 9-8.
crest length. Another advantage is that the velocity
of approach is automatically controlled if the correct Ramp flumes have relatively small head losses and
size of flume is chosen, and the flume is oriented are able to tolerate high submergence (85 percent
as it should be; that is, as an in-line structure. of the measuring head for a vertical downstream
9-l 0
Instrumentation for Physical Measurement
crest face and 93 percent of the measuring head A major advantage of a ramp flume is the ability to
with an added 6 horizontal to 1 vertical diverging numerically calibrate the flume using post-
downstream ramp). Therefore, the minimum construction dimension measurements. Thus,
required head loss for flow measurement is construction errors or flume settlement can be
15 percent of the measuring head on flumes with better accounted for with these measurements. A
vertical drops and 7 percent of the measuring head computer program is available to generate a
for ramp flumes with 6:1 sloped downstream discharge table. Another advantage of ramp flumes
diverging ramps. Discharge measurement errors is that they can usually be installed in existing canal
increase rapidly beyond the submergence limit. sections with minimal canal modification.
Generally, ramp flumes are designed for step To ensure approximate parallel flow (assumed for
heights from 40 to 60 percent of the approach numerical calibration purposes), the basic design
canal normal flow depth. Thus, the minimum head criteria of approach measuring head, H" relative to
loss (using 50 percent) that can be allowed while the length of crest in the direction of flow, La, is:
still permitting flow measurement is 7.5 percent of
the approach flow depth for a ramp flume with a (HILa> < 0.50 9.6
vertical drop and 3.5 percent of the approach flow
depth for a ramp flume with 6:1 sloped downstream
ramp.
9-11
Canal Systems Automation Manual
Also, the head at the measuring station should be eo Weirso-Weirs are one of the oldest, simplest,
greater than one-twentieth of the crest length to and most reliable structures that can be used to
assure that undulating flow (caused by frictional measure water flow in canals and laterals. Weirs
control) does not occur on the crest. Thus, are available in many designs, including
rectangular, V-notch, trapezoidal, and Cipolletti.
(HI/~) > 0.05 9.7 The critical components are easily inspected, and
any improper operations can be easily detected
and quickly corrected. Weirs can be used most
Accuracy comparisons of field and model effectively whenever a fall of about 0.15 m (0.5 ft)
calibrations with numerical (computer program) or more is available in the canal, lateral, or ditch.
calibrations indicate that numerically calibrated See figure 9-9 for a weir.
ramp flumes are as accurate as Parshall flumes (in
the range of 3 to 5 percent) [6]. A weir may be defined as an overflow structure
built across an open channel, usually to measure
Addition of an accurate water level encoder to a the rate of flow of water. Weirs are acceptable
properly installed ramp flume provides an excellent measuring devices because, for a weir of a specific
fiow-measuring device for a controller or RTU. size and shape with free-flow steady-state
Flows accurate from 3.0 to 5.0 percent can be conditions and proper weir-to-pool relationships,
expected. only one depth of water can exist in the upstream
9-12
Instrumentation for Physical Measurement
Figure 9-9.-Weir.
pool for a given discharge. Discharge rates are The addition of an accurate water level encoder to
determined by measuring the vertical distance from a properly installed weir provides an excellent flow
the crest of the overflow portion of the weir to the measuring device for a controller or RTU. Flows
water surface in the pool upstream from the crest, accurate from 3.0 to 5.0 percent can be measured.
and then referring to computations or tables which
apply to the size and shape of the weir. For f. Current meters and propeller meters.-Current
standard tables to apply, the weir must have a meters (propeller, pygmy, price) are not typically
regular shape, definite dimensions, and be set in a used to provide a measurement. These devices
bulkhead and pool of adequate size so the system are useful in the verification and calibration of one
performs in a standard manner. of the flow measuring devices described above. A
velocity profile is determined by making measure-
Depending upon the shape of the opening, weirs ments at a number of points in a plane perpen-
may be termed rectangular, trapezoidal, triangular, dicular to the flow of water. This velocity profile
etc. In the case of rectangular or trapezoidal weirs, and the cross section of the stream or canal is then
the bottom edge of the opening is the crest, and used to calculate flow. These devices measure the
the side edges are called sides or weir ends. The velocity and direction of the water at a given place.
sheet of water leaving the weir crest is called the
nappe. Weirs operate best when they discharge g. Differential pressure {venturi meters).-
freely into the atmosphere. In certain submerged Differential pressure (venturi) meters are not usually
conditions, the under-nappe airspace must be applicable to open channel flow. Venturi meters
ventilated to maintain near-atmospheric pressure. are usually applied to pipe turnouts and pumping
9-13
Canal Systems Automation Manual
plants where conditions are appropriate. Venturi probably result in greater use of the meters in the
meters are perhaps the most accurate type of flow future. Many variations of the meter exist, each of
measuring device that can be used in a water which is tailored to meet the requirements of
supply system. They contain no moving parts, specific types of installations.
require very little maintenance, and cause very little
head loss. Venturi meters operate upon the h. Orifices .-An orifice is a well-defined, sharp-
principle that flow in a given closed-conduit system edged opening in a wall or bulkhead through which
moves more rapidly through areas of small cross waterflow may occur. If the upstream water surface
section than through areas of large cross section. drops below the top of the opening, the flow ceases
to follow the laws of orifice flow and tends to follow
Total energy in the flow, consisting primarily of those of flow over a weir. Flow through an orifice
velocity head and pressure head, is essentially the may either discharge freely into the air or into water
same within the meter. Thus, the pressure must as submerged flow. The submerged orifice
decrease in the constricted throat where the conserves head and is therefore used where
velocity is higher. Conversely, the pressure must insufficient fall exists for a weir, and where for
increase upstream from the throat where the some reason, a flume cannot be justified. Both free
velocity is lower. The reduction in pressure from and submerged orifices may be contracted or
the meter entrance to the meter throat is directly suppressed. In a suppressed orifice, the perimeter
related to the rate of flow passing through the partly or fully coincides with the sides of the
meter and is the measurement used to determine approach channel.
flow rate. Tables or diagrams of this head
differential versus rate of flow may be prepared. The discharge through a vertical, sharp-edged,
contracted, submerged orifice is given by Corbett
The relationship of rate of flow, or discharge, to the and others as:
head and dimensions of the meter is:
Q=CdA(2gH)‘R 9.9
9.8 where:
where: Q = discharge
C,, = coefficient of discharge
A, = cross-sectional area of the throat A = area of orifice
h = difference in pressure head between g = acceleration caused by gravity
upstream pressure measuring section H = head on orifice, equal to difference of
and the downstream pressure head on upstream and downstream
measuring section sides of orifice
9 = acceleration caused by gravity
r = ratio of the throat diameter to pipe A negligible velocity of approach, complete orifice
diameter = D2 / Q contractions, and an effective head large enough to
Cd = Coefficient of discharge for the venturi minimize errors in its measurement are essential for
meter obtaining accurate results.
D, = upstream diameter of pipe
D2 = downstream diameter of pipe When velocity of approach becomes applicable, the
equation becomes:
The coefficient of discharge for the venturi meter
will range from about 0.935 for small throat 9.10
Q=C,A[2g(H+h)]”
velocities and diameters to 0.988 for relatively large
throat velocities and diameters.
where:
Historically, the expense of venturi meters and the
fact that they must always operate with the pipeline h = the velocity head in the approach to the
full have restricted their use on a broad scale in orifice, and the other terms are as
irrigation systems. Requirements for more accurate previously defined
flow measurements in pressure conduits will
9-14
Instrumentation for Physical Measurement
9-4. Gate and Valve Position Measurements position equation or look-up table can be provided
where more accurate gate position is required.
a. Radial gate hoist, drum rotation.- The radial This approach will probably be required to provide
gate (tainter gate) is commonly used in canal the necessary accuracy to determine flow using
systems. The radial gate is positioned with a drum gate opening and water levels.
and cable hoist mechanism. As the drum rotates,
steel cables attached to the drum and gate raise An inclinometer or angle transducer can also
and lower the gate. The drum is rotated using a provide radial gate position. The inclinometer
gear assembly with a motor or handwheel. Gate provides an accurate trigonometric output which is
position can be derived from a rotational sensor then converted to a linear gate opening. The
attached to the drum shaft or an intermediate shaft inclinometer is attached to one of the arms of the
in the gear assembly. Rotational sensors for gate radial gate. Installation is easy because no other
position include potentiometers, digital shaft mechanical connections are required. However,
encoders, rotational voltage differential transformers the installed location of the inclinometer on the gate
(RVDT), and selsyn encoders. Figure 9-10 makes repair and maintenance difficult.
illustrates a radial gate showing the installation of a
potentiometer gate position sensor. b. Slide gate position.-Slide gates are used in
many canal systems. The slide gates may be
Radial gate position is often considered linear, and installed vertically or set at an angle. Slide gate
a straight line relationship between the encoder opening requires a different hardware approach.
output and the gate position is assumed. A gate Two applications are described.
9-15
Canal Systems Automation Manual
Usually, the hoist mechanism is a screw hoist for a with or fouled by debris, they must be housed in a
threaded rising stem attached to the gate. The protective enclosure. This method can be applied
screw hoist operator may have a geared auxiliary to radial gates.
shaft that can be used to drive a rotational sensor
as for the radial gate hoist. The rotational sensor A linear voltage differential transformer (L VDT) can
(potentiometer, RVDT, or digital encoder) must also be used. The linear device is attached to the
match the rotation of the shaft. The geared shaft gate using a cable or rod parallel to and in the
with a rotational sensor provides an accurate gate same plane as the gate. The linear device must
position signal. The slide gate travel is linear; have a range of travel at least equal to the gate
therefore, the gate output signal is linear and travel or the lever equivalent. Protection from
requires only offset and scaling to provide English tampering and the environment is required.
or metric gate position output. A typical installation
is shown on figure 9-11. c. Gate and valve position.-Closed conduit gates
and valves are used in canal systems for turnouts,
canal-side pumping plants. and in-Iine canal
pumping plants. Position indication may only
require open or closed status or may require actual
position such as in metering and flow control
applications. Mechanically coupled limit switches
can provide status-open or closed. The switches
can be set to change position as the valve starts to
open or when the valve is fully open.
9-16
Instrumentation for Physical Measurement
determine component failures, a need for site Because the quantity is either on or off, a small
maintenance and repair, or even a local emergency variation in the amplitude is not a problem.
where manual or local onsite control is required. However, digital implementation is more
complicated. Digital data require either multiple
Equipment measurements can be made in almost conductors or a multiplexing system to provide for
any form-analog signals (voltage or current), communication of each weighted position or digit
single or multiple digital voltages, or on-off voltage between the digital instrument and the RTU. Inputs
signals. for each signal or demultiplexing is required for
each digital variable.
b. Analog signal.-An analog signal is a measured
variable (voltage or current) that varies with time.
The signal from a pressure transducer, for example, 9-6. Equipment Status
may vary from 0 to 5 volts as the pressure
increases from zero to maximum. An operator can Equipment status can often be determined by a
provide an input parameter by setting an analog simple on/off status contact. Many of the types of
quantity using a potentiometer. An operator can equipment used in canal systems are provided with
provide a local control setpoint-target water level, auxiliary switches for this purpose. Motor-operated
for example. valves are often equipped with open and closed
limit switches. Motor controllers have auxiliary
Analog signals are subject to noise because the contacts that can be used to determine if a motor is
information is represented by the amplitude of the running or stopped. Some additional examples of
signal. Noise appears on the signal as a random two position or on/off status are:
variation in the amplitude. This noise can be
reduced by using current output devices when l Gates-open/closed limit switches
available and by using good wiring practice and . Pumps-running/stopped
proper shielding. . Electrical power-on/off voltage sensor
. Temperature-high/normal
Analog quantities cannot be used directly by l Control switches-on/off position
computer-based canal-side controllers and RTU’s.
The analog quantity must first be converted to These parameters allow various conditions and
digital using an a-to-d converter. operations in a control sequence to be used by the
controller and monitored by the control operator.
c. Digital signal.-A digital signal is a variable
represented by a series of one or more on and off Equipment status is not limited to simple on/off
signals or voltages. Each signal in the series has a status. Analog signals can also provide useful
weighted value. The simplest signal is an alarm or information. Battery voltage, a typical analog
status represented by one position or digit (binary parameter, provides information on condition of the
digit). If the voltage is present, the digit represents electrical system. This information can indicate a
the “on” state. If the voltage is not present, the defective battery charger and warn of a possible
digit represents the “off” state. A mechanical limit power loss to an RTU. Other analog signals
switch or a contact switch on a door can also include:
provide this input.
. Motor speed
A digital variable such as the output of an absolute 9 Wind speed
digital shaft encoder can be represented by 8, 10, l Temperature
or more positions or digits. Each digit has a weight l Water quality
or value; an 8-digit output would include the . Air or hydraulic pressure
following weighted values: (128+64+32+16+ l Water level
8+4+2+1 = 255). The first has a value of 128, the
second 64, the eighth 1. An 8-binary-digit
representation provides a count from 0 to 255, a 9-7. Alarms
resolution of 1 part in 256.
Alarms are an essential part of the control and data
Digital signals are not subject to distortion or acquisition package. Alarms get an operator’s
interference that degrades analog signals. attention when something is out of the ordinary,
9-17
Canal Systems Automation Manual
equipment has malfunctioned or failed, or a serious at points above and below the normal range of
condition has developed. An RTU with its water operations. These alarms act as a backup
extensive message capability can generate the system and confirmation of a serious problem such
specific alarm information from its data base and as loss of control, stilling well problem, encoder
send an ASCII message to the master station. problem, or transducer failure. Figure 9-l 2
However, a local controller alarm may only be illustrates the level switch, which can be used as an
capable of generating a common alarm that is alarm or limit switch.
initiated when any one of several events happen.
Water level is probably the most important variable
An alarm may be initiated by a limit switch on a used in canal control. Most control schemes are
piece of equipment, a high or low water level float based on water level or flow derived from a water
switch in a stilling well, or an intrusion alarm level. Multiple sensor configurations are worth
initiated by a door switch on the equipment consideration for important parameters such as
enclosure. Alarms actuated by the opening or water level. A dual sensor system with limit
closing of a switch contact are contact alarms. checking and comparing will assure an almost fail-
proof system for providing water level input.
An alarm can also be calculated from analog and
digital parameters and a set of limits or conditions, b. Status alarms.-Status alarms include many
or can even be inferred when a certain combination contact or on-off alarms. Loss of a-c power and
of status inputs and/or calculated events occur. entry alarms are included in this group.
These “logic alarms” are derived from a formula or
calculation. An RTU cannot respond without power. The
master station can detect the lack of a response
Many types of both contact and logic alarms exist. with a software communication routine. However, a
Some general headings useful in canal control will more responsive system can be provided by using
be provided, followed by some specific examples: battery power for RTU’s. Gates and other
equipment cannot operate when primary power is
a. Water level alarms.-Water level alarms can be lost, but a battery operated RTU can continue to
generated several ways. Both contact and logic provide information not only on the power failure,
alarms can be used. Separate limit switches, such but also valuable telemetry from the site. The
as high and low water, can be provided to indicate telemetry provides complete information about the
low or high water. The analog water level can be site to evaluate the urgency of corrective action,
checked against preset limits in the software to such as manual onsite operation and site repair. A
derive high or low water alarms, or two analog communications failure or RTU failure will still
water levels may be used to verify and control cause a no response or communications failure
water level based on the most realistic signal. alarm. Obviously, specific information is not
Often, several schemes are combined to provide a available without information from the RTU.
redundant system. The following example However, many other failures such as gate failure
illustrates some applications of water level alarms. to operate, water level encoder failure, and even
loss of primary power (when the RTU is operated
The water level signal is limit checked. A set of on batteries) can be provided to the master station
limits, called soft limits, is set slightly above and when the RTU is operational.
below the desired water level. These limits warn
the operator that something may need attention but Loss of communications can result from a number
not immediately. A second set of limits is provided of failures, including loss of RTU power, RTU
to initiate different levels of response. The second failure, or actual failure of the communication
set of limits has a wider range and might indicate system. The alarms can be made more specific by
loss of control, equipment failure, or a serious operating the RTU and communications equipment
control problem. A third set of limits, zero and full from battery power and continuously charging the
scale, is often included. This set usually indicates batteries. In this way, a-c power failure can be
an equipment problem, such as a transducer detected and specifically alarmed. A simple
failure, rather than an actual water level. mechanical or solid-state relay provides the status
alarm point.
A set of alarms controlled by a separate float or
level switch can also be used. These limits are set
9-l 8
Instrumentation for Physical Measurement
Figure 9-12.-B&W water level alarms (relay is displayed on the left; probe is displayed on the right).
Intrusion or entry alarms are used to detect wrong direction, and exceeding limits. The control
unauthorized entry into a structure or enclosure. algorithm generates an alarm if an incorrect
The alarm consists of a hardware switch located operation is detected.
near and operated by the entrance door to the
structure or enclosure. The alarm initiates an A multiple approach should be used. The algorithm
indication at the master station to advise the must be provided with travel limits and direction
operator of entry .The alarm contact can also checks to detect problems. The same algorithm
trigger a horn, siren, or lights at the local site to should also override the control function and stop
discourage the intruder. control. The function may allow a retry of the
control function or stop control all together. An
c. Equipment failures.-Equipment failures include additional safeguard for most control functions is a
two types of failure: (1) the equipment did not mechanical limit switch to lock out continued
operate and (2) the equipment operated incorrectly. operation beyond the limits. This function helps
The type of failure can often be determined by logic prevent damage to the equipment and can be used
(software). A motor-operated gate will be used to to generate an external alarm to the RTU.
illustrate these failures. The gate position is
monitored in most control algorithms. When gate Equipment failures can include many subsystems
operation is required, the algorithm calls for the and components. A number of alarms are
gate operation and then monitors the gate described to assist in maintaining system integrity
movement. Incorrect gate operation includes failure and safe operation of a control site.
to stop, incorrect position,
9-19
Canal Systems Automation Manual
d. Control failures.-Control failures can be caused will depend on the specific application. In most
by any of a number of problems in the hardware applications, the potentiometer is used as a voltage
from the RTU or controller to the controlled divider. In divider applications, the linearity controls
structure or the input sensors. Control failure the accuracy of the output, and the resistance is
requires continuous program monitoring of the not a major factor in determining accuracy. The
variable and status inputs. Variable inputs require voltage divider output is supplied to an a-to-d
limit parameters in the RTU or controller data base converter to provide digital information for the RTU.
to verify the variables are within the expected The digital information can then be scaled and
range. Input readings outside the range should offset to provide a representation in engineering
cause an alarm. RTU’s can provide specific alarms units.
to the master station.
Potentiometers have shown excellent reliability with
Water level is an excellent indicator of control an installed life of over 10 years when used as an
problems. Software program limits are operator- encoder for a float, pulley, and counterweight water
adjusted software high and low limit alarms that level measurement system or radial gate hoist
provide a specific alarm when the monitored mechanisms. Overall accuracy is in the O.l-percent
parameter (water level) moves out of the limits. range for a linear travel of 15 inches or more.
Hardware limits are mechanical switches that are
adjustable at the site and provide indication when Potentiometers are also available as linear devices
operated. These limits are external or hardware and have been used for slide gates in some field
generated and detect loss of control by detecting applications. Linear potentiometers are used
operation (water level) out of the expected control similarly as rotational potentiometers to convert
range. These alarms function similarly to the gate linear motion directly to an analog voltage.
limit alarms in that they provide a check on the
analog input parameters. b. Digital shaft encoders.-Digital shaft encoders
can be used in place of potentiometers for
rotational encoding. The encoders are available as
9-8. Sensors both absolute and incremental encoders.
A description of sensors will complete the Absolute digital shaft encoders are rotational
discussion on gates and valves. Numerous devices in which the input position is converted
sensors are available for application in canal directly to digital data. Absolute encoders use
automation. The actual sensors used will depend coded disks with wipers or light-emitting diodes and
on the adaptability to the application, the desired light-detecting semiconductors to provide the
accuracy, cost, and maintainability. encoded position. The data are then transmitted in
parallel using multiple conductor cable or converted
a. Potentiometers.-Potentiometers have been to a serial data word and sent over a wire pair.
used in many canal automation applications. Absolute encoders are used to prevent lost count
Potentiometers are available in many different during power interruptions. Digital shaft encoders
varieties and are easily adapted to gate hoists, are available from 1 to 64 turns and overall
water level devices, and many other applications in accuracy of 1 part in 65,536. The position is
which the desired input is represented by a rotating represented by up to 16 binary bits either in a serial
shaft. Potentiometers are available in single and string or 16 parallel transistor logic compatible
multiple-turn applications, including 2, 3, 5, 10, 15, signals. The major deterrent to using absolute
and 20 turns, and in a variety of resistance values digital shaft encoders is the increased cost and the
from about 10 ohms to 1 megohm. Potentiometers difficulty of maintenance and repair. Reliability can
are available with resistance tolerances of 3 to be a problem in some field sites with weather and
10 percent. Linearity of a potentiometer is about power surges.
0.1 to 3.0 percent.
Incremental encoders provide a step and direction
Lower resistance values dissipate more electrical output or separate step-up and step-down pulse
power, and higher resistance values are more outputs. Incremental encoders rely on a computer
susceptible to electrical interference and noise. to maintain the accumulated position. Accuracy of
Good results have been obtained with 2,500- to incremental encoders is in the 3.0-mm (O.Ol-ft)
lO,OOO-ohm values. The number of turns required range for a lOO-count-per-revolution encoder. The
9-20
Instrumentation for Physical Measurement
position count can be lost any time a power valves for position indication. Because of close
interruption or movement of the encoder occurs tolerances between the core and transformer ,
while power is off. When this loss occurs, the RVDT's and LVDT's can bind or be damaged by
position must be reset to agree with the actual sand and dirt. LVDT's and RVDT's therefore
measured quantity. This operation is not desirable require a protected environment. They provide
in canal systems because the position must be excellent accuracy and good reliability when built
reset by an operator at the site. Incremental into an operator such as a gate valve operator or
encoders are not recommended for use in canal slide gate operator.
automation. Figure 9-13 shows a potentiometer
and digital encoder. d. Inclinometers.-lnclinometers (angle
transducers) produce a sine or linear output
c. Linear voltage differential transformers.-L VDT's corresponding to the angle of rotation of the
and RVDT's are also analog output devices. The transducer. The transducer need only be mounted
transformers use a moving core to change the on the radial gate arm. The output of a sine wave
coupling between transformer windings, resulting in must be converted to a linear function, then scaled
a change in the voltage output. An electronic and offset to gate opening. The inclinometers
component uses the output from the transformer to should work well with computer-based equipment.
produce a linear output propor1ional to the linear Inclinometer operation requires that the transducer
displacement or angle of rotation. These devices be rotated through an angle to produce an output.
can provide a more accurate output than Radial gate arms move through an angle as they
potentiometers, but the cost and complex are opened and closed and can easily be
electronics restrict their use in canal applications. instrumented with inclinometers. Overshot gates,
These devices are used in many motor-operated such as bladder type gates, also work well with
9-21
Canal Systems Automation Manual
Figure 9-14.-lnclinometer.
Figure 9-15.-Syncro.
e. Selsyns and syncros.-Selsyns and syncros can
be used for rotational measurement. Selsyns
provide a 3-phase voltage output in which the linked or driven by a gear assembly to provide
voltages represent a specific shaft position. This multiple-turn resolution. Accuracies approaching
voltage relationship can drive a second selsyn 3.0 mm (0.01 ft) can be obtained.
device to output the same mechanical position and
drive a conventional encoder. The output can also g. Pressure transducers.-Pressure transducers are
drive an electronic system which outputs a digital or finding their way into canal automation for
analog signal that represents the mechanical measurement of water levels. They are an
position. The single-turn (or speed) devices are not excellent choice where an onsite chart record is not
recommended for much the same reason that required. Pressure transducers are available in
incremental shaft encoders are not recommended. numerous pressure ranges, signal outputs, and
The actual position is generated in the RTU. New actual transducer types. Many transducers are
multistage selsyns use two encoders to maintain submersible and easily adapted to canal
coarse and fine position. The second selsyn is automation. Transducer outputs include a range of
geared to the first and provides turn indication for voltages and currents. Current outputs are
the first. These devices provide an absolute available in 0- to 1-milliampere, 0- to 5-milliampere,
position output. Multistage selsyns can be applied and 4- to 20-milliampere ranges, all easily used for
to canal systems where single-turn selsyns are not inputs to RTU's. Voltage outputs range from 0 to
recommended for canal automation. Figure 9-15 is 10 millivolts to 0 to 10 volts; the higher outputs are
a photograph of a syncro. desirable for automation use. Figure 9-16 is a
photograph of a pressure transducer.
f. Resolvers.-Resolvers are similar to selsyns in
that the output is converted into electrical signals. Transducers with current output are excellent
The difference is that the output is resolved into two choices for automation. The current output
signals that are perpendicular to each other. The provides a high noise immunity and simple
output consists of the sine and cosine of the angle installation. These advantages are particularly
of rotation. These devices can be mechanically useful for long wire runs of up to 1.6 kilometers
(1 mile) and noisy environments.
9-22
Instrumentation for Physical Measurement
Measurements required to solve this formula Proper fertilization, pH correction, and the proper
include weather data, soil conditions, and water amount of water can minimize water runoff and
quality. reduce the chemicals in the water returned to the
drainage systems.
9-23
Canal Systems Automation Manual
Gaging stations and instrument platforms are the c. Location.-Location of the equipment is by
most common facilities for providing data collection necessity at the site where the information is
for reservoirs, rivers, streams, and canal systems. derived. The equipment is thus located along the
Gaging stations and instrument platforms provide canal near a control structure, and by virtue of the
valuable information such as water level, flow, canal, susceptible to lightning (and power surges if
turbidity, and weather data. This information is a-c powered and/or if wire communication circuits
collected and used to determine water availability, are used). Tampering and malicious mischief can
releases, and distribution. also be a factor because of the remote location of
the equipment.
9-24
Instrumentation for Physical Measurement
A satisfactory and reliable installation can usually required in the winter to heat the enclosure to
be accomplished with proper installation maintain temperature above a system minimal
techniques, the required protection from lightning required temperature.
and power transients, and features to minimize
tampering. A typical RTU or controller installation
is not much different than these installations. The INSTRUMENTATION
same concerns and guidelines apply.
9-12. Instrument Classification
The following considerations need to be evaluated
in selecting a site: Instrument classification for almost all devices falls
into one of two output categories-analog or digital.
1. The parameters are being measured. Many of the instruments are available in either
2. The power requirements can be met: digital or analog form. Analog and digital
. Power (a-c) for larger facilities classifications have been introduced in preceding
l Adequate sun for solar powered sections. This discussion will cover the specific
systems characteristics, advantages, and disadvantages of
3. Communication requirements can be met: each. The end result of either must be a digital
l Communication line representation of the data so a microcomputer can
. Radio path to repeater or base then manipulate the data by offset, scale and/or
l Satellite path compare, or telemeter data over a communication
circuit.
9-25
Canal Systems Automation Manual
9-26
Instrumentation for Phvsical Measurement
9-27
Canal Systems Automation Manual
Using a water level float encoder and stilling well as Using a 12-bit a-to-d converter provides a
an example, the following items must be evaluated: 0.1005-percent accuracy and does not significantly
degrade the accuracy of our original water level
. Flow approach to the stilling well signal. The lo-bit a-to-d converter provides a
. Entrance conditions to the stilling well 0.1414-percent accuracy and appreciably affects
. Lag caused by the ratio of stilling well area the overall accuracy of the measured quantity.
to inlet opening
. Error resulting from the float-pulley c. Repeatability.-Repeatability of a measurement
assembly (0.2 to 1.0 percent) is the agreement of multiple readings of the
. Error caused by the encoder (0.05 to measurement system for the same value of input
1 .O percent) made under the same measurement conditions,
. Conversion error caused by the a-to-d approaching from the same direction, and using full
encoder (1 count or 0.02 percent for a scale traverses.
12-bit encoder)
d. Measurement uncertainty.-Measurement
The system accuracy is the square root of the sum uncertainty is the estimated amount by which the
of the squares of all the individual errors. measured quantity may depart from the true value.
9-28
Instrumentation for Physical Measurement
high side. Systematic errors can often be components in equipment not adequately protected.
corrected by offset, scaling factors, or a Attention to proper installation of grounding
logic equation. systems, power systems, and communication is of
the utmost importance to prevent lightning damage.
e. Reliability.-Reliability is the ability to operate Lightning and powerline transients can also alter
without failure, repair, or adjustment over a long the contents of information and programs contained
period of time. Foregoing some accuracy to obtain in the memory of computer-based equipment.
a more reliable instrument is usually an acceptable
option. Concrete blockhouses or heavy steel enclosures
may be required in areas of high vandalism.
f. Calibration requirements.-Calibration Relocation of the equipment is sometimes a
requirements could be considered par-l reliability possible solution to vandalism.
and part maintainability. If the device is difficult to
calibrate, calibration will be delayed, carelessly i. Maintainability.-Maintainability is a primary
done, or even not done at all. If the device consideration in automation projects. The
requires calibration often, the task will not be done equipment will be difficult to maintain if it is
in a timely manner, and the desired accuracy may unreliable, and numerous trips will be required to
not be provided. keep it functioning. Components will not be
repaired if they are difficult or costly to repair. The
g. Availability.-Availability can also be considered system should function with the failure of some of
in two parts. The original installation should use the components and, ideally, should provide some
equipment that is readily available from a indication of the problem. In a Supervisory Control
recognized supplier. Secondly, a readily available and Data Acquisition system, the telemetry data
product will be easier to replace, and spare parts should contain some diagnostics and component
for repair will be easily obtainable. failure notification.
9-29
Canal Systems Automation Manual
BIBLIOGRAPHY
[l] Leopold & Stevens, Inc., Stevens Water [4] Chief, Office of Water Data Coordination,
Resources Data Book, Fourth Edition, National Handbook of Recommended
Beaver-ton, Oregon, 1987. Methods for Water Data Acquisition,
U.S. Geological Survey, Reston, Virginia.
[2] Bureau of Reclamation, Water Measurement
Manual, Second Edition, rev. reprint, [5] Dodge, R.A., Ramp Flume Model Study-
Denver, Colorado, 1984. Progress Summary, Bureau of Reclamation
Report No. GR-82-14, Denver, Colorado,
[3] Buyalski, C.P., Discharge Algorithms for Canal 1982.
Radial Gates, Bureau of Reclamation
Report No. REC-ERC-83-9, Denver,
Colorado, December 1983.
9-30
CHAPTER 10
ELECTRICAL AND MECHANICAL SYSTEMS
Automated canals include control structures with bearing assemblies. The leaf consists of a radially
electrical and mechanical components. This curved faceplate stiffened by horizontal beams and
chapter discusses gates, gate operators, pumps, vertical end girders. At each vertical end girder, the
motors, and other electrical and mechanical leaf is connected to a radial arm. The arms pivot
equipment for canal control. Most Bureau of on pin bearing assemblies anchored to concrete
Reclamation (Reclamation) canals use check pedestals integrally formed with the walls of the
structures with radial gates or slide gates for structure. The resultant thrust from the water
primary control. Recently, AMIL gates and pressure against the faceplate is transmitted
Obermeyer gates have been used on a few through the beams, girders, and arms to the pin
projects. Other types of gates (e.g., motorized bearings and wall pedestals. Music-note-type
overshot gates) are not discussed in this chapter neoprene side seals are mounted on the upstream
because they have not been widely used in faceplate, and a rectangular or music-note
Reclamation projects. neoprene seal is mounted across the bottom of the
faceplate. The seals contact stainless steel
wallplates and gate sills embedded flush in the
10-l. Gates and Gate Operators concrete walls and floor of the structure. The gate
is raised by lifting the faceplate and allowing the
Radial and slide gates are primary control devices gate to pivot on the pin bearings, providing a wide,
for regulating canal flow. These gates are used in clear, water passage under the gate. In some
canal systems to regulate or shut off the flow of installations, a radial gate may be used in a
water through check structures, siphons, turnouts, rectangular orifice opening by providing a top
and wasteways or sluiceways. Each of these gates sealing surface.
can be operated manually, electrically, or
hydraulically. Because canal automation typically The gate size is based on the hydraulic require-
requires automatic or remote operation of the ments of the structure, keeping in mind that the
gates, this chapter will only deal with the electrically gate width should not be more than three times the
and hydraulically operated systems. height, and normally the height should allow for
about 300 millimeters (mm) (12 inches [in]) of
a. Radial gates.-Radial gates (sometimes referred freeboard. The geometry of the gate and structure
to as tainter gates) regulate open channel flow should conform to the criteria on figure 1O-l.
through a rectangular opening. The face of the
gate is rectangular in shape and has a width Generally, the vertical height of the pin should be
to match the opening and a height greater than between 0.5P and 1.OOP. The vertical height
the depth of the water surface, as shown on should not be greater than 1.OOP unless RI is
figure 10-l. The radial gate is a welded and bolted increased over 1.25/? In no case should S be
steel structure consisting of a leaf, arms, and pin greater than T.
Canal Systems Automation Manual
The slope of the pin block, K, should be calculated (1) Gate hoist.-Normally, radial gates are hoisted
to the nearest l/4 using: by a two-drum, manually or power-operated wire-
rope hoist. Usually, the hoisting ropes are
connected to lugs near the bottom of the upstream
12 (S - P/3) face of the gate. In the case of top-seal radial
K=
10.1
p?:- (S - PMyp gates, the connection is made at the top of the
gate. A typical radial gate hoist appears on
figure 10-2.
Total water load on the gate is calculated from the
following formula: Gate hoists come in standard sizes and are
selected based on the horizontal projected area of
the gate, as shown in table 1O-l.
w= 34 BP2 10.2
1o-2
Electrical and Mechanical Systems
10-3
Canal Systems Automation Manual
cylinders, care must be taken to ensure the part of the gate frame (self-contained gate) or part
cylinders are synchronized to prevent racking of the of the headwall structure. The gate stem must be
gate during operation. sized such that the Ur ratio does not exceed 200,
where L is the unsupported length of the stem and
b. Slide gates.-Slide gates regulate flow through a r is the radius of gyration of the stem. Stem guides
circular or rectangular orifice by raising or lowering firmly mounted to the structure must be used to
a cover plate or leaf, allowing water to pass through reduce the unsupported stem length. The load
the exposed opening. These gates are mounted required to lift a gate leaf is calculated from:
on the upstream face of a headwall covering the
water passage, allowing the water pressure to be
transferred to the structure. To prevent leakage, a L=@tia+w+w 10.3
frame surrounding the orifice provides support for
the leaf and a sealing surface. Slide gates may where:
also be used for open channel flow by mounting
the gate frame in slots on the side wall and floor of L = load on the lift
a rectangular chute. Slide gates are separated into P = coefficient of friction
two distinct groups based on their construction- A = area of the gate opening
cast iron sluice gates (also referred to as cast iron H = head from water surface to center of
slide gates) and fabricated slide gates. the closed leaf
a = density of water
The manufacture of cast iron sluice gates is W = weight of the leaf and stem
governed by the American Water Works UC = wedge force
Association (AWWA) Standard C501. These gates
have frames and leaves of cast iron construction, To start the gate leaf from the closed position, a
with machined seating surfaces of bronze, or coefficient of static friction of 0.6 is used. Wedge
stainless steel on the frames and the leaf. The force (cast iron sluice gates) is equal to half the leaf
gates have adjustable wedges on the frames that weight.
force the leaf against the frame in the closed
position, allowing the gate to seal against an The diameter of the stem for the gate must be
unseating head. Because of their machined sized to safely handle the maximum column loading
seating surfaces, these gates have an AWWA on the stem. Euler’s column formula is used to
specified leakage tolerance. calculate the critical buckling load, P,, for the stem:
1o-4
Electrical and Mechanical Systems
Unit Efficiency = 0.5 (typically) 10.6 Other factors that must be considered in selecting
the lift are the locked rotor torque and the duty
cycle. The locked rotor torque (maximum
possible motor output) should not be less than
Unit Ratio = Motor (rlmin) + Gate Speed 10.7
Stem Lead
2.5 times motor operating torque. The duty cycle,
10-5
Canal Systems Automation Manual
which can be defined as permissible running time Position indication may be obtained by using a
at maximum load (typically 15 or 30 minutes), hydraulic cylinder equipped with a linear
should not be less than the full cycle operating time displacement transducer (LDT). The LDT is
of the gate. attached to the top of the cylinder with a rod
extending through a bore hole down the axis of the
The slide gate manufacturer will normally size the piston stem. A magnet attached to the top of the
gate lift given the maximum head on the gate, gate piston stem provides the position indication as it
speed, voltage, elevation, and ambient temperature moves along the rod. Another method of position
extremes. indication involves attaching a line with a
counterweight to the piston stem outside of the
(2) Hydraulic operators.-Normally, hydraulic cylinder and running the line through a pulley
operating systems for slide gates consist of a mounted to the cylinder, which is attached to an
hydraulic cylinder to raise and lower the gate and a encoder or potentiometer. A line may also be
hydraulic power unit used to control one or more attached from the stem to a direct-line-type position
cylinders. Hydraulic motors attached to manual indicator.
gate lifts are sometimes used to operate gates.
c. AMIL, AVIS, and AVIO gates.-The AMIL gate,
Typically, hydraulic operators are used in the shown on figure 10-4, is a specialized radial gate
following situations: that automatically maintains a constant water level
on the upstream side of the gate. It operates
. Multiple gate installations where one control without any outside power or motor, free of any
system can be used to operate all of the manual intervention, irrespective of incoming flow or
gates downstream water level. The gate is directly
l Where frequent gate operations are actuated by the water level it controls. The
required supporting frame rotates about a horizontal shaft
. Submerged operating conditions which and includes ballast containers for easy and
would be unsuitable for electric operators accurate balancing of the gate. Frictionless, non-
. Where emergency operation is required in stick operation is guaranteed by the tapered shape
the event of a power failure and of the leaf.
accumulators can be used for limited
operations AVIS and AVIO gates are similar except they are
designed for downstream control.
Hydraulic cylinders must be sized to lift the
maximum gate load at the desired operating d. Obermeyer gates.-The Obermeyer gate, shown
pressure. The operating pressure should be about on figure 10-5, belongs to a larger gate category
75 percent of the maximum system pressure. The generally referred to as overflow gates. Because of
operating pressure, P, is calculated as follows: its unique design, it has found applications in canal
systems. Normally, this gate is used as an
adjustable weir or wasteway gate. The gate is
P = L x (A, - As) 10.11 simply a rectangular plate sized to match the width
of the channel and has a height greater than the
water depth. The bottom edge of the plate is
where: hinged to the floor of the structure. An inflatable
rubber bladder which extends the entire width of
L = maximum load the gate is attached beneath the gate at the hinge.
A, = area cylinder Air pressure in the bladder is used to support the
A, = area stem gate in position, and varying the pressure will raise
or lower the gate. Stainless steel plates are
The operating pressure must also include the mounted flush in the chute walls to provide a
system and line pressure loss at the desired seating surface for rubber seals mounted on the
operating speed. When using sluice gates with gate.
wedges, the closing pressure must be reduced to
compensate for the larger closing area at the top of
the piston.
1 O-6
Electricaland MechanicalSystems
10-2. Canal-Side Pumping Plants of the units with a minimum of outages. However,
one unit should not be used for a water supply
Canal-side pumping plants are used to pump water dependent on continuous operation; a standby
from the main canal to elevated distribution pump should be provided.
systems. Vertical turbine pumps are the type most
often used. The vertical turbine pump operates When regulation of the water delivery is required, a
with its bowl assembly submerged in a sump and is number of pumps, or even two or more pump sizes,
suspended by the pump discharge column. The should be used. A common selection uses two
pump base supports the unit over an opening in the units at l/3 plant capacity, one unit at l/6, and two
concrete floor above the sump through which the units at l/12 plant capacity. This combination
assembled pump column and bowl assembly can provides flow increments of l/12 plant capacity, and
be installed and withdrawn. only l/3 capacity is lost when the largest unit is out
of service. The nominal discharge of each pump is
a. Selecting number and size of units.-In selecting normally increased by 5 percent (commonly called
the number and size of pumps, consideration must a wear factor) to assure that the plant will continue
be given to reliability, flexibility, efficiency, and cost. to deliver the required discharge after it has been in
One or two pumps may be adequate where service operation a number of years.
is intermittent, thus permitting time for maintenance
1o-7
Canal Systems Automation Manual
10-8
Electricaland MechanicalSystems
3,‘4 D
alternating-current (a-c) motors. Typically, motors motors are generally lower in cost but have several
are provided in a weather-protected enclosure such deficiencies with regard to canal automation.
as weather-protected Type II or totally enclosed fan Single-phase motor applications which involve
cooled to protect them from the elements and reversing operation present several problems.
environmental factors. Single-phase capacitor start motors require special
wiring and controls to provide reversing features.
When retrofitting existing installations for canal For radial gate applications, electrical brakes are
automation, an understanding of the characteristics required to stop motors from coasting, and if the
of existing motors and driven equipment is brakes should fail, a fail-safe detection circuit is
important to assure that the desired automation needed to prevent continued operation in the wrong
operation does not cause excessive wear to the direction.
equipment or exceed equipment capabilities. Most
motors have limitations in start-stop cycling and Three-phase motors are preferred where three-
minimum rest-run times which should be phase power is available. These motors are built
considered in implementing an automated system. for reversing operation which is easily achieved by
reversing the electrical phase rotation of the motor
For high torque applications such as slide gates or power through the use of motor contactors. Three-
valve operators, the motor operator may have a phase motors will always start in the proper
time duty rating such as 15 or 30 minutes, which direction without the problems noted above for
limits the amount of run time allowed during one single-phase motors.
time interval. This run time limitation should be
factored into the overall design of the canal control The greatest stress on motor windings and driven
system. equipment occurs on initial startup. Automation
controls should try to minimize start and stop
a. Alternating current motors.-Alternating current operations and significant cycling of equipment.
motors are used in almost all motor-driven Additional motor accessory equipment which
equipment whenever commercial power is readily reduces these startup stresses while allowing
available from nearby powerlines or underground greater control flexibility consists of soft start
utility circuits. controllers and adjustable speed drives discussed
below.
Single-phase motors are typically used when only
single-phase power is available. Single-phase
1IO-9
r .-
Canal Systems Automation Manual
b. Direct current motors.-Direct current (d-c) d. Adjustable (variable) speed operation.-A clear
motors are not usually considered for motor-driven understanding of the operating criteria for gates,
equipment for canal systems. However, for isolated valves, and pumps is necessary to evaluate
sites where commercial power is not available, d-c whether adjustable speed operation of this
motors may be used in conjunction with a battery equipment is desired or needed for a given system.
and solar cell charging system. These battery- Chapter 5 addresses how to determine operating
operated remote sites are normally only considered criteria for various components of the canal system.
for small gates with limited control because of
limitations in power supply. Automatically controlled gates will typically require
significant gate movement with variables such as
Direct current motors are also readily adaptable to maximum gate movement per hour, minimum
adjustable speed applications because of their increment of movement, gate movement speed,
inherent characteristic to maintain high torque etc. As the number of gate operations per hour
output over the entire speed range. When using increases, and as the need for closer regulation
d-c motors, this feature should be incorporated increases, adjustable speed becomes more
where applicable to enhance control flexibility. advantageous.
c. Soft start controllers .-Full voltage starting of Adjustable speed operation of gates and pumps will
motors places high mechanical stresses on the allow greater flexibility in operation by adjusting the
motor windings; inrush current values can reach speed of this equipment through an open or closed
600 to 700 percent of rated. Most soft starters loop control scheme to regulate flow. Fixed speed
today are solid-state devices with microprocessor operation requires step increments to achieve
controls. Soft start controllers gradually ramp up desired flow and can be limited by minimum motor
the voltage and current to the motor during starting. rest-run times. Adjustable speed control is also the
These controllers are used in conjunction with a-c preferred method for large systems when
motors to limit current and voltage to the motor Proportional-Integral Derivative (PID) loop control is
during starting and will therefore minimize motor being used.
winding stress and extend motor life.
The two general systems being used today to
Special coordination in the application of these achieve adjustable speed operation for canal
devices with the motor and motor load is required equipment are hydraulic and electrical. Hydraulic
to assure that adequate torque is available during systems achieve adjustable speed by using a
initial breakaway conditions when reduced voltage regulating valve in the hydraulic system which
and current are applied to the motor. Most controls flow to a hydraulically operated gate or
controllers have a kick-start or boost feature to valve, thus providing adjustable speed. The
provide a high current pulse (500 percent of full electrical method of adjustable speed involves
load current) to provide necessary breakaway controlling the motor speed through the use of a
torque. Soft starters generally cannot be used solid-state electronic device called an adjustable
effectively for constant high torque applications speed drive.
such as slide gates because sufficient torque is not
available during startup. Adjustable speed drive equipment for motors
involves an electrical conversion from fixed
Because soft starters gradually accelerate motors frequency a-c input power to variable frequency a-c
up to speed, some fixed time interval (typically 2 to output power. The variable frequency output of the
10 seconds) must be allowed for the unit to come drive controls the motor speed directly. Adjustable
up to speed. This acceleration ramp period is speed drives for motors on canal systems are
normally adjustable and must be coordinated with generally sized for constant torque application
the other control system parameters. (constant torque over speed range). The two most
common drives are the voltage source inverter and
To implement an effective control scheme, soft the pulse width modulated inverter.
starters should be considered whenever frequent
cycling of the motors is anticipated. For existing or Standard induction motors are generally suitable for
retrofit applications, the soft starter can be placed adjustable speed applications; however, the drive
in-line with the motor incoming leads. manufacturer should be contacted for any special
10-10
Electricaland MechanicalSystems
10-l 1
Canal Systems Automation Manual
Electrical/mechani-
Canal flow Mechanical cal operating Typical motor Typical
control structure equipment mechanism range power supply
Check structure Radial gate hoist Gear motor a. 1,705 N a. 1 -phase 208 volts
connected to worm- (7,500 lb) (V) or 3-phase
gear reducer 1.3 to 4 kW 208 or 480 V
(1 to 3 hp)
Canal-side Vertical or horizontal Typically sump Varies with flow 3-phase 480 V for
pumping plant pump motors pumping units which capacity and head 13 to 536 kW (10 to
pump into a conditions 400 hp)
discharge line
Above 536 kW
(400 hp) 2,300 V or
higher
Adjustable weir Obermeyer gate Adjustable air Air compressor I- or 3-phase 230 V
gate pressure motors sized for
within bladder system and will be 12- to 24-V dc (solar)
controls gate position in 1.3- to 4-kW for up to 0.17-kW
(1- to 3-hp) range (l/8-hp) compressor
10-12
Electrical and Mechanical Systems
the range of 1.3 to 13 kW (1 to 10 hp). These source. Engine-generators can be used for
demonstration projects require a massive network standby power when commercial power is
of solar panels and a large battery bank to meet available. Propane powered engine-generators
this high power demand. Costs for these systems can be used for power requirements up to 100 kW.
are extremely high and cannot normally be justified Above 100 kW, diesel powered engine-generators
for any automated canal structure. are the only option.
b. Battery and alternating current system.-The The engine-generators are sized to provide the
battery and alternating current system is similar to necessary surge for the load without exceeding a
the solar battery except that a-c power is readily lo-percent voltage drop. Staggered starting of
available and is used to charge the batteries in the motors will reduce the size of engine-generator
system. required. Tables listing characteristics of typical
load and sizing programs are available from
c. Air systems.-Compressed air can be used as engine-generator manufacturers.
an alternate or a backup system. The air
compressor is used to compress air in a 76- to Accessories for engine-generators include
84-liter (20- to 30-gallon) tank. The compressor automatic transfer switches, monitoring and control
can be driven by a fractional to l- or 3-kW (l- to equipment, exhaust systems, and fuel systems.
2-hp) motor when a-c power is available. Motors of Diesel tanks that are located above ground must be
about 0.17 kW (l/8 hp) or less would be used for double walled and must comply with Underwriters
the solar-based system. The tank of air provides Laboratories Standard 142. Propane tanks are
the reserve power to operate a system such as the rated for a 17-bar (250-pound-per-square-inch)
Obermeyer gate or other air operated systems. working pressure and are American Society of
Mechanical Engineers code stamped. Propane fuel
These systems work well with battery powered tanks comply with National Fire Protection
controllers where a small separate battery provides Association Codes No. 30, 54, and 58, and any
the power for the controller, radio, and air control other Federal, State, and local codes. Electric or
solenoids. The air stored in the tank provides the propane fuel vaporizers are sometimes used with
energy to fill the bladder or operate an air motor. propane fuel systems. The minimum ambient
The air is replenished while power is available and temperature determines when vaporizers are
provides a reserve should the power fail. necessary.
10-13
Canal Systems Automation Manual
switch. An operator will select a particular control In the supervisory automatic mode, additional
mode based on the desired level of control for that protection is provided by constantly monitoring all
structure and its related interface with the rest of parameters of the canal system and associated
the canal control system. Typically, one master equipment to achieve desired operation. Problems
selector control switch will be provided for all with any part of the system, whether gate
equipment associated with one system (i.e., one equipment or control related, are detected early
selector switch for all radial gates at a check and adjustments or alarms are provided
structure), although multiple levels of selector accordingly. As in the automatic mode, if problems
switches are found on some installations. are detected within the supervisory mode or the
communication channels, then the automatic
Ttie manual mode of operation places control of the controls should revert to the next appropriate level
equipment under an operator (pushbutton initiation) of control (manual supervisory or local manual).
at the equipment site location. The off position
disables operation of equipment from any source b. Equipment limit settings.-Typically, limit
and locks out equipment from operation. The switches are provided for motor-operated gates and
automatic mode allows control of the equipment to valves for remote indication and to limit operation or
be initiated through either local controllers or a travel of the gate or valve past the fully open or
supervisory system. closed position. Limit switches for hydraulic hoists
are used for remote indication in the full open or
When operating in any of these control modes, closed position. Motor-operated valves have the
safety features have been provided to minimize limit switch mechanism provided within the valve
damage to equipment, recognize improper operator. Radial gate structures typically have the
operation or erroneous signals, and provide a fail- limit switches mounted within an enclosure on one
safe mode of operation should problems develop. of the drum units. Hydraulic cylinders have
externally mounted switches which are operated by
In the manual mode, the motor is protected from a lever or bracket. Some float-operated cam
overload by the motor overload relays, which will systems (Little-Man, Colvin [chapter 31) use limit
trip out the motor for high sustained motor currents. switches to set upper and lower limits of the
Limit switches (pressure switches for hydraulic deadband.
units) are also provided for any gate operation to
shut down the driving motor when the gate reaches Limit switches in motor-operated gate lifts are set in
either extreme of travel (fully opened or closed). the field by adjusting the cam portion of the limit
These safety features are also inherent in all other switch to make mechanical contact at the desired
modes of operation (automatic and supervisory) travel limits (typically fully open or closed).
and serve as the primary means for protecting Electrical contacts off the limit switch are then used
equipment. in the control circuit to stop the gate or valve
operation. Normally, at least one set of contacts is
In the local automatic mode, a control algorithm is arranged to open in the fully closed position and
typically implemented to adjust the gate based on one set of contacts is arranged to open in the fully
water level signals. These control systems are open position. These switches are highly reliable
typically tied into a centralized control station to and provide primary protection against gate or
alarm for abnormal conditions such as equipment valve overtravel and motor or hoist damage.
failure, high or low water levels, control equipment
failure, local power outages, and communication Limit switches may need to be adjusted periodically
channel failure. A backup feature should also be in as the gate hoist cable or valve seal seating
place which transfers over to manual control characteristics change. Auxiliary contacts can be
whenever any emergency problem occurs within provided off the limit switches to provide indication
the automatic control system (loss of control signal at the control board or master station that the gate
or control logic malfunction). or valve is fully opened or closed.
10-14
Electricaland MechanicalSystems
c. Float and pressure switches.-Float switches are instrumentation provided for that device. Signals
used in oil reservoirs of automated hydraulic power which are clearly outside the design range for a
units. The switches are used to protect the parameter, abruptly change state, or have a rate of
hydraulic pump by automatically stopping it at low change which is not physically possible, should
oil level. The switches typically use a two-stage initiate an alarm within the control system and
circuit-one for warning indication and the other for either transfer control to a backup operation or shut
pump shutdown. that portion of the system down.
Pressure switches are used in hydraulic power unit Simple checks for analog control signals would
circuits to stop the pumps when the gate reaches include verification that the control signal is within
the end of travel. As the gate reaches the end of the 4- to 20-milliamp, 0- to 1-V d-c, or 0- to 5-V d-c
travel, the pressure in the hydraulic hoist rises. range as applicable. Also, lower and upper limits of
This pressure is sensed by the pressure switch, the parameter representing normal equipment
which breaks the electrical circuit to the motor- operation should be checked for agreement
operated oil pump. The pressure setting of the with calibrated value (i.e., 4-milliamp lower limit,
switch is set typically at 75 percent of the system 20-milliamp upper limit). A signal which indicates a
design pressure and should not be used instead of 3-m opening for a 2-m gate would obviously
the system relief valve. constitute an erroneous signal that should be
disregarded. However, the signal system should be
d. Dual measurement.-Different methods of checked.
measuring water level and flow and the associated
instrumentations systems were discussed in Digital,signals can also be monitored in a similar
chapter 9. The reliability and accuracy of these fashion to that described above for analog signals.
measuring devices must be considered when In addition, a need may exist to monitor excessive
integrating them into a canal automation control rates of change (abnormal fluctuations) of a
system. Dual measurement of critical level or flow parameter signal to alarm and transfer control for
parameters should be provided if erroneous signals control signal problems.
or loss of signals could lead to unstable or erratic
operation, which may lead to potential damage or f. Vandalism protection.-Automated gates and
safety problems. control systems are particularly susceptible to
vandalism, so special precautions must be taken as
Dual measurement for critical water level shown on figures 10-7 through 10-10. Hydraulic
parameters in the system can be achieved by cylinders, exposed fluid lines, and pushbutton
having two different measuring systems (float and stations must be protected from damage by
pulley, pressure transducer, capacitance probe, covering them with bulletproof enclosures. Control
etc.) or by having similar measuring methods at two houses should be windowless or should have
different locations along the canal. The method for protection over window openings.
transmitting the control signal (cable, fiber optic,
microwave) can also be used to provide
redundancy by allowing more than one control path 10-7. Other Equipment
back to controlling location.
a. Trashracks .-Trashracks are positioned in
The methods for evaluating control signal integrity the flow of waterways and conduits that serve
for resolution and accuracy are discussed in equipment needing protection. Trashracks, which
chapter 9. A dual measurement system provides usually consist of rows of parallel bars, are used
another method to check the accuracy of the water to protect equipment and waterways from
level or flow signals received through a comparison objectionably large or damaging debris or as a
check. A dual measurement system also allows safety rack for unwary swimmers or boaters.
continued full capacity operation as long as at least Trashracks are also used for the protection or
one of the signals is within range and reasonable. restriction of fish.
1O-l 5
Canal Systems Automation Manual
10-16
Electrical and Mechanical Systems
10-17
Canal Systems Automation Manual
BIBLIOGRAPHY
Aisenbrey, A.J., R.B. Hayes, H.J. Warren, [2] Bureau of Reclamation, Water Operation and
D.L. Winsett, and R.B. Young, Design of Maintenance Bulletin, No. 171, 21 pp.,
Small Canal Structures, Bureau of Denver, Colorado, 1995.
Reclamation, rev. reprint, 435 pp., Denver,
Colorado, 1978.
lo-18
CHAPTER 11
CANAL AUTOMATION EQUIPMENT
11-l. Planning, Failure Mode Studies, and Site All functions needed in the new control system and
Preconditioning all the hardware interfaces envisioned should be
included. The new control system should serve the
a. Planning.-For new projects, the engineering entire project (not only the operators), although the
group should determine the type of automation that operators are the primary users.
will provide the best control. Existing systems
present difficulties in identifying the most likely This phase also encompasses a thorough review of
group to start planning for a new control system, expansion plans and the definition of operational
upgrading, or expanding an existing control system. requirements and procedures to be supported by
Typically, operation or engineering personnel the new control system over its expected life.
recognize the need for improved or expanded Based on the review, the hardware and software
control or replacement of obsolete equipment. components can be identified and evaluated to
Then an attempt is made to justify purchasing a provide a man-machine interface (MMI)
new control system, upgrading, or expanding the configuration satisfying the functional requirements
existing system. of the operators. The agency can issue a request
for budgetary estimates by vendors. For
Planning for a new control system or for upgrading competitive reasons, such budgetary estimates are
or expanding an existing control system should be often purposely vague. Budgetary cost estimates
accomplished by an automation team. The and schedules can then be refined to determine
automation team should include one control project funding requirements.
systems expert and representatives from each
major area of the organization that will be affected A failure mode study should be made for the new,
by the new, upgraded, or expanded control system. upgraded, or expanded control system. Each piece
The automation team should produce at least two of control system equipment should be listed with
reports which contain the data necessary to the anticipated failure modes and the effect of the
evaluate the operation of the new, upgraded, or failure upon control system operations. A more
expanded control system. The automation team detailed study dealing with simultaneous failure
should produce a requirements report and a modes may be desired depending upon budgetary
justification report. constraints and the acceptable degree of system
reliability. Based upon the study results and the
The requirements report should establish: acceptable degree of system reliability, a plan
should be made to mitigate different failure mode
(1) New, upgraded, or expanded system consequences and maximize the system reliability.
requirements.-For example, new or modified The plan should define operator or hardware-
control processes and new or modified data software procedures to be executed for each failure
collection requirements. mode or modes to attain this goal. The plan might
Canal Systems Automation Manual
consist of adding equipment redundancy and l The power requirements at each site for the
software to define actions for each failure condition. current and future system must be
determined (e.g., quantity, type,
(2) System reliability and maintainability.-System requirement for backup power, length of
reliability and maintainability are dictated by the time backup power is to be available, etc.).
quality oi the system hardware and system . The environmental requirements at each
software and the expertise of the maintenance site for the current and the future system
personnel. must be identified (e.g., the ambient and
electrical environments).
The system design team can dictate hardware and . The communications requirements to/from
software quality by writing a stringent system each site for the current and the future
design document. The design document should system must be determined (e.g., type, how
encompass all system hardware (current and often, failure mode communications, etc.).
future), all system software (current and future), . The status and control requirements for
and maintenance personnel training. each site current and future must be
identified. For each site in the system, a
Maintainability begins with quality hardware and site input and output points interface must
software and is completed by a highly skilled and exist or be created. A site input and output
motivated maintenance staff. The system design points inter-face is created by terminating all
team can dictate the system training requirements, required input and output circuits at one
including training aids and duration of training in the location. Each input and output point
design document. should be terminated on terminal blocks.
Each input and output point should be
(3) System availability.-The automation team must clearly labeled. Input and output points
determine the acceptable system availability. Some should be arranged in a logical manner
criteria to examine in order to determine an (e.g., grouped by device). Extensive and
acceptable availability are: the Size of the control costly retrofitting will be required if existing
system (number of remote control sites and the equipment does not provide auxiliary
number of status and control points per site), the contacts and routing paths to the interface
type of control system, the equipment being from the controlled devices for input and
controlled, the replacement cost of the equipment output points needed for the control
being controlled, the location of the remote control system.
sites, and the cost of catastrophic failure. The list . Modification to equipment control circuits
of criteria is not exhaustive and is not in order of may also be required if the circuits are not
importance. compatible with the proposed control.
Attention must be paid to required status
(4) The acceptable system life cycle.-The and control circuits, control circuit voltage,
automation team should examine the life cycles of and current ratings to assure proper
each major hardware and software component that insulated conductor ratings, terminal block
is intended for use as part of the control system. terminal ratings, and conductor shielding.
Selecting components that are well advanced in . The site interface should be located near
their life cycle will dramatically affect (shorten) the the site control device to avoid unnecessary
life cycle of the control system. voltage drops and noise in the control
device’s input and output circuits. A
(5) Facility requirements (site preconditioning).- primary power source, communications
The automation team must determine what site channel via metallic wire, radio, telephone
preconditioning is required for existing and future leased line, microwave, etc., for the control
control sites. Site preconditioning must include device should be provided. Conduit or
each site in the system and each aspect or each cable tray paths to the control device for
site: power, environment, communications, status, power, communications, and all input and
and control. The following items must be output points should be installed.
considered and exist prior to the control system
installation:
11-2
CanalAutomationEquipment
. Physical space for the control device, its range from being totally mechanical to being
power supply, and backup batteries if microprocessor based with electromechanical
required must be allocated with adequate circuitry. Local control systems operate by sensing
clearance for enclosure ventilation and current site conditions and executing a control
maintenance. operation dictated by the control algorithm that has
been implemented in the local controller. Typical
(6) The schedule.-An important part of the types of local controllers include:
requirements report is the proposed project
schedule showing the various tasks leading to the a. Water-powered controllers.-Water-powered
procurement and installation of the new, upgraded, controllers are the most basic type of local
or expanded control system. It is important that the controllers. These controllers use floats that are
schedule be realistic in the time allotted to complete attached to regulating gates to emulate an
the various tasks. upstream or a downstream control algorithm.
Controlling the water level immediately upstream or
(7) Cost estimate.-During the initial stage of the downstream from the controlled gates is the only
planning process, reliable budgetary cost estimates control possible. Floats must be sized and placed
are impossible to determine. The primary reason in the proper position on the regulating gate to
for the lack of a definitive estimate is the lack of assure accurate emulation of upstream or
data concerning the requirements of the new, downstream water level control.
upgraded, or expanded control system. An
accurate, detailed estimate for the new, upgraded, b. Microprocessor-based controller with
or expanded control system should be produced electromechanical circuitry.-Microprocessor-based
from the requirement studies. controllers are the most sophisticated type of local
controller. These controllers use transducers to
The justification repot-l should contain: measure process variables and can emulate
multiple upstream and downstream control
1. Review and evaluation of present operating algorithms. Controlling the water upstream and
procedures, facilities, and staffing downstream from the regulating gate or valve is
2. Review of existing and future plans for only one of many control functions that the
control system features and resources controller can provide.
3. Review of likely features to be automated
4. Review of alternate control system A well-designed, microprocessor-based local control
configurations and procurement methods system can contain failover and failsafe operating
5. Determination of the best possible control procedures to:
system solution and procurement method
6. Definition of a preliminary implementation l Detect bad input data by comparing data
plan including: values to a predefined rate of change,
deadband, or predefined data characteristic
. Budget estimates . Detect defective transducers
. Basic system block diagrams for the . Detect defective system hardware
recommended system components
l Preliminary manpower requirements l Detect defective system software modules
. Preliminary facility requirements
11-3
Canal Systems Automation Manual
this collected data to a remote site; and the remote- distances are required, the telemetry system will be
site, MMI which remotely displays collected data in comprised of units that function as multiplexors and
a useful form to the end user. The type of data demultiplexors. The multiplexor’s purpose is to
transmitted (status and analog), the accuracy of the convert multiple measured analog or status signals
control algorithms, the MMI display requirements, into a single analog or digital signal. The signal is
the distance from the collecting site to the then transmitted over a communications media and
controlling site, and the alarming capability demultiplexed at a MMI. A variety of equipment
determine what type of telemetry system and may be used to function as multiplexors or
equipment are required. demultiplexors. The equipment selected will depend
on the quantity and type of monitored signals, the
a. Hard-wired telemetry systems.-The simplest speed at which the monitored signals will be
telemetry systems consists of remote readouts hard transmitted to and displayed at the MMI, and the
wired to transducers. Short distances between the available multiplexor to demultiplexor
transducer and the readout for a few measure- communications link type and speed.
ments are a good application for hard-wired
telemetry systems. The simplest and least expensive multiplexor used
in canal systems automation is a data concentrator
Hard-wired canal depth and gate position telemetry which, depending upon the manufacturer, will
systems can be either current or voltage output output either a digital signal or an analog frequency
circuits with remote readouts located from 9 to division multiplexed signal. Programmable logic
2,300 meters (m) (30 to 7,500 feet [ft]) from the controllers may also function as multiplexors and
transducer. The readout device consists of a high demultiplexors. Multiplexors and demultiplexors are
accuracy and high precision, temperature purchased as a unit because the multiplexor to
compensated, scalable process meter with a demultiplexor communication software protocol
current to voltage conversion circuit. used is proprietary to the specific manufacturer.
However, some vendor protocols are public, which
For greater range in depth or gate position is very useful when interfacing an existing
measurement, a multiturn resolver may be used multiplexor signal to an existing system is desired.
with the measurement displayed up to 150 m
(500 ft) from the measurement site. The resolver, One can expect the following from inexpensive
resolver signal encoding method, and the readout telemetry systems: slower measured signal scan
device are unique and proprietary to each resolver rates; limited number of measured signal types;
manufacturer. may not provide measured signal optical isolation;
multiplexor protocol proprietary to one
Hard-wired status data consist of a contact closure manufacturer; minimal MMI readout devices; and
transducer connected to an alternating- or direct- output signal availability at an output terminal
current voltage source. The readout device can board. The more costly telemetry systems will
consist of something as simple as a light-emitting typically provide: higher measured signal scan
diode or incandescent panel lamp. The distance rates; telemetering of all types of the standard
from the measurement sight to the readout is transducer signals; input signal optical isolation; a
limited by current induced voltage drop in the hard- high level of communications system data security
wired circuit. to prevent erroneous control and readout signals;
MMI readout at the multiplexor side of the telemetry
Hard-wired water flow in a conduit is usually a as well as at the demultiplexor side; sophisticated
pulsed direct-current output signal; the frequency of input signal conditioning and processing to
pulses is proportional to the rate of flow. The minimize erroneous and extraneous data; and
pulses are transmitted to a readout which counts multiplexor communications protocol to
the pulses and displays instantaneous and communicate with numerous existing telemetry
cumulative flow. Transducer to readout distances systems and with supervisory control and data
involved may be up to 305 m (1,000 ft) or greater acquisition systems.
depending upon the signal and cable characteristics
involved. The alarming portion of a telemetry system may
use public telephone system dual-tone multiple
b. Multiplexed telemetry systems.-Where larger frequency subscriber lines or ultra-high
quantities of measured signals and greater readout frequency/very-high frequency (UHFAIHF) radio to
11-4
Canal Automation Equipment
deliver alarm messages. Ultra-high frequency SCADA systems may operate in one of several
radio-based personal pager systems and cellular modes that allow project resources to be scheduled
phone systems may also be used effectively and or optimized. The modes of control refer to the
economically to transmit alarm messages. participation of an operator in overall project
Telemetry systems can be used to notify an control. The typical modes of control were
operator of an analog or digital status change discussed in sections 1 through 7 of volume 1.
requiring immediate attention if the MMI is not
manned 24 hours per day, 365 days per year. a. Types of control.-Four types of control will be
discussed. The use of a particular type of control is
Telemetry communications system requirements based on the operational constraints of the
range from 300- to 3,000-hertz full duplex equipment, the operational requirements of the
bandwidth analog communications channels to a system, and the particular control requirements of
44-megabit-per-second fiber optics channel. These the selected control algorithms. The four types of
communications systems may be metallic wire, fiber control are:
optic, UHF/VHF/microwave radio, public telephone
leased lines, cellular phones, satellite, and meteor l Supervisory/manual
burst. System selection is determined by the l Supervisory/automatic
required system bandwidth. l Computer directed
l Optimization
11-5
Canal Systems Automation Manual
Control of a device by the master station via a mode. The RTU operation is based on the type of
communication channel rather than providing the control necessary to provide the desired overall
additional capability in the RTU to perform the system operation. For example, a schedule may
required calculations for the necessary control is be based on facility equipment operating
called open-loop control because the process parameters, or it may be based on control
hardware and the process software do not reside at variables. If the schedule produces actual device
the same site. Open-loop control is not a settings for each facility, then the RTU is operating
recommended control method. in the supervisory/manual mode. If the schedules
produce control parameters such as flow and water
(2) Supervisory/automatic.-Reclamation designers levels that require the RTU to maintain a particular
refer to automatic control of project facilities, by an rate or level, then the RTU is operating in the
RTU functioning without intervention from the supervisory/automatic mode.
master station, as the supervisory/automat
mode of control. The RTU adjusts each controlled This type of control is used for system operations
device to the desired position or setpoint value and that require adjustment of facility equipment based
maintains the device position based on system on unpredictable system loads or demands.
conditions without operator intervention.
The data acquisition requirements for this mode of
Data monitoring requirements at the remote sites operation are similar to those required for the
must be extensive enough to execute the required supervisory/automatic mode of operation with the
supervisory/automatic control functions and/or addition of system data that may be collected at
algorithms. Alarm monitoring should be extensive, additional sites. System information is required to
so the operator is notified of abnormal and/or perform the necessary calculations to operate the
aborted control functions or algorithms. Data system to meet load or demand, reject load or
presentations at the master station should allow the demand, and operate in an efficient manner.
operator to alter each control function and/or These data are not always available at the remote
algorithm parameter, limit, and deadband. Data site, and additional remote-site equipment may be
presentation at the master station should be in a necessary to collect the required data.
clear format because the data presented to the
operator will allow the operator to check for proper (4) Optimization.-The optimization mode of
function and/or algorithm execution and to decide control refers to the same mode of control as the
on proper corrective action or actions. computer-directed mode, except that system
operation is optimized to produce the most efficient
(3) Computer directed.-Reclamation designers system operation. This mode requires data
refer to computer-directed mode of control of regarding facility equipment rating curves and
project facilities as control functions being efficiency data. For example, generators and
performed by the master-station computer in pumps may have a certain capacity in which they
conjunction with the communication equipment and run most efficiently based on their calibration/
the RTU’s. This control mode requires no operator efficiency curve data. This type of information
intervention to perform the necessary system would be used, in conjunction with the system data,
control. In this mode of control, each remote-site to produce the most efficient operation of the
RTU is polled by the master station, the master- pumps or generators. In addition, electrical
station computer performs the necessary algorithm demand type functions such as onpeak and off-
calculations using the system data and other peak pumping requirements can be used with the
appropriate data as input by the operator, and optimization mode to produce the most efficient and
control commands are then issued to the RTU’s to economical system operation. The optimization
adjust facility equipment operation as necessary. mode can be used, in conjunction with a scheduling
For this mode of operation, the commands issued program, to provide the most efficient system
to each RTU should be schedules. Schedules can operation during the particular scheduled time.
be executed by the RTU for long periods of time
without intervention by the master station. The optimization mode requires no operator
intervention during operation of the system. If the
The RTU may operate in the supervisory/manual system demands are such that the optimization
mode or in the supervisory/automatic mode when process will not allow the demands to be satisfied,
the system is operating in the computer-directed the computer-directed mode is automatically
11-6
Canal Automation Equipment
initiated, and the operator is notified that a operator to generate reports and compile records of
particular facility is no longer being optimized. The the overall system operation for which the operator
operator may then try to correct the facility is responsible.
operation to obtain the best operation. Operator
control would be initiated from the supervisory/ The data collected also satisfy the need for data
automatic mode. Any system emergencies that from other segments of the organization. For
occur during the optimization process will cause the example, the data could be used to provide records
optimization mode to be automatically transferred to for scheduling and billing purposes. Operations
the computer-directed mode. In all cases, the personnel and designers would be interested in the
optimization mode can be initiated or canceled by operation of protective equipment after failures or
the operator as desired or as necessary. abnormal operations occur. Maintenance
personnel would use the data in regard to the
The data acquisition requirements for the frequency of operation of certain equipment and
optimization mode of operation are the same as for records for the determination of periodic
the computer-directed mode of operation. maintenance required for the facility equipment.
Additional data required by the optimization mode Planning personnel would be interested in the data
of operation would be the equipment rating and for determining the required water releases that
efficiency data for the facility equipment. may be required to meet operational demands of
the system. Also, various levels of management
b. Benefits of centralized control.-A properly would use the data in the form of summary reports
designed and implemented SCADA system that provide information on the performance of the
provides numerous benefits to the operators of a overall water system operations.
water project. The two most obvious benefits are
the increased efficiency of overall project operations Because many departments within an organization
and the reduction of operating cost because of may be interested in the data collected by the
reduced personnel requirements. The efficiency of SCADA system, the needs or desires of all
overall project operations cannot be obtained with departments must be considered during the design
any of the other methods of project automation. of the system.
Although the initial cost of the SCADA system is
greater than the other automation methods, the The ability to schedule and optimize the water
long-term overall system operation, reaction to system operations is possible with a SCADA
abnormal conditions, correction of operating system because the data required for the operation
problems, and efficiency of operation will provide of the system are centralized. Scheduling
benefits that the other less expensive methods of operations can be performed well in advance of
automation cannot provide. Cost/benefit ratio implementation, and these schedules can then be
calculations for SCADA system control must include implemented at the correct time through the
cost factors that account for more efficient SCADA system. Scheduled operation can be either
operation, less waste, and rapid identification of automatic or manually controlled by the operator.
system operational abnormalities. The specific To provide scheduled operation, data from all
benefits related to SCADA system control will be facilities within the system must be collected, and
discussed for both normal and abnormal the equipment within each remote site must be
operations. controllable from the master station.
c. Normal operation.-The primary purpose of a Optimizing water system operations is also possible
SCADA system is to provide water system with SCADA systems. Optimization of system
operators with information and control capabilities operation is intended to provide the best and most
that are necessary and desirable to properly efficient operation of a system during normal
manage water system operations. The information operation. Changing system conditions are
collected and control capabilities are intended to immediately detected and analyzed by the SCADA
alert the operator to abnormal system conditions system and used in the optimization process. In
and to allow a timely and effective response to addition to data collected by the control system,
emergency conditions that occur in the water data received from other systems, agencies, or
system. The data collected are also used for the water districts can be used to further optimize water
system operation.
11-7
Canal Systems Automation Manual
d. Abnormal operations.-The SCADA system information update time is the interval of time
provides the operator with system data in real time, required by the master station to record the data it
so reaction to abnormal system conditions can be collects from the RTU’s in the data base and
performed in a short time. The data presentations modify all system data to reflect the most recent
at the master station can be organized into logical scanned data. Typical system information update
groups, so when an abnormal condition is present, times for water control systems can range from
the appropriate alarms can alert the operator to the 0.5 second to 5 seconds. In general, the system
abnormal condition, and the operator can react to total response time can range from 1.5 seconds to
the problem without long delays. 10 minutes.
With all of the system data available at the master It is important to determine what the data
station, the organization of alarm presentations is monitoring and control requirements are for each
extremely important. Overwhelming the operator remote site so the master station and the
with too much alarm information can cause long communication system can be designed to provide
delays in correcting system problems. The ability the proper real-time response to each remote site
to prioritize alarm information and present only to maintain control of the system. It is also
information that has changed since the last data important to determine how the data will be used at
request is important in maintaining efficient system the master station so the data being monitored can
operation during abnormal conditions. be collected at the proper frequency to maintain the
correct system or process control response time.
Historical data before, during, and after abnormal For example, if water flow data are needed for
conditions occur can be automatically obtained by online optimization, the flow data should have
the master station; therefore, when an abnormal frequency of collection consistent with the
condition occurs in the system, analysis of what requirements of the control algorithm.
caused the abnormality can be performed by
engineering personnel. b. Availability requirements.-Availability is defined
as:
11-8
Canal Automation Equipment
operation of the remote-site equipment, and single and double bit message errors in multiple
(2) eliminate and protect against multiple and byte messages. Long messages should be
cascading component failures. transmitted as packets of 256 bytes.
The design goals for the system maintainability are The efficiency of the message transmission can be
as follows: (1) minimize the time interval between defined as follows:
a failure of a system component and the call for
maintenance service (administrative time), Message Efficiency = (TMB - [SB + OB])ITMB
(2) minimize the time interval between the call for
maintenance service and the arrival of the where:
maintenance personnel at the site with the
necessary test equipment and repair parts TMB = total message bytes
(transport time), and (3) minimize the time required SB = security bytes
to repair the failed equipment and to restore to OB = overhead bytes
normal operations (repair time).
Message efficiency for short messages should be
The availability figure is usually expressed in greater than 55 percent. Short messages are
percent. This percentage indicates how well the messages of less than 17 bytes. Return messages
overall SCADA system will perform. For computer- from RTU’s that contain no data under the report by
based SCADA systems, the availability figure can exception method of operation should not be
range from 95 to 99.9 percent. The system considered when determining message efficiency.
configuration, spare equipment assemblies, spare
parts inventory, and type of maintenance service The select-before-operate security sequence is
determine directly the availability figure. It is primarily associated with controlling remote-site
important for the automation team to define how equipment. The select-before-operate sequence is
long the master station can be out of service. The usually designed to perform the following functions:
out-of-service time should be based on the overall (1) prohibit control operations at the RTU site if
system requirements. After the out-of-service time both the select and execute messages do not
has been determined, the system configuration can coincide to define the same control output,
be defined, and the control system equipment can (2) reset the selected control output if any other
be designed to meet the availability requirement. message is received prior to an execute message,
and (3) reset the selected control output if the
c. System security requirements.-The SCADA execute message is not received by the RTU within
system must be designed to operate the equipment 10 to 60 seconds.
at remote sites over a communications network.
Because control information is being transmitted In general, the select-before-operate sequence is
over a communication network, some type of data designed to operate as follows:
security must be employed to prevent incorrect
remote-site equipment operation. Generally, two Select-The device to be controlled is selected
types of data security measures are used in by the operator at the master station. The
SCADA systems: message securjv and the control message is sent to the RTU. The RTU
select-before-operate sequence. checks the message and arms the requested
control output. The RTU retransmits the
Message security is the process of attaching a message to the master station. The master
security code to all messages that are transmitted station compares the message with the original
over the communication network. The security message sent. If all checks pass, then the
techniques must provide a high degree of master station is ready for the operate
protection against error in the message received by command.
the RTU and must also maintain a relatively high
data transmission rate. The most common method Operate-The device execute function is
of message security employed by the SCADA performed by the operator at the master
systems is the Cyclical Redundance Check-16 station. The operate command is transmitted
method. The 2-byte security code will detect all to the RTU. The RTU checks the message
and, if it passes the checks, the previously
armed control output is executed.
11-9
Canal Systems Automation Manual
In addition to the above security features, the The RTU does not usually require any supple-
following items should also be taken into mental air-conditioning equipment; however,
consideration as part of the overall system security heating equipment is usually required. Typical
scheme: environmental data for RTU’s are:
11-10
Canal Automation Equipment
11-6. SCADA System Design b. How many analog data are required to be
sent to the master station in the defined
a. SCADA system hardware.-A SCADA system response time?
consists of the following basic elements or c. Is collection of status data based on
subsystems: reporting all status changes on each data
request, or is it based on reporting only the
. Power centers and uninterruptible power changes in status since the last data
supply equipment request?
l Central processing equipment and d. How frequent is the closed-loop control
peripherals algorithm required to calculate changes in
. Operating system software equipment operating points and issue
- SCADA software including man- appropriate control commands?
machine interface software
l Communication system Based on the answers to these questions, the
. RTU designer can make some decisions on the master-
- Data acquisition and control equipment station hardware configuration and the RTU
- Transducers requirements. If the data acquisition and control
requirements are significant and the response time
The SCADA system equipment design and is short, the designer must consider a
configuration are based on the requirements of the communication front end processor (FEP) to
application, as discussed in the previous section, provide the processing and execution of data
and on the particular elements that comprise the acquisition and control commands. By processing
overall water system. The designer needs the system communications data in a separate
information regarding the functions to be performed computer, the master-station main computer system
by the system, the desired operational capabilities is free to do other system-related tasks, and the
and features, and the initial and projected ultimate system response to operator requests and actions
size.of the project in order to provide the proper can be maintained. If the communication
master-station configuration design. These data messages to the RTU’s require security encoding
allow the designer to propose the most efficient and and decoding for safe control operations, the FEP
economical configuration to satisfy the needs of the can perform the necessary message security
overall project operations. The following is a processing.
general discussion on the basic elements of data
acquisition and control, central processing The quantity of data being collected throughout the
equipment and peripherals, and RTU’s. Software system will give an indication of the size of the
packages will be discussed under the SCADA master station’s main computer. If the response of
system software section. Power centers have the system can be relatively slow, then an auxiliary
already been discussed in previous sections. MMI memory device (usually a disk drive) may be
and RTU’s will be discussed in the paragraphs that acceptable for data base storage.
follow. Communications systems and basic
equipment grounding are discussed in chapter 8. (2) Central processing equipment and peripherals.-
The configuration of the master-station equipment
(1) Equipment configurations.-The data will depend upon the system operational
acquisition and control subsystem consists of the requirements. The design criteria mentioned above
RTU for interfacing to the remote-site equipment, concerning the response time and availability
master-station equipment for interfacing the (reliability and maintainability) will influence the
operator to the system, and the communication master-station computer equipment configuration.
system. The configuration of the master-station In large control systems, the dual redundant/
equipment depends upon the data acquisition and computer configuration is the most common. The
control subsystem in terms of: dual redundant computer system is shown in
simplified form on figure 11-l.
a. Do the communication channels allow a
separate channel for each RTU, or do The on-line computer equipment and its associated
RTU’s have to share a communication auxiliary memory devices must be large enough to
channel on a party line basis? manage all of the real-time functions for the
11-11
Canal Systems Automation Manual
t
t
Communication interface
equipment
remote terminals
system. Common practice involves having the on- The FEP’s provide all of the polling, data
line computer store information collected from the acquisition, message security encoding and
system (data base) on both the on-line and backup decoding, data formatting, and communication
auxiliary memory devices. This redundancy channel monitoring functions so that the on-line
ensures that, when the on-line computer fails, the computer system is free to perform the other real-
backup computer has an updated copy of the time related functions. This configuration enhances
system conditions stored on the auxiliary memory system response time and allows the on-line
and can assume real-time operation with minimum computer system to perform many closed-loop
system interruptions. The same scenario applies to control functions in addition to the supervisory
a failure of the on-line disk. The backup disk can control functions. The FEP configuration allows
be used by the on-line computer without causing more flexibility for adding communication channels
system operation interruption or loss of real-time and operating channels with different
data. communication protocols.
The backup computer system can be used to do Another configuration that is becoming more
other functions associated with the real-time popular for larger systems is the distributed
system. These functions include scheduling, processing approach. In this type of configuration,
system modeling, training, report generation, and a symmetrical backup system to the on-line system
other functions related to the system operations. does not exist. Backup is achieved by having one
By allowing the backup computer to perform these computer as a dedicated backup or having a
tasks, the on-line system response is maintained, degraded backup in which a computer performs its
and real-time system operations are not interrupted own function and picks up the function of the failed
because of long processing delays. processor. Each processor has its own set of
tasks, but neither one acts as the primary
If the data collection requirements are large and the processor. Communication between processors
required response time is extremely short, then a occurs through a combination of communication
dual redundant computer configuration with FEP’s channels, shared memory, and shared auxiliary
to handle the communications is used. This memory. A simplified distributive processing
configuration is shown on figure 11-2. configuration is shown on figure 11-3.
11-12
Canal Automation Equipment
t
I Communication
1,
interface
Figure 1 l-P.-Dual
+TChannels
redundant
to remofe terminals
Network
i A
t t t
Online computer Online computer Online computer
ci
Common
memory
r- Online
11-13
r-’
Canal Systems Automation Manual
project. The peripherals that are required to support SCADA system will not function as effectively as is
real-time operations are based primarily on the possible, and the operator cannot function as
master-station configuration and are usually effectively as is possible; hence, system operation
determined as part of the overall supervisory will be degraded. The severity of degradation
control and data acquisition, scheduling, and depends upon how many critical factors were not
optimization requirements of the system. considered or known when selecting the operating
system or the SCADA software.
(3) Man-machine interface equipment.-The MMI
subsystem consists of the operator’s console(s), The following paragraphs and subparagraphs
color CRT’s, cursor control device(s), and contain guidelines to aid in the selection of an
keyboards. The operator’s console design should operating system and SCADA software and to
be carefully planned so that the operator can briefly discuss some of the more important features
communicate with the SCADA system in an of operating systems and SCADA software. The
efficient, simple manner. The console should be of larger and more complex a SCADA system is, the
modular construction to allow for modifying control more important each of the following features
room arrangements and convenient shipment. The becomes.
main operator’s console should have a minimum of
two color limited graphic CRT’s so that the operator (1) Operating system software.-An operating
can view overall system diagrams at the same time system is defined as an organized collection of
plots, trends, bar charts, or remote-site conditions system programs that interface computer hardware
are being viewed. The operators console should (the central processing unit [CPU], disks, CRT’s,
contain one operations keyboard with a cursor printers, etc.), computer software, and users. An
control device (lightpen, trackball, etc.). operating system provides the users with a set of
tools to simplify the design, coding, debugging, and
The keyboard should contain special user definable maintenance of system and application programs;
function keys. Sample canal automation function at the same time, the operating system controls the
keys are raise/lower, start/stop, alarm acknowledge, allocation of computer hardware and software to
etc. The operations keyboard (also referred to as assure execution of scheduled system and
the alphanumeric keyboard) controls the editing application programs.
and interface to the CRT display system. This
keyboard is also used for alphanumeric entries The three basic types of operating systems are:
required on the control displays. The CRT’s should batch, time-sharing, and real-time. An operating
be built into the console to allow easy viewing and system is defined as real-time if it services on-line
cursor control by the operator. A low-profile external processes having well-defined timing
console design will be required if the operator must constraints that generate interrupt signals that direct
look over the top of the console to observe a large the resources of the operating system. A SCADA
mimic panel. The CRT’s must be mounted in the operating system must be a real-time, interrupt-
console in such a way that they will not obstruct the driven operating system.
view of the operator. Sometimes, this type of a
console design is not suited for lightpen or touch The operating system components described in this
screen methods for cursor control; therefore, the manual are not all the components contained in
designer must be aware of the “basic” console any manufacturer’s operating system. The
design decisions early in the project design. operating system components described in this
manual are those components experience has
b. Master-station software.-The two critical shown to be critical to satisfactory operation and
components of the master-station software are the maintenance of a SCADA system. Not all
operating system and the SCADA software. manufacturers have named the components of their
System operation will be enhanced if these two operating system with the same name used to
components are properly selected because the describe the recommended critical operating
software will aid the operator in making decisions, system components in this manual. It is vital that
or the system will make decisions automatically the features contained in each component
based on accurate real-time data and a well- description be performed by an operating
defined set of rules. If neither the operating system component before the operating system is
nor the SCADA software are selected properly, the considered for use as part of a SCADA system.
11-14
Canal Automation Equipment
(a) Command control language.-The operating of hardware that is part of the master station.
system should be furnished with an extensive These diagnostic routines should provide extensive
command control language. The command control printout and interactive input via a CRT and
language allows the SCADA system manufacturer keyboard. These detailed device diagnostics
to write command procedures that cause the should provide more details on device failures that
master-station software and hardware to function as have been identified by the periodic on-line
a real-time SCADA system. diagnostics. The off-line diagnostics should identify
a device failure down to the chip level.
(b) Executive.-The executive coordinates all CPU
processing by performing the functions of task (e) System management services.-The following
scheduling, resource allocation, queuing, software system management services software should be
interrupt processing, and input/output (I/O) control. provided as part of the operating system:
Queuing and scheduling processes must take place
according to the type and priority of the request. i. System configuration.-System configuration
software should provide reconfiguration of the
(c) Device drivers.-As a minimum, a device driver system hardware by assigning or deleting devices
for each different piece of master-station hardware from the system based on device availability.
(disk(s), tape(s), printer(s), plotter, keyboard,
communications ports, etc.) should be included as ii. System backup.-A disk memory management
part of the operating system. Each device driver (DMM) utility should be furnished as part of the
should operate in conjunction with the remainder of operating system. The DMM should operate on all
the operating system to process all l/O requests for types of disk and tape media furnished as part of
the device. The qperating system should identify the master station; i.e., hard disks, floppy disks,
the I/O device requested via the hardware vectored optical disks of all types, and tapes of all sizes and
interrupt method and transfer control to the correct types. The purpose of the DMM is to provide an
driver so the device dependent task can be easy means of creating and modifying program and
completed. data records to the system. The DMM should
assist in these operations by controlling and
(d) Diagnostic software.-Diagnostic software aids recording the allocation of disk memory. Disk
in producing and maintaining a high degree of memory management software should determine
confidence in system operation and aids in the how the areas of disk memory are used and by
reduction of MTTR. To accomplish the tasks of what software. DMM should be structured to allow
producing and maintaining a high degree of the programmer to create files (including naming
confidence in system operation and reducing the them, locating them, etc.), delete files, append files,
MTTR, two levels of diagnostic software should be substitute files, concatenate files, merge files, move
included as part of the operating system: files, sort files, and display the contents of a file or
the disk memory map on a designated output
i. Periodic on-line diagnostics.-On-line diagnostic device.
software should provide periodic analysis of each
piece of master-station hardware. Master-station iii. Device utilization software.-The operating
hardware that should be analyzed periodically system should include device utilization software
includes the CPU, the solid-state memory, the disk that measures and outputs utilization data for the
memory, the controllers, the printers, and all other CPU and disk memory devices. The types of
peripheral devices. The on-line diagnostic software utilization data available upon request should
should detect failures or faults in the master-station include:
hardware and should be periodically executed
without being requested by an operator. l CPU utilization.-Performance
measurements of the CPU should consist
Periodic on-line communications diagnostic of measuring processing time, bookkeeping
software should perform operational checks on time, and idle time. CPU utilization should
each of the communication links and on the always be the total processing time added
communication system hardware. to the total bookkeeping time and should be
defined in percent utilization per second.
ii. Off-line diagnostics.-Off-line diagnostic software
should provide detailed diagnostics for every piece
11-15
Canal Systems Automation Manual
11-16
Canal Automation Equipment
iii. Alarm data .-Complete definitions of all alarm (c) CRT display compilers.-A CRT display
limits, messages, and conditions. compiler must be provided for the generation of
new color CRT displays and modification of existing
The I/O points data base manager should be able CRT displays. These display generation and
to output complete and detailed hard copy data editing facilities should allow on-line production of
base(s) maps for user reference. CRT graphic and alphanumeric displays of any
format. The programmer or operator should be
The data base editor should be furnished as part of able to specify all parameters, including color
the data base management software. The data designations, required to generate both
base editor should be furnished with adding, alphanumeric and graphic displays. The dynamic
deleting, and changing functions. Any data base data control points and data entry fields shown on
parameter affecting system performance and displays should be automatically established by the
operation should be modifiable using the data base compiler. The linkages should be designed such
editor. The data base editor should execute from that any data base(s) modification(s) (even those
any workstation or console in the system. As a modifications resulting in insertions into a table or
minimum, the data base editor should perform the file and changes in table or file sizes) do not
following: require redefinition on existing displays.
* Add, delete, or change any data point in . Data entry fields, control points, and poke
the system points may be selectively added, relocated,
l Change any equation that defines or deleted from new or existing displays.
calculated data . Color may be associated with individual
l Modify I/O terminals characters when defining the fixed portion
l Add new RTU(s) of displays.
. Different characteristics, such as the
References made to points in the system data base number or type of characters, color, blink,
by an applications program should be made directly etc., should be definable for the same data
by device designation, not by RTU device address. point being displayed on different displays
When a data point is defined, its device designation or on different portions of the same display.
should be defined. All further references to that . Any data field on a display may be defined
point should allow use of the device’s designation by the user as nonenterable or enterable
number. dependent upon the mode of the
workstation on which it appears.
Modification to the data base should be buffered; . Reasonability limits or references to special
direct modification to the system’s on-line data base conversion calculations should be
is not recommended. A copy of the old associable with each data entry field.
(unmodified) data base should be maintained while . Any display may contain dynamic data
the new data base is verified. The new data base fields presenting data acquired from any
should be verified by being placed on-line. number of RTU’s.
Following verification, the new data base should be . Any data may be shown on more than one
given permanent status. At any time during the display.
verification process, the programmer or operator . Dedicated alarm display and message entry
should be able to command the system to revert to areas should be user assignable during the
open?& n using the old (unmodified) data base. definition of the display(s) format.
. Any data field on a display may be defined
(b) High level programming language.-The as controllable or noncontrollable
SCADA system software should be written in a dependent upon the mode of the
high-level programming language. The high-level workstation from which control is being
programming language should have real-time attempted (only if hardware to control the
extensions for operating in a real-time environment point associated with the data field exists).
defined by supervisory control, data acquisition, . The software should allow the programmer
CRT display, and logging requirements. The high or operator to edit text strings.
level programming language should be an accepted . The software should allow the operator to
standard (ANSI, IEEE) high level programming copy functions or any part of a CRT
\anguage. display.
11-17
Canal Systems Automation Manual
(d) Data archival.-As data are collected by the Access to all data base items
system, provisions must be made for archival or Algebraic calculation capabilities using both
deletion. The method of archival and the quantity numerical data base items and constants;
of data stored will determine the type of archival arrays for calculating, storing, and reporting
system required. As large amounts of data are data within the report writer
stored, the archived data can be off-loaded to tapes Boolean operation capabilities using any
or optical disks and stored onsite or offsite. logical data base items
Automatic page and margin handling using
(e) Inventory records.-Spare part inventory either default or specified values
management software can be furnished to allow Summation, multiplication, exponentiation,
spare equipment and parts to be identified and to division, maximum or minimum
provide total records management. The spare part determination, addition, subtraction,
management system is interfaced to the SCADA logarithmic operations, statistical analysis,
data base. averaging, subtotals, and totals to be
performed on report or log data on a
(f) Maintenance records.-Maintenance scheduling column or row basis
and management software can be furnished to Page line location specifiable by either an
allow equipment to be identified for maintenance absolute line number or as a displacement
based on maintenance data information entered from the previous line
into the scheduling system. Equipment or systems Columnar location of data specifiable by
requiring periodic maintenance can be automatically either an absolute column or as a
identified when the equipment or system has displacement from the previous item within
reached an in-service time that would indicate the line
preventive maintenance is needed. The Data conversion and output formatting
maintenance scheduling software should be support for:
interfaced to the SCADA data base. - Alphanumerics with optional right and
left justification
(g) Report writer.-A report writer should be - Decimals with automatic insertion of the
provided as part of the SCADA MMI software. The decimal point, +, -, and $ signs
report writer should be menu driven, should stack - Automatic insertion of commas to
menus, and should allow the user to define both separate groups of three decimal digits
content (input and output data and comments) and - Scientific and engineering notation
format (layout) for reports or logs made from active - Automatic zero suppression of leading
data files or historical data files containing the zeros with defeat option
following data: - Optional suppression or inclusion of
variable numbers of trailing zeros to the
l On-demand snapshots of one or more real- right of the decimal point
time data items - Automatic daylight savings time
. Periodic (hourly, etc.) snapshots of one or handling
more real-time data items - Optional precision selection of report
. Hourly or half-hourly accumulator data data
. On-demand snapshots of one or more
calculated values Conditional capabilities should be provided to allow
. Periodic snapshots of calculated values the production of reports or logs based uponthe
. Conditional snapshots of one or more real- occurrence of some events (i.e., a status change,
time data items analog limit excursion, etc.). The following
l Conditional snapshots of one or more additional capabilities should be provided:
calculated values
. Conditional statements including “if then” i. Editing.-
blocks
. “Go to” statements . Report or log addition
a Report or log modification
The report writer should provide the user with the . Report or log deletion
following report/log building features:
11-18
Canal Automation Equipment
The date and time are usually shown on every Three different methods of presenting
display. The date is automatically updated by a numerical data are typically provided. The first
software perpetual calendar including leap years. should allow the actual numerical value to be
The time is updated each second. The software displayed with sign and units information. The
should be designed to allow the time to be adjusted second should allow numerical data to be
for daylight savings time.
11-19
Canal Systems Automation Manual
presented in bar chart form. The third should actions should be inhibited until the invalid request
allow numerical data to be presented in line is inactive.
graph (trend) form.
The “Timeout” statement should appear in flashing
A multilevel hierarchical scheme is desirable for white on the CRT whenever one of the selection
presenting information on displays. System features has timed out. The window presently
level displays provide the operator with displayed and the flashing device should be cleared
information from the entire system (i.e., data from the screen when the timeout occurs. Also, the
acquired from more than one RTU). RTU level “Control Failure” statement should appear in
displays should provide data acquired from one flashing white on the CRT whenever a controllable
RTU. Additional levels of displays may be device has failed to operate after proper initiation of
required. a control action by the operator.
Special display groups can be allocated for iii. Display request or access procedures.-A
system-oriented displays such as menus, SCADA system requires many different display
indices, summaries, and overviews. A typical screens. Overall screens show the entire system.
display organization scheme is as follows: Various other screens, including alarm lists,
individual plants, and individual pieces of equipment
. System level displays include alarm show parts of the system in greater detail. The
summaries, analog bar charts, analog line large number of screens in a SCADA system
graphs (trends), analog limits, requires an organized system to make accessing
communication system status and activity, the screens as simple as possible. A target may
configuration control or indication, appear on the screen, or a function key on the
deactivated data summaries, keyboard may be used for selecting displays.
deactivated RTU summaries, event Methods of selecting displays include the following:
summaries, index display, index display to
provide selection of all major CRT displays . Direct.-These schemes directly request a
in the system, maintenance (general), specific CRT display:
SCADA system maintenance logs, one-line - Selection from an index list.-The
displays menu, reports menu, RTU menus, cursor is placed on the desired screen
substituted data summaries, system on a list. The lists could be subdivided
overview display menu, and tag summaries. into smaller lists.
. RTU equipment level displays include alarm - Selection from alphanumeric
summaries, alarm lists, alarm inhibit code.-Each display has a number
summaries, alarm inhibit displays, which is typed in. This method can be
annunciator list, deactivated data summary, difficult for a large system which would
one-line diagrams, outage summaries, tag have a large number of displays, but
summaries, and lists of all input and can be useful as a secondary method
outputs. The display should list all of selecting screens.
applicable alarms and inhibits that are - Selection from targets.-Labeled
active. Alarm lists should display all alarms targets may be selected by the cursor
(acknowledged and unacknowledged) that to access specific screens.
have not returned to normal. - Selection by device.-Selecting a
device with the cursor can bring up a
ii. Invalid request, timeout, and control failure.-An display showing available commands
“Invalid Request” statement appears on the CRT and information.
whenever the operator performs a function . Indirect.-Requests for displays may also
incorrectly or out of sequence. Typical error be the result of indirect actions. The
statements are: page number is invalid, device following are types of indirect display
under clearance, and no more than one control requests:
point may be selected at one time. - Alarm lists.-A visual alarm indication
can be provided in the display header
After occurrence of an invalid request, the “Invalid area of all displays to request specific
Request” statement disappears when the operator alarm list displays.
selects “CANCEL” or a new function. New control
11-20
Canal Automation Equipment
iv. Data entry procedures.-Text and numbers vi. Device tagging.-The SCADA system must be
must be entered into the system at various times. updated when devices are taken out of service.
Text includes entering free-form data into Tagging is used to indicate restrictive operating
messages. conditions and prevent certain control operations.
Complete records of tagging can be stored in the
Numbers include: data base for report production. Tags are usually
indicated by color-coded alphabetic characters
l Entering numbers into predefined entry displayed adjacent to the devices with which they
fields for use as operating/analog/setpoint are associated. Types of device tags should be
limits and operating parameters determined by the people performing the
l Data to be entered to override a status or maintenance.
numerical data value which is known to be
in error After a tag is placed on a device, the system
should prevent supervisory control of tagged
v. Deactivate or reactivate point or RTU devices. The ability to place multiple tags on a
equipment.-Removal of input and output points device is desirable. The indication of a device’s
from the system for testing purposes is sometimes highest precedence tag should be displayed in
desirable when doing maintenance on the system. inverted video whenever more than one tag is
Typical requirements are as follows: active on a device.
1l-21
Canal Systems Automation Manual
. The device is not under supervisory control. The EXECUTE function should cause the
. The device’s control is software inhibited necessary control routines and confirmation
because of the presence of a tag. software to be initiated.
l The control point associated with the device
is deactivated or the entire RTU serving the Upon the system’s acknowledgment of the
device is deactivated. EXECUTE command, the operator may proceed to
. The control selection requested is not valid. other displays and actions, prior to completion of
. An excessive period of time (programmable the confirmation process, without affecting its
parameter) has elapsed since the last execution. The results of the confirmation process
selection took place during the control should be displayed to the operator upon
sequence. completion.
The rejection of a selection should be accompanied The operator should have the option to cancel the
by a message appearing on the CRT explaining the control sequence at any point in the selection
reason for the rejection. Rejected selections should sequence for device control. Depressing a
also be logged on the event logger. “Cancel” key should abort the command sequence
and return the display to the previous state.
Several control types that can be controlled through
supervisory control procedures are defined below: A time delay is usually provided to cancel devices
selected for control if the operator has not taken the
. Two-state control, such as turning a pump next required step of control action. The time
on and off, can be performed simply by should be reset and restarted each time a valid
selecting the device and then selecting the device selection is made in the control sequence.
control function desired.
. Incremental control is attained when a Some typical control modes for devices are as
device such as a gate is opened a small follows:
amount at a time. This process can be
performed by selecting the device and then . Local manual mode.-All control is
selecting a jog function repeatedly (to jog accomplished by an operator locally from
the device to the desired position) or the control board at the device. All
entering a value specifying the number of supervisory control from the SCADA master
incremental control actions desired and is disabled when the equipment is in the
then depressing an EXECUTE pushbutton. local manual mode. When a device is in
. Setpoint control is attained when a result is the local mode, a mode switch is used to
desired, such as a certain waterflow. A physically inhibit RTU control. When the
gate can be raised and lowered to maintain mode switch is in the “LOCAL MANUAL”
the flow. The operation of the gate would position, a color coded “LM” is displayed
be similar to two-state control, except that a adjacent to the device symbol on each
setpoint entry field would be provided for appropriate display.
entry of the desired flow. All setpoint . Local automatic mode.-The process
entries must be subjected to reasonability control is accomplished by local automatic
and limit checks. Appropriate messages control equipment (local relays or
should be provided when entry errors are programmable controllers) located at the
detected. If a new setpoint is not entered, control board. All supervisory control from
the setpoints should retain their previous the SCADA should be disabled when the
values. mode switch is in the “LOCAL
AUTOMATIC” position. Whenever the mode
Verification must take place upon each operator switch is in the “LOCAL AUTOMATIC”
selection to check the validity of each selection position, a color coded “LA” is displayed
step. When a control action has been selected and adjacent to the device symbol on each
validated, an indication should be given to the appropriate display.
operator to indicate that the selection was valid and l Supervisory mode.-All control is
the system is prepared to EXECUTE the command. accomplished by the RTU equipment in
11-22
Canal Automation Equipment
conjunction with the SCADA master. selection of the target should step through
Whenever the mode switch is in the all area alarms lists possessing active
“SUPERVISORY” position, a color coded alarms in order of increasing class number.
“S” is displayed adjacent to the device
symbol being controlled by the RTU on Devices on CRT displays should visually
each appropriate display. indicate an alarm condition by flashing.
l Clearance mode.-All control is locked out The color of the device should continue to
for the purpose of maintenance, failed indicate the state of the device.
equipment, etc.
The word ALARM adjacent to the alarm
General types of control options for equipment target should indicate an alarm by flashing
devices are as follows: and changing color to inverted yellow.
Selection of the alarm target should cause
l Pump units.-The following control options page 1 of the alarm list to be displayed.
can be provided for pumping units: start,
stop, lockout, and speed control. Unacknowledged alarm conditions should
l Gates and valves.-The following control be indicated on the alarm lists by flashing
options can be provided for gates and the alarm message. The message should
valves: raise, lower, open, close, setpoint, be displayed with a color code to indicate
emergency close, and emergency raise. the class of the status or analog/binary
coded decimal @CD) change as described
viii. Events or alarms.-An event is a non- in the subparagraph on color and flash
emergency condition, such as changing a mode standards.
switch from local to remote. An alarm is an
abnormal condition that requires immediate Numerical data (limit information) that are
attention from the operator. Events and alarms displayed and are at or beyond limit
must be in the system so the operator has full settings should indicate the alarm condition
knowledge of the condition of the system being by flashing and changing color.
controlled and monitored. Too many events and
alarms slow down the system and overwhelm the The alarm list information should include
operator with information that cannot be assimilated date and time of occurrence, area
in a short period of time. Alarms should be identification, device designation, and alarm
grouped into different classes depending on the description
degree of urgency. System designers should
classify alarms during system design. Alarm acknowledgment, acknowledgment
indication, and silencing.-These functions
l The occurrence of an alarm should cause should only be performed in the same
audible and visual indications. Different workstation mode category as the
audio tones can be used to differentiate workstation from which acknowledgment is
between different types of alarms. permitted.
l Visual indication.-Visual indication of an
alarm condition should be given in a - Silencing.-A silence function should
reserved area of the display header. The be furnished which causes the audible
indication area should include a target alarm indication of the lowest numerical
which, when selected, causes page 1 of the class of existing alarms to silence each
alarms list to be displayed. The alarms list time the function is activated. To
displayed should be the list for the area completely silence simultaneous alarms
from which the alarm was reported. If more in differing classes, the silence function
than one alarm is reported at the same should require activation several
time, the alarm list for the area reporting successive times. The silence function
the lowest numerical class of alarm should should be activated through depression
be displayed. If the target is selected of a SILENCE key.
again, the area alarms list for the area - Alarm acknowledgment.- Acknowledg-
reporting the next lowest numerical class of ment of an alarm should be possible
alarm should be displayed. Repetitive from any single-line, tabular list, station
11-23
Canal Systems Automation Manual
alarm list, or system alarm list CRT requested, a “PRINT CRT busy” message
display on which the alarming point, should be output on the CRT of the
numerical data item, or alarm message requesting workstation. A busy message
appears. Acknowledgment should be should not inhibit workstation operation.
accomplished by positioning the cursor . CRT line graphing (trending).-Features
on the alarming point, numerical data can be provided which allow operators to
item, or alarm message and depressing assign data base resident numerical points
an ACK (acknowledge) key. for line graph recording. Assignments
- Acknowledgment indication.-The CRT should be made on line graph assignment
displays should be returned to their CRT displays that allow duration and other
pre-alarm condition, and alarm bells line graphing parameters to be specified for
should be silenced once alarms are each assigned point. Line graph selection
acknowledged. CRT displays should be provided to permit
- Master-station equipment alarms.- an operator to specify up to six line graphs
Alarm and event status inputs are to be displayed on a selected workstation
usually provided for all master-station CRT. Points being line graph recorded
equipment. These status inputs should be stored in the historical data base.
indicate alarm or event conditions for Scaling values and offsets should be
the following equipment: CPU’s, disks, automatically established from the limit and
printers, and workstations. Alarms are conversion data associated with the
also provided for master-station numerical points being recorded.
software errors (traps) and Operators should be able to override
communication system failures. automatic scaling and input their own
values through use of line graph
ix. Logging.-Each event, alarm, and control action assignment displays.
can be printed on a logger. Events and alarms can
be assigned to separate loggers. Messages are Line graph displays can be used to show
usually one line in length and similar to the CRT the changes in values over time.
displayed message. Each log message usually
contains the designation of the point or device and . Bar charting.-Features can be provided to
the abbreviation of the site that pertains to the allow operators to assign any numerical
message. Date and time information is usually data base quantity to be a horizontal or
included in the message. The date and time vertical bar chart. Also, features should be
reported should be the detection time (RTU time provided to allow quantities to be plotted in
tagged time) for the alarm or event which initiated stacked bar chart form. Assignments of
production of the message and the time the control quantities should be made on bar chart
was executed for control action messages. CRT selection displays that allow the bar
chart parameters to be assigned to each
. CRT printing or copying.-At the operator’s charted quantity. Bar chart selection CRT
option, a printout of any CRT display from displays should be provided to permit an
any workstation can occur through use of a operator to select up to 16 recorded
PRINT CRT function. Access to the numerical quantities to be bar charted on
function can be by selecting the PRINT the selected workstation. Points being bar
CRT target on the CRT display. The charted can be stored in the historical data
display on the requesting workstation is base.
output to the selected printer when the
PRINT CRT function is requested. The x. Reports or logs.-The report or log feature
CRT display in its entirety is printed (all should be interactive and normally interface with
static and dynamic information). Any notes users through any workstation.
or comments manually entered on the
screen prior to the PRINT CRT request Modifications to the data base(s) should not
should also be printed. The CRT display necessitate redefinition of existing reports or logs.
as it exists when the PRINT CRT request is When desired by the operator, changes made to
made should be printed. If a PRINT CRT one report should ripple through to other associated
request cannot be accomplished when reports.
11-24
Canal Automation Equipment
The operator should be able to produce both l Monitored and calculated resource
prescheduled and on-demand reports. information (if the report entry is data from
Prescheduled reports are produced automatically at the resource monitoring function)
specific times such as hourly, daily, and monthly. . Deactivated points report.-This report
On-demand reports are printed at the operator’s should list all status, analog, and BCD
request. Reports can be stored in memory, output points which are deactivated at the time the
to disk, or output to printers. A separate logging report is requested. The report should
device is often used to print out alarms only so that additionally include data on those points
it is not interrupted by noncritical reports. which have been manually over-ridden.
The report entries should be sorted by RTU
Typical daily reports are as follows: abbreviation.
l A report listing tag placements and (i) Workstation partitioning.-A large system
removals sometimes requires more than one operator at
l Reports that summarize all analog or BCD separate workstations. Each workstation is limited
limit violations which result in alarms to certain functions depending on which mode it is
. Reports that summarize the communication currently in.
errors to all remote sites, local sites, and
external communication channels The partitioning scheme should allow control
capabilities and information to be segregated and
A typical on-demand report might involve SCADA assigned to workstations only as necessary to allow
system equipment performance. This report should personnel to perform their duties. The scheme
be a log of all detected SCADA system equipment should allow workstations in any partition access to
failures and resource monitoring data collected all CRT displays but should restrict applications
during the time prior to the report request. Specific usage, control, tagging, data manipulation,
information to be presented on the report would alarming, and acknowledgement capabilities in
include: accordance with partition definitions.
l CPU failures (local area network, Master, A CRT display that assigns partitions should be
FEP) provided. Use of the display should only be
l Workstation failures (CPU, disk, keyboard, possible from workstations partitioned for the
trackball, mouse, etc.) configuration mode. All partitions should be
l Logger failures assignable from this display except that for the
l Disk failures configuration mode. A method should be provided
l Line-printer failures which allows the automatic, preprogrammed
l I/O equipment failures (RTU’s, RTU cards, reassignment of workstation partitions in cases of
etc.) workstation failure.
l Communications equipment or processor
failures (modems, network interface cards, Workstations should operate in only one partition at
etc.) a time. Workstations should be assignable to more
l System resources monitoring data such as than one partition (i.e., given permission to operate
daily peak, average, and minimum CPU, in the partition). The workstation modes are:
auxiliary memory, and I/O channel operations, configuration, observation, training, and
utilization programming and engineering.
Each report entry should contain the following (3) Network management software.-Each network
information: should have its own network operating system
(NOS). Each NOS must be compatible with each
l Time of report entry associated CPU operating system. Each NOS
. Device identification (or report entry should supervise and monitor the allocation and
identification) utilization of the network resources. Each NOS
l Failure information (if the report entry is for should detect network malfunctions, support normal
a failure) supervisory control and data acquisition operations,
11-25
Canal Systems Automation Manual
11-26
Canal Automation Equipment
l l ,-27
Canal Svstems Automation Manual
alarm conditions (power failure, high limit, etc.). l Solid-state discrete output (SSDO) type.-
These major types of control inputs can be The SSDO type consists of compatible
categorized as follows: signal “contact closure” developed by a
solid-state device (either a silicon controlled
(a) Electrically separate binary input (ESBI) type.- rectifier, triac, or transistor). These devices
The ESBI type is a dry contact input with two are used to operate the equipment directly
states. The states are either “open” or “closed.” without using “interposing electromechani-
cal relays” and are suitable for card or
(b) Voltage supplied binary input (VSBI) type.- printed wire board mounting for high-
The VSBI type is a contact operation that supplies density packaging. Many control outputs
a voltage indication of the state of the contact. The and no-maintenance requirements dictate
states are “no-voltage/open” or “voltage/closed.” the use of SSDO type control outputs.
. Electrically separate discrete output
(2) Control outputs.-Control outputs are designed (ESDO) type.-The ESDO type consists of
to withstand the high-energy electrical transients electromechanical relay contacts. These
associated with the switching of high-inductance outputs are used to operate control
loads. Control outputs are normally momentary equipment when few control outputs are
operation type with typical operation times of available and space is available for
250 milliseconds to 10 seconds. Applications that mounting the individual relays. Also, these
require a “maintained” type of output or latching outputs are well suited when multiple
type output are performed by special applications contacts are required to operate the
programs within the RTU. equipment or are required to switch high
inductance loads.
Operation of critical equipment requires select- . Electrically separate discrete output dual
before-operate (SBO) security operation, and the (ESDOD) type.-The ESDOD type consists
output types must be designed to ensure that only of two electromechanical relays and
the correct control output is operated. In addition, associated contacts. These outputs
some RTU’s will allow only one control output to provide dual contact outputs for the control
operate at any one time to further enhance of two-state devices that are inherently self-
operation security. The SBO security scheme latching. Devices that require two-state
provides for an end-to-end system check whereby type outputs are power circuit breakers
the master station sends a control output select (trip/close), motors (start/stop), and
message and receives a check-back message from electrical set/reset types of devices.
the RTU before an execute command is accepted
or issued. (3) Analog inputs.-The analog input (ANI) type will
accept a variable direct-current signal. The direct-
An additional safeguard to prevent incorrect control current signal represents a telemetry value such as
output commands would be a timer that only allows volts, flow, position, etc., and is derived from
the control output to be selected for a few seconds. instruments equipped with an electrical transducer.
In some applications, such as closed-loop process The input quantity can be either a voltage or
control, the SBO operation may not be desirable, current. The analog signal inputs are multiplexed
so some control outputs may be used as direct within the RTU and each is sampled using one
operate types. In applications such as automatic common analog-to-digital converter. The design of
generation control, the required raise and lower these inputs must be carefully considered to
pulse outputs are of the direct control type. prevent unwanted electrical noise and transients
from causing incorrect instrument readings.
The control outputs provide the interface between
the RTU equipment and the site facility equipment (4) Analog outputs.-The analog output type will
to allow the site facility equipment to be controlled produce a variable direct-current signal. The signal
from the master station. The type of control produced is either a voltage or current and is
outputs will vary depending on the type of device proportional to a digital quantity. These outputs are
that requires control. The major types of control usually used to operate direct-current recorders,
outputs can be categorized as follows: and the variable direct-current voltage output can
be used to control variable speed motor controllers.
11-28
Canal Automation Equipment
(5) Digital inputs.-The binary coded decimal input charger should have a current rating sufficient to
(BCDI) type will accept parallel digital binary coded supply the full rated load in addition to providing the
decimal data (8421 code). The binary coded required current to fully charge a completely
decimal data is usually derived from absolute digital discharged battery within 12 hours. Batteries
encoding equipment. The BCD data is usually should be of the sealed celluloid type to minimize
used to indicate equipment positions or water levels battery maintenance and ventilation requirements.
when resolution to the hundredth of a foot is Separate power supplies or separate isolated
required. The BCD data is in the form of 3-digit, outputs from each power supply should be
4-digit, 5-digit, or 6-digit decimal data. available to provide voltages to meet RTU optical
isolation and power requirements. Voltage divider
(6) Digital outputs.-The binary coded decimal networks should not be used. Battery voltages and
output type is represented as BCD data. This type equipment operating voltage requirements should
of output is rarely used but could be used to drive be matched as closely as possible to minimize the
local digital displays, providing an indication of use of direct-current-to-direct-current converters.
setpoint values or process variables.
e. Enclosures .-RTU enclosures should provide a
(7) Pulsed inputs.-A pulsed input circuit will accept separate compartment for data acquisition
a momentary pulsed contact closure. Pulsed microprocessors and associated equipment,
signals can be derived from wattmeters and communications equipment, and battery chargers
flowmeters. The pulsed signals are input into the with batteries. The enclosure should be of the
RTU and are totalized or accumulated. required National Electrical Manufacturers
Association rating suitable for the enclosure dust
c. Operator interface requirements.-The RTU and moisture environment. Ventilation should be
should provide an operator’s panel to allow: control provided to dissipate equipment-generated heat
of local devices, the entry of setpoints and and minimize condensation while preventing the
schedules, indication of RTU analog and BCDI entrance of rodents, insects, dust, and moisture. In
variables, checking or changing the RTU data base, extremely cold or damp environments, internal
checking RTU operating conditions (battery voltage, thermostatically controlled enclosure heaters should
RTU temperature, system time, etc.), and input be used. The enclosure should be designed to
algorithm parameters. The operator’s panel should minimize transfer of battery charger and power
be provided with coded access to the RTU to supply generated heat to microprocessor enclosure
prevent unauthorized access to the operator’s panel compartments. For outdoor installations, sun
functions. shields should be provided to limit solar heat
buildup within the enclosure. Openings in the
d. Power supply requirements.-The power supply enclosure tops should be avoided to prevent the
should supply power to all of the RTU components, entrance of moisture. The enclosure mechanical
including analog transducers and ESBI and SSDO design should make use of hinged, latched, exterior
wetting voltages if required. The power supply doors, hinged swing-out panels, and standard size
primary power input should be transient protected rack mount panels arranged in a manner to allow
to limit input peak voltage to a 200-V maximum ease of access to the rear as well as the front of
within 5 nanoseconds. Over-voltage protection to equipment. A grounding bar with a single-point
open the primary power circuit if the input voltage grounding system, including a ground lug for a
exceeds 135 V root mean square within ground cable, should be provided.
5 nanoseconds should also be provided. The
protection circuit minimum power dissipation f. Software requirements.-The RTU software
should be sized according to the total RTU load; provides real-time interfacing between the
8,000 watts for 1 millisecond is typical for a associated master station and the RTU, monitors
15-ampere, 120-V, alternating-current circuit. site conditions, executes closed-loop control
commands, and reports site conditions to the
A battery charger with batteries should be provided master station. RTU software may provide some or
to allow the RTU to function for a user specified all of the following functions:
time period during the loss of normal alternating-
current power. The RTU battery should provide . RTU primary power failure.-Alarm the
power for all RTU functions, including analog master-station operator concerning the
transducer and wetting voltage power supplies. The power loss and other user predetermined
1 l-29
Canal Systems Automation Manual
site conditions occurring after the power software failure in interrelated simultaneous
loss. Shutdown before the RTU battery RTU control processes as well as in single
level causes erratic RTU operation. The processes. The control software should
RTU should be designed so that failover to a user predefined state and
primary power loss to the RTU or an notify the master-station operator upon
RTU failure does not cause inadvertent error or failure detection.
operation of external equipment. This . The software can automatically update the
design requires that, during a failure, master station if an alarm occurs at the
each output should remain in a user RTU and the next scheduled master-station
selectable, predetermined state, usually pole is not within the RTU interrupt update
its current state. time.
. RTU primary power restoration.-The RTU . Analog sensor digital filtering software
should boot from dead start and be fully should be provided to aid in the elimination
operational within a user specified time. of spikes, surges, and ripple caused by
Upon power restoration, the RTU should problems in the analog transducer,
not perform any control operations until the converting, or telemetering hardware.
RTU has received a new schedule or Analog data received by the system should
command sequence from the master be optionally assignable to digital filter
station. Analog output points should not processing. Typical filters are rectangular
change state until positions are verified to integration, trapezoidal integration,
ensure that, if a device has been manually multistage averaging, and smoothing filters.
controlled during an RTU power down, the l The RTU software should provide setpoint
RTU does not issue erroneous commands routines for control of all controllable
on powering up. devices such as gates, valves, pumps, and
. Communication failure.-The RTU should generators. The routines should include
failover to a user predetermined failure the necessary algorithms for closed-loop
mode such as executing the last control control, commonly proportional integral
setpoints or schedule that it had received differential algorithms, or equivalent. The
from the master station and continue to setpoint routines should operate within a
archive data as required. user selectable time interval, during which
l Time tagging should be accurate to within a time the RTU scans the sensors included in
user-specified time period. For powerplant the setpoint control loop, performs the
sites, this period is typically 1 millisecond. necessary calculations and data base
For other sites, a l-second period is accesses, and makes decisions whether
acceptable. the controlled device should be controlled
. User selectable, independently adjustable (raise/lower, open/close, stop, etc.).
deadbands should be provided for each Control loops should be implemented within
analog controlled variable such as a gate or the individual RTU’s with no loops closed
valve. The deadband defines how far the back through the master station. Changes
analog controlled variable may deviate from in control algorithm parameters should be
the setpoint value before the RTU will take made at the master station or at the RTU
corrective action to readjust the controlled operator panel if present. The changes
variable. The deadbands should prevent should modify a table of values associated
excessive gate or valve operation caused with each algorithm stored in the RTU.
by minor changes in the water surface Changes made at the operator’s panel
elevation or flow. should cause an alarm signal to be sent to
. User selectable, independently adjustable the master station along with the value, or
analog value scaling should be provided by values, of the changed parameters.
the RTU software. . Arithmetic operations should be clamped to
l The RTU should provide analog and BCD avoid overflow and prevent reverse control
checks for sensor failures and out of limit action. Control loops should be designed to
conditions, alarming the master-station ensure that no device movement occurs
operator upon their presence. when changing from one control mode to
l The RTU should provide error detection another. An operator selectable control
and diagnostic software to detect control interval for each RTU algorithm and control
11-30
Canal Automation Equipment
loop should be provided. An internal RTU scanning the I/O points to provide values to
scan interval that is significantly faster than RTU microprocessor-based control
the control interval should be provided algorithms.
(100 times faster is typical). The scan
interval is the interval at which the RTU is
11-31
GLOSSARY
TERM DEFINITION
A
Accumulator Device used to store hydraulic pressure.
Acoustic transducer Transducer that measures sound pressure in the auditory range.
Balanced operation Operation of a canal system where the water supply exactly
matches the total flow demand.
Binary Coded Decimal (BCD) Binary representation using four binary bits to represent a decimal
number 0 through 9. Remaining combinations are discarded and a
new set of four is used for the next decimal number.
Block diagram Pictorial representation of the relationship between the input and
output of elements in a control system.
Boundary conditions Flow conditions imposed at the ends of a pipeline or canal reach by
various physical structures, which must be described mathe-
matically to solve the general equation of flow for hydraulic
transient computer models.
Glossary
TERM DEFINITION
Closed-loop control A classificaltion of control that corrects errors in the system being
controlled by monitoring the controlled value and comparing it with
a standard representing the desired performance.
Collector system Conveys water from several individual sources such as ground-
water wells and drains and surface inlet drains for rainstorm and
snowmelt runoff to a single point of diversion. The collector system
is associated with projects that increase water supply and decrease
flood damalge.
Colvin algorithm A canal flow control structure technique that operates the gates
based on the rate of deviation of the water surface level from the
setpoint.
Communication channel type Simplex (one direction), half duplex (both directions but only one at
a time [switchable]), and full duplex (both directions concurrently).
Comparator A circuit or device that compares two electrical signals and provides
an indication of agreement or disagreement.
Computer directed mode Canal operating mode in which a computer monitors and directs
operation of a canal.
Connector system Conveys water from a single source to a different location typically
without intermediate collection or diversions. The connector system
is associated with regulation reservoirs and intakes to pumping
plants or powerplants.
Constant head orifice turnout A calibrated structure containing an adjustable orifice gate and a
gate down:stream to control a constant head differential across the
orifice gate to divert and measure water from a main irrigation canal
to a distributing canal.
Constant volume operation method A canal operation that maintains a relatively constant water volume
in each canal pool.
Control element A part of a control system through which the system’s process is
regulated.
(G-3
Glossary
TERM DEFINITION
Distribution system Delivers waiter from the main canal-side turnout to individual water
users or to other smaller distribution systems.
E
ELFLO controller The Electronic Filter Level Offset (ELFLO) controller is a
proportional and integral controller that uses an electronically
filtered (delayed and smoothed) water level signal from the
downstream1 end of a canal reach. ELFLO controllers are used for
control of multiple reach canals and require communications circuits
between check structures.
F
Fade margin Amount of radio or microwave signal exceeding the minimum
required for reliable communication.
G-5
Glossary
TERM DEFINITION
Hydraulic gradient pivot point A location along the water surface in a canal reach where the water
level remains essentially constant during changes in flow.
I
In-channel storage Water storage volume in a canal above the minimum water level
required for conveyance.
lnline reservoir A reservoir constructed in line with the canal used to regulate flow
for balanced operation.
Input/Output (I/O) The input and output signals to computer-based control system or
SCADA.
Integral (reset) control A mode of control in which the output is proportional to the time
integral of the error. Integral control is used in conjunction with
proportional control in a hydraulic system.
Inverted siphon A closed pipe used to convey canal flow under drainage channels,
depressions, roadways, or other structures. Also referred to as a
sag pipe.
L
Lateral A branch canal or pipeline that diverges from the main canal or
other branclhes.
Linear Displacement Transducer (LDT) Device used to measure and transmit gate position.
G-7
Glossary
TERM DEFINITION
Mode selector switch Device to switch the operating mode of a controlled item such as a
gate; typical settings are manual, automatic, and off.
0
Off-line reservoir Constructed to the side of the main canal, usually in a natural
drainage channel. In canal systems, used to store surplus water
runoff during the winter season for use during the irrigation season.
Off set The differeince between the controlled variable and the referenced
input (i.e., ithe difference between the water level in a canal system
and the water level at design flow).
Open channel system A system of conveyance channels where the top flow boundary is a
free surface (e.g., canal systems).
Operating criteria Design and institutional criteria that determine the operating limits
of a water system.
Optimization mode Canal operating mode which is monitored and directed by computer
with algorithms to optimize performance.
P
P+PR Proportional plus Proportional Reset (P+PR) algorithm is similar to
the ELFLO + Reset algorithm except that the P+PR algorithm is
applied to ithe automatic upstream control of canal systems.
Peak time Time interval between the step change and the time at which the
response r’eaches its maximum value.
G-9
Glossary
TERM DEFINITION
Resonant peak amplitude Maximum value of the magnitude of the closed-loop frequency
response.
Response time The time required for the depth, pressure, or flow to reach and
remain within a certain percentage of its steady-state value after a
control correction has been initiated.
Rise time Time interval for the response to change from 10 percent to
90 percent of its steady-state value. Sometimes other percentages
are used.
Rotation delivery Water delivlery where a relatively constant supply flow is rotated to
different users at varying times.
S
Sag pipe See inverted siphon.
Sensor A device for measuring water level, flow, gate position, etc., for
input to a local automatic controller or remote terminal unit (RTU).
Setpoint A value of water level, flow, etc., that the control system maintains;
also called the target.
Setpoint positioning A control operation that compares an existing value, such as gate
position, with a desired value and uses the difference (error) to
initiate a corrective action (raise or lower gate).
Settling time Time interval between the step change and the time for the
response to be within the allowable tolerance.
G-l 1
Glossarv
TERM DEFINITION
Time lag The time required for a change in the input to a system to cause a
change in the output. Time lag is a result of dead time, measure-
ment delay between sensing point and controller, or delay in signal
transmission between controller and process.
Transient flow Unsteady flow during a change from a steady-flow state to another
steady-flow state.
Translatory wave A gravity wave that propagates in an open channel and results in
displacement of water particles in a direction parallel to the flow.
Twisted pair Typical type of metallic cable in which two conductors are twisted
over their entire length.
Two-position control A mode of control that responds to the deviation from setpoint by
operating the controlled device to either of two extreme positions.
Also referred to as On-Off control.
U
Ultra high frequency (UHF) Ultra-high frequency type of radio system (300 to 3,000 megahertz).
Ultrasonic transducer Transducer that measures sound pressure in the ultrasonic range.
Uninterruptible power supply (UPS) A battery-powered device to provide alternating current power to a
system through power interruptions and eliminate the transients
resulting from these interruptions.
GI-13
NOMENCLATURE
Flow
Q = flow, pool flow
Q, = flow at point 1 (different numbers for different locations)
Oi = initial flow
Q, = final flow
QC = flow through a check structure
QC, = flow through check structure 1
QT = flow through a turnout structure
QT, = initial turnout flow
Qmax= maximum pool flow
Qmin= minimum pool flow
AQ = flow change
Depth
Y = water depth
Y, = depth at point 1
y. = initial depth
Y, = final depth
Yrna.u= maximum depth
yrnin = minimum depth
AY = depth change
YT = target depth
YF = filtered depth
Y” = normal depth
Pool Properties
A = cross-sectional flow area
B = canal bottom width
c = wave celerity
D = hydraulic depth
L = pool length
S = longitudinal slope of canal invert
T = top width
z = side slope (run/rise)
Velocity
V = instantaneous velocity
v, = velocity of leading edge of wave
V, = mean flow velocity
v, = average velocity at normal depth
VW = translatory wave velocity
Nomenclature