FIREPAK-ED21
Fire
Pumps Set
Designation of Fire Pumps Set The first pump to be triggered is the jockey pump in the set. If this pump
cannot restore the pressure level, then one of main pumps starts.
FIREPAK - E 2 1 - 120 / 80 - WTM 80-250 / 55 + DJ MV Since there is more than one main pump, the pumps start in cascade
FIREPAK: Package Type Fire Pumps Set sequence with the starting pressure switches set at different pressure
E: All pumps in the set electric driven levels.
2: No. main pumps
1: no. jockey pump The pressure switches of the main pumps are used for automatic starting
120: Rated Flow per main pump (m3/h) and adjustable time automatic stopping. Weekly test system is included
80: Rated Pressure (Hm) in the sets which are above 7,5 kW main pumps’ power. The membrane
WTM 80-250/55: 1 main + 1 stand by pump type of expansion tank with the capacity of 24 liters-16 bar execution is
DJ MV: Jockey Pump Set being mounted in fire pumps set for the absorbtion of water hammer.
997
FIREPAK-E21 & FIREPAK-ED21
Fire Pumps Set
Specifications
• Other voltage and frequency ratings and ambient temperatures available • Mains input 3~50/60 Hz 400V+/-10%
on request. • 400V/24V transformer for auxiliary circuits
• Very low voltage input for control via 1 caller/running pressure switches
Diesel Engines: (NO contact with pressure system and electric pump stationary: on
Diesel engines are equipped with NMD, NMS and WTM series of our pumps. closure of the contact the pump starts up)
They are direct-injection types fitted with electric control box, fuel tank, • Very low voltage input MIN LEVEL FLOAT SWITCH
starter battery and exhaust silencer. • AUTOMATIC-0-MANUAL (EMERGENCY) selector: in AUTOMATIC position
The cooling of engine can be by air, or water cooled by internal cooling electric pump start-up via signals from caller pressure switch; in
system loop. MANUAL(EMERGENCY) position electric pump start-up manual by means
of START/STOP buttons; in “0” position, pump start-up disabled.
Hydraulic Components • Pump MANUAL START selector for manual test
• All pumps in fire system are being delivered on a common base plate • Voltmeter and ammeter
with suction and discharge manifolds as a package type, ready for use. • Green light for motor on
• The controllers of pumps are also being mounted ın this common base • Red light for THERMAL PROTECTION
plate complete with internal cabling between controllers and motors/ • Blue light for POWER SUPPLY
engines. • Settable timed delay of pump shutdown
• Each main pump in the system has its own eccentric reducer + butterfly • Electric pump control contactors sized to AC3
valve at suction side and concentric reducer + butterfly valve + check • Timed, settable Star-Delta contactor switching
valve at discharge side. • Timer for weekly test (optional)
• Manometer is fitted on discharge manifold. • Motor protection fuses
• Pressures switch one for each pump in the set, and expansion tank is • Current transformer for 1 phase
being mounted on discharge manifold. • Auxiliary protection fuses
• Jockey pump is fitted with inlet/outlet valves and check valve and • General disconnect switch with door lock
dry running protection float switch equipped in its controller on the • Alarm output with contact for signal “MOTOR ON”(C-NC-NO)
common base plate of fire pumps set. • Alarm output with contact for signal “THERMAL PROTECTION” (C-NC-NO)
• For jockey pump
Electric Boxes - Control input from NO contact (pressure switch)
Firepak -E21 Fire Pumps Set Electric Controller features are as follows; - Alarm control input from NO contact (float/pressure switch)
This equipment enables automatic or manual management of an electric - Input for motor winding thermal protection
Start-delta starting pump according. They are assembled in painted sheet - Push buttons for operating motor in “Automatic-Off-Manual” modes
metal housing with IP55 protection class and made in accordance with the - “Mains power on” LED
CEI standards in force. - “Alarm” LED for min/max water level
• Electric Star-Delta starting pump electromechanical panel. - “Motor on” LED
998
FIREPAK-E21 & FIREPAK-ED21
Fire Pumps Set
Specifications
999
FIREPAK-E21 & FIREPAK-ED21
Fire Pumps Set
Specifications
1000
FIREPAK-E21 & FIREPAK-ED21
Fire Pumps Set
Specifications
1001
FIREPAK-E21 & FIREPAK-ED21
Fire Pumps Set
Specifications