You are on page 1of 3

CERTIFICATE OF EXAMINATION AND TEST OF OVERHEAD CRANE

Certificate No.: MSC/EOT/23948/21/24K Job No.: MSCJ 14636


Name & Address of Owner of the Equipment: Name & Address of Maker or Supplier of Equipment:
GULFSAIL GALVANISING FACTORY LLC GURALP CRANES
ICAD , ABUDHABI , UAE
Location: Survey Requested by: Type of Inspection:
ICAD, ABU DHABI Mr.Suman THOROUGH

Description of Equipment:
ELECTRICALLY OPERATED SINGLE GIRDER CRANE

Maker Serial No. Owner Distinguishing Mark/No.: Year of Manufacturer / Installation:


NA TMI-22 2009

No. of Hoist/Trolley: Date of Previous Test: Previous Test Done By:


TWO NA NA

:.MSC Test Method No Reference Regulations:


MSC/TM/05 BS 7121 -2-7 : 2012
Safe Working Load (SWL): Proof Load: Actuall Deflection (SWL): Max. Allowable Deflection:
(2.5)x2 t NIL 12 mm 18.30 mm

Lifting Height: Span:


5.6 meter 14.0 meter

Travelling Length: Wire Rope/Chain Dia. x Falls:


66.0 meter (8 mm X 4 falls) x2

Date of Inspection: Date of Expiry:


22-11-2021 21-11-2022

Name and position of person who Authorized signatory authenticating


carried out the inspection and test: this certificate/report:

______________
Inspection Engineer

.This Certificate Becomes Invalid, If Any Alteration/Repair /Modification Is Made


THIS IS TO INFORM YOU: that the undersigned a surveyor or representative did attend to examine this machine (equipment) to assure that it is in safe working
condition. Examination indicate that the said equipment has no indigenous defects or sighted deformation and in safe working condition. The said equipment is found
.to be satisfactory for further use, provided there is continues maintenance applied and qualified operators employed
This certificate is granted subject to the condition that is agreed & understood. Master Safety Consultancy L.L.C liability shall be limited to the acts or premises of its
employees, subcontractors. Under no circumstances whatsoever shall Master Safety Consultancy L.L.C be liable for any injury or damage to any person or occurring by
.reason of negligent operation or any defect in materials, machinery, equipment or other items other than such defects ascertainable normally
We hereby report that the all particulars in this report are correct at the time of test/inspection Daily inspection & operational maintenance is the sole responsibility
.of the users

Doc. No. QF-07/03-05 Rev. No. : 04 Issue Date: 01-05-2020 Page 1 of 2


Continuation of Certificate No.: MSC/EOT/23948/21/24K Job No.: MSCJ14636
Over Head Traveling Crane Inspection Check List
Sr Sr Description
DESCRIPTION REMARKS
No. No.
Documentation 29 Sheave S
Equipment manufacturer’s 30 Winding Condition S
intruction & operational
manual, & last 31 Gear Box S
1 S 32 Bearings S
test
report/certificate/manufacturin 33
Hook Block SWL Markings S
g details available
34 Rope End Termination Type &
STRUCTURES S
Condition
2 Rail Condition S 35 Chains N
3 Base Trolley S 36 End Chain Termination N
4 Ladders , Stairs & Ring Guards S 37 Auxilliary Hoist Condition(If Any) N
5 Access Platform & Walk Ways N 38 Drum Surface S
Access Guard Rail and Toe 39
6 N Abnormal Sounds S
Board
7 End Carriages S 40 Rope Anchorages S
8 Joints S 41 Grooves S
9 Bridge Girders S 42 Rope Pulleys S
10 Long Travel Beam Condition S 43 Long Travel Condition S
11 Buffers S 44 Long Travel Limit Switch S
45 CrossTravel Limit Switch S
12 End Stops S
46 Hoist Limit Switch S
13 Warning & Safety Signs S 47 Over Load device S
14 Cable Reeler S 48 Anti Collission S
15 Frame Structural Sections S 49 Audible alarm N
16 Cabin Condition(If Any) N 50 Long Travel Brake S
17 Fire Extinguisher S 51 Cross Travel Brake S
Pendant Control & Operation
18 Ventillation(Cab) N 52 S
Markings
19 Pendant Traveling Cable S 53 Long Travel Limit Switch S
ELECTRICALS 54 BridgeTravel Limit Switch S
Earthing / grounding
20 S 55 NDT ( DP/MP/US/RG ) N
Continuity
21 Electrical Panel Board
S LOAD TEST
Condition
22 Electrical Wiring & Cables S 56 100% of SWL Load Test (Periodic) S
23 Electrical Guardings & 57
S 110% of SWL Load Test (Dynamic) N
Security
24 Motor Condition & Security S 58 125% of SWL Load Test (Static) S
25 Main Switch S 59 Hoist Brake @ SWL (Upper) S
26 Hoist / Winch 60 Hoist Brake @ SWL (Lower) S
27 Wire Rope Condition S 61 Over Load Limiter S
28 Motor Condition S 62 Defflection @ SWL S

Status : S = Satisfactory X = Deficiency R = Recommendation N = Not Applicable

REMARKS & RECOMMENDATIONS

Visual, functional & load test was carried out and the crane was found Satisfactory at the time of inspection.

Inspected By : Haseeb Ahmad


Position: Inspection engineer
Doc. No. QF-07/03-05 Rev. No. : 04 Issue Date: 01-05-2020 Page 2 of 2
Doc. No. QF-07/03-05 Rev. No. : 04 Issue Date: 01-05-2020 Page 3 of 2

You might also like