Modelling and Transient Analysis of a 3-Phase Multi-Layer HTS Coaxial Cable using PSCAD/EMTDC
have been actively researched to maximize normal state. The results of this study
the advantages such as reduction of confirm the reliability of the fault current
superconducting wires and miniaturization bypass of the TPMHTSC cable and can be
compared to other types of HTS cable. The used effectively in a real system application
TPMHTSC cable has a multi-layer coaxial in the future.
structure, and the formers made of copper
located at the cable center and at each
conducting layer serve as a pathway to 2. Modeling of a TPMHTSC Cable in
bypass the fault current (Lee, 2019). PSCAD/EMTDC
The analysis of the transient state of the
TPMHTSC cable itself basically requires 2.1 TPMHTSC Configuration
before installation according to the impedance
level of the cable which is dramatically The TPMHTSC cable has a multi-layer
changed in the case of quench at fault structure consisting of HTS wires twisted
conditons, and the level of fault current will clockwise and counter-clockwise along the same
consequently be saturated on a certain value. axis. Between the layers of the cable is filled
The saturated current value is decided by with insulator material and there is a shield
the condition of power system and the layer outside the conducting layer. The structure
characteristics of the HTS tape wound as a of the TPMHTSC cable is shown in Fig. 1.
HTS cable core. This requires a computer
simulation, but currently there are no
appropriate tools available to simulate the
TPMHTSC cable, so as an alternative, the
TPMHTSC cable can be modelled and
transient characteristics can be analyzed using
PSCAD/EMTDC (Hamajima et al., 2005; Bang
et al., 2007; Kim et al., 2009; Ha et al., 2012).
In this paper, we modelled the TPMHTSC
cable using PSCAD/EMTDC and analyzed the
transient characteristics. The specifications of
the TPMHTSC cable are 22.9 kV, 60 MVA,
which is equivalent to the actual distribution Fig. 1 Structure of the TPMHTSC Cable
cable specification for the Korean system.
Table 1 and 2 show the obtained parameters
The transient state of the TPMHTSC cable is
through the process in Fig. 2.
modelled by creating components in
PSCAD/EMTDC based on electrical and
2.2 Simulation Model of the TPMHTSC
thermal characteristics. As a result, when a
Cable in PSCAD/EMTDC
fault occurred in the TPMHTSC cable, most
of the fault current was bypassed through the
The components of PSCAD/EMTDC consist
former layers and the overall temperature of
of a graphic tap, a parameter tap, and a script
the cable rose up to about 8 K. After the
tap. The graphic tap is where the inputs and
fault is cleared, the cable returns to its
- 26 -
Journal of the Korea Industrial Information Systems Research Vol. 25 No.1, Feb. 2020 : 25-30
Table 1 Specifications of the TPMHTSC Cable 2004). Fig. 3 depicts the simulation model
applied to a 1 km TPMHTSC cable of 22.9
Items Values
kV/60 MVA class.
Voltage/capacity 22.9 kV/ 60 MVA
Rated current 2200 A
Cable length 1 km
- 27 -
Modelling and Transient Analysis of a 3-Phase Multi-Layer HTS Coaxial Cable using PSCAD/EMTDC
of the TPMHTSC cable under the 3-phase the conducting layers are increased due to the
fault In Fig. 5, all the phase currents are superconducting characteristic. When this
balanced. resistance is higher than the resistance of each
When the fault occurs at 0.5 sec, the fault former layer, the fault current on each
current of the TPMHTSC cable is TPMHTSC cable is bypassed through the
unbalanced, even though the 3-phase fault is former layers. The total temperature of the
a balanced fault. Since the resistance of each cable rose up to about 8 K and the highest
layer of the TPMHTSC cable has different temperature rise occurred in the former layer of
values for reasons of material and number of phase B, the main passage of the fault current
wires, each phase under the fault condition is bypass. The results obtained here in the
affected by the different critical currents of simulation can be changed by the variables
each phase and the inherent imbalance status. such as the number of wires, materials of
The TPMHTSC cable temperature distribution conducting layers and formers, pitch length, etc.
is also closely related to resistance. As shown of the TPMHTSC cable.
in Fig. 6, when a fault occurs and an
overcurrent flows through the HTS conducting
layers of the TPMHTSC cable, the resistance of
- 28 -
Journal of the Korea Industrial Information Systems Research Vol. 25 No.1, Feb. 2020 : 25-30
- 29 -
Modelling and Transient Analysis of a 3-Phase Multi-Layer HTS Coaxial Cable using PSCAD/EMTDC
이 준 엽 (Jun-Yeop Lee)
∙학생회원
∙창원대학교 전기공학과 학사
∙창원대학교 전기공학과 석사
과정
∙ 관심분야 : 초전도 전력 응용
기기, 에너지 산업, 신재생
대체에너지
이 석 주 (Seok-Ju Lee)
∙정회원
∙창원대학교 전기공학과 학사
∙창원대학교 전기공학과 석사
∙창원대학교 전기공학과 공학
박사
∙관심분야 : 에너지 산업, 전력
시스템, 초전도전력 응용기기, 신
재생 대체에너지
박 민 원 (Minwon Park)
∙정회원
∙창원대학교 전기공학과 학사
∙일본오사카대학교 전기공학과
석사
∙
일본오사카대학교 전기공학과
박사
∙ 현재: 창원대학교 전기공학과 교수
∙ 관심분야 : 초전도 전력 응용기기, 신재생 전
력변화 시스템, 전력전자 시스템,
RTDS/RSCAD
- 30 -