Abstract
Numerical study is carried out of a simplified system of solar-wind tower for ventilation of dwellings. The conservation equations for
mass, momentum and energy for mixed convection in two-dimensional coordinates are solved by the control volume method and Simpler
algorithm. The governing parameters of the problem are Rayleigh number Ra, Reynolds number, Re (or Richardson number, Ri), the
dimensionless conductivity of the solid medium, kr and the geometrical parameters. Nusselt number Nu and dimensionless volume flow
rate V_ are calculated as a function of the governing parameters, and streamlines and isotherms are produced. The results show that the
important parameters affecting the ventilation performance are Ra, Re (or Ri), and the geometrical parameters, the aspect ratio A, the
exit port size h1/L and to a lesser degree, the wall thickness ‘1/L.
r 2007 Elsevier Ltd. All rights reserved.
Keywords: Solar tower; Wind tower; Solar wind; Solar chimney; Numerical simulation
1. Introduction the solar chimney for ventilation were also reported. The
results of these studies showed that ventilation by solar
In hot and arid regions, use of conventional wind towers chimney was possible; the mass flow rate was increasing
to achieve comfort is a well-known traditional technique. function of chimney surface temperature, reverse flow was
The wind towers maintain natural ventilation through observed for certain channel sizes and the ventilation
living spaces due to wind as well as buoyancy effects (see, increased with increasing inlet port size. In another study,
e.g., [1]). The mechanisms of functioning and operation of Bansal et al. [6] proposed to use an open-ended solar
wind towers depends on (i) the time of operation, nights or collector system installed separately from the wind tower.
day time, (ii) the availability of wind, i.e. windy or not Their results show that the effect of solar system is more
windy periods, (iii) the type of wind towers. In addition, important than that of wind and the combined system may
they are only used in summer time and closed down in be more effective in ventilating living quarters by increa-
winter. Description and operation of various cases are sing the mass flow rate of air by several times.
described; advantages and operational problems are The conventional wind tower can be conceived as a
discussed [1]. An experimental study with actual wind combination of solar and wind tower for ventilation of
towers is reported by Yaghoubi et al. [2]. They found that dwellings. In this case, the tower does not function as a
the wind towers were effective not only in strong wind but wind catcher but it rather functions as a chimney for
also in calm weather by providing a certain air circulation ventilating air from the dwelling. The opening at the top is
to provide comfort in dwellings. At downside, they found oriented against the cardinal wind direction, thus it will be
that when the tower was subject to strong solar radiation in depression region most of the time. The tower itself can
and the tower structure was heated up, the circulating air be used as a solar collector and energy storage system,
was heated up by hot surfaces causing discomfort. at the same time providing wind tower function (see
Experimental studies [3,4] and a numerical study [5] on Fig. 1(a)). The air will be evacuated from the dwelling to
the ambient by suction in the tower due to negative wind
Corresponding author. Tel.: +514 340 4711x4579 fax: +514 340 5917. pressure at the opening (the so-called venturi effect) and
E-mail address: bilgen@polymtl.ca (E. Bilgen). due to the buoyancy force developed in the chimney by hot
0960-1481/$ - see front matter r 2007 Elsevier Ltd. All rights reserved.
doi:10.1016/j.renene.2007.03.001
ARTICLE IN PRESS
H.F. Nouanégué et al. / Renewable Energy 33 (2008) 434–443 435
openings will be presented at the end of the mathematical energy, and inclusion of the massive wall, we will have a
model. conjugate heat transfer by mixed convection and conduc-
In this study, the aspect ratio, A ¼ H/L, the massive tion in the tower.
wall thickness, ‘1/L, the exit port height, h1/L and the We note that our aim in this study is to establish the
non-dimensional massive wall conductivity, kr ¼ k/kf effect of governing parameters on the system thermal
will be taken as variable. The air channel width, performance and to do it we use a simplified system with
‘2/L ¼ 0.5 and the inlet port size, h2/L ¼ 1.05 will be kept the following assumptions: the effect of the third dimension
constant. Due to combined effects of wind and solar is negligible like in the solar collector systems with a
massive wall, the flow mode is laminar, which is most of the
time justified for systems with small channel size and small
Table 1 velocities (see, e.g. [7]), and infrared radiation heat
Comparison of the results for free convection between vertical plates exchange in the channel is negligible. With these assump-
tions, two-dimensional conservation equations for mass,
Ra/A Nu/2A [10] Nu/2A (this study)
momentum and energy are used with Boussinesq approx-
100 0.0403 0.04100 imation. By choosing L as the length scale, Uo as the
101 0.3780 0.3700 velocity scale, DT ¼ q00 L2/rCpUo as the temperature scale,
102 1.8518 1.8420 rU2o as the pressure scale and t/(L/Uo) as the time scale, we
103 4.1660 4.1790
104 7.4686 7.5200 obtain following dimensionless equations in terms of
dimensionless primitive variables for mixed convection
20 Re=1000
15
Nu
Ra=2x103
Ra=2x104
10 Ra=2x105
Ra=2x106
Re=100
1500
Re=1000
1200
Ra=2x103
V
900
Ra=2x104
Ra=2x105
600 Ra=2x106
Re=100
300
0
20 40 60 80 100
kr
Fig. 2. Nusselt number and volume flow rate V_ as a function of wall conductivity kr for the base case of A ¼ 15, h1/L ¼ 1.05, ‘1/L ¼ 0.5, and Rayleigh
and Reynolds numbers as variable parameters.
ARTICLE IN PRESS
H.F. Nouanégué et al. / Renewable Energy 33 (2008) 434–443 437
and conduction h1/L are the geometric parameters and kr is the thermal
qU qV parameter.
þ ¼ 0, (1) The average Nusselt number at the exit port is calcu-
qX qY
lated as
qU U qU V qU qP 1 q2 U q2 U R1
þ þ ¼ þ þ , (2) 1h1 =L ððqy=qX Þ þ PrRe UyÞ dY
qt qX qY qX Re qX 2 qY 2 Nu ¼ R1 . (5)
1h1 =L y dY
qV U qV V qV qP 1 q2 V q2 V
þ þ ¼ þ þ The volume flow rate, V_ is calculated as
qt qX qY qY Re qX 2 qY 2 Z
Ra
þ y, ð3Þ V_ ¼ U dY . (6)
Pr Re2 x¼0
2 The stream function is calculated from its definition as
qy U qy V qy l qy q2 y
þ þ ¼ þ þ 1, (4)
qt qX qY Pr Re qX 2 qY 2 qc qc
U ¼ ; V¼ . (7)
where l is equal to kr for solid media and 1 for fluid media. qY qX
The governing parameters of the problem are Ra, Re c is zero on the solid surfaces and the streamlines are
(or Ri ¼ Ra/Re2 as seen in Eqs. (2)–(3)) and Pr, which are drawn by Dc ¼ ðcmax cmin Þ=n where n is the number of
defined in the Nomenclature. In addition, A ¼ H/L, ‘1/L, increments.
15
Nu
10
Re = 100
Re = 500
Re = 1000
5
1500
Re = 10 0
1200
Re = 50 0
Re = 1000
V
900
600
300
0
103 104 105 106
Ra
Fig. 3. Nusselt number and volume flow rate V_ as a function of Rayleigh number for the case of A ¼ 15, h1/L ¼ 1.05, ‘1/L ¼ 0.5, kr ¼ 20 and Reynolds
number as variable parameter.
ARTICLE IN PRESS
438 H.F. Nouanégué et al. / Renewable Energy 33 (2008) 434–443
35
Ra =2 x103
30
Ra =2 x104
25 Ra =2 x105
Ra =2 x106
20
Nu
15
10
4000
A = 15 h1/L = 1.05 1/L = 0.5 kr = 20
3500
3000
Ra=2x103
2500 Ra=2x104
Ra=2x105
2000 Ra=2x106
V
1500
1000
500
Fig. 4. Nusselt number and volume flow rate V_ as a function of Richardson number for the case of A ¼ 15, h1/L ¼ 1.05, ‘1/L ¼ 0.5, kr ¼ 20 and Rayleigh
number as variable parameter.
ARTICLE IN PRESS
H.F. Nouanégué et al. / Renewable Energy 33 (2008) 434–443 439
of 20 200 within 0.065% in Nusselt number and 0.094% in 0.10 m massive wall thickness, ‘2 ¼ 0.10 m air channel
extremum stream function. Using a system with a mobile width, H ¼ 2–4 m height and fairly large entrance and
processor of 2 GHz clock speed, for A ¼ 15, 20 200 grid exit ports to reduce the flow resistance of air to and
size, at Ra ¼ 106, the typical execution time was 218 s. from dwellings (see, e.g. [11]). Thus, we carried out the
A converged steady-state solution was obtained by numerical study with the air channel width,
iterating in time until variations in the primitive variables ‘2/L ¼ 0.5 ¼ constant and the size of the inlet air port,
between subsequent time steps were very small h2/L ¼ 1.05 ¼ constant. We varied the other parameters
X
ðfold 4 as follows: the aspect ratio, A ¼ H/L from 10 to 20,
i;j fi;j Þo10 , (13)
the massive wall thickness, ‘1/L from 0.1 to 0.6, the
where f stands for U, V, and y. massive wall’s non-dimensional conductivity, kr ¼ k/kf
Within the same time step, residual of the pressure term from 20 to 100, the exit port height, h1/L from 0.75
was less than 103 [7,8]. In addition, the accuracy of the to 1.5. Rayleigh number is varied from 103 to 106,
solution was double checked using the energy conservation Reynolds number from 102 to 103. Pr is constant at
on the domain to ensure it was less than 104. 0.71 for air. The results will be presented as the
Nusselt number and the volume flow rate as a function
4. Results and discussion of the other parameters, the streamlines and isotherms
will be presented to visualize the flow and temperature
Non-dimensional geometrical parameters are based fields. The base case is with A ¼ 15, h1/L ¼ 1.05,
on the experience with the Trombe wall systems ‘1/L ¼ 0.5. Then we will present sensitivity studies for
with ventilation: typical dimensional values are ‘1 ¼ each parameter.
Fig. 5. Streamlines and isotherms for the case of A ¼ 15, h1/L ¼ 1.05, ‘1/L ¼ 0.5, kr ¼ 20. (a) Ri ¼ 0.1, (b) Ri ¼ 1 and (c) Ri ¼ 100. Streamlines are shown
on the left and isotherms on right for each case.
ARTICLE IN PRESS
440 H.F. Nouanégué et al. / Renewable Energy 33 (2008) 434–443
We present for the base case Nusselt number, Nu and number greater than 105, Nu and V_ become an increasing
volume flow rate V_ through the exit port as a function of function of it. The cross plot of the same data in Fig. 3, Nu
conductivity ratio, kr with Ra and Re parameters in Fig. 2. and V_ as a function of Re number with Ra as a parameter
We see that Nu and V_ are not too sensitive to the variation showed that both Nu and V_ were increasing function of Re
of kr. We conclude that kr is not an important parameter and Ra numbers. These observations are expected since the
and we can take a typical value and evaluate the other tower system should perform better when both Ra and Re
parameters. The reason is that the boundary condition is numbers are high, the first indicating the thermal effect and
adiabatic along the massive wall at x ¼ 0 and kr is only the second, the forced convective flow effect on the mixed
important in storing and releasing energy from the wall to convection and ventilation.
the air circulating through the channel. Thus, we take We present Nu and V_ as a function of Richardson
kr ¼ 20 for the rest of the study and the base case becomes number, Ri ¼ Ra/Re2 in Fig. 4 for the base case and for
with A ¼ 15, h1/L ¼ 1.05, ‘1/L ¼ 0.5, kr ¼ 20. four Ra numbers. We can see that both Nu and V_ are
For the base case, we present Nusselt and volume flow decreasing function of Ri for a given Ra number. As
rate as a function of Rayleigh number in Fig. 3, where expected, for Rio1, Nu and V_ are strong function of Ri for
Reynolds number is a parameter. We see that Nu and V_ are a given Ra number. They decrease with increasing Ri
increasing with increasing Re number at all Ra numbers. number until about Riffi1 thereafter, for Ri41 they
As expected, for a given Re number, at low Ra numbers Nu converge to an asymptotic value. In addition, for higher
and V_ are quasi-invariant to it, since we have conduction Ra numbers, the observed dependence of Nu and V_ on Ri is
dominated natural convection regime. At higher Ra amplified. The dependence of Nu and V_ on Richardson
45 A = 15 h1/L = 1.05 kr = 20
40
Ra=2x103
35
Ra=2x104
30 Ra=2x105
Ra=2x106 Re=1000
25
Nu
20
15
10 Re=100
Re=1000
1200
900
V
Ra=2x103
600 Ra=2x104
Ra=2x105
Ra=2x106
300
Re=100
0
0.1 0.2 0.3 0.4 0.5 0.6
1/L
Fig. 6. Nusselt number and volume flow rate V_ as a function of wall thickness ‘1/L for the case of A ¼ 15, h1/L ¼ 1.05, kr ¼ 20, and Rayleigh and
Reynolds numbers as variable parameters.
ARTICLE IN PRESS
H.F. Nouanégué et al. / Renewable Energy 33 (2008) 434–443 441
number is explained by the fact that forced convection is In case (c) Ri ¼ 100, both flow and temperature fields show
the dominant mode for Rio1, the natural convection natural convection-dominated mixed convection. There is
becomes the dominant mode for Ri41 and both forced clearly a reverse flow at the exit and the isotherms show
and natural convections have equal importance for Riffi1. stratification in the air channel. Compared with case (b),
We examine the flow and temperature fields for these three which is also with Ra ¼ 106, the effect of forced convection
modes in Fig. 5. Again for the base case with A ¼ 15, is not discernible and we have a less favorable ventilation in
h1/L ¼ 1.05, ‘1/L ¼ 0.5, kr ¼ 20 and three cases are shown: the tower.
(a) Ri ¼ Ra/Re2 ¼ 105/(103)2 ¼ 0.1, (b) Ri ¼ 106/(103)2 ¼ 1 Next, we will present the results of the sensitivity study
and (c) Ri ¼ 106/(102)2 ¼ 100. The streamlines are shown on the wall thickness ‘1/L, the exit port size h1/L and the
on the left and the isotherms on the right for each case. We aspect ratio A.
see that for (a) Ri ¼ 0.1 there is a strong convection with Fig. 6 shows Nu and V_ as a function of the wall
some reverse flow at the exit and the cooling of the heated thickness, ‘1/L with Re and Ra as parameters. At small
surface is effectively with high gradients on the surface. wall thickness, Nu is not too sensitive to the variation of
This case is forced convection-dominated mixed convec- ‘1/L. At high ‘1/L, the same trend is observed at low Re
tion. For (b) Ri ¼ 1, both forced and natural convections number. Nu is a strong function of ‘1/L at its higher values
play an important role with high-temperature gradient on and when Re number is high. The effect of Ra number is
the surface. We note that due to additional contribution by mixed although it is a little higher at low Ra numbers at
natural convection, the reverse flow at the exit is amplified. both Re numbers. The volume flow rate, V_ is insensitive to
A = 15 1/L = 0.5 kr = 20
25
20 Re=1000
Nu
15
Ra=2x103
Ra=2x104
10 Ra=2x105
Ra=2x106
Re=100
A = 15 1/L = 0.5 kr = 20
1800
1500
Re=1000
1200
V
Ra=2x103
900
Ra=2x104
Ra=2x105
600
Ra=2x106
300 Re=100
0
0.8 1.0 1.2 1.4
h1/L
Fig. 7. Nusselt number and volume flow rate V_ as a function of exit port size h1/L for the case of A ¼ 15, ‘1/L ¼ 0.5, kr ¼ 20, and Rayleigh and Reynolds
numbers as variable parameters.
ARTICLE IN PRESS
442 H.F. Nouanégué et al. / Renewable Energy 33 (2008) 434–443
the variation of ‘1/L at low Re number, and it is a decreased for a given amount of energy transported
gradually increasing function of it at high Re number. It is through the chimney. We note also that depending on the
insensitive to Ra number. operation conditions, there may be optimum aspect ratio
We present the effect of the exit port size, h1/L on Nu to obtain the best ventilation performance, as seen for the
and V_ with Ra and Re parameters in Fig. 7. We can see case of Rao106 and Re ¼ 103, for example.
that Nu and V_ are gradually increasing function of h1/L for
both Ra and Re numbers. Following our earlier observa- 5. Conclusions
tion in Fig. 3, the effect of h1/L is more important at high
Ra and Re numbers. This is expected because to prevent We carried out a numerical study on a solar-wind tower
choking at the exit we need larger exit port size when the system for ventilation of dwellings. We solved the
mixed convection and ventilation are increased. equations for the conservation of mass, momentum and
The effect of the aspect ratio, A on Nu and V_ is shown in energy using the control volume method. The governing
Fig. 8 where Ra and Re are parameters. We observe that parameters are Rayleigh and Reynolds numbers (or
Nu is a decreasing function of A while V_ is slightly Richardson number) and constant Prandtl for air; the
increasing function of it, i.e. there is an inverse relationship. geometrical parameters are the aspect ratio, the exit port
Indeed, it is a known practical observation to have an size, the wall thickness and the wall conductivity. Our aim
increased draft when a chimney is taller. On the other has been to establish important parameters affecting the
hand, for an increased draft the heat transfer at the exit is ventilation performance of the solar-wind tower systems
30
h1/L = 1.05 1/L = 0.5 kr = 20
25
20
Re=1000
Nu
15 Ra=2x103
Ra=2x104
Ra=2x104
10
Ra=2x106
Re=100
5
1800
h1/L = 1.05 1/L = 0.5 kr = 20
1500
Re=1000
1200
V
900 Ra=2x103
Ra=2x104
600 Ra=2x105
Ra=2x106
300
Re=100
0
10 12 14 16 18 20
A=H/L
Fig. 8. Nusselt number and volume flow rate V_ as a function of aspect ratio A for the case of h1/L ¼ 1.05, ‘1/L ¼ 0.5, kr ¼ 20, and Rayleigh and Reynolds
numbers as variable parameters.
ARTICLE IN PRESS
H.F. Nouanégué et al. / Renewable Energy 33 (2008) 434–443 443
considered in our study. In view of the results, and for (vi) Generally, for a given location, material used in
the simplified system and the boundary conditions tower construction and operation condition, the
considered in this study, we summarize the following geometrical parameters, A, h1/L and ‘1/L should be
conclusions: optimized.