You are on page 1of 27

© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

No further reproductions authorized. May 11, 2016.


© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .
No further reproductions authorized. May 11, 2016.
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .
No further reproductions authorized. May 11, 2016.
S
T
N
C
F
O
E
L
B
A
Page
1.0 INTRODUCTION..................................................................................................................1
1.1 General .............................................................................................................................1
1.2 Definitions ........................................................................................................................1
1.3 Manufacturer’s Warranty .................................................................................................1
1.4 Service Agreements ..........................................................................................................2
1.5 Membrane Identification..................................................................................................2
1.6 Rooftop Access .................................................................................................................2
1.7 Roof System Access..........................................................................................................3

2.0 ROOFING SYSTEM HISTORICAL RECORD ...........................................................................3

3.0 CAUSES OF ROOF PROBLEMS ...........................................................................................4


© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

3.1 Natural Causes .................................................................................................................4


3.2 Man-Made Causes ...........................................................................................................4
3.3 Other Causes ...................................................................................................................5

4.0 ROOF INSPECTIONS...........................................................................................................5


4.1 Regular Periodic Inspections ............................................................................................5
4.2 Special Inspections............................................................................................................6
4.3 Inspection Procedure .......................................................................................................6

5.0 OWNER PERFORMED MAINTENANCE ..............................................................................10

6.0 EMERGENCY REPAIR ......................................................................................................12


6.1 General ..........................................................................................................................12
6.2 Leak Repair Procedures..................................................................................................12
6.3 Wind Damage Repair Procedures .................................................................................14
6.4 Permanent Repair Requirements .................................................................................16

7.0 INSTALLATION OF NEW PENETRATIONS AND EQUIPMENT...............................................17


No further reproductions authorized. May 11, 2016.

8.0 CONCLUSION ..................................................................................................................18

9.0 APPENDIX ......................................................................................................................19


Historial Record ............................................................................................................19
Roof Plan Grid ..............................................................................................................20
Owner Maintenance Inspection ....................................................................................21
1.0 INTRODUCTION

1.1 General 1.2 Definitions

Maintenance has always been a con· Inspection is defined as a critical ex·


cern to owners of buildings, but amination of the components of the
previously it has been associated only roof system. Maintenance is defined as
with equipment and the processes the the work of keeping a building,
buildings house. It is only recently, machinery, roof, etc., in a state of
however, that owners have recognized good repair. Some examples of roof
the need for ongoing inspection, maintenance include cleaning drains
maintenance, and repair of the roof· and removing debris.
ing systems that protect these
buildings and their contents. Even Repair is defined as returning to good
though manufacturers' warranties may condition after damage, decay, etc.;
be provided for the roofing systems, mend; fix. Some examples of roof
they generally do not relieve the repairs include patching a puncture in
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

owner of the responsibility for proper the membrane or flashing, or replac·


maintenance. ing components damaged by high
winds.
Periodic roof inspection and mainten·
ance programs are now being routine· I. 3 Manufacturer's Warranty
ly implemented with increasing
frequency. Designers, contractors and One of the most important things a
manufacturers can be a valuable re· building o·wner with a manufacturer's
source to building owners regarding warranty can do is to read and
the necessary aspects of roof understand the warranty for the roof .
maintenance. ing system installed on his building.

This manual offers some basic recom· A manufacturer's warranty is a legal


mendations for building owners and contract between the owner and the
their representatives that will assist in manufacturer. It can be voided like
keeping roofs watertight and performing. any other contract, whether knowingly

With the support of


No further reproductions authorized. May 11, 2016.

professional roofing
contractors and roof­
ing material manufac­
turers, owners should
develop ongoing
maintenance pro­
grams to optimize
roof service life.
or inadvertently. Common occurrences The best time to establish a service
can arise after the warranty has been agreement is when the roofing system
issued which may result in a voided is installed. A building owner should
warranty. These occurrences may in· contact his professional roofing con·
elude, but are not limited to: tractor for recommendations concern·
ing the type of service or maintenance
• Neglect of the roofing system by not contract that would be appropriate for
performing inspections, repairs and his roof(s).
routine maintenance in a timely
manner; 1. 5 Membrane Identification

• Failure by the owner to notify the Although many single-ply roofing


membrane manufacturer of leaks in membranes look alike, they may re·
the roofing system in a timely man­ quire different materials for repair.
ner (most warranties will explicitly The type of single-ply roofing material
state a time limit); used should be noted on the mem·
brane warranty, its related paperwork,
• Failure by the owner to notify the or in the historical record (see Section
membrane manufacturer of work re· 2.0) for the roofing system. If, how·
quired to repair damage or to add
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

ever, these sources do not identify the


rooftop equipment; membrane, contact your professional
roofing contractor or other roofing
• Failure to have permanent repairs professional to aid in the identifica·
or maintenance performed in tion of the roofing material. It is im·
accordance with the manufacturer's portant to identify the roofing material
instructions, such as: in question so the correct materials
and repair method may be selected.
-use of material not manufactured
by the warranting manufacturer, 1. 6 Rooftop Access
or the use of an incompatible
material for a repair; The building owner, or the owner's
representative at the building site, is
-work performed by a contractor responsible for controlling access to
not approved or authorized by the roof. Generally, roofing systems
the membrane manufacturer to are not designed for traffic other than
perform such work. that required for maintenance as per·
formed by trained personnel. In order
• A change in the use of the building; to limit access to approved personnel,
No further reproductions authorized. May 11, 2016.

the roof hatches or access doors


• A change of ownership of the should be kept secured. A sign should
building; many warranties are non· be posted at the point of access to the
transferable. roof stating that only authorized per­
sonnel are allowed onto the roof. In
1.4 Service Agreements addition, a log should be kept of all
individual visits to the roof and the
A service agreement is generally in the corresponding reasons for such visits.
form of a maintenance or service con·
tract between the building owner and Prior to accessing the roof in cold
the professional roofing contractor for weather, check with the membrane
a specific time period, with a possible manufacturer to see if there are cold
option for renewal. Typically covered weather precautions or limitations.
are periodic inspections and the per·
formance of specific routine mainte· Note: When the roof membrane is
nance. A report of the general roof identified as unreinforced PVC, roof·
condition is usuaJly submitted to the top traffic should be avoided when
building owner after each inspection, the ambient temperature is below
with recommendations for immediate approximately 50 ° F. The individual
and future action. manufacturer of a product should be
consulted for a specific recommenda·
tion regarding minimal temperature.

2
Access to the roof
should be limited to
authorized, trained
personnel.
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

1.7 Roof System Access roofing membrane for inspection or


repair difficult. Should one of these
Some single-ply roofing systems have roofing systems be encountered, and if
aggregate or concrete paver surfacing. removal and reinstallation of the
Additionally, protected membrane material covering the membrane is re·
roof systems have an insulation layer quired, it should be performed by a
above the waterproofing membrane. professional roofing contractor.
These systems make accessibility to the

2.0 ROOFING SYSTEM HISTORICAL RECORD

The building owner should maintain a to document all subsequent inspec·


No further reproductions authorized. May 11, 2016.

historical record of the roofing system. tions, maintenance and repairs per­
This historical record will provide the formed on the roof system since its
owner · with data concerning the installation. This information should
original roofing installation such as minimize the cost of repair and
membrane type, the contractor that in· maintenance work. A sample
stalled the roof system and the mem· Historical Record form is included in
brane manufacturer. The owner the Appendix.
should also use the historical record

Keeping complete
historical records
should help to
minimize the cost of
maintenance and
repair.

3
3.0 CAUSES OF ROOF PROBLEMS

All roofing systems have a finite • Manufacturing detects, such as errors


service life. Thjs service life can be in formulation or in fabrication
optimized by performing periodic in·
spections, routine maintenance, and • Use of products or components that
repairs. Similarly, this service life can have exceeded their shelf lives
be reduced by a number of causes.
This section identifies some of the • Improper addition of roof penetra·
causes of problems that affect roof tions after the original installation
service life. Because of the potential of the roofing system. A common
development of problems, routine source of improper additions is
periodic inspections are recommended "tenant-finish" of the interior building
for early detection. space, which typically includes
penetrations for HVAC (heating, ven­
Any of the following conditions may tilation, and air conditioning) units,
result in decreased roof service life. antennae, and plumbing vent stacks.
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

3.1 Natural Causes • Lack of proper maintenance of


items such as pitch pockets at roof
• Long-term exposure to the elements, penetrations, building joint sealants
such as sun, water and freeze-thaw (caulking), counterflashings, drains,
cycles copings, embedded edge metal,
masonry walls, and rooftop units.
• Exposure to air pollutants and
industrial atmospheres • Incorrect, or lack of, response to
problems can result in compound·
• Extreme weather, such as hail, ing the original problem. Roof
lightning, high winds and drenching problems should be corrected pro·
rains (which raise the water level mptly to avoid time-consuming and
above the flashing heights) costly corrections at a later date.

• Structural movement such as • Changes in interior use of the


building settlement, seismic building, such as the change of an
movement, and thermal expansion office space to a laundry. The
No further reproductions authorized. May 11, 2016.

and contraction original roofing system may not


have been designed for the subse·
• Animal intrusion, including insects quent high indoor relative humidity
and birds generated by a laundry and may
consequently experience condensa­
• Biological growth including tion problems.
vegetation, fungus, and algae
• Contamination of the membrane by
3.2 Man-Made Causes substances which are not compatible
·with the roofing materials. These
• Design deficiencies, including contaminants may be spilled or ex·
improper or inadequate design of hausted onto the roof, may be air·
elements of the roofing system such borne, or may be mistakenly used
as structure, details, drainage, and as repair materials on the roof.
loading
• Abuse, vandalism, rooftop traffic,
• Workmanship deficiencies, other trades or any individual who
including improper preparation of either does not belong on the roof
the substrate, improper storage of or who has little regard for the per·
materials prior to installation, formance requirements of the roof·
inclement weather during applica· ing system. As stated previously (see
tion, and failure to follow manufac· Section 1.6), only trained, author­
turer's specifications and details ized personnel with business on the

4
roof should be allowed onto the -drainage system
roof. -water piping and gas, electric, or
other utility lines
3.3 Other Causes -louvers
-windows
• Condensation, or moisture that may -skylights/smoke hatches
be erroneously identified as a roof -walls and sealant joints
leak, may adversely affect the roof­
ing system's performance. • HVAC (heating, ventilation, and air
conditioning) equipment, in addi·
• Water infiltration may be tion to being a source of water en·
erroneously attributed to defects in try, can also cause unacceptable
the roofing system and may ad· differential building air pressures
versely affect the roofing system. which may affect the wind perfor·
Water may infiltrate through any of mance of the roofing system.
the following building elements:

4.0 ROOF INSPECTIONS


© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

One of the key elements of any roof understands the design and basic
maintenance program is regular roof components of the roofing system.
inspection. Another key element is Many professional roofing contractors
immediate attention to all identified provide this service upon request for
problems. a fee.

If the roofing system is currently It is recommended that the spring in­


covered by a manufacturer's warranty, spection be performed by a roofing
both the roofing membrane manufac· professional; the owner or the owner's

Periodic inspection by
a knowledgeable
inspector is a key
element of a roof
maintenance
program.
No further reproductions authorized. May 11, 2016.

turer and the roofing contractor representative should accompany the


should be contacted if problems are roofing professional during this in·
detected in the roofing system during spection if he/she is going to perform
an inspection. In the absence of a the inspection in the fall. The spring
warranty, either a professional roof· inspection should be done early
ing contractor or the membrane enough to allow for any maintenance
manufacturer should be contacted to or repair required to take place in
obtain sound repair and maintenance the prime construction season.
advice.
Late in the fall an inspection by a
4.1 Regular Periodic Ins pections roofing professional, or the owner or
the owner's representative, should be
Every spring and fall, the roof should scheduled to assure the roof is ready
be inspected by a person who for the upcoming winter season.

5
4.2 Special Inspections 4. 3 Inspection Procedure

\.\'hen extraordinary situations occur Each inspection should follow a


which may affect the roof, inspections prescribed routine which enables the
should be made as soon as possible by inspector to examine each visible com·
a roofing professional. Special inspec­ ponent of the roofing system. A sam­
tions are recommended when: ple Owner Maintenance Inspection
form is included in the Appendix for
• construction affects the roof or your use.
adjacent roof areas;
The starting point of an inspection
• new equipment is installed on the should be the interior of the building.
roof; The interior should be checked for
leaks; check interior walls and ceilings
• unusual weather conditions occur, for signs of water and staining. A
such as large hail, high winds, floor plan/roof plan should be
unusually heavy snow loading, or developed from this interior inspec·
other extraordinary weather tion to indicate where there may be
phenomenon; problems at the roof level. After in·
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

Extraordinary situa­
tions, such as
unusual weather con­
ditions, signal the
need for special,
unscheduled
inspections.
No further reproductions authorized. May 11, 2016.

• any maintenance, repair, or reroof­ specting the interior, check the ex­
ing on the roof or an adjacent area terior walls and overhangs for cracks,
is undertaken; (It is best to perform movement and signs of moisture.
a special inspection prior to and
after the completion of this type of The roof should then be inspected by
work.) checking the roof components in the
following order.
• there is a fire or other known
damage to an adjacent roof area.

6
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .
No further reproductions authorized. May 11, 2016.
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .
No further reproductions authorized. May 11, 2016.
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .
No further reproductions authorized. May 11, 2016.
In addition to check­
ing the condition of
penetrations, the
membrane should be
inspected closely for
damage, such as
punctures or tears,
caused by workers
maintaining rooftop
equipment.
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

5.0 OWNER-PERFORMED MAINTENANCE

The life of a roofing system may be them until a professional roofing


optimized with regular, periodic contractor is available to repair the
inspections and a few simple membrane after their removal.
maintenance procedures.
• Remove obstructions (such as leaves
The Owner Maintenance Inspection or dirt) from roof drains and/or
form found in the Appendix notes scuppers, and ensure that they are
numerous items which are followed by flowing freely. If there is a possibili­
an "action needed" recommendation. ty that a roof drain or scupper is
Items such as weathered sealants, loose still obstructed after clearing the
No further reproductions authorized. May 11, 2016.

base flashings, and protruding obstruction, it should be water tested


fasteners should be referred to the ap· with a hose for draining ability.
propriate professional as noted on the
inspection form. Note: If a roof drain or scupper is
blocked by ice, do not physically
There are several other items which break or chip away the ke. (Use of
building maintenance personnel or a heat tapes may avoid drain freezing
professional roofing contractor should and the use of deicing salts.)
perform after each inspection:
• Ballast should be continuously
• Gather debris such as paper, bottles, distributed (except for occasional
broken glass, tree limbs, vegetation, small bare spots, as previously
or any other foreign matter and discussed). Ballast should be redistri­
dispose of them properly. buted with a push broom as neces­
sary to cover the membrane and
Note: Remove any tree limbs or prevent uneven loading. ff ballast
other items that could fall onto the redistribution is a recurring prob·
roof and cause damage. If vegeta­ lem, consult the roofing contractor
tion has roots extending into the or membrane manufacturer for recom­
roof membrane, do not remove mendations to correct this problem.

10
6.0 EMERGENCY REPAIR

6.1 General If literature cannot be located or if


procedures are not detailed for
Emergency repairs may be required emergency repairs, the following
after severe weather because leakage guidelines are suggested:
into a building can occur at any time
(nights, holidays, weekends, etc.). 1) Protect the interior: Control the
Caution: It is generally not advisable spread of water in the interior by col­
to attempt roof repairs until after the lecting the water in containers or by
severe weather has ceased, due to the using plastic sheeting to protect the
danger of high winds and the possi­ building contents.
bility of a lightning strike. Caution
should be exercised when inspecting 2) Remove excess water from the roof:
a roof after there has been severe Check roof drains and scuppers to be
weather, or when there is suspect certain that they are open and func·
damage to the roofing assembly, tional. A frequent cause of roof
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

because storm damage may have left leakage and roof collapse is excessive
the roof in a hazardous condition. If ponding on the roof surface due to
the roof condition is questionable, clogged drains and/or scuppers.
have a professional roofing contractor
perform the inspection and necessary Caution should be exercised when
repairs. In the event a professional clearing debris from drains. Signifi·
roofing contractor is not available, cant suction forces can be created by
and to minimize damage to the in· draining water, which can suck tools,
terior building finishes and contents, hands, or arms placed within these
emergency repairs may be performed. vortices quickly into the drain.

Emergency repair procedures should 3) Locate the source of a leak: In at·


be as simple as possible so they may tempting to determine the source of a
be performed safely by building leak, locate the point on the roof sur­
maintenance personnel or similar face above the area of leakage in the
nonroofing professionals. These building interior. From this point, first
repairs should be considered tern· check the condition of rooftop
porary. Permanent repairs should be mechanical equipment, then check all
No further reproductions authorized. May 11, 2016.

made by a professional roofing con· flashings at terminations and penetra·


tractor as soon as weather permits. tions. Second, if the system is ballasted
remove ballast from the immediate
If the roofing membrane is under a leak area, then check the membrane
manufacturer's warranty, the roofing surface for cuts or punctures. Finally,
membrane manufacturer should be check the seams (laps) in the roofing
contacted as soon as possible. membrane.

Following are emergency repair In many cases, it can be extremely dif·


guidelines that may be performed by ficult to locate the source of a leak on
building maintenance personnel, a roof membrane that has been install·
similar nonroofing professionals, or by ed over insulation placed on a struc·
professional roofing contractors. tural concrete deck, or over an
existing membrane or vapor retarder.
6.2 Leak Repair Procedures
If the source of a leak into the
There are too many different types of building cannot be readily located, the
roofing membranes to tailor emergen· owner or building maintenance per­
cy repair procedures for each. Consult sonnel may have no recourse except
the roofing membrane manufacturer's to control the spread of water until a
literature for products and procedures professional roofing contractor can be
recommended for emergency repairs. contacted and arrives at the site.

12
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .
No further reproductions authorized. May 11, 2016.
manufacturers, roofing materials Place two of these wood blocks, one
distributors, and roofing contractors. on top of the other, through the hole.
Then staple or nail the edge of the
Duct Tape membrane to the wood blocking to
prevent the cut hole from enlarging
Make a patch for the roofing mem­ due to stress placed on the membrane.
brane using common duct tape. (Note: This procedure will raise the hole
The sheet must be clean and dry in several inches above the roof surface,
order for the tape to stick. Cleaning out of any ponding or surface water,
guidelines are described in the and should immediately stop the leak.
"Sealant and Roof Tapes" section.) Place a small metal cap, cone, or
bucket over the hole through which
Wood Block the wood blocks were inserted and
secure the cover to stop additional
If there is a puncture in the mem· water entry. This procedure avoids
brane or a small seam problem where any contamination of the membrane
the membrane is not totally adhered, and should keep the building dry un·
ti! a permanent repair can be made.
Punctures or small
seam problems can When a permanent repair is made,
be prevented from the wood blocks should be removed.
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

developing into a
significant leak b'f the Bentonite Clay
use of the temporary
''wood blocking''
technique. Spread bentonite clay granules ap·
proximately 1" thick in the area of the
leak. The bentonite clay will expand,
forming a water impermeable seal
which bonds to the membrane surface.
The hole is enlarged
and a small wood The bentonite product is a natural
block Is inserted to
clay which should not have a
elevate the opening
above the water line. deleterious effect on the membrane
surface. However, the seal is tern·
porary and should be replaced with a
permanent patch as soon as possible.
(Note: Bentonite clay should be kept
After the block is in away from all roof drains to avoid
place, a bucket is drain blockage.) Use of bentonite clay
No further reproductions authorized. May 11, 2016.

positioned. .
generally necessitates extensive clean·
up of the membrane surface prior to
permanent repair.

6. 3 Wind Damage Repair Procedures


and weighted to keep If roof damage is observed during a
it in place. storm, it is generally not advisable to
attempt repairs or damage control un·
til after the storm because of the
danger of high winds and the
possibility of a lightning strike.

In some instances, however, repairs


during a storm may prevent or
minimize further wind damage. For
example, if a loose metal edge flashing
make a small circular incision at the
is observed, securing it during a storm
puncture or seam. The incision should
may prevent subsequcm lifting, peel·
be large enough to allow a 2" x 4" x
ing, and blow-off of the membr,me. If
4" wood block through the hole,
work is performed during a storm it
under the membrane.
should be done by a professional roof·

14
temporary ballast around the perimeter If any of the above conditions are
to achieve the 40 pound load will observed, a professional roofing con­
depend on the weight of the ballast tractor should make the permanent
being used.) Place the temporary repairs.
ballast on top of the remaining
lightweight pavers to provide tem· If a mechanically attached membrane
porary protection against further wind is observed billowing, consult the
damage until permanent repairs are membrane manufacturer. While some
made. ln conjunction with setting tem· billowing may be normal, an excessive
porary ballast of 40 pounds per linear amount would indicate that design
foot around the perimeter of a bare enhancements may be advisable.
area, also apply temporary ballast to
secure the membrane when the bare If all or a portion of the membrane is
area exceeds 50 square feet. peeled back, the building is vulnerable
to water infiltration. In some in­
In some instances, insulation boards stances, it is possible to reposition the
below the membrane are displaced. membrane to provide temporary pro·
Displaced boards should be reposition· tection. Repositioning should be per·
ed prior to final redistribution of formed by a professional roofing
ballast. If membrane cutting is re­ contractor if one ls available within a
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

quired to reposition the boards, it reasonable time period. After reposi·


should be performed by a professional tioning, the membrane should be
roofing contractor. fastened at the perimeter, the damage
repaired, and temporary ballast installed.
When bare areas exceed 50 square
feet or when ballast is blown off the If membrane is too damaged to be
roof, consult the membrane manufac­ repositioned for temporary protection,
turer because, in either of these cases, replacement material will be needed.
design enhancements may be advisable. If a professional roofing contractor
cannot provide temporary or perma·
Mechanically Attached and Adhered nent roofing service within a
Systems: After high winds, the ex­ reasonable time period, it may be
posed membrane should be inspected necessary to utilize large tarps or
for damage from flying debris. If sheets of polyethylene secured at the
fasteners have backed out or popped perimeter and temporarily ballasted as
up and punctured the membrane, or previously described.
if debris has punctured or torn the
membrane, temporarily repair it as 6.4 Permanent Repair Requirements
No further reproductions authorized. May 11, 2016.

described in Section 6.2.


The emergency repair procedures
Mechanically attached membranes described in the previous sections are
should also be inspected tQ determine strictly temporary in nature and must
if any batten bars or fastening plates be replaced with permanent and com·
were uplifted, or if the membrane has plete repairs by a professional roofing
separated from them. Likewise, fully contractor in a timely manner. If the
adhered membranes should be in· roofing system is covered by a mem·
spected to see if they separated from brane warranty, notify the manufac·
the substrate. If the membrane is unat· turer of the roofing membrane as
tached from the substrate or fastening soon as possible to obtain instructions
system, and the area exceeds 50 and recommendations to facilitate a
square feet, temporary ballasting permanent repair.
should be performed as described
previously under "Ballasted Systems."

16
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .
No further reproductions authorized. May 11, 2016.
7.0 INSTALL ATION OF NEW PENETRATIONS
OR EQUIPMENT
One of the most common causes of stallation will allow the manufacturer
leakage is the improper installation of to recommend how to incorporate the
new roof penetrations or equipment. new penetration or equipment and

Discussion with the


roofing manufacturer
prior to installation of
new penetrations or
equipment should en­
sure that proper pro­
cedures are used by
the professional roof­
ing contractor.
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

To avoid roofing problems associated how to protect the membrane warran­


with new penetrations or equipment, ty, if one exists.
notify the manufacturer of the roofing
membrane prior to the installation of The addition of penetrations or equip­
rooftop penetrations or equipment, in­ ment to the roofing system should be
cluding items that may be set upon undertaken by a professional roofing
the membrane. This would include contractor qualified to perform such
such items as TV antennae, sign or work. The name, address, and telephone
equipment supports, skylights, plumb­ number of a roofing contractor
ing soil stacks, and HVAC equipment. qualified to perform the work can be
No further reproductions authorized. May 11, 2016.

obtained from the roofing membrane


The name and telephone number of manufacturer, if the original roofing
the roofing membrane manufacturer contractor is not available. Improper
should be written on your historical installation of penetrations or equip­
record form. Notification prior to in ment may void the roof warranty.

17
8.0 CONCLUSION

By making a commitment to periodic ing roof access, the roofs service life
roof inspections, appropriate mainte­ can be optimized and the building
nance and repairs, along with control- owner's roofing investment maximized.

Owners that make a


commffment to proper
roof maintenance can
maximize the value of
their roofing
Investments.
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

Photo Acknowledgements

Carlisle SynTec Systems, Carlisle, Pa. National Roofing Contractors


Cooley Roofing Systems, Pawtucket, Association, Rosemont, Ill.
R.l. Roofblok Limited, Fitchburg, Mass.
Firestone Building Products, Carmel, Sarnafil Inc., Canton, Mass.
Ind. Tamko Asphalt Products Inc., Joplin,
No further reproductions authorized. May 11, 2016.

W.P. Hickman Co., Asheville, N.C. Mo.


Wright Brown Roofing Co., Detroit,
Mich.

18
9.0 APPENDIX
Historical Record
All information and records pertinent to this roofing system should be a part of this record, e.g., meeting
minutes, copies of repair records, etc.
General Information

Building: Tenant:
Location: Phone:
Contact:
Owner: Architect/Consultant:
Roofing Contractor:
Membrane Manufacturer:
Warranty Terms: Dates Installed:
Warranty Coverage Period:
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

Membrane: From: To:


Membrane T hickness: Roof Access: Ladder Hatch
Insulation: Building Height:
Design Windspeed: Roof Area: sq. ft.

Specification Information

Construction If recover, describe existing


Type: 0 New D Tear-Off D Recover system:
Roof Deck
Concrete: thickness Type: D Poured O Precast O Plank D T-Beams
O Lightweight D Other Concrete:
Wood: thickness Type: D Tongue & Groove O Plywood
Steel: gauge
Gypsum: thickness Type: D Slab D Plank
No further reproductions authorized. May 11, 2016.

Other:

Roof Slope: inch/foot Areas of Inadequate Drainage: 0 Yes O No


Drainage System: Briefly describe the roof drainage system, including drains, plumbing, scuppers, gutters,
downspouts and sumps, if any.

Single-Ply Membrane
Thermoset: D CSPE (Hypalon) O ECH D EPDM O Neoprene

Thermoplastic: D CPE D 0./A O EIP D NBP O PIB D PVC

Modified Bitumen: D APP O SBS


Installation Method: Surfacing:
D Ballasted D None D Stone: Type
D Mechanically Fastened O PMR D Pavers: Type
O Fully Adhered D Granules O Coating: Type
D Partially Adhered O Other

19
Roof Plan Grid
No. _____
For use in conjunction with the Owner Maintenance Inspection Form.
Buildin g: Inspection Date: _________ _ _ _
_
Location·----------------- Inspector:.________________
Scale: 1" = _____
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .
No further reproductions authorized. May 11, 2016.

20
Owner Maintenance Inspection
No._____
Provide the roof plan using the roof plan grid on page 20 to indicate the location of observed conditions
keyed to this inspection report. Use the item codes to show location.
Building: Inspection Date:_____________
Location:. ____________ ___ Inspector:________________
Contact:. __ ____________________________ _____
Membrane:·--------------�. Surfacing:.________________
Attachment:._______________
Has the occupancy or use of the building changed since the last inspection?
D No D Yes If yes, how?_______________________ ___�
Have any changes, additions or new penetrations been made to the roof since the last inspection?
O No D Yes If yes, how?___________________________�
Has there been leakage?
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .

D No D Yes If yes, under what condition? D Light Rain D Heavy Rain


D Wind Driven Rain O Leaks Continuously
Were emergency repairs performed? 0 No O Yes Describe: _________________

Inspection Checklist:
Perform an initial general building inspection; condition may indicate roof problem. Note location for in­
vestigation on roof:

ITEM CONDITION ACTION ACTION


CODE PRESENT NEEDED TAKEN
INTERIOR rfr = Roofing Contractor
Roof deck mfr = Membrane Manufacturer
A1. Rusting Contact rfr/mfr
A2. Spalling Contact rfr/mfr
A3. Cracking Contact rfr/mfr'
No further reproductions authorized. May 11, 2016.

A4. Buckling Contact rfr/mfr


AS. SaQging Contact rfr/mfr
A6. Open Joints Contact rfr/mfr
Walls
81. Movement Contact rfr/mfr
82. Settling Contact rfr/mfr
83. Cracks Contact rfr/mfr
84. Spalling Contact rfr/mfr
85. Paint Peeling
86. Water Stains
EXTERIOR
Walls
C1. Mortar Joints Contact rfr/mfr
C2. Cracks Contact rfr/mfr
C3. Stains
C4. Efflorescence
cs. Sealant Joints
C6. Windows

21
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .
No further reproductions authorized. May 11, 2016.
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .
No further reproductions authorized. May 11, 2016.
© NRCA Reprint permission granted to Robert Manson at Delta Engineering & Inspection Inc. .
No further reproductions authorized. May 11, 2016.

You might also like