Professional Documents
Culture Documents
1 4
2
• Almost 90% of the surveyed houses • there is sufficient air exchange due to
would have at least one month during wind or stack effect to meet the house-
the heating season when the average hold’s needs.
air-leakage rate was less than 0.3 ach.
Provide needed amount of air exchange
• Virtually all of the surveyed houses (99%)
The system would be able to deliver
would have at least one 24-hour period over
enough outdoor air to meet the probable
the heating season in which the average
maximum needs of the household. It
air-leakage rate was less than 0.3 ach.
would also be capable of modulating deliv-
These results seem to indicate that a
ery so that it did not deliver more outdoor
majority of houses being built in Canada
air than required at times of reduced need.
using normal construction practices are
A system that does not have this capability
close enough to being airtight that air leak-
is likely to provide too much outdoor air
age through the envelope cannot be relied
most of the time it is in operation, resulting
on to provide the rate of air change deemed
in excess energy costs and low humidity.
necessary to maintain adequate indoor air
As well, a system that is unresponsive can
quality in a typical household. While the
annoy the occupants, possibly to the point
rate of air change through the building
that they simply turn it off altogether.
envelope may be adequate most of the time,
it may not be all of the time. Therefore, to Distribute outdoor air where needed
ensure that a satisfactory rate of air change It is not enough that the mechanical
is attainable at all times throughout the ventilation system change the air in the
heating season, these houses must be pro- house as a whole to meet the standard of
vided with mechanical ventilation systems. 0.3 ach. The system must also be able to
deliver the outdoor air to those parts of the
Characteristics of an Ideal house where the occupants are likely to
Mechanical Ventilation System spend most of their time — the living room,
Currently available technology is not able the kitchen and the bedrooms.
to provide an ideal mechanical ventilation Be quiet
system for houses. But before looking at the The system would be quiet enough so that
methods of mechanically ventilating houses the occupants would not be tempted to turn
that are available today, it is helpful to identify it off to reduce noise.
the characteristics of an ideal system:
Not interfere with other systems
Operate when needed There is significant potential for mechanical
The system would operate whenever addi- ventilation systems to interfere with the
tional indoor/outdoor air exchange is operation of other systems, such as certain
needed and would do so without the need types of fuel-fired heating systems. Under
for occupant intervention. these circumstances, if the ventilation
Operate only when needed system creates a high negative pressure in
This is important since a mechanical venti- the house, the products of combustion
lation system has costs associated with it — (which can be harmful to the occupants)
the cost of the electricity to run it and the cost can spill into the house rather than flowing
of heating the outdoor air that the system up the chimney to the outdoors.
brings in. (The latter can be reduced by Not interfere with the building envelope
incorporating heat-recovery capabilities in the The system would not create significant
system, but cannot be eliminated altogether.) positive pressure in the house since this
Therefore, the system should not operate could drive humid air from the house
during those periods when no indoor/out- through the building envelope, resulting in
door air exchange is required. The length, interstitial condensation.
timing and frequency of such periods vary
from household to household. Air Demand-Controlled Ventilation
exchange is not required when: The first two characteristics of the ideal
• there are no occupants in the house mechanical ventilation system described
• there are no activities or processes above are related to the issue of control. A
underway that generate pollutants system that embodies these characteristics
is known as a “demand-controlled ventila-
tion system.” Such a system would ideally
3
be controlled by an array of sensors — one For a discussion of current approaches
for humidity and one for every possible to mechanical ventilation systems for
pollutant that the ventilation system would houses, please see Construction
have to respond to, including carbon Technology Update No. 15.
monoxide, carbon dioxide, formaldehyde,
volatile organic compounds, etc. The References
system would bring in outdoor air and/or 1. ASHRAE 62-1989, Ventilation for
extract indoor air until all of these sensors Acceptable Indoor Air Quality. American
determined that specific pollutants were at, Society of Heating, Refrigerating and
or below, predetermined safe levels. Air-Conditioning Engineers, Atlanta, GA.
Whenever a sensor detected a pollutant 2. Standard CAN/CSA-F326-M91,
above its safe level, the ventilation system Residential Mechanical Ventilation
would operate. Systems. Canadian Standards
A less-than-ideal demand-controlled Association, Etobicoke, ON.
ventilation system would have at least one 3. National Building Code of Canada, 1995.
sensor. For example, many ventilation sys- Canadian Commission on Building and
tems are controlled by dehumidistats: the Fire Codes, National Research Council
system operates until the dehumidistat has of Canada, Ottawa.
determined that the humidity in the house 4. 1989 Survey of Airtightness of New,
is at a safe level. Excess humidity is one of Merchant Builder Houses. Haysom, J.C.,
the main reasons that ventilation is Reardon, J.T., and R. Monsour. Indoor
required, but not the only one. The Air ’90: The Fifth International
amount of ventilation required to control Conference on Indoor Air Quality and
humidity may not be sufficient to control Climate, v. 4, Toronto, 1990.
other pollutants since this depends on the 5. Residential Air System Design. Heating
activities of the occupants, on the relative Refrigerating and Air-Conditioning
strengths of other pollutants and on the Institute of Canada (HRAI), Islington,
level of humidity. ON, 1986.
Carbon dioxide (CO2) sensors are some- 6. Complying with Residential Ventilation
times used to control ventilation systems Requirements in the 1995 National
in large buildings, and this technology is Building Code. Canada Mortgage and
just now becoming available for residential Housing Corporation, Ottawa, 1996.
use. Increasing CO2 concentration is usu- 7. Airtightness and Energy Efficiency of
ally a good indicator of decreasing air qual- New Conventional and R-2000 Housing
ity but it may not be adequate in cases in Canada, 1997. Canada Centre for
where there are unusual pollutants, such as Mineral and Energy Technology, Natural
those generated by certain hobbies. Resources Canada, Ottawa.
The ideal system requires the full array
of sensors mentioned above. However, at
present this ideal is not attainable because: Mr. John Haysom is a senior technical advisor
• there is insufficient knowledge and with the Codes and Evaluation Program of the
National Research Council’s Institute for
information to determine Research in Construction.
- which pollutants should be monitored,
and Dr. J.T. Reardon is a research officer with the
- what the acceptable levels for a partic- Indoor Environment Program of the National
ular pollutant are. Research Council’s Institute for Research in
• practical, reliable and economical detec- Construction.
tors for all pollutants of concern are not
available.
While research and development is
underway in many countries to try to
address these issues, breakthroughs are not © 1998
National Research Council of Canada
expected in the near future. May 1998
ISSN 1206-1220