You are on page 1of 4

C o n s t r u c t i o n Te c h n o l o g y U p d a t e N o .

1 4

Why Houses Need


Mechanical Ventilation
Systems
by J.C. Haysom and J.T. Reardon
This Update is the first of two that discuss mechanical ventilation systems in
houses. It explains why houses need to be mechanically ventilated, and
examines the main characteristics of an ideal system from the standpoint of
design and installation.
The Need for Mechanical In the past, this natural form of ventilation
Ventilation worked fairly well. Houses built before the
History of Ventilation in Houses 1960s tended to be quite leaky and pressure
Houses need to have an indoor/outdoor differences between the inside and outside,
exchange of air to replenish oxygen used by caused by wind or temperature difference,
the occupants and to remove pollutants were sufficient to provide a significant
generated by breathing, household activities amount of air exchange most of the time.
and emissions from building materials and However, a leaky building envelope does not
furnishings. For many years, houses were always guarantee adequate air exchange.
constructed without mechanical ventilation The movement of air requires both a
systems and relied on air leakage through the pathway (e.g., a leak) and a pressure
building envelope to provide this indoor/out- difference, and even a leaky house will
door air exchange during the winter months. experience periods when there is no
indoor/outdoor air exchange. These periods
are most likely to occur during the spring
or fall, when winds are light and there is
little or no indoor/outdoor temperature
difference that can create a stack effect. The
leakier the house, however, the less frequent
the periods of inadequate air exchange.
Since most fuel-fired systems consume
air from the house, and this air must then
be replaced by leakage from outdoors, the
operation of fuel-fired systems promotes
some indoor/outdoor air exchange. The
chimneys associated with these systems
also provide a major leakage point, thus
promoting air exchange even when the
heating system is not operating. As well,
a chimney tends to raise the level of the
neutral pressure plane, thus reducing the
Canada Mortgage and Housing Corporation, “Complying with Residential
outward pressure difference across the
Ventilation Requirements in the 1995 National Building Code” (1996), cover photo building envelope and, with it, the
potential for interstitial condensation How Much Indoor/Outdoor Air Exchange
(i.e., condensation that occurs within the Is Necessary?
building envelope) caused by air leaking The air-change needs of houses are not
out of the house. uniform. Not only do they vary from house
In houses built prior to the 1960s, the to house according to the number of
amount of air exchange provided by leakage occupants, and the presence and strength
was generally regarded as sufficient. But in of various pollutant sources, but, for any
the ‘60s, a number of factors changed this given house, they also vary with time as
picture, including the increased use of occupants come and go, and pollutant
electric heating in houses. Unlike fuel-fired sources wax and wane. Nevertheless,
systems, electric heating systems do not ASHRAE Standard 62, Canadian Standards
require the replacement of air, nor do they Association Standard CAN/CSA-F326 and
require chimneys. Consequently, electrically the National Building Code of Canada
heated houses have a greater tendency to (NBC) have all established levels of air
experience high humidity levels, interior change that can be expected to meet the
surface moulds and interstitial condensation. peak or near-peak needs of a majority of
In the early 1970s, in response to these normal households. (The latter two are
problems associated with electrically based to some extent on ASHRAE
heated houses, Canada Mortgage and Standard 62.)
Housing Corporation (CMHC) took the All three approaches suggest an air
step of requiring all NHA-financed electri- change rate of about 0.3 air changes per
cally heated houses to incorporate exhaust hour (ach). This is the level of air change
fans, a requirement that was eventually used internationally as the norm in terms
incorporated into the National Building of analyzing the success of various ventila-
Code. By the mid-70s, these problems had tion schemes. Again, it is recognized that
became so apparent that CMHC contem- few, if any, houses require constant air
plated not allowing electric heating in change at the rate of 0.3 ach. However,
houses financed under its National Housing if a house is so tight that leakage fails to
Act mortgage insurance program. provide this level of air change for signifi-
In addition to the increase in the use of cant periods of time, it is likely that many
electric heating, the 1960s brought the con- such periods of shortfall will coincide with
struction of houses that were much more periods when this level of air change is
airtight as a result of new products and required. When this happens, poor indoor
practices, which included the substitution air quality, high humidity, surface moulds
of panel sheathings, such as plywood and and interstitial condensation can result.
waferboard, for board sheathing; the replace- How Airtight Are Recently Built Houses?
ment of paper-backed insulation batts by In 1989, a study to determine the airtight-
friction-fit batts and polyethylene film; ness of recently constructed houses in
improved caulking materials; tighter windows various regions of Canada was conducted.
and doors; and more efficient heating systems. Airtightness was measured by carrying
When the energy crisis developed in the out fan-depressurization tests on nearly
early 1970s, considerable emphasis was placed 200 houses throughout the country. The
on reducing air leakage in order to conserve test results were analyzed to estimate the
energy. The use of electric heating systems indoor/outdoor air change rate that could
was encouraged and higher efficiency fur- be attributed solely to the air leakage likely
naces were developed further reducing air- to be experienced by each house over a
change rates in buildings. This trend towards typical heating season. The results of the
greater airtightness and higher efficiency study allowed the researchers to make the
furnaces gave rise to concerns that the following predictions:
exchange of air in houses by natural means • More than 70% of the surveyed houses
might be insufficient in some instances to would have an average air-leakage rate of
provide adequate air quality thus increasing less than 0.3 ach over the entire heating
the risk of health problems among the occu- season.
pants. Condensation problems resulting from
higher humidity levels were also a concern.

2
• Almost 90% of the surveyed houses • there is sufficient air exchange due to
would have at least one month during wind or stack effect to meet the house-
the heating season when the average hold’s needs.
air-leakage rate was less than 0.3 ach.
Provide needed amount of air exchange
• Virtually all of the surveyed houses (99%)
The system would be able to deliver
would have at least one 24-hour period over
enough outdoor air to meet the probable
the heating season in which the average
maximum needs of the household. It
air-leakage rate was less than 0.3 ach.
would also be capable of modulating deliv-
These results seem to indicate that a
ery so that it did not deliver more outdoor
majority of houses being built in Canada
air than required at times of reduced need.
using normal construction practices are
A system that does not have this capability
close enough to being airtight that air leak-
is likely to provide too much outdoor air
age through the envelope cannot be relied
most of the time it is in operation, resulting
on to provide the rate of air change deemed
in excess energy costs and low humidity.
necessary to maintain adequate indoor air
As well, a system that is unresponsive can
quality in a typical household. While the
annoy the occupants, possibly to the point
rate of air change through the building
that they simply turn it off altogether.
envelope may be adequate most of the time,
it may not be all of the time. Therefore, to Distribute outdoor air where needed
ensure that a satisfactory rate of air change It is not enough that the mechanical
is attainable at all times throughout the ventilation system change the air in the
heating season, these houses must be pro- house as a whole to meet the standard of
vided with mechanical ventilation systems. 0.3 ach. The system must also be able to
deliver the outdoor air to those parts of the
Characteristics of an Ideal house where the occupants are likely to
Mechanical Ventilation System spend most of their time — the living room,
Currently available technology is not able the kitchen and the bedrooms.
to provide an ideal mechanical ventilation Be quiet
system for houses. But before looking at the The system would be quiet enough so that
methods of mechanically ventilating houses the occupants would not be tempted to turn
that are available today, it is helpful to identify it off to reduce noise.
the characteristics of an ideal system:
Not interfere with other systems
Operate when needed There is significant potential for mechanical
The system would operate whenever addi- ventilation systems to interfere with the
tional indoor/outdoor air exchange is operation of other systems, such as certain
needed and would do so without the need types of fuel-fired heating systems. Under
for occupant intervention. these circumstances, if the ventilation
Operate only when needed system creates a high negative pressure in
This is important since a mechanical venti- the house, the products of combustion
lation system has costs associated with it — (which can be harmful to the occupants)
the cost of the electricity to run it and the cost can spill into the house rather than flowing
of heating the outdoor air that the system up the chimney to the outdoors.
brings in. (The latter can be reduced by Not interfere with the building envelope
incorporating heat-recovery capabilities in the The system would not create significant
system, but cannot be eliminated altogether.) positive pressure in the house since this
Therefore, the system should not operate could drive humid air from the house
during those periods when no indoor/out- through the building envelope, resulting in
door air exchange is required. The length, interstitial condensation.
timing and frequency of such periods vary
from household to household. Air Demand-Controlled Ventilation
exchange is not required when: The first two characteristics of the ideal
• there are no occupants in the house mechanical ventilation system described
• there are no activities or processes above are related to the issue of control. A
underway that generate pollutants system that embodies these characteristics
is known as a “demand-controlled ventila-
tion system.” Such a system would ideally

3
be controlled by an array of sensors — one For a discussion of current approaches
for humidity and one for every possible to mechanical ventilation systems for
pollutant that the ventilation system would houses, please see Construction
have to respond to, including carbon Technology Update No. 15.
monoxide, carbon dioxide, formaldehyde,
volatile organic compounds, etc. The References
system would bring in outdoor air and/or 1. ASHRAE 62-1989, Ventilation for
extract indoor air until all of these sensors Acceptable Indoor Air Quality. American
determined that specific pollutants were at, Society of Heating, Refrigerating and
or below, predetermined safe levels. Air-Conditioning Engineers, Atlanta, GA.
Whenever a sensor detected a pollutant 2. Standard CAN/CSA-F326-M91,
above its safe level, the ventilation system Residential Mechanical Ventilation
would operate. Systems. Canadian Standards
A less-than-ideal demand-controlled Association, Etobicoke, ON.
ventilation system would have at least one 3. National Building Code of Canada, 1995.
sensor. For example, many ventilation sys- Canadian Commission on Building and
tems are controlled by dehumidistats: the Fire Codes, National Research Council
system operates until the dehumidistat has of Canada, Ottawa.
determined that the humidity in the house 4. 1989 Survey of Airtightness of New,
is at a safe level. Excess humidity is one of Merchant Builder Houses. Haysom, J.C.,
the main reasons that ventilation is Reardon, J.T., and R. Monsour. Indoor
required, but not the only one. The Air ’90: The Fifth International
amount of ventilation required to control Conference on Indoor Air Quality and
humidity may not be sufficient to control Climate, v. 4, Toronto, 1990.
other pollutants since this depends on the 5. Residential Air System Design. Heating
activities of the occupants, on the relative Refrigerating and Air-Conditioning
strengths of other pollutants and on the Institute of Canada (HRAI), Islington,
level of humidity. ON, 1986.
Carbon dioxide (CO2) sensors are some- 6. Complying with Residential Ventilation
times used to control ventilation systems Requirements in the 1995 National
in large buildings, and this technology is Building Code. Canada Mortgage and
just now becoming available for residential Housing Corporation, Ottawa, 1996.
use. Increasing CO2 concentration is usu- 7. Airtightness and Energy Efficiency of
ally a good indicator of decreasing air qual- New Conventional and R-2000 Housing
ity but it may not be adequate in cases in Canada, 1997. Canada Centre for
where there are unusual pollutants, such as Mineral and Energy Technology, Natural
those generated by certain hobbies. Resources Canada, Ottawa.
The ideal system requires the full array
of sensors mentioned above. However, at
present this ideal is not attainable because: Mr. John Haysom is a senior technical advisor
• there is insufficient knowledge and with the Codes and Evaluation Program of the
National Research Council’s Institute for
information to determine Research in Construction.
- which pollutants should be monitored,
and Dr. J.T. Reardon is a research officer with the
- what the acceptable levels for a partic- Indoor Environment Program of the National
ular pollutant are. Research Council’s Institute for Research in
• practical, reliable and economical detec- Construction.
tors for all pollutants of concern are not
available.
While research and development is
underway in many countries to try to
address these issues, breakthroughs are not © 1998
National Research Council of Canada
expected in the near future. May 1998
ISSN 1206-1220

“Construction Technology Updates” is a series of technical articles containing


practical information distilled from recent construction research.

For more information, contact Institute for Research in Construction,


National Research Council of Canada, Ottawa K1A 0R6
Telephone: (613) 993-2607; Facsimile: (613) 952-7673; Internet: http://irc.nrc-cnrc.gc.ca

You might also like