STRUCTURAL DESIGN

COMPUTATIONS

For

Proposed Two Storey with Attic


Residential
Lot 17 & 18, Blk 97, Grand Centennial Homes
Brgy Magdalo, Kawit Cavite
2022

DG Design
PROJECT: Proposed Two (2) Storey House with Attic Residential
Date:
Engineer:
Owner: Phil Yading Real Estate Corporation
SUSPENDED CONCRETE SLAB

FY=40KSI
FS= 20KSI
F'C= 3 KSI

LOADS:
D.L WALL/PARTITIONS-------------------------------45 LBS./ S.F
FLOOR (CERAMICS)------------------------------10LBS./S.F.
CEILING (JOIST/P,W,)---------------------------5 LBS./S.F.

LL RESIDENTIAL---------50 LBS./S.F.
-----50 LBS./S.F.
COMMERCIAL---------10 LBS./S.F.

TOTAL LOADS (L.L + D.L 110 LBS./S.F

MIN THICKNESS OF SLAB = "T"

TYPE OF MEMBER END CONDITION MINIMUM THICKNESS OF SLAB


FY=40 FY=60
L/25 L/20
SOLID ONE SIMPLE SUPPORT ONE END L/30 L/24
WAY SLAB CONT BOTH END CONT L/35 L/28
CANTILEVER L/12.50 L/10

ASS.B = "12"

DG Design
15.40(12)
MIN. T= L/30= = 6.6 SAY 6"
30

WT. OF SLAB = 6"/12 X 150 = 75.00 LBS. /S.F

TOTAL LOADS= 110.00 +75.00 = 185 LBS./S.F

APPROX. DESIGN FACTORS FOR CONT SLAB

N(MAX) = ⅒WL ² = (185) (15.40)²= 4, 387.46

NOTE: TAKE 1.00 FT STRIP

BALANCE SECTION RPOPERTIES FOR RECT CONC. SECTION WITH TENSION REINFORCEMENT
ONLY

FS F'C N K D P R
20 2.0 11.30 0.337 0.888 0.0109 0.135
2.5 10.10 0.362 0.879 0.0146 0.135
3.0 9.20 0.383 0.872 0.0184 0.226
40.0 8.00 0.419 0.860 0.0226 0.324

D= 6" - (.75 + .75/2) = 4.875

RESISTING MOMENT

MR = RBD²
= 0.226 (12) (4.875)² = 64.45 KIP-IN

MR
64.45 KIP-IN 1000
= =
12
5,371.03 FT. LBS

5,371.03 FT , -LBS. >


4,387.46 FT. = LBS O.K

DG Design
*ADEQUATE FOR FLEXURAL STRESS

MAX. SHEAR (V)


INTERIOR SPAN WL/2

1.15 WL/2
END SPAN/ DISC. END
INCREASED BY 15 %

MAX SHEAR=1.15 wl/2 =V


V= 1.15 X 185 X 15.40 = 1,638.18 LBS
2

MAX. SHEAR STRESS = V /BD = 1.638.18 LBS. = 35.23 PSI


12 x 3.875

LIMIT = 1.1 √F.C = 1.1 √3000

60 PSI > 35.23 PSI OK

T.: 0.52 AVE. 0.47


B.B: 0.42

MAX SPACING =3 X THICKNESS


= 3 X 6 = 18 IN

DESIGN MOMENT = M= F X WL²


= F ( 185) (15.40)² FT LBS. 12
= 526, 495.2 F IN.-LBS

DG Design
J = 0.872 SAY 0.90

A= M/ FSJD = 526, 495.2 F


= 6.00 F

BAR DESIGNATION DIAMETER AREA


#2 ¼ 0.05
#3 3\8 0.11
#4 ½ 0.20
#5 5\8 0.31
#6 ¾ 0.44

TYPICAL SLAB DETAIL

SPACING IN INCHES #2 #3 #4
3 0.20 0.44 0.79
3½ 0.17 0.38 0.67
4 0.15 0.33 0.59
4½ 0.13 0.29 0.52
5 0.12 0.26 0.47
5½ 0.11 0.24 0.43
6 0.10 0.22 0.39
6½ 0.09 0.20 0.36
7 0.08 0.19 0.34
7½ 0.08 0.18 0.31
8 0.07 0.17 0.29
8½ 0.07 0.16 0.28
9 0.07 0.15 0.26
9½ 0.07 0.14 0.25
10 0.06 0.13 0.24
11 0.05 0.12 0.21
12 0.05 0.11 0.19

DG Design
REINFORCE CONCRETE BEAM

BEAM

LOADS ON SLAB
LL + DL = 110 LBS/F.S
EXCL LL = 60 LBS/ F.S

ASS OPP BEAM 12 IN WIDE

AREA SUPPORTED BY BEAM = 15.40 FT X 15.40 FT.

REDUCTION IN % = R = 0.08 (A -150)


R =.08 ( 237-150)
=6.96 % SAY 7:00 %

AVE. 1.825

DG Design
ASS BEAM WT . OF 200 LBS/FT

USE 97 % LIVE LOAD OR 48.5 PSF DUE TO REDUCTION

W= 15.40 (60+48.5) + 200 = 1, 870.90

FA FC N K J P R
20 2.0 11.30 0.337 0.888 0.0076 0.0135
2.5 10.10 0.362 0.879 0.0102 0.0179
3.0 9.20 0.383 0.872 0.0129 0.226
4.0 8.00 0.419 0.860 0.0188 0.324

R= 0.226 J= 0.872 P= 0.0129

* LARGEST NEGATIVE MOMENT OCCUR AT THE OUTSIDE FACE OF INTERIOR COLUMN WHERE THE
MOMENT FACTOR IS ⅒

M MAX. = ⅒ WL ² = ⅒ (1.87) (15.40)²


= 44.53 KIPS-FT.

USING THE RELATIONSHIP M= RBD ²

BD² = M/R = 44.35 (12)/0.226 = 2, 354.87


SAY 2, 355.00

TRY COMBINATIONS OF B &D

IF B = 8" D= √2.355/8" = 17.16 SAY 18"


IF B= 10" D= √2.355/10 = 15.35 SAY 16"
IF B= 12" D= √2.3555/12 =14.01 SAY 14"
IF B= 14" D=√2.335/14 =12.97 SAY 13"

DG Design
VC = 1.1 √FC = 1.1 √3000= 60 PSI
MAX. PERMITTED END SHEAR = V = 2VCBD
V= 2 (60) (10") (16")
V= 19, 200.00

MAX. DESIGN SHEAR = V = 1.15 X WL /2

V= 1.15 {( 1.870.90) (15.40) /2 }

V= 16, 566.82 < 19, 200.00'

S A F E

NOTE: USE10MM
OF DIA. STIRRUPS WITH MAX SPACING OF 2.0 M.O.C

DG Design
REINFORCED CONCRETE BEAM

MIN BEAM HEIGHT

TYPE OF MEMBER END OF CONDITION MIN. HT OF BEAM


SIMPLE SUPPORT L/20
ONE END CONT L/23
BOTH END CONT L/26
CATILEVER L/10

MIN BEAM HT = L/23 = 15.40 (12)/23 IN


=8.03 IN .
FOR - M =16" - 35" = 12.50 IN
FOR + M =16" -2.5" = 13.50 IN

-M= M/ FSJD= CWL²/ FSJD = C (1.87) (5.40)² (12)/ (20) (.88) ( 12.5)
= 5,321.87/220 (C ) =24.19 C

+M = M/FS (D- T/2) =C (1.87) (5.40) ² (2)/ (20) (13.5- 6/2)


= 5,321.87/210 ( C)= 25.34 C

TYPICAL FLOOR BEAM DETAIL

DG Design
REINFORCED CONCRETE BEAM

REINFORCEMENT BARS:
NO. DIA. (IN) DIA (MM) WEIGHT AREA
#2 1/4" Ø 6MM Ø 2.37 0.05
#3 3/8 Ø 10MM Ø 3.70 0.11
#4 1/2 " Ø 12MMØ 5.33 0.20
#5 5/8" Ø 16MM Ø 9.47 0.31
#6 3/4" Ø 20MM Ø 14.8 0.44
#7 1"Ø 25MMØ 23.12 0.79
#8 1 1/4 "Ø MM Ø 30.22 1.22
#9 1 3/8" Ø MM Ø 1.48
#10 1 1/2" Ø MM Ø 1.77

1 PSI = 6.9 KPA


1 MPA = 145 PSI
1 MPA = 1000 KPA

DG Design
DATA

F'C = 3000 PSI SOIL BEARING CAPACITY = 3000 PSF


FY= 40, 000 PSI
FS= 20,000 PSI

DL + L.L (AS COMPUTED)= 160 LBS/ S.F.

LOAD ON SLAB--------- 16.40 X 16.40 X 110 X 2 ----------------= 59, 171.20

SLAB WEIGHT ---------16.40 X 16.40 X 0.50 X 150 X 2 -------= 40, 344.00

BEAM WEIGHT--------- 0.83 X 1.33 X 32.80 X 150 X 3----------= 16, 293.57

ROOF & ROOFING FRAME ------ 16.40 X 16.40 X 10 -------------= 2.689.60

TOTAL VERT LOADS---------------------------------------= 118, 498.37

SAY 118, 500.00 LBS.

DG Design
TYPICAL FOOTING SECTION

FC = 3000 PSI
FS= 20, 000 PSI

ASS= 12 IN X 12 IN TIED COLUMN

P= 118.50 KIPS

AG = 12 X 12 = 144.00 SQ. IN

AS= 8- 16 MM . DIA ; 8 X 0.31= 2.48

PG= AS/AG = 2.48/144=.017

DG Design
P= 0.85 [ AG (0.25FC +FSPG )]

P= 0.85 [ 144 (0.25X3000 + 20000X0.017)]

P= 0.85 [144 (750 + 20000 X 0.017)]

P= 133, 416.00 LBS > 118, 500 LBS O.K

TYPICAL COLUMN DETAIL

NOTE: IF THERE IS A DISCREPENCY BET. THE STRUCT PLANS AND STRUCT DESIGN ANALYSIS,
STRUCTURAL DESIGN ANALYSIS WILL PREVAIL

DG Design
BAY AREA
SOIL PRESSURE 2500-3000 NO. OF SIZE NO. SIZE
COL LOAD (KIPS) SQ COL SIZE(IN) SQ FTING WDTH (FT-IN) DEPTH (IN) F'C = 2500 F'C =3000
20 12 3-4 10 4-4 3-4
40 12 4-8 10 8-4 8-4
60 12 5-9 12 11-4 11-4
80 12 6-7 13 11-5 11-5
100 12 7-5 14 14-5 14-5
120 12 8-2 16 15-5 15-5
140 12 8-11 17 13-6 13-6
160 14 9-6 18 15-6 15-6
180 14 10-2 19 17-6 17-6
200 14 10-9 20 19-6 19-6
220 14 11-3 21 15-7 15-7
240 16 11-10 21 17-7 17-7
260 16 12-3 22 18-7 18-7
280 16 12-10 23 15-8 15-8
300 16 13-4 24 16-8 16-8

BAY AREA
SOIL PRESSURE 2500-3000 NO. OF SIZE NO. SIZE
COL LOAD (KIPS) SQ COL SIZE(IN) SQ FTING WDTH (FT-IN) DEPTH (IN) F'C = 2500 F'C =3000
40 12 3-3 10 7-4 6-4
80 12 4-7 12 12-4 11-4
120 12 5-8 15 16-4 10-5
160 14 6-6 16 14-5 14-5
200 14 7-4 19 12-6 12-6
240 16 8-0 20 14-6 14-6
280 16 8-8 21 17-6 17-6
320 16 9-3 23 15-7 15-7
360 16 9-11 24 17-7 17-7
400 18 10-5 25 14-8 14-8
440 18 11-0 27 12-9 12-9
480 20 11-6 27 12-9 12-9
520 20 11-11 28 15-9 15-9
560 20 12-5 30 16-9 16-9
600 22 12-10 30 17-9 17-9
640 22 13-4 31 18-9 18-9
680 22 13-9 32 19-9 19-9
720 24 14-2 33 20-9 20-9
760 24 14-7 33 22-9 22-9

DG Design
REINFORCED CONCRETE BEAM

REINFORCEMENT BARS

NO. DIA. (IN) DIA (MM) WEIGHT AREA


#2 1/4" Ø 6MM Ø 2.37 0.05
#3 3/8 Ø 10MM Ø 3.70 0.11
#4 1/2 " Ø 12MMØ 5.33 0.20
#5 5/8" Ø 16MM Ø 9.47 0.31
#6 3/4" Ø 20MM Ø 14.8 0.44
#7 1"Ø 25MMØ 23.12 0.79
#8 1 1/4 "Ø MM Ø 30.22 1.22
#9 1 3/8" Ø MM Ø 1.48
#10 1 1/2" Ø MM Ø 1.77

1 PSI = 6.9 KPA


1 MPA = 145 PSI
1 MPA = 1000 KPA