You are on page 1of 2

Parada, Valenzuela City

Telefax: (+632) 291-1261


VAT Reg TIN: 218-113-464

INSULATION TEST REPORT

PROJECT TITLE: MACTAN NEWTOWN SOFT STARTER DATE: January 23, 2024
CUSTOMER: ESTATE MANAGEMENT/THE MACTAN NEWTOWN
REF. P.O #: TMNEA-23-00010
LOCATION: NEWTOWN MACTAN,LAPU-LAPU CITY CEBU

TYPE: 3 PHASE INDUCTION MOTOR


BRAND: TECO Rated Voltage: 380V
Model: AEEFS1-YC1 TEMP: 30
Designation:SBR2 Current rating: 83.4A
Location: PUMP ROOM

I. INSULATION RESISTANCE TEST (Ω)


VOLTAGE SETTING: 500

CONNECTION TEST VALUE IN MΩ


W1 -V1 76.50
W1-U1 65.40
U1-V1 89.40
W2-V2 71.10
W2-U2 126.00
U2-V2 113.00

REMARKS: Minimum resistance per ANSI/NETA 2017 Table 100.1


is 100 Mega Ohms.
Winding of SBR2 failed the minimum resistance as per
Ansi/NETA standards.
Repair/Replacement is recommended.

WITNESSED BY:

ENGR. JONATHAN M. DELA CRUZ,REE ENGR. GILBERT P. GUERRERO,PEE


TEST CONDUCTED BY: CERTIFIED BY:
Parada, Valenzuela City
Telefax: (+632) 291-1261
VAT Reg TIN: 218-113-464

INSULATION TEST REPORT

PROJECT TITLE: MACTAN NEWTOWN SOFT STARTER DATE: January 23, 2024
CUSTOMER: ESTATE MANAGEMENT/THE MACTAN NEWTOWN
REF. P.O #: TMNEA-23-00010
LOCATION: NEWTOWN MACTAN,LAPU-LAPU CITY CEBU

TYPE: 3 PHASE INDUCTION MOTOR


BRAND: TECO Rated Voltage: 380V
Model: AEEFS1-YC1 TEMP: 30
Designation:SBR1 Current rating: 83.4A
Location: PUMP ROOM

I. INSULATION RESISTANCE TEST (Ω)


VOLTAGE SETTING: 500

CONNECTION TEST VALUE IN MΩ


W1 -V1 204.00
W1-U1 163.00
U1-V1 146.00
W2-V2 236.00
W2-U2 144.00
U2-V2 165.00

REMARKS: Minimum resistance per ANSI/NETA 2017 Table 100.1


is 100 Mega Ohms.
Winding of SBR1 passed the minimum resistance as per
Ansi/NETA standards.

WITNESSED BY:

ENGR. JONATHAN M. DELA CRUZ,REE ENGR. GILBERT P. GUERRERO,PEE


TEST CONDUCTED BY: CERTIFIED BY:

You might also like