You are on page 1of 1

LEGENDS

PIPE SUPPORT SCHEDULE SYMBOL DESCRIPTION


AS PER NFPA 13, 2022 EDITION, TABLE 17.4.2.1(b), 1/2" UPRIGHT SPRINKLER HEAD (79°C) STD RESPONSE(K-5.6)

ALARM CHECK VALVE ASSEMBLY

1 25Ø 3.70 m 0.90 m HANGER SUPPORT


PART-1
PART-2

PART-3
PART-2
2 32Ø 3.70 m 1.20 m FE-2 5 KG CO2 FIRE EXTINGUISHER

3 40Ø 4.60m 1.50 m FE-1 6 KG DCP FIRE EXTINGUISHER


12 13 14 15 16 17 18 19 20 21 22 23
4 50Ø 4.60m 1.50 m ACV ALARM CHECK VALVE

5 65Ø 4.60m 1.50 m SRP SPRINKLER RISER PIPE

6 80Ø 4.60m 1.50 m RN RISER NIPPLE

7 100Ø 4.60m 1.50 m ARV AIR RELEASE VALVE


8 150Ø 4.60m 1.50 m
NOTES:
9 200Ø 4.60m 1.50 m
1. ALL PIPE SHALL BE BLACK STEEL ERW PIPE
AS PER ASTM A53 GRADE.B SCH-40
2. FITTINGS-
a. SIZE UP TO 50 MM DIA SHALL BE DUCTILE IRON,THREADED FITTING 500PSI
b. SIZE 65 MM DIA AND ABOVE SHALL BE DUCTILE IRON GROOVED FITTINGS

HANGER ROD SIZE (AS PER NFPA-13, 2022 EDITION) TABLE 17.2.3.5.1 3. ALERT SIGNAL FROM SPRINKLER/FIRE FIGHTING SYSTEM TO BE INTERFACED WITH
FIREALARM SYSTEM
PIPE SIZE(mm) HANGER ROD DIAMETER(MINIMUM)

UP TO AND INCLUDING 100mm 10.0mm.


125,150 & 200mm 13.0mm.
250mm 16.0mm.
300mm 20.0mm.

FIRE EXTINGUISHER SIZE AND PLACEMENT FOR CLASS 'B' HAZARD

BASIC MINIMUM MAXIMUM TRAVEL


TYPE OF HAZARD
EXTINGUISHER RATING DISTANCE TO EXTINGUISHERS
(m)
5-B 9.14
LIGHT(LOW)
10-B 15.25
ORDINARY 10-B 9.14
(MODERATE) 20-B 15.25
40-B 9.14
EXTRA
80-B 15.25

FIRE EXTINGUISHER SIZE AND PLACEMENT FOR CLASS 'A' HAZARD

BASIC MINIMUM MAXIMUM TRAVEL


TYPE OF HAZARD
EXTINGUISHER RATING DISTANCE TO EXTINGUISHERS
(m)
LIGHT(LOW) 2-A 22.9m
ORDINARY
(MODERATE) 2-A 22.9m

EXTRA 4-A 22.9m

DESIGN CRITERIA :

SI.NO DESCRIPTION EXHIBITION CENTER

01 SPRINKLER SYSTEM STANDARD NFPA 13 , 2022 EDITION


00 FOR APPROVAL 27/11/2023

02 HAZARD CLASSIFICATION ORDINARY HAZARD GROUP I (NFPA 13, A.4.33.1)


REV. NO. DESCRIPTION Date

03 DESIGN DENSITY 0.15 gpm/ft² (6.1 lpm/m²) (TABLE 19.2.3.1.1)


PROJECT NAME :
04 DESIGN AREA 140 m² (1500 ft²) (NFPA 13, 19.2.3.1.1)

05 MINIMUM REQUIRED SPRINKLER WATER DEMAND 140 x 6.1 = 854 LPM (226 GPM)
NEOM STEEL STRUCTURE 70X200m
946.25 LPM (250 GPM)
06 HOSE STREAM ALLOWANCE (NFPA 13, TABLE 19.2.3.1.2)
07 DURATION OF WATER SUPPLY 60 (or) 90 MINUTES

CONSULTANT :
ZONE CONTROL
SIZE AREA PROTECTED UPRIGHT SPRINKLER
VALVE ASSEMBLY

ACV-01 150Ø 4691 M² 408

ACV-02 150Ø 4691 M² 408

ACV-03 150Ø 4691 M² 408

CONTRACTOR:

FIRE PROTECTION BY :
R

O O O
NAFFCO
NATIONAL FIRE FIGHTING MANUFACTURING FZCO.
RIYADH - K.S.A. TEL: +966 (1) 282 4444; FAX:+966 (1) 282 4333
WEBSITE : www.naffco.com E-MAIL : info@naffco.com

NFPA
R

DRAWING TITLE :
PART-1
PART-2

PART-3
PART-2

FIRE PROTECTION LAYOUT -


PART PLAN -3

DRAWING NO : REVISION NO:

NF-SD-FF-NS-003 00
SUBMISSION DATE : SCALE :

27/11/2023 1:125 on A0
PROJECT ID : PLAN ID :

You might also like