Professional Documents
Culture Documents
DUOBIAS-M
APPLICATIONS GUIDE 5
CONTENTS FIGURES
1
5 APPLICATIONS GUIDE
position, in this case 20%. In this position, a secondary current above example in Fig.3, the H.V. interposing C.T. multiplier
equivalent to 20% of the load or through fault current will flow would require to be set to 0.95.
in the differential circuit.
With delta connected transformers, the line currents are the
To minimise the differential current due to the range of the tap resultant of the currents in two of the transformer phase
changer, it is normal to choose main C.T. ratios which give windings and are therefore different in phase position from the
balance at the mid-point of the tapping range. For the +10% phase winding currents. Depending on the configuration of the
to -20% example, the C.T. ratios would be chosen to give H.V. and L.V.windings, (vector group), the H.V. and L.V. line
balance at the -5% tap changer position so that the maximum currents can have differing phase positions which must be taken
deviation is 15%. The example below shows a single line into account in the biased differential system. With dedicated
diagram of a typical transformer with the calculation of the biased differential relays, the compensation for these phase
optimum C.T.ratio. differences require the use of interconnected interposing C.T.s
of the appropriate ratios but, with the Duobias-M, the required
2.2.1 Example of Optimising vectorial compensation can be made directly to the relay.
In all cases the CT ratios should be selected so that the The biased differential arrangement will detect an interturn
secondary load currents fed into the relay are as close as fault; free from earth, since it will be seen by the protection as
possible to the relay nominal rating (1A or 5A) at maximum an additional, short-circuited winding on the transformer.
load current and midtap voltage ratio. The current amplitude
correction (0.5 to 1.5x) can then be used to fine tune the level The discussion of biased differential protection has, up to this
of secondary currents so that perfect balance is achieved at the point, been confined to two and three winding transformers.
relay rated current of 1A or 5A. In achieving this the relay However, it is possible to treat an auto transformer as a two
biased differential characteristic and therefore relay sensitivity winding transformer and apply biased differential protection.
are optimised. This arrangement is shown later in Fig.6b and it can be seen
that the need for neutral end connection C.T.s is eliminated.
132/33KV 90MVA Yd11 Transformer The H.V. and L.V. C.T.s must now have ratios appropriate to the
rated voltage of their associated windings and the ratios must
Tapchanger range +10% -20% be optimised as shown in Fig.3. The biased differential
protection must be set to cover the magnetising inrush current
At the 33kV side, and the differential current due to the tap changer.
Full load amps = 1000xMVA/kV
= 1000x90/33 2.3 PROTECTION OF A Y.d.11
= 1575A TRANSFORMER.
2
APPLICATIONS GUIDE 5
terminal 13, the 'B' phase to terminal 6 and the 'C' phase to multiple of the rated current which gives an adequate margin
terminal 3. The L.V. 'B' and 'C' connections are similarly crossed over the protected transformers maximum inrush current and
Over. With this arrangement, the Duobias-M relay can be set to any other predictable unbalance such as that due to the
correspond to the vector group of the main transformer,.i.e. transformer tap changer.
Yd11,30°.
4.0 SUMMARY OF PROTECTION
Of the two methods, that shown in Fig.4b is preferred since it SETTINGS
gives a setting which corresponds with the nameplate vector
group of the main transformer.
The Duobias M relay has been designed with protection
functions which compliment one another. Therefore as many of
2.5 PROTECTION OF STAR/STAR AND these functions as is appropriate for the particular application
AUTOTRANSFORMERS should be used. Two examples of the complimentary nature of
these functions are stated below.
The star/star transformer shown in Fig.5a has a phase shift of
zero but still requires the zero sequence shunt which, in the Restricted earth fault (REF) protection can be installed where a
dedicated relay arrangement, is provided either by delta neutral to earth connection is provided for a star connected
connected main C.T.s or by a star/delta interposing C.T. With winding is provided with an earthing transformer. The REF
the Duobias-M relay, this is provided by setting both the H.V. element provides extremely fast detection of earth faults within
and the L.V. interposing C.T. connection settings to the same its zone and is inherently more sensitive and provides greater
Yd. setting. They can be either Ydl,-30° or Yd11,30° but the degree of earth fault protection to the winding than biased
H.V. and L.V. must have the same setting. relays. The restricted earth fault relay would not detect an in
zone phase fault clear of earth as the currents entering and
Note 1. The connection setting can also be Yd1,-30° but leaving the REF zone would still balance. This type of fault
both sides must be the same would however be detected by the biased differential function.
Note 2. The HV and LV CTs must be of appropriate ratio Differential high set overcurrent function is included in the relay
for their associated system voltage and the transformer MVA to provide very fast clearance of high magnitude faults which
rating. are fed directly from a strong power source. The clearance
time of this element is typically around 15ms which is ideal for
Note 3. The change in transformer ratio due to the tap clearance of these high fault levels. The biased differential relay
changer must be taken into account and the interposing CT compliments this function as it can be set to detect lower level
multipliers set accordingly. faults where the fault clearance time is not as critical.
Note 4. The effect of the tap changer and of magnetising Where the Duobias M relay is to be applied to trnasformers
inrush current must be taken into account when setting the bias where sustained overexcitation is in excess of 1.1pu are
and the differential high set overcurrent. allowed on the power system a slight increase of +10% of the
initial bias and bias slope is advised. This is necessary because of
The auto-transformer shown in Fig.5b can be treated in the the odd harmonic current content associated with over fluxing
same way as the double wound, star/star transformer shown in of the transformer core. This additional bias to that normally
Fig.5a and will have the same interposing C.T. connection required for the tap change range and CT tolerances will
settings. It is not equipped with neutral C.T.s however so it ensure the relay will remain stable for all systems overvoltages.
cannot have R.E.F. protection.
The 5th harmonic content of the current waveform is
3.0 STABILITY OF INSTANTANEOUS sometimes used to detect over excitation conditions within the
PROTECTION. transformer core. In practice this is often difficult to set because
detailed magnetising characteristics of each transformer is
Because the differential functions of the relay are instantaneous required. The Duobias M relay contains filtering circuits which
i.e. R.E.F. protection and unbiased differential protection as attenuate the 5th harmonic by 2.75 times (50Hz) and 3.85
applied to auto transformers, the relays must remain stable times (60Hz). This allows the Duobias M relay to remain stable
under switching and through fault conditions. This is achieved with application of suitable relay settings.
by including stabilising resistors in the relay operating circuits;
these limit the differential current caused by the transient As over fluxing of the transformer core can be caused by
behaviour of the C.T.s, to a value less than the relay setting. sustained under frequency or over voltage system conditions
we recommend a suitable V/f over fluxing type relay be applied.
The procedure for establishing the relay settings and resistor
values is explained in our publication "Application Guide, The following is a summary of the functions of the protection
Restricted Earth Fault" settings.
The Duobias-M relay is equipped with differential, H.S.O.C. Differential, Initial setting
protection to provide fast back-up to the biased differential This is the value of current, expressed as a percentage of the
protection. If this feature is required, it must be set to a chosen current rating, at which the relay will operate with zero
3
5 APPLICATIONS GUIDE
bias current. Its setting should be the same as that for the L.V.B. Interposing C.T. connection
Differential, Bias slope. As the H.V. connection but now applied to the L.V. B. C.T.s.
4
APPLICATIONS GUIDE 5
A remote risk with this arrangement is that of the "stuck- meet the requirements for both protection systems.
breaker" condition which will probably result in damage to the
output relay contacts. When the output relay is arranged to 6.0 PROTECTION OF THREE WINDING
drive an external latched tripping relay, this risk is transferred to TRANSFORMERS
the tripping relay contacts and it is a matter of judgement as to
which arrangement is most acceptable.
Transformer:-
132/33/11KV 90MVA Yd11y0.
5.0 CURRENT TRANSFORMER 33KV DELTA WINDING 60MVA.
REQUIREMENTS 11KV STAR WINDING 30MVA.
TAPPING RANGE +10% TO -20%.
The guidance on C.T. requirements is that the C.T. knee-point
voltage must be equal to, or exceed Vk=4Itf(A+C) for star Fig.6 shows Duobias-M protection applied to a three winding
connected C.T.s. Itf is the maximum C.T. secondary current for transformer. The example chosen shows a transformer which
a three phase through fault and A and C are the C.T. secondary has a rating of 90MVA. Its H.V. winding is rated at 132kV and is
winding and C.T. wiring phase resistances respectively. The star connected; it has two L.V. windings, one star connected
volt-drop due to the Duobias-M relay is negligible compared rated at 30MVA, llkV. and the other delta connected rated at
with A and C and is not included in the calculation. The 60MVA, 33kV. The H.V. winding has an on-load tap changer
recommended method of checking the C.T.s suitability is to with a tapping range of +10% to -20%. The procedure to
determine its knee-point voltage, either by reference to its determine the C.T. ratios and protection settings is as follows.
manufacturers design data, or by measurement; and to check
its compliance with the minimum knee-point voltage. Each combination of H.V./L.V. winding, i.e. 132/llkV. and
132/33kV. must be treated separately and the settings
The formula Vknee = 4 x Itf(A+C) to specify the knee point determined as shown in earlier examples. The H.V. winding is
common to both combinations so its settings must obviously be
requirements for the Duobias-M has been establised so as to
compatible for each arrangement. Considering the 132/33kV.
ensure for all possible internal fault conditions a fast operate
arrangement first; this is the same as that shown in Fig.3B and
time can be achieved either through the differential or the
the same C.T. ratios and protection settings can be chosen. The
highset element. It must be emphasised that the value of Itf is
L.V. C.T. ratio must be four times the H.V. ratio of 400/1, i.e.
the maximum through fault level (which is limited by the
1600/1, because the main transformer voltage ratio is 132/33kV,
impedence of the transformer itself , say typically a figure of 4x
i.e. 4/1. Because the H.V. C.T. ratio was chosen to be
to 25x rated) and NOT the maximum internal fault level of the
appropriate to 90MVA, this means that the 33kV. ratio of
transformer which can be very much higher (say 50x upto 250x
1600/1 is also appropriate to 90MVA.
rated)
Since the 33kV winding is rated at 60MVA, the use of lower
If the formula Vknee = 2 x Itf(A+C) is used then the relay
ratio C.T.s may be preferred; this can be achieved conveniently
under certain specific conditions (an internal fault current of just by suitable selection of the L.V. interposing C.T. multiplier
below the HIGH SET setting) will operate at a speed more setting. In this example, the C.T. ratio chosen is 1200/1 which is
comparable to present electro-mechanical differential appropriate to 60MVA. This is used in conjunction with an L.V.
protections. For all other fault conditions the relay will remain interposing C.T. multiplier setting of 0.75 giving an effective
as a high speed protection. ratio of 1600/1 for protection balancing purposes.
An indication of the suitability of a protective C.T. whose Considering the 132/llkV. arrangement, this is the same as that
performance is defined by a B.S.3938 classification can be shown in Fig.6A for a Yy0 transformer and the same settings
obtained. The product of its rated burden expressed in ohms can be chosen. Once again, a more suitable llkV. C.T. ratio of
and the secondary current equivalent of its accuracy limit 2400/1 can be used in conjunction with the minimum L.V.
primary current will give an approximation of the secondary interposing C.T. multiplier of 0.5 giving an effective ratio of
voltage it can produce while operating within the limit of its 4800/1.
stated composite error. However this is an approximation and
should not replace the recommended method. It can be seen that the H.V. interposing C.T. connection settings
required for the 132/33kV. and 132/llkV. arrangements are
For Restricted Earth Fault protection it is recommended that all compatible so the settings shown in Fig.6 would be applied. If
current transformers should have an equal number of the three winding transformer shown was re-arranged to be of
secondary turns. vector group Yd1y0, then the H.V. interposing C.T. connection
and the llkV.,L.V. interposing C.T. connection would both have
Line current transformer ratios should be selected to match the to be set to Ydl.-30.
main transformer rating and ratio. Other ratios can be used
provided these are in the range of the relay current multiplier The settings must, of course. balance when the L.V.
adjustment and do not exceed the current transformer and winding combination is treated as a two winding transformer
relay ratings. and the procedure described above will produce the correct
settings. In the Fig.7 example, if the 11/33kV. combination is
Where one set of current transformers are used for both viewed as a Y/dll transformer, the connection settings will be
differential and Restricted Earth Fault protections they must
5
5 APPLICATIONS GUIDE
seen to correspond with those for the Y/dll example shown in transformer windings differ greatly most of the ratio correction
Fig.4B and the C.T. multiplier settings will also be seen to must be achieved by the appropriate selection of the CT ratio
produce the required balance with effective C.T. ratios of as the interposing CT multiplier is limited to 0.5 to 1.5. The
4800/1 and 1600/1 reflecting the voltage ratio of 11/33kV. appropriate CT ratio’s to be used can be found by calculating
primary currents to a common MVA base (usually the highest
When applying the three winding Duobias M relay to MVA rated winding).
transformers where the rated voltage and therefore CT ratio of
Notes
6
APPLICATIONS GUIDE 5
7
5 APPLICATIONS GUIDE
L.V.
'A' Phase
H.V.
Differential Relays
L.V.
'B' Phase
N
H.V.
L.V.
'C' Phase
H.V.
Tap Changer
A a
B b
C c
A B C
8
APPLICATIONS GUIDE 5
420/1 1600/1
A a
B b
C c
Earth
Trans
Ref.
Ref.
420/1
1600/1
1/0.577
A B C
Figure 3a Yd11 Transformer with Dedicated Biased Differential, H.V. and L.V. R.E.F. Protection with the associated Interposing C.T.s.
400/1 1600/1
A a
B b
C c
Earth
Trans
400/1
1600/1
3 1 1 3
2 2
6 4 4 6
5 5
13 11 11 13
12 12
16 14 14 16
Module 3 Module 4
9
5 APPLICATIONS GUIDE
400/1 1600/1
A a
B b
C c
Earth
Trans
400/1
1600/1
3 1 1 3
2 2
6 4 4 6
5 5
13 11 11 13
12 12
16 14 14 16
Module 3 Module 4
Figure 4a- Yd11Transformer with Primary Cross - Connections giving 90° Phase Shift Full Correction Applied to Duobias-M Relay
400/1 1600/1
A a
B b
C c
Earth
Trans
400/1
1600/1
3 1 1 3
2 2
6 4 4 6
5 5
13 11 11 13
12 12
16 14 14 16
Module 3 Module 4
Figure 4b - Primary Arrangement as in 4a but Correction Applied by making CT Secondary Wiring Cross-Connection to
Correspond with Main Connections
10
APPLICATIONS GUIDE 5
400/1 1600/1
A a
B b
C c
1600/1
400/1
3 1 1 3
2 2
6 4 4 6
5 5
13 11 11 13
12 12
16 14 14 16
Module 3 Module 4
Figure 5a - Yy0 Transformer with Biased Differential and Earth Fault, Duobias-M Protection.
1600/1
a
400/1
A
b
B
c
3 1 1 3
2 2
6 4 4 6
5 5
13 11 11 13
12 12
16 14 14 16
Module 3 Module 4
11
5 APPLICATIONS GUIDE
1600/1
a
400/1
A c
Earth
B 2400/1 a Trans
1200/1
C b
c
400/1
2400/1
3 1 1 3
2 2
6 4 4 6
5 5
13 11 11 13
12 12
16 14 14 16
Module 3 Module 4
1 3
2
4 6
5
11 13
12
14 16
Module 5
Figure 6 - Duobias-M Protection Applied to Three Winding Transformer with 11KV star and 33KV Delta LV Windings.
12
APPLICATIONS GUIDE 5
APPENDIX 1 – APPLICATION TO YY6Y6 Minimum multiplier which can be applied on LVA/B sides is
0.5x.
TRANSFORMER (3 WINDING)
Therefore after interposing CT correction,
1.1 Introduction
LVA relay current = LVA CT secondary current x 0.5 = 1.05A
Relay settings appropriate for the protection of a Yy6y6
transformer where the red phase is at 8 o’clock (transformer LVB relay current = LVA CT secondary current x 0.5 = 1.05A
phase C) on the primary winding and at 10 o’clock (transformer
phase B) on the secondary windings. HV multiplier = LVA relay current / HV CT secondary current
= 1.05/0.875 = 1.2x.
1.2 Design Considerations
The transformer connection implies a 60 degree phase shift Transformer Yy6y6 HV LVA LVB
between the primary and secondary windings i.e. the Voltage (kV) 66 11 11
transformer is overall a Yy2y2 connection. Rating (MVA) 60 30 30
CT Ratios 600/1 1500/1 1500/1
This at first suggests protection by using Yy2 interposing Multipliers 1.20 0.50 0.50
connection on the HV interposing current transformers and Interposing CT Yd3 Yd1 Yd1
Yy0 on the LV interposing transformers. Connection
13
5 APPLICATIONS GUIDE
2.1 Introduction
400/1 2000/1
C a
B b
A c
3 1 1 3
2 2
6 4 4 6
5 5
13 11 11 13
12 12
16 14 14 16
Module 3 Module 4
14
APPLICATIONS GUIDE 5
2.3 Duobias M Settings because balance cannot be guaranteed at the limit of the tap
changer range.
Differential Initial Setting: 20%
This is chosen to take account of the percentage tolerance 66kV x 0.95/11kV = 5.7
difference of line CTs. This setting should be the same as that
for the Differential Bias Slope. LV rated current at mean tap: 349.9A x 5.7 = 1994.43A
Magnetising Inrush Restrain: 20% This example shows the flow of current for a through fault
A safety factor of 2 times the expected inrush secondary condition. Unbalanced loads produce the same effect.
current is used. This commonly gives a factor of 20%. Note
that the lower the setting the more stable the relay because this
level represents the level of second harmonic which will cause
the relay to be inhibited.
HV CT ratio: 400/1
15
5 APPLICATIONS GUIDE
400/1 a 2000/1
B r
A F
3
1.73 3
b
W w
B
1.73
c
R b
C
1.73 1 3
1 2 3
1.73 1 0
2 1 0
0 0 0
1 1 0
The net effect of using a Yy0 LV interposing CT would be to produce a 3 phase differential trip.
16
APPLICATIONS GUIDE 5
HV interposing CT Yd5
LV interposing CT Ydy0
This example shows the flow of current for a through fault
condition.
400/1 a 2000/1
B r
F
A 3
1.73 3
b
W w
B
1.73
c
R b
C
1.73 1 2 1 3
1 2
1.73 1 1 1 0
2 1
0 0 1 1 0
1 1
Through faults and load unbalance conditions result in stability of the differential relay with zero sequence removal.
17
5 APPLICATIONS GUIDE
HV CT ratio: 200/1
LV CT ratio: 1600/1
18