604671
604671
16/1/2024
Elena Vargas Espinoza
Synixtor
EJ 604671
Special Conditions: Max 24 in x 24 in 22 gauge (or heavier) steel duct to penetrate a concrete block,
concrete structural wall assembly. Requesting solution using FD 150+ and MW.
Application Details: To firestop this application, install in accordance with UL System W-J-7111 with the
following modifications/clarifications:
1. The inclusion of FD-150+ is not expected to adversely affect the performance of the system
in a fire scenario, provided all other system parameters are met.
NOTE: Due to the size of the ducts exceeding the maximum allowable size, damper manufacturer
must approve in writing this size damper to be used in conjunction with this firestop system.
NOTE: If the ducts are dampered, this Engineering Judgment is null and void. Dampered ducts must
be fire stopped per damper manufacturer’s installation instructions. The ducts must be constructed
to IMC and/or SMACNA guidelines for gauge, construction, and support.
SYNIXTOR SAC
Email: jgutierrez@synixtor.com