Consider self weight of footing and back fill is 10% column load
Now the total load on the column = Factor load + 10% column load
= 1800+120 =1920 kN
Let us consider the square footing which is having length and width as B
310(2700-2d) = 1116d
Depth of
isolated footing
Step 5: Check for punching shear / Two way shear
= 1741.5 kN
Vc2 = Ksb0d
Where b0 = 4(C1+d)
= 4(400+550)
= 3800
Vc2 = 1X1.118X3800X550
= 2336.62 kN
Mu = ((0.2X3100)/8) (3100-400)2
Mu = 564.975 kN.m
Mu = 0.87fyAstd(1-(Astfy/bdfck))
Spacing = (A/Ast)XB
= (201/2951.4)X3100
= 211.12 mm
So the final reinforcement for isolated footing as per IS 456-2000 code is obtained as
use 16mm diameter bars at 210 C/C distance in both X direction and Y direction.