Professional Documents
Culture Documents
1282844012-EXP 7 and 8 and 9 - P I and D Individual
1282844012-EXP 7 and 8 and 9 - P I and D Individual
Procedure:
Connection for Proportional controller are as shown in the figure
1. After making, all required connection on board which on the power supply and Start the
experiment.
2. Ground PV an inputs of summing block which are not in use.
3. Set +0.5V at test point t.p.l.
4. Apply set point to proportional input.
5. Check the output of proportional block with digital voltmeter given on board.
6. Vary slowly the Kp value, observe the change in the output, and find out the proportional band
that is PB = 100/Kp
7. In the same manner, we can check by applying square and triangular wave.
Diagram :
Observations:
Analysis:
Conclusion:
BVM Engineering College, V V Nagar (An Autonomous Institute)
Electrical Engineering Department
B.Tech – VIth Semester IIIrd Electrical Engineering
Lab manual: 3EE10: Control Systems (AY 2021-22)
Experiment No.: Date:
Procedure :
Connection for integrator controller are as shown in figure.
1. After making, all required connection on board which on power supply and start the
experiment.
2. Ground PV and inputs of summing block which are not in use.
3. Apply square wave to the input of integrator.
4. Check the output of integrator block with CRO and compare with the table no. 1 shown above.
5. Vary slowly the KI value and observe the changes in the output.
6. In the same manner can check by applying triangular wave.
Diagram :
Observations:
Analysis:
Conclusion:
BVM Engineering College, V V Nagar (An Autonomous Institute)
Electrical Engineering Department
B.Tech – VIth Semester IIIrd Electrical Engineering
Lab manual: 3EE10: Control Systems (AY 2021-22)
Experiment No.: Date: