Professional Documents
Culture Documents
Norma GB 25972-2010
Norma GB 25972-2010
Foreword
The standard 4.1, Chapter 5 (5.5.12, 5.13.3.5 excluded) and Chapter 7 (except 7.2.1) is
compulsory
Rests are recommends.
Annexes A to Z of this standard are normative, while the Annexes A to Annexes C is is
informative.
This standard is put forward by Fire Bureau of the Public Security Ministry.
This standard is under the jurisdiction of the Second Committee of National Fire
Protection Standard Technical Committee (CS113/SC2).
Units attending this draft: Tianjin Fire Protection Research Institute of the Public
Security Ministry,
1 Scope
This standard specifies the performance requirements, test methods, test rules and
marking of the gas fire extinguishing system and its components, such as fire
extinguishing cylinders, vessels, nozzles, selector valves, check valves, manifold,
connecting pipes, safety relief devices, drive mechanism, control panels, leak
detecting devices, signal feedback devices, pressure reducers, hook brackets, pipes
and fittings.
This standard is intended for Heptafluoro-Propane(HFC-227ea) fire extinguishing
system, trifluoromethane fire extinguishing system and Inert gasfire extinguishing
system(including IG-01 fire extinguishing system, IG-100 fire extinguishing
system ,IG-55 fire extinguishing system and IG-541 fire extinguishing system).
2 Normative references
The following referenced documents are applicable to this Standard if being cited. For
dated cited references, all the subsequent modified list (not including the revised
content) or the revised edition are not applicable to this Standard. Yet, we encourage
each part that has come to agreement according to this Standard to study whether or
not the latest version of this Standard can be used. For undated references, the latest
edition of the referenced document applies.
1
GB25972-2005 Gas suppression system and components
2
GB25972-2005 Gas suppression system and components
cylinder with the maximum filling density (or the maximum filling pressure), placed in the
upper limit of the temperature range’s equilibrium pressure.
For Stored pressure gaseous suppression system is filling suppression agents in the storage
cylinder with the maximum filling density, placed in the upper limit of the temperature
range’s equilibrium pressure.
For drive gas cylinder is fill by the maximum filling density or gas pressure in the cylinder,
placed in the upper limit of the temperature range’s equilibrium pressure.
3
GB25972-2005 Gas suppression system and components
自定义:Customize
加压方式[自压式(不标注);N 代表内贮压式]:Pressure method [of gravity (not marked); N on behalf of
the stored pressure]
灭火剂瓶组容积,单位升(L):Cylinders of group volume, units liter (L)
贮存压力,单位兆帕(MPa):Storage pressure in MPa (MPa)
系统类别(Q 代表七氟丙烷,S 代表三氟甲烷,Y 代表氩气,D 氮气,DY 代表IG55,H 代表IG541):
System Type (Q representatives HFC227ea, S representatives HFC23, Y representatives argon, D
representatives nitrogen, DY representatives of IG55, H representatives IG541)
气体灭火系统:Gas suppression system
Example: QMQ4.2/90N, on behalf of the stored pressure, suppression agent volume of cylinders 90 L, the
storage pressure of 4.2 MPa HFC227ea gas suppression system.
4.2 The method for the model components see Annexe A.
5 Requirements
5.1 system
5.1.1 Basic parameters
5.1.1.1 Working temperature range
a) HFC-227ea fire extinguishing system: 0℃-50℃;
b) HFC-23 fire extinguishing system: -20℃-50℃;
c) Inert gas fire extinguishing system: 0℃-50℃;
Permanent mark shall be made on main components such as nameplates and cylinders if
products’ design working temperature range exceeds the upper limits.
4
GB25972-2005 Gas suppression system and components
5
GB25972-2005 Gas suppression system and components
5.1.3Appearance
5.1.3.1 Each part of the system shall have no obvious machining defects or
mechanical damage. The outer surface of the components shall have preservative
treatment. Anticorrosion coating and plating shall be complete as well ashomogenous.
5.1.3.2 Names of fire extinguishing systems or products are marked on facade of the
vessels with clearly writings. For gas cylinders, types of the gases shall be marked.
5.1.3.3 Each operating part shall be marked with words or graphics to indicate the
operation methods. For check valves and selector valves, flow directions of the media
shall be signed too.
6
GB25972-2005 Gas suppression system and components
5.1.3.4 Nameplate shall be set firmly and obviously on each component. It contains
equipment name, type-specification, standard code, storage pressure, total amount of
the extinguishing agent, allowable temperature range, factory name, product serial
number, product date, etc.
5.1.3.5 warning plate should be set firmly and obviously on each component, the Inert gas
suppression system warning contents is: "The system action will make nozzle discharge
high-pressure gas; For HFC227ea suppression systems, HFC23 suppression system warning
contents is:" the decomposition of the gas will fire a certain amount of hydrogen fluoride gas".
the contents of warning signs should be clearly and readable 3m away from the plate in the
general lighting conditions.
5.1.4 Quasi-working state
Operational position of the function units, control and watch function of the control
panels shall all be in quasi-working state.
Leak detecting devices for extinguishing agent and gas shall be in normal monitoring
state. The extinguishing agent shall same as the designed value.
7
GB25972-2005 Gas suppression system and components
5.1.5.4.3 Displays, warnings and actions of the output terminals in(after) injection process
should confirm to the requirements of 5.13.
8
GB25972-2005 Gas suppression system and components
regulation of 5.2.4. The cylinder valves can be right opened automatically or manually.
5.2.9Connecting pipes
Cylinders has connecting pipes, the connecting pipes material should be use extinguish
agent corrosion resisted material.
5.2.10 Error discharge protection devices
Cylinders should have the protection devices to prevent the agent error discharge thru the
cylinder valves in the transport, handling and storage, protective devices Opening should
make the suppression agent sprayed evenly and not put too much recoil produced, and
should not be flushed out.
5.2.11 gas sampling requirements
Cylinders (cylinder or cylinder valve) should be equipped with suppression agent sampling
ports, and under the condition of should not open the cylinder valve or not fully open the
cylinder valve (the port still could closed after sampling the agent),sampling the extinguish
agent from the cylinders..
5.2.12 extinguish agent release time
Cylinders with the maximum filling density or filling pressure, the time of suppression agent
discharge from the cylinder valve should not exceed the 80% of the discharge time according
the requirements of 5.1.1.3
5.2.13 Extinguish agent and refill requirements
HFC227ea suppression agents shallB `` shall comply with the requirements of GB 20128.
Other extinguish agents shall be The Fire Agencies of Ministry of Public Security announced
products.
Pressurized should be use pure nitrogen gas and should comply with the requirements of
GB/T8979.
5.2.14 mark
Cylinders set in a clear area shall be permanently marked: extinguish agent name, work
pressure, filling volume, filling pressure, filling the date, Unit, or trademarks.
9
GB25972-2005 Gas suppression system and components
Fill pressure of the drive gas cylinder s should be the same as nominal value label on cylinder.
5.3.4 Sealing requirements
Conduct the air tightness test according to the methods of 6.4.2.The cylinders shall have no
bubble leakage, Test pressure, which lasts 5 minutes, is the maximum working pressure.
5.3.5 Strength requirements
The method prescribed by 6.3 hydraulic strength test, Suppression agent of the cylinders
should have no leakage. Test pressure is 1.5 times of the maximum working pressure, the
pressure keep time is 5 min.
5.2.6 Anti-seismic requirements
Conduct the anti-seismic test in accordance with methods of 6.12.1. Each part of the
driver gas cylinders shall not have any structure damage. Net loss of gas shall not be more
than 0.25% of the total amount.The driver gas cylinders valves will open after test without any
fault.
5.2.7 Thermal cycle leakage requirements
Conduct the thermal cycle leakage test according to methods of 6.13. Net loss
of the gas shall not be more than 0.25% of the total amount. The driver gas cylinders valves
will open automatically after test without any fault.
5.2.8 Toppling impact-resistance requirements
Conduct the toppling impact-resistance test according to the methods of 6.14. Any
part of the driver gas cylinders shall have no damage. Gas-tightness of the driver gas cylinders
shall satisfy the regulation of 5.2.4. The cylinder valves can be right opened automatically or
manually.
5.3.9 Error discharge protection devices
Error discharge protection devices should meet the requirements of 5.2.10.
5.3.10 mark
In significant parts of the driver gas cylinders shall be permanently marked: Gas name, work pressure,
filling pressure, filling date, the manufacturer or trademarks.
5.3.11 pressurized gas requirements
Pressurized gas should be use nitrogen and should comply with the requirements of GB/T8979.
5.4 Vessels
5.4.1 Cylinder design, manufacture, testing
Cylinder design, manufacture, testing should comply the relevant provisions of GB5099,
GB5100, GB150.
5.4.3 Nominal Working Pressure
10
GB25972-2005 Gas suppression system and components
the nominal working pressure of extinguish agent storage cylinders not less than the
maximum working pressure of the system; the nominal working of the drive gas cylinders
not less than the drive gas cylinder maximum working pressure.
5.4.4 Volume and diameter
Nominal cylinder volume and diameter (or diameter) should meet the relevant provisions of
the GB5099, GB5100.
5.4.5 Materials
Seamless steel cylinders materials should be comply with the provisions of GB5099, welding
steel cylinders materials should be comply with the provisions of GB5100. Corrosion
resistance feature of cylinder materials should also allow for the agent of long-term storage.
5.4.5 Colors and Symbol
The color of the cylinder should be red. Seal the cylinder tag and nameplate shall comply to
GB5099, GB5100 requirements.
11
GB25972-2005 Gas suppression system and components
12
GB25972-2005 Gas suppression system and components
conduct the working reliability test according to the methods of 6.6.1, the valves
shall be opened correctly and reliably.
5.5.10.2 Stress corrosion-resistance
Conduct the stress corrosion test according to the methods of 6.11. The
cylinder valves and its accessories shall have no obvious corrosive damage. Strength
performance of the valves after test shall satisfy the requirements of 5.5.4.
5.5.10.3 Sulfur dioxide corrosion-resistance
Conduct the sulfur dioxide (SO2) corrosion test according to the methods of 6.10. The
cylinder valves and its accessories shall have no obvious corrosive damage.
Airtightness performance of the valves after test shall satisfy the requirements of
5.5.5. Then conduct the working reliability test according to the methods of 6.6.1,
the valves shall be opened correctly and reliably.
5.5.11 Manual operation requirements
The cylinder valves shall allow to be mechanical started up on emergency. Conduct
the contingency manual start-up test according to the methods of 6.15, the following
requirements shall be satisfied:
a) Manual operation force shall be no more than 150N;
b) Finger-pull operation force shall be no more than 50N;
c) Finger-push operation force shall be no more than 10N;
d) All displacements of manual operations shall be no more than 300mm.
e) The operating torque of rotating the cylinder valve to open should not exceed 10N • m, the
rotation angle should not exceed 270 º.
5.5.12 structural requirements
the cylinder valve install the pressure monitor, installation port of pressure monitor should set
checkvalve.
5.6 Nozzles
5.6.1 Marks
Information such as factory name, brand, type-specification, code or equivalent
diameter shall be marked obviously and permanently on the nozzles.
5.6.2 Structure and size
5.6.2.1 For HFC-227ea and HFC-23 fire extinguishing systems, the nozzle-codes and
the equivalent port sizes shall satisfy the requirements of Table 2.
5.6.2.2 A filter screen shall be used if the jet orifice cross-sectional area of the nozzle
less than 7 mm2. The granularity of the mesh shall be no more than 60% of the jet
13
GB25972-2005 Gas suppression system and components
orifice diameter. The total area shall be no more than 10 times size of the jet orifice
cross-sectional area.
5.6.2.3 Use protective cap to prevent the jet orifice from being plugged. Make sure the
nozzles are in good condition. Protective cap should be from the nozzle under the 0.01MPa ~
0.3MPa pressure according the tested methods provided by 6.40. No person shall have any
injuries.
Table 2 code and equivalent port sizes
Code Equivalent Code Equivalent
diameter(mm) diameter(mm)
1 0.79 9 7.14
2 1.59 10 7.94
3 2.38 12 9.53
4 3.18 14 11.11
5 3.97 16 12.70
6 4.76 20 15.88
7 5.56 24 19.05
8 6.33 48 38.10
nozzle code of series increase every 1 step, equivalent diameter of hole increase 0.79 375 mm.
14
GB25972-2005 Gas suppression system and components
5.6.3 Materials
All components shall be made of materials with corrosion resistance. Also,
Mechanism strength and heat resistance required in this standard shall be confirmed.
15
GB25972-2005 Gas suppression system and components
16
GB25972-2005 Gas suppression system and components
according to the methods of 6.8.1 and get equivalent length of the selector valve. Difference
value between the equivalent length and the given value shall be no more than 10%.
For Inert gas suppression system, the Local resistance losses of selector valve are using
the pressure loss curve. Conduct the test according to the methods of 6.8.2 and get equivalent
length of the selector valve. Difference value between the measured pressure loss curve and
the given value shall be no more than 10%.
5.7.8 Corrosion-resistance performance
5.7.8.1 Salt spray corrosion-resistance
Conduct the salt spray corrosion test according the methods of 6.9. The selector
valves and its accessories shall have no obvious corrosive damage. Air tightness of
the valves after test shall satisfy the requirements of 5.7.5. Then conduct the working
reliability test according to the methods of 6.6.1, the valves shall be opened correctly
and reliably.
5.7.9.2 Stress corrosion-resistance
Conduct the stress corrosion test according the methods of 6.11. The
selector valves and its accessories shall have no crack or damage. Strength
performance of the valves after test shall satisfy the requirements of 5.7.4.
5.7.9.3 Sulfur dioxide corrosion-resistance
Conduct the sulfur dioxide (SO2) corrosion test according the methods of 6.10. The
selector valves and its accessories shall have no obvious corrosive damage. Air
tightness of the valves after test shall satisfy the requirements of 5.7.5. Then conduct
the working reliability test according to the methods of 6.6.1, the valves shall be
opened correctly and reliably.
5.7.10 Manual operation requirements
The selector valves shall allow to be mechanical started up on emergency. Conduct
the contingency manual start-up test according to methods of 6.16, the following
requirements shall be satisfied:
a) Manual operation force shall be no more than 150N;
b) Finger-pull operation force shall be no more than 50N;
c) Finger-push operation force shall be no more than 10N;
d) All displacements of manual operations shall be no more than 300mm.
e) The operating torque of rotating the selector valve to open should not exceed 10N • m, the
rotation angle should not exceed 270 º.
17
GB25972-2005 Gas suppression system and components
5.8.1 Marks
Information such as factory name, brand, type-specification, working pressure and
media flow directions shall be marked obviously and permanently on the valves.
5.8.2 Materials
Bodies of the valves and mechanical components inside are made of stainless steel
and alloy cuprum. Other kinds of metals with higher intensity and
corrosion-resistance can be used too..
5.8.3 Working pressure
Nominal working pressure of check valve not less than the maximum cylinder working
pressure..
5.8.4 Strength requirements
Conduct the hydraulic pressure strength test according to the methods of 6.3. The
valves and accessories shall have no leakage, deformation or damage.
The test pressure, which lasts 5 minutes, is 1.5 times higher than the maximum
working pressure.
Forward and backward strength of the check valves share the same requirements.
5.8.5 Forward seal requirements
Conduct the air tightness test according to the methods of 6.4.3.The check valves shall
have no bubble leakage.
Test pressure, which lasts 5 minutes, equals the maximum working pressure.
5.8.6 Backward seal requirements
For check valves used in the circulating pipes of the fire extinguishing agent, conduct
the backward air tightness test according to the methods of 6.3.3. The bubbles leakage
shall be no more than 20 per minute under the maximum working pressure.
For check valves used in gas control pipes, no bubbles leakage is allowed under the
maximum working pressure.
5.7.8 Working reliability requirements
Conduct the working reliability test according to the methods of 6.6.2. The check
valves shall support 100 times of “open-close” operational tests. Each motion of the
valves shall be flexible and reliable without any fault or structure damage.
5.7.9 Opening pressure requirements
Conduct the test according to the methods of 6.22. The opening pressure of the check
valves shall be less than the standard value. Motions of the valves under the opening
pressure shall be correctly and reliably.
5.7.10 Local resistance losses
18
GB25972-2005 Gas suppression system and components
For HFC23 and HFC227ea suppression system, the Local resistance losses of check valve
are expressed as the equivalent length of the connecting pipe. Conduct the test according to
the methods of 6.8.1 and get equivalent length of the check valve. Difference value between
the equivalent length and the given value shall be no more than 10%.
For Inert gas suppression system (including the cylinder valve and connecting pipe joints),
the Local resistance losses of check valve are using the pressure loss curve. Conduct the test
according to the methods of 6.8.2 and get equivalent length of the check valve. Difference
value between the measured pressure loss curve and the given value shall be no more than
10%.
5.7.11 Corrosion-resistance performance
5.7.11.1 Salt spray corrosion-resistance
Conduct the salt spray corrosion test according the methods of 6.9. The check valves
and its accessories shall have no obvious corrosive damage. Backward air tightness
of the valves after test shall satisfy the requirements of 5.8.6. Then conduct the
working reliability test according to the methods of 6.6, the valves shall act correctly
and reliably.
5.7.11.2 Stress corrosion-resistance
Conduct the stress corrosion test according the methods of 6.11. The check
valves and its accessories shall have no crack or damage. Backward air tightness of
the valves after test shall satisfy the requirements of 5.8.6. Strength performance of
the valves after test shall satisfy the requirements of 5.8.4.
5.7.11.3 Sulfur dioxide corrosion-resistance
Conduct the sulfur dioxide (SO2) corrosion test according the methods of 6.10. The
check valves and its accessories shall have no obvious corrosive damage. Backward
air tightness of the valves after test shall satisfy the requirements of 5.8.6. Then
conduct the working reliability test according to the methods of 6.6, the valves shall
act correctly and reliably.
5.9 manifold
5.9.1 Materials
The manifold are made of seamless pipes. The materials shall be with corrosion
resistance or anticorrosion coatings in and out of the surface.
5.9.2 Working pressure
The working pressure not less than the maximum cylinder working pressure..
5.9.3 Stress requirements
19
GB25972-2005 Gas suppression system and components
Conduct the hydraulic pressure strength test according to the methods of 6.3. The
manifold shall have no leakage, deformation or damage.
The test pressure, which lasts 5 minutes, is 1.5 times higher than the maximum
working pressure.
5.9.4 Seal requirements
Conduct the air tightness test according to the methods of 6.4.5.The manifold
shall have no bubble leakage.
Test pressure, which lasts 5 minutes, equals the maximum working pressure.
5.9.5 Flow requirements
Conduct the Flow test according to the methods of 6.4.5 methods prescribed by 6.41,
manifold should ensure that the pool gas discharged in maximum discharge time, the
manifold should not be damage in discharge time.
5.10 connecting pipes
5.10.1 Materials
The connecting pipes are high-pressure hoses, metal tubes with reasonable
compressive strength and impact resistance can be used too.
Materials of the connecting pipes shall be good at corrosion resistant.
5.10.2 Working pressure
Working pressure of the connecting pipes between the cylinder valves manifold not less than
the maximum cylinder working pressure; Working pressure of the connecting pipes between
the controlling pipes not less than the maximum not less than the maximum drive gas cylinder
working pressure
5.10.3 Strength requirements
Conduct the hydraulic pressure strength test according to the methods of 6.3. The
pipes shall have no leakage, deformation or damage.
The test pressure, which lasts 5 minutes, is 1.5 times higher than the maximum
working pressure.
5.10.4 Seal requirements
Conduct the air tightness test according to the methods of 6.4.5.The connecting pipes
shall have no bubble leakage.
Test pressure, which lasts 5 minutes, equals the maximum working pressure.
5.10.5 Hot air aging resistance of nonmetal pipes
Conduct the hot air aging test according to the methods of 6.24. No crack or damage
on the nonmetal hose is allowed. The stress and seal performance of the hoses after
test shall satisfy the requirements of 5.10.3 and 5.10.4.
20
GB25972-2005 Gas suppression system and components
21
GB25972-2005 Gas suppression system and components
22
GB25972-2005 Gas suppression system and components
23
GB25972-2005 Gas suppression system and components
24
GB25972-2005 Gas suppression system and components
pressure displays under the test pressure which is 4 times of the maximum working
pressure for 5 minutes. No components of the displays are allowed to be spurted out.
25
GB25972-2005 Gas suppression system and components
26
GB25972-2005 Gas suppression system and components
5.15.8Corrosion-resistance performance
5.15.8.1 Salt spray corrosion-resistance
Conduct the salt spray corrosion test according the methods of 6.9. The devices shall
have no obvious corrosive damage. Action requirements of the devices shall satisfy
requirements of 5.15.1 after test. Contact resistance shall satisfy requirements of
5.15.9.
5.15.8.2 Sulfur dioxide corrosion-resistance
Conduct the sulfur dioxide (SO2) corrosion test according the methods of 6.10. The
devices shall have no obvious corrosive damage. Action requirements of the devices
shall satisfy requirements of 5.15.2 after test. Contact resistance shall satisfy
requirements of 5.15.9.
5.15.9 Contact resistance
Contact resistance of the devices shall be less than 0.1Ω in normal condition and less
27
GB25972-2005 Gas suppression system and components
28
GB25972-2005 Gas suppression system and components
pipeline not less than the maximum working pressure of drive gas cylinder
5.17.5 Action requirements
Low venting high close valve design shall ensure the valve always in the open position in
the quasi-statue of system. the closure pressure should not more than 0.5 times of minimum
open pressure of the valve and not less than the 0.1MPa
5.17.6 Strength requirements
Conduct the hydraulic pressure strength test according to the methods of 6.3. The
valves shall have no leakage, deformation or damage.
The test pressure, which lasts 5 minutes, is 1.5 times higher than the maximum
working pressure.
5.17.7Seal requirements
Conduct the air tightness test according to the methods of 6.4.5.The valve
shall have no bubble leakage.
Test pressure, which lasts 5 minutes, equals the maximum working pressure.
5.17.8Working reliability requirements
Conduct the working reliability test according to the methods of 6.6.2. The check
valves shall support 100 times of “open-close” operational tests. Each motion of the
valves shall be flexible and reliable without any fault or structure damage.
5.17.5 Marks
Information such as factory name,, brand, type-specification and close pressure should be
marked obviously on the Low venting high close valve.
29
GB25972-2005 Gas suppression system and components
Conduct the air tightness test according to the methods of 6.3. No bubble leakage is
allowed.
The test pressure, which lasts 5 minutes, equals the maximum working pressure.
5.18.5 Local resistance losses
For HFC23 and HFC227ea suppression system, the Local resistance losses of Pipes and
fittings are expressed as the equivalent length of the connecting pipe. Conduct the test
according to the methods of 6.8.1 and get equivalent length of the check valve. Difference
value between the equivalent length and the given value shall be no more than 10%.
For Inert gas suppression system, the Local resistance losses of Pipes and fittings are
using the pressure loss curve. Conduct the test according to the methods of 6.8.2 and get
equivalent length of the check valve. Difference value between the measured pressure loss
curve and the given value shall be no more than 10%.
5.18.6 Marks
Information such as factory name, brand, nominal dimension and working pressure
shall be marked obviously and permanently.
5.18 Hooks and brackets
5.18.1 Materials
Hooks and brackets are made of carbon steels.
5.18.2 Load capacity
Conduct the load capacity test according to the methods of 6.38.Deformation of the
hooks and brackets shall be less than 5mm after loading half of the tension test’s loads
for 1 minute. The hooks and brackets shall not break down after loading the tension
test’s loads for 1 minute.
Loads of tension test for pipes of different nominal diameters are shown in table 3.
Table 3
30
GB25972-2005 Gas suppression system and components
6 Tests
6.1 Test requirements
Performance tests of the components shall refer to the design patterns and relative
technologies of the samples. Conduct the tests according to the methods of this
standard.
Air tightness test shall always be conducted after hydraulic pressure tests for any
component.
Except as otherwise specified in referenced sections, all tests shall be carried out
under the following normal atmospheric conditions:
a) Temperature:15 ºC ~ 35 ºC;
b) Relative humidity:45 %RH ~ 75 %RH;
c) Atmospheric pressure:86 kPa ~ 106 kPa.
6.2 Visual examinations
6.2.1 Exam the samples through visual measurement or instruments according to
design patterns and relative technology datum. Basic parameters such as working
temperature, fill density, fill pressure, working pressure and discharge time shall
confirm to specifications of Chapter 4. Structures and sizes of the samples, stamping
gases of the extinguishing systems, volumes and diameters of the storage cylinders,
materials of components shall confirm to specifications of Chapter 5. Requirements
on designs and technologies shall be satisfied too.
6.2.2 Check the components through visual measurement, all marks and fix modes
shall satisfy requirements of this standard.
6.2.3 Exam the process consistence of the samples through visual measurement.
Check the samples if there is any machining defect, surface coating defect or
mechanical damage. Relevant regulations and design requirements shall be satisfied.
6.3 Hydraulic pressure tests
6.3.1 Hydraulic source of the test shall be able to eliminate pressure pulse and
maintain the pressure stability. Accuracy grade of the instruments for pressure tests
shall be higher than 1.6 class. Pressurization rate of the test equipments shall be
continuously tunable within the working pressure range.
Hydraulic pressure test for pressure displays can be conducted on piston pressure
testers.
6.3.2 Connect the entrance of samples with the test equipment and make sure all the
valves are opened. Discharge air in the connecting pipes and samples cavity and
close all the outlets of the samples. Increase the pressure to the test pressure in a rate
31
GB25972-2005 Gas suppression system and components
which is no more than 0.5MPa/s. Maintain the samples working for 5 minutes before
pressure release and exam the samples. The test results shall confirm to relevant
regulations of this standard.
Pressurization rate of the pressure test for connecting pipes shall be no less than
0.5MPa/s.
6.4 Air tightness tests
6.4.1 Requirements
Conduct the air tightness test using N2 or compressed air as pressure source. Accuracy
grade of the instruments for pressure tests shall be higher than 1.6 class.
Pressurization rate of the test equipments shall be continuously tunable within the
working pressure range.
Test temperature of the water for leakage test shall be no less than 5℃.
6.4.2 Tests for fire extinguishing cylinders, signal feedback devices, Low venting high
close valve, ect.
Connect the entrance of samples with the air pressure source and close other outlets
of the samples. Increase the pressure to the test pressure in a rate which is no more
than 0.5MPa/s. Immerse the samples into the water for a depth more than 0.3 meter.
Maintain the samples working in the reserve time.
6.4.3Tests for cylinder valves, selector valves and check valves
Test conditions and procedures are same as 6.3.2. Keep the cylinder valves and
selector valves closed and the check valves positive open. Test results shall comply
with 5.4.5, 5.6.5 and 5.7.5 separately.
Keep the cylinder valves and selector valves reverse open and repeat the tests
upwards. repeat the above test, check the samples and record the test results.
6.4.4 Tests for pressure displays
Install the samples into the test lines and increase the pressure to 2/3 of the upper limit.
Maintain for 7 days before dipping the samples into the water for 10minutes.Depth from the
samples to the liquid surface is more than 0.3 meter Check the samples and record the test
results.
6.5 Overpressure tests
6.5.1 Test instruments are as same as those ruled in 6.3.1.
6.5.2 Connect the entrance of samples with the test instruments. Keep the cylinder
valves and selector valves open and the check valves positive open. Protection
measures of the pressure displays can prevent the components inside from dashing out
of the samples. Discharge air in the connecting pipes and samples cavity and close
32
GB25972-2005 Gas suppression system and components
all the outlets of the samples. Increase the pressure to the test pressure in a rate
which is no more than 0.5MPa/s. Maintain the samples working for 5 minutes before
pressure release and exam the samples.. Check the samples and record the test results
6.6 working reliability tests
6.6.1 Tests for cylinder valves and selector valves
6.6.1.1 Conduct the working reliability tests on the special test facilities. Use
compressed air or N2 as gas source. Volumes of the test facilities and working states
of the drives shall make sure the tested valves are fully open after starting up. Connect
the outlets of the tested valves with straight tubes (shorter than 0.5m) and nozzles.
Nominal diameter of the straight tubes equals that of the outlet. Effective aperture of
the nozzle is no less than 3mm.
6.6.1.2 Fix the tested valves on the special test facilities. Connect the control parts and
keep them working in the given condition. Conduct the tests as follows:
a) Supercharge pressure for the tested valves to the storage pressure P. For selector
valves of the Inert gas extinguishing systems which have pressure reducers, P means
the outlet pressure of the pressure reducers if they are in the entrance of the selector
valves. Keep the pressure for more than 5s;
b) Start the control drive parts to open the tested valves;
c) Close the tested valves until the pressure inside the test instruments is less than
0.5MPa/s;
d) Supercharge pressure again and repeat the test procedure.
Replace the damaged components which are allowed to after each test.
6.6.1.3 Conduct the cycle tests for 100 times under normal temperature(20℃±5℃).
Remove the test instruments and samples into the temperature test chamber and
conduct the tests for 10 times under the maximum and minimum working temperature
separately. Put the samples in the test environments for more than 2 hours for before
the first test. For the other tests, put the samples in the test environments until fully
balanced temperature between the samples and the test chamber reached.
Check the samples and record the test results
33
GB25972-2005 Gas suppression system and components
system with the pressure relief devices of their own, ,the P is the pressure value of the outlet
of the cylinder valve)forwardly and backwardly to fully open (or close)the check valves
orderly. Switch frequency shall be less than 30 times per minute, Conduct the open-close
cycle test for 100 times, Checks the samples and record the test results.
34
GB25972-2005 Gas suppression system and components
L=LX-(a+b)………………………………………………….(2)
Where:
L——equivalent length of the samples (m);
Lx ——equivalent length of the samples and tested pipes (m);
a——see figure 1a) and 1b) (m);
b——see figure 1a) and 1b) (m)。
…….........................(3)
Where:
p——pressure drop (Pa);
d——actual inner diameter of the pipes (m);
c——roughness coefficient of the pipes (120 for galvanize pipes);
Q——flow rate (L/min);
For test-instruments shown in figure 1a), minus the static pressure of the liquid
column (H) to get value of P.
Figure 1a) instrument for equivalent length test
Figure 1b) instrument for equivalent length test
6.8.2 Pressure loss test
Pressure loss test in Figure 1c) or Figure 1d) on the test device, pressure measured by
pressure gauge or pressure sensor. Test medium using the corresponding Inert gas suppression
agent or compressed air, initial pressure of test medium is the 20℃corresponding to the
storage system appropriate pressure. The test devices of cylinder valve pressure loss test
shown as the Figure 1c), The volume of cylinder no less than 90 L,
The cylinder valve inlet side and outlet side should set pressure sample point, The outlet
sampling points position in the straight pipe connected to cylinder valve should away from the
cylinder valve outlet at least 10 times of the inside diameter, position see Figure 1c). The
35
GB25972-2005 Gas suppression system and components
outlet of the straight pipe connect the nozzle (the number of nozzle connected should be same
with the practical application) or connect the orifice which inner diameter equivalent to the
diameter of the nozzle connected. Test to take pressure loss curve and Compare with the
production units.
Selector valve, check valve, pipe pressure loss curve test carry out in test device show as
Figure1d. the gas source should be guaranteed at least 1min
The samples inlet side and outlet side should connected the straight pipe, The pressure test
points position in the straight pipe connected to samples should away from the samples outlet
or inlet at least 10 times of the inner diameter, position see Figure 1d).
The outlet of the straight pipe connect the nozzle (the number of nozzle connected should
be same with the practical application) or connect the orifice which inner diameter equivalent
to the diameter of the nozzle connected. Test to take pressure loss curve and Compare with
the production units.
36
GB25972-2005 Gas suppression system and components
Figure 1c) the cylinder valve pressure loss diagram of testing device
1 - cylinder;
2 - pressure sensor (differential pressure gauge);
3 - the sample;
4 - nozzle.
Figure 1d) selection valve, check valve, pipe pressure loss diagram of testing device
1 - pressure sensor (differential pressure gauge);
2 - the sample;
37
GB25972-2005 Gas suppression system and components
3 - nozzle.
6.9 Salt spray corrosion tests
Conduct the test in the salt-spray-corrosion-box. Concentration of the salt solution for
the test is 20% and range of its density can be from 1.126g/m3 to 1.157k/cm3.
Clear the oil stain of the samples; plug the inlets and outlets of the valves to protect
the intracavity from salt spray corrosion. Hang the samples in the middle of the test
box as normal. Maintain the temperature at 35℃±2℃.Solution dropped from the test
samples can not be used again. Collect the salt spray at two sites (at least) in the
room to adjust the spray rate and concentration of the salt solution of the test
procedure. Collect the salt spray every 80cm2 for 16 hours continuously. Collect
1.0mL to 2.0mL solutions each hour. Concentration of the solutions shall be in the
range of 19% to 21%.
Spray the salt continuously in the test period of 10 days. Wash the samples after test
and place it in the environment at the temperature of (20±5)℃ and relative humidity
lower than 70% for a drying period of 7 days. Check the corrosion behavior of the samples
and record the test results..
6.10 SO2 corrosion tests
Conduct the test in the device for chemical gas corrosion. Fill the working room with
SO2 at a volume ratio of 1% every 24 hours. Inject sufficient water into the
flat-bottom vessel placed on the ground. Get the moist environment by natural
volatilization and maintain a temperature of (45±2) ℃.
Clear the oil stain of the samples and hang it in the middle of the test box as normal.
Droplets from the crest of the working room shall not drop on the samples.
Test period is 16 days. Take the samples out at the 8th day, wash it and put it back
into the test box for another 8 days. Place the samples after test in the environment at
the temperature of (20±5)℃ and relative humidity lower than 70% for a drying
period of 7 days. Check the corrosion behavior of the samples and record the test results..
SO2 for the test can be prepared with the solution of Na2SO3*5H2O and dilute H2SO4.
6.11 Stress corrosion tests
6.11.1 Stress Corrosion Test Methods
Use contain more than 15% zinc‘s copper alloy parts for the material carry out the Ammonia
stress corrosion tests comply with 6.11.2.
Use Austenitic stainless steel parts for the material carry out the Magnesium Chloride stress
corrosion tests comply with 6.11.3.
6.11.2 Ammonia stress corrosion test
38
GB25972-2005 Gas suppression system and components
Conduct the test in the device for chemical gas corrosion. Place a flat-bottom vessel
on the ground and inject the ammonia with density of 0.94g/cm3 into it at the rate of
0.01mL/cm3. Get the moist mixed gas with ammonia and air in the working room by
natural volatilization. The mixed gas is comprised of ammonia (35%), steam (5%)and
air (60%).
The samples inlet filled with de-ionized water and using the non-reactive materials (eg
plastics) sealed to prevent the ammonia enter the internal components. Surface of the sample
should not have any permanent protective layer. If the sample must have the protect layer,
must clean the oil in the sample. Samples should be complied with the production units
requirements for installation threaded connections torque and flange connections torque.
Simulate an installation load.
After the sample clean as above requirement. Hang it in the middle of the test box as
normal. Maintain the temperature of the working room at (34±2) ℃. Test period is 10 days.
Washing and drying the samples after test, The drying time at least 2 d, dried and checked
the corrosion behavior of samples.
6.11.3 Magnesium chloride corrosion test
After the sample with the oil-clean treatment, Placed in the bottle with wet condenser. Add
about half of the flask magnesium chloride’s solution with the concentration of 42%. The
cylinders placed in a thermostatically controlled electric heater and maintained at +150℃ ±
2 ℃ boiling temperature, the test period is 500 h.
After the test, remove the sample washed with de-ionized water and drying, the drying time
at least 2 d, dried and check the corrosion behavior.
6.12 Shake tests
6.12.1 Tests for cylinders and pressure displays
Fill the extinguishing cylinders to its maximum fill density (or fill pressure) with
Extinguishing agent and stamp to storage pressure. Fill the driving gas cylinders to the
design maximum fill pressure. Place the pressure displays onto the extinguishing cylinders (or
driving gas cylinders) according to its working site and allow it to work in the normal state.
Minimum division value of the weighing equipment shall be no more than 2/10000.
Place (or replace) precise pressure measure instrument for test on the samples for
pressure loss judgment. Place the samples in the thermostatic chamber for 24h at the
temperature of (25±1)℃ and get the pressure of the tested cylinders. Record the weight of the
samples only for mass loss judgment. Constant temperature is not necessary.
Conduct the test on the shaking table and shake the table at X, Y and Z-axis for 2h in
turn at the amplitude of 0.8mm and shake frequency of 20Hz.
39
GB25972-2005 Gas suppression system and components
After test, get the pressure and weight of the cylinders as subscribed above. Start the
cylinders automatically. Weights the cylinders and calculate the filled agent weight.
6.12.2 Tests for control panels
Conduct the test on the shaking table. Fix the samples onto the table according to its
working site. Test procedures as below
a) Conduct a frequency scanning cycle at the rate of frequency course per minute
and amplitude of 0.19mm in the frequency range of 5Hz—60Hz—5Hz.
b) If no resonance frequency occurs, conduct the shake test at the frequency of 60Hz
and amplitude of 0.19mm for (10±0.5)min.
c) For resonance frequency which lasts less than 4 hours, conduct the shake test at
each sympathetic vibration frequency for (10±0.5)min with an amplitude of
0.19mm.
d) For resonance frequency which lasts more than 4 hours, conduct the frequency
scanning cycle tests for 2 times at the rate of frequency course per minute and an
amplitude of 0.19mm in the frequency range of 5Hz—60Hz—5Hz.
Conduct the tests at each direction of the samples’s 3 mutually perpendicular axes.
The test results shall comply with 5.12.6.3.
6.13Thermal cyclic leakage tests
Conduct the tests in the temperature test box. Procedure of the pressure reading and
weighing before test is same as that of 6.12.1.
Put the samples in the box for 24h each orderly at the temperature shown below.
a).The maximum operating temperature ± 2 ℃;
b) Minimum operating temperature ± 2 ℃;
c) The maximum operating temperature ± 2 ℃;
d) Minimum operating temperature ± 2 ℃;
e) The maximum operating temperature ± 2 ℃;
f) Minimum operating temperature ± 2 ℃.
Place the samples in the environment with a temperature of (25±5) ℃ for 24d
after test. Repeat the test, Place the samples in the environment with a temperature of
(25±5) ℃ for 24d again.
After test, get the requirements for pressure and weight of the cylinders as subscribed
above. Start the cylinders automatically. Then weight the cylinders and calculate the
extinguisher agent weight.
Conduct the pressure discharge tests for the safety relief devices on the cylinders according
to the methods of 6.14.Conduct the indication error tests and air tightness tests for the
40
GB25972-2005 Gas suppression system and components
41
GB25972-2005 Gas suppression system and components
valves with the dynamometer. Measure and record the maximum operation force and
stroke.
6.17 Flow characteristic tests for nozzles
Test instruments are shown in figure 3. Diameter of the connecting pipe between the
cylinder valve and the nozzle shall be no less than the nominal diameter of the
nozzle’s inlet. Accuracy rate of the load sensor shall be over 2/1000.
Opening dimensions of the nozzles shall coordinate with volumes of the extinguishing
agents containers to complete the discharge in time.
Fill the nozzles with extinguishing agent to the fill density and stamp to the storage
pressure. Install the nozzles onto the test instruments after standing for 2h and then
open the cylinder valves automatically. Record the change curve of the pressure and
agent mass with time before. Calculate the mass flow of the nozzle with different
discharge pressure according to the orifice area of the nozzle.
6.18 Heat and pressure resistance tests for nozzles
Test instruments are shown in figure 4. Place the nozzle inside the temperature test
box. Use N2 or compressed air for test. Cross-section of the connecting pipe shall not
be less than 3 times of injection area of the nozzle.
Place the nozzle into the test system, locate the relief valve at its working site, and
maintain the test box at a temperature of (600±20)℃ for 5 minutes. Open the test
box quickly to spurt out the airflow. Keep the pressure of the nozzle at the given value
for 10s within the discharge time.
Figure 3a) flow characteristic test instrument (weight and balance method)
1 - measured nozzle;
2 - pressure sensor;
3 - fire Cylinders group;
4 - weight;
5 - Data acquisition and processing system;
42
GB25972-2005 Gas suppression system and components
6 - load sensors.
Figure 3b) characteristics of the nozzle flow schematic diagram of test equipment (suspension
method)
1 - load sensor;
2 - pressure sensor;
3 - Data acquisition and processing system;
4 - measured nozzle;
5 - extinguish agent cylinder group.
43
GB25972-2005 Gas suppression system and components
7 - nozzle.
44
GB25972-2005 Gas suppression system and components
45
GB25972-2005 Gas suppression system and components
46
GB25972-2005 Gas suppression system and components
The opening above the fuel tanks could be close, keep the opening above the fuel tank open.
In the pre-combustion period of fuel.
a high baffle should be se t between the nozzle and the fuel tank .with the same height as
test space, the position of baffle shown in Figure 7a), Figure 7b), baffle width should be 20%
of the test space width.
6.20.4.5 Test
Ignite the fuel tank, pre-combustion 30 s, boot the system.
6.20.4.6 Test record
Test records meet the requirements of 6.20.3.
6.21 Impact test for nozzles
Test instruments are shown in figure 8.Fix the hammers, swing links, hubs and
matching blocks on the fixed mount with rolling bearings and rotation axis. The
hammer is made of aluminum alloy. The attacking surface , with a rake of 60°, shall
be hard enough to prevent it from any damage.
Place the test nozzle onto the test instrument as shown in figure 7. Adjust the height of
the nozzle to get impacts on the centerline of the attacking surface. Velocity of the
hammer is (1.8±0.15)m/s with an impact energy of 2.7J.
Figure 6, the maximum mounting height of the nozzle test measuring point arrangement
diagram
M1 ~ M3 - Sampling point of oxygen concentration measurement;
M4 - temperature measuring points;
a – length of test space;
b - width of test space;
47
GB25972-2005 Gas suppression system and components
48
GB25972-2005 Gas suppression system and components
49
GB25972-2005 Gas suppression system and components
low vent and high closed valve conduct the test with the air tightness test instruments of 6.4.
The accuracy rate of the manometer shall be no less than 0.4.
Connect the inlet of the tested valve with test instrument. Allow the valve to stay at its
normal open state. Increase the pressure gradually and record the closed pressure of
the valve. Conduct the test for at least 3 times.
6.24 Hot air aging tests
Conduct the hot air aging resistance test of nonmetal pipes in the test box.
Curve the test pipes to an angle of 90°as required and put it in the test box. Touches
between the sampless, or between the samples and the wall are forbidden.
Conduct the test at the temperature of (140±5)℃ for 10d. If the sampless are
softened at that high temperature, conduct the test at a lower temperature for a longer
time. Calculate the test time as follow:
D = 229000*e−0.693t……………………………….(4)
Where:
D——test time(day);
t——test temperature(℃).
e——the value is 2.71828.
Take the samples out after test and cool them for 24h before the examinations.
6.25 Voltage withstanding tests
Conduct the test with withstands voltage tester. Test voltage shall be continuously
tunable from 0V to 1500V. Boost the voltage automatically at a rate from 100V/s to
500V/s after value set of the test voltage. Depress the voltage automatically at the
setting time of (60±5)s.
6.26 Insulation resistance measurements
Conduct the test with insulation resistance testers (megohmmeter or megger can be
used too). Test voltage is 500Vd.c and test range is from 0MΩ to500 MΩ.
Make sure that the contacts contact reliably with each other and insulation resistances of the
lead wires are large enough.
6.27 Power supply
Make control panel in a normal state, connect the adjustable power supply, standby power
charge should be in a normal working condition.
the adjust supply voltage is 187 V ~ 242 V, 50 Hz. All loops of the control panel in the
alarm and drive spraying status, inspection the working status. Disconnect the main power
supply, standby power in the normal monitoring state, after 24 h, make a loop of the control
panel in the alarm and drive discharge state, check system working conditions.
50
GB25972-2005 Gas suppression system and components
51
GB25972-2005 Gas suppression system and components
High-and-low temperature tests for control panels, weighting units and liquid level
detectors are conducted in high (or low) temperature test box separately. Maintain
error of the temperature to stabilize at ±2℃ and calculate the test time after the
given temperature value reached. Conduct the function exam immediately after the
tests completed.
6.31 Hygrothermal tests
Conduct the hygrothermal test for control panels in the hygrothermal test box.
Maintain the control panels to stabilize in the quiescent condition and raise the
temperature gradually to (40±2) ℃. Increase relative humidity to the given value
after the tested sample gets the temperature equilibration. Keep the test for 24h and
conduct the function exam immediately after the test completed.
6.32 Basic properties tests for pressure displays
6.32.1 Indexing plate
Examine the graduation, color and sign etc. of the indexing plate with visual
measurement according to design patterns and technological files. All results shall
comply with 5.13.2.2.
6.32.2 Intrinsic error of the indication
Examine the intrinsic error using piston manometer as pressure source. If indication
delay caused by oil pressure is too large, use gas as pressure source instead. Accuracy
rate of the manometer shall be no less than 0.4.
Allow the pressure displays stabilize in the quiescent condition. Conduct the
indication exam in the pressor and depressor process for 2 times separately.
6.33 Alternative load tests for pressure displays
Fit the pressure displays on the alternative load test table. Adjust the alternative
frequency and amplitude and then conduct the test for 1000 times.
6.34 Contact resistance tests for signal feedback devices
Get value of the contact resistance through digital milliohm meter. Or we can measure
the current and voltage reduction between contacts and calculate the contact
resistance. Accuracy rate of the electrical mater shall be no less than 1.5. Measure the
contact resistance for 5 times and get the average value.
6.35 overload tests for weighting units
Fit the weighting units on the brackets correctly. Load the weighting units with heavy
weight or poise whose quality equals 2 times of extinguishing cylinders’ quality. Keep
for 15 minutes before unloading and examine the state and alarm function of the
samples.
52
GB25972-2005 Gas suppression system and components
53
GB25972-2005 Gas suppression system and components
54
GB25972-2005 Gas suppression system and components
7 Test rules
7.1 Test classification, Test items and test procedure
7.1.1 Test classification
If one of the following occurs, the type inspection shall be carried out.
a) Trial manufacturing design appraisal of new products;
b) After formal production, if the product structure, materials, technique, key process
and so on have substantial modifications and may affect the product performance;
c) A major quality non-conformance has occurred;
d) The resumption of production after shutdown of more than one year;
e) Required by the Quality Supervision Organizations.
7.1.2 Test items
Conduct the type inspection according to table 4. Delivered ex-factory inspection projects
should not be less than the items specified in Table 4.
7.1.3 Test procedure
See rules in annex A to annex Z.
7.2 sample method and sample number
7.2.1 sample method and sample number of ex-factory
the sample base of components according the factory inspection by the production units based
on the production, the system assembled from the components by a randomly selected sample.
Number of samples identified with the table in Annex 4 and Annex D ~ Z requirements.
7.2.2 sample method and sample number of type inspection
the sample base of components of type test should no less than five times the number of
samples of the provisions of Annex D ~ Annex Z requirements. Components using a one-time
random Sampling, the system assembled from the components by a randomly selected
sample.
55
GB25972-2005 Gas suppression system and components
56
GB25972-2005 Gas suppression system and components
57
GB25972-2005 Gas suppression system and components
58
GB25972-2005 Gas suppression system and components
manual operation ★ — ★ — — ★
Table 4 (Continued)
59
GB25972-2005 Gas suppression system and components
Table 4 (Continued)
60
GB25972-2005 Gas suppression system and components
marks ★ ★ — — — ★
Table 4 (Continued)
61
GB25972-2005 Gas suppression system and components
8 Operating instructions
Operating instructions shall comply with GB 9969.1 with least contents as follows:
a) Brief introduction of the system (work principle mainly)
b) Systems safe use warning, Inert gas system should be at least introduction like that
"extinguish agent storage cylinders pressure is MPa, when the system action, the nozzle
will release high-pressure gas may cause damage to nearby people or objects, "and so on. For
HFC227ea and HFC23 suppression system should be at least introduction like that "the
system filled suppression agent would decomposition of a certain amount of hydrogen
fluoride Gases when the system action, high concentration of hydrogen fluoride gas could
cause injury to people ".
c) Primary parameters of the system;
d) Sketch map;
e) Operation procedures;
f) Items of the parts, such as name, type-specification, primary parameters,
instructions for installation and maintenance, items need to be pay attention to, etc.
g) Fill procedure of the extinguishing agents;
h) After service;
i) Name, address, zip code and telephone of the product unit.
9 extinguish agent filling
Filling of Inert gas suppression agents should be authorized by state and qualified gas
filling units. Gas filling production units should kept filling record at least until the next
filling.
HFC227ea, HFC23 extinguisher gas filling should be filled by a professional Gas filling
company, Gas system production units should be kept records at least until the next filling..
If the gas system manufacturer filling the gas by themselves, should be establish
appropriate operating procedures and inspection procedures, in addition to preservation filling
record. they also need drawn suppression agent from this amount of suppression agents to
keeps the type to seal, the preservation of filling records and suppression agents sealed type at
least until the next Filling.
62
GB25972-2005 Gas suppression system and components
Annex A
(Informative)
Component model methodology
The model methodology of gas suppression system, consisted by the system category code, components,
code, the main parameters and the manufacturer definition themselves, four sectors
The main parameters divided into the first and second sub-primary parameters.
System model in the category code, see 4.4.1.
Component code and the main parameters in Table A.1
Example: QMP70/4.2 stand for the storage pressure is 4.2 MPa, the volume of suppression agent cylinders
is .70 L
Table A.1 Main parameters of the main parameters and the main parameters of component code
Main specification 1 Main specification 2
Part name Part code
Name Unit Name Unit
nominal working
vessel R volume L MPa
pressure
nominal working
cylinder valve RF nominal diameter mm MPa
pressure
inlet nominal
Total flooding nozzle PT nozzle code - mm
diameter
local application inlet nominal
PTJ nozzle code - mm
nozzle diameter
nominal working
selector valve XZ nominal diameter mm MPa
pressure
check valve for main nominal working
YD nominal diameter mm MPa
cylinder pressure
check valve for drive nominal working
QD nominal diameter mm MPa
gas cylinder pressure
nominal working
manifold JG nominal diameter mm MPa
pressure
nominal working
connection pipe RG nominal diameter mm MPa
pressure
63
GB25972-2005 Gas suppression system and components
64
GB25972-2005 Gas suppression system and components
Annex B
(Informative)
Suppression Concentration of extinguishing class B heptanes fire and the Class A surface fire of wood crib
Suppression Concentration of various types of suppression agent extinguishing class B heptanes fire and
the Class A surface fire of wood crib shown in Table B.1.
Table B.1 Suppression Concentration of various types of suppression agent extinguishing class B heptanes
fire and the Class A surface fire of wood crib
Class B heptanes fire Class A surface of wood crib Vapor specific volume
fire m3/kg
65
GB25972-2005 Gas suppression system and components
Annex C
(Informative)
the experiment methods of define the Suppression Concentration of extinguishing class B heptanes fire and
the Class A surface fire of wood crib
C.1 test space
Test space volume no less than 100 m3, length, width no less than 4 m, height about 3.5 m ~ 4 m. if test
space set pressure relief port , the installation position should be located at 3 / 4 height space above or at the
top.
C.2 Measurement Parameters
C.2.1 Measurement of oxygen concentration
Measurement of oxygen concentration test space position shown in Figure C.1. Oxygen concentration
measurement device resolution no less than 0.1% (by volume), should be able to continuously collection
and recording the oxygen concentration within the test space. Accuracy of measuring equipment should not
be affect by the combustion products. The using the range for test is 17% ~ 21% (by volume). The
frequency of data storage at least 4 Hz.
C.2.2 nozzle pressure measurement
Pressure sensor should be used to monitor nozzle pressure, the sensor accuracy no less than 0.5%, the
distance between the pressure sensor and the nozzle does not exceed 1 m.
C.2.3 test space temperature measurement
Temperature measuring point position of the test space shown in Figure C.1, Time constant of the
thermometer no less than 1 s, number of channels should take 3, Measurement should using a
continuous value,
Measuring range: 0 ℃ ~ +1 200 ℃.
Using the 1 mm K-type thermocouple (Ni-CrNi)
C.2.4 temperature measurements near the nozzle
For the liquid suppression agent, the vent temperature should be recorded.
C.3 suppression system using for tests
Fire system designed by manufacturer.
Cylinders should be in +20℃ ± 2 ℃ temperature for 16 h or more.
System release time of suppression agent should meet the following requirements:
For the liquid suppression agent, liquid and gas-liquid two-phase discharge time should be 8 s ~ 10 s;
For non-liquid suppression agent, discharge time should be 50 s ~ 60 s, could be using the installed control
device in the position near the nozzle cut off suppression agent discharging;
In experiment, the release of suppression agent should not affect test fire combustion.
66
GB25972-2005 Gas suppression system and components
Figure C.1 The diagram of class A and class B fire fighting test arrangement
M1 ~ M3 - The sample point measuring the oxygen concentration in;
M4 ~ M6 - temperature measuring points;
a - length of test space;
b - width of test space;
H - height of test space;
h – the height of oil pan and crib from the ground.
67
GB25972-2005 Gas suppression system and components
68
GB25972-2005 Gas suppression system and components
normal air condition. Changes of the oxygen concentration caused by the combustion products before the
agents’ discharge shall be within 1.5% (volume ratio).
The values get from compare with the cooling discharge specification.
Seal the test space for 10 minutes after discharge is over. Remove the wood crib from the test space after 10
minutes, Observe the wood cribs whether resurgence or not.
C.6.4 Test records
Test shall be recorded the following:
a) embers or recrudescence within the 10 minutes, Observing and recording the surface temperature and
embers of wood crib in Soaking time, Observing the state of the resurgence should adopt Infrared
Camera;
b) mass loss of the wood crib;
c) oxygen concentration change at each oxygen measuring point;
d) temperature change at each temperature measuring point;
e) delay time and discharge time of the fire system; pressure before nozzles;
f) extinguishing time;
g) mass of the extinguishing agent released into the test space;
69
GB25972-2005 Gas suppression system and components
Annex D
(Normative)
System test procedures and the number of samples
D.1 Test Procedure
Test procedures shown in Figure D.1.
70
GB25972-2005 Gas suppression system and components
Annex E
(Normative)
Cylinders and sample groups the number of test procedures
E.1 Test Procedure
Test procedures shown in Figure E.1.
71
GB25972-2005 Gas suppression system and components
Annex F
(Normative)
Driving gas cylinders testing procedures and the number of samples
F.1 Test Procedure
Test procedures shown in Figure F.1.
72
GB25972-2005 Gas suppression system and components
Annex G
(Normative)
The number of test procedures and sample cylinders
G.1 Test Procedure
Test procedures shown in Figure G.1.
73
GB25972-2005 Gas suppression system and components
Annex H
(Normative)
Cylinder valve test procedures and the number of samples
H.1 Test Procedure
Test procedures shown in Figure H.1.
74
GB25972-2005 Gas suppression system and components
(Normative)
The number of nozzles and sample test procedures
I.1 test procedures
Test procedures shown in Figure I.1.
75
GB25972-2005 Gas suppression system and components
Annex J
(Normative)
Select valves test procedures and the sample number
J.1 test procedures
Test procedures shown in Figure J.1.
76
GB25972-2005 Gas suppression system and components
Annex K
(Normative)
Check valve test procedures and the number of samples
K.1 test procedures
Test procedures shown in Figure K.1.
77
GB25972-2005 Gas suppression system and components
Annex L
(Normative)
Manifold test procedures and the number of samples
L.1 test procedures
Test procedures shown in Figure L.1.
78
GB25972-2005 Gas suppression system and components
Annex M
(Normative)
Connected pipe test procedures and the number of samples
M.1 test procedures
Test procedures shown in Figure M.1.
79
GB25972-2005 Gas suppression system and components
Annex N
(Normative)
Safety relief devices and the number of samples testing procedures
N.1 test procedures
Test procedures shown in Figure N.1.
80
GB25972-2005 Gas suppression system and components
Annex P
(Normative)
Drive the number of test procedures and sample
Drive test procedures and the provisions of the sample volume GA61.
81
GB25972-2005 Gas suppression system and components
Annex Q
(Normative)
Control panel testing procedures and the number of samples
Q.1 test procedures
Test Procedure Figure Q.1.
82
GB25972-2005 Gas suppression system and components
Annex R
(Normative)
Weighing device testing procedures and the number of samples
R.1 test procedures
Test Procedure Figure R.1.
83
GB25972-2005 Gas suppression system and components
Annex S
(Normative)
Pressure monitor testing procedures and the number of sample
S.1 test procedures
Test procedures shown in Figure S.1.
84
GB25972-2005 Gas suppression system and components
Annex T
(Normative)
Level measurement device test procedures and the number of sample
T.1 Test Procedure
Test Procedure Figure T.1.
85
GB25972-2005 Gas suppression system and components
Annex U
(Normative)
Signal feedback device testing procedures and the number of samples
U.1 test procedures
Test Procedure Figure U.1.
86
GB25972-2005 Gas suppression system and components
Annex V
(Normative)
pipeline, accessory testing procedures and the number of samples
V.1 test procedures
Test procedures shown in Figure V.1.
87
GB25972-2005 Gas suppression system and components
Annex W
(Normative)
Hook, bracket, the test procedures and number of sample
W.1 test procedures
Test Procedure Figure W.1.
88
GB25972-2005 Gas suppression system and components
Annex Y
(Normative)
Pressure reducer device test procedures and the number of samples
Y.1 test procedures
Test Procedure Figure Y.1.
89
GB25972-2005 Gas suppression system and components
Annex Z
(Normative)
low venting high close test procedures and the number of samples
Z.1 test procedures
Test Procedure Figure Z.1.
90