You are on page 1of 16

§ 3174.1 43 CFR Ch.

II (10–1–17 Edition)

Subpart 3174—Measurement of conditions where a series of meter fac-


Oil tors have been determined over a range
of normal operating conditions.
SOURCE: 81 FR 81504, Nov. 17, 2016, unless
Event log means an electronic record
otherwise noted. of all exceptions and changes to the
flow parameters contained within the
§ 3174.1 Definitions and acronyms. configuration log that occur and have
(a) As used in this subpart, the term: an impact on a quantity transaction
Barrel (bbl) means 42 standard United record.
States gallons. Gross standard volume means a vol-
Base pressure means 14.696 pounds per ume of oil corrected to base pressure
square inch, absolute (psia). and temperature.
Base temperature means 60 °F. Indicated volume means the uncor-
Certificate of calibration means a docu- rected volume indicated by the meter
ment stating the base prover volume in a lease automatic custody transfer
and other physical data required for system or the Coriolis meter in a CMS.
the calibration of flow meters. For a positive displacement meter, the
Composite meter factor means a meter indicated volume is represented by the
factor corrected from normal operating non-resettable totalizer on the meter
pressure to base pressure. The com- head. For Coriolis meters, the indi-
posite meter factor is determined by cated volume is the uncorrected (with-
proving operations where the pressure out the meter factor) mass of liquid di-
is considered constant during the vided by the density.
measurement period between provings. Innage gauging means the level of a
Configuration log means the list of liquid in a tank measured from the
constant flow parameters, calculation datum plate or tank bottom to the sur-
methods, alarm set points, and other face of the liquid.
values that are programmed into the
Lease automatic custody transfer
flow computer in a CMS.
(LACT) system means a system of com-
Coriolis meter means a device which
by means of the interaction between a ponents designed to provide for the un-
flowing fluid and oscillation of tube(s) attended custody transfer of oil pro-
infers a mass flow rate. The meter also duced from a lease(s), unit PA(s), or
infers the density by measuring the CA(s) to the transporting carrier while
natural frequency of the oscillating providing a proper and accurate means
tubes. The Coriolis meter consists of for determining the net standard vol-
sensors and a transmitter, which con- ume and quality, and fail-safe and tam-
vert the output from the sensors to sig- per-proof operations.
nals representing volume and density. Master meter prover means a positive
Coriolis measurement system (CMS) displacement meter or Coriolis meter
means a metering system using a Cor- that is selected, maintained, and oper-
iolis meter in conjunction with a ter- ated to serve as the reference device
tiary device, pressure transducer, and for the proving of another meter. A
temperature transducer in order to de- comparison of the master meter to the
rive and report gross standard oil vol- Facility Measurement Point (FMP)
ume. A CMS system provides real-time, line meter output is the basis of the
on-line measurement of oil. master-meter method.
Displacement prover means a prover Meter factor means a ratio obtained
consisting of a pipe or pipes with by dividing the measured volume of
known capacities, a displacement de- liquid that passed through a prover or
vice, and detector switches, which master meter during the proving by
sense when the displacement device has the measured volume of liquid that
reached the beginning and ending passed through the line meter during
points of the calibrated section of pipe. the proving, corrected to base pressure
Displacement provers can be portable and temperature.
pmangrum on DSK3GDR082PROD with CFR

or fixed. Net standard volume means the gross


Dynamic meter factor means a kinetic standard volume corrected for quan-
meter factor derived by linear inter- tities of non-merchantable substances
polation or polynomial fit, used for such as sediment and water.

534

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00544 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
Bureau of Land Management, Interior § 3174.2

Outage gauging means the distance § 3174.2 General requirements.


from the surface of the liquid in a tank
(a) Oil may be stored only in tanks
to the reference gauge point of the
that meet the requirements of
tank.
§ 3174.5(b) of this subpart.
Positive displacement meter means a
meter that registers the volume pass- (b) Oil must be measured on the
ing through the meter using a system lease, unit PA, or CA, unless approval
which constantly and mechanically for off-lease measurement is obtained
isolates the flowing liquid into seg- under §§ 3173.22 and 3173.23 of this part.
ments of known volume. (c) Oil produced from a lease, unit
Quantity transaction record (QTR) PA, or CA may not be commingled
means a report generated by CMS with production from other leases, unit
equipment that summarizes the daily PAs, or CAs or non-Federal properties
and hourly gross standard volume cal- before the point of royalty measure-
culated by the flow computer and the ment, unless prior approval is obtained
average or totals of the dynamic data under §§ 3173.14 and 3173.15 of this part.
that is used in the calculation of gross (d) An operator must obtain a BLM-
standard volume. approved FMP number under §§ 3173.12
Tertiary device means, for a CMS, the and 3173.13 of this part for each oil
flow computer and associated memory, measurement facility where the meas-
calculation, and display functions. urement affects the calculation of the
Transducer means an electronic de- volume or quality of production on
vice that converts a physical property, which royalty is owed (i.e., oil tank
such as pressure, temperature, or elec- used for tank gauging, LACT system,
trical resistance, into an electrical CMS, or other approved metering de-
output signal that varies proportion- vice), except as provided in paragraph
ally with the magnitude of the physical (h) of this section.
property. Typical output signals are in (e) Except as provided in paragraph
the form of electrical potential (volts), (h) of this section, all equipment used
current (milliamps), or digital pressure to measure the volume of oil for roy-
or temperature readings. The term alty purposes installed after January
transducer includes devices commonly 17, 2017 must comply with the require-
referred to as transmitters. ments of this subpart.
Vapor tight means capable of holding (f) Except as provided in paragraph
pressure differential only slightly high- (h) of this section, measuring proce-
er than that of installed pressure-re- dures and equipment used to measure
lieving or vapor recovery devices. oil for royalty purposes, that is in use
(b) As used in this subpart, the fol- on January 17, 2017, must comply with
lowing acronyms carry the meaning the requirements of this subpart on or
prescribed: before the date the operator is required
API means American Petroleum In- to apply for an FMP number under
stitute. 3173.12(e) of this part. Prior to that
CA has the meaning set forth in date, measuring procedures and equip-
§ 3170.3 of this part. ment used to measure oil for royalty
COA has the meaning set forth in purposes, that is in use on January 17,
§ 3170.3 of this part. 2017 must continue to comply with the
CPL means correction for the effect requirements of Onshore Oil and Gas
of pressure on a liquid. Order No. 4, Measurement of oil,
CTL means correction for the effect § 3164.1(b) as contained in 43 CFR part
of temperature on a liquid. 3160, (revised October 1, 2016), and any
NIST means National Institute of COAs and written orders applicable to
Standards and Technology. that equipment.
PA has the meaning set forth in (g) The requirement to follow the ap-
§ 3170.3 of this part. proved equipment lists identified in
PMT means Production Measurement §§ 3174.6(b)(5)(ii)(A), 3174.6(b)(5)(iii),
pmangrum on DSK3GDR082PROD with CFR

Team. 3174.8(a)(1), and 3174.9(a) does not apply


PSIA means pounds per square inch, until January 17, 2019. The operator or
absolute. manufacturer must obtain approval of
S&W means sediment and water. a particular make, model, and size by

535

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00545 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
§ 3174.3 43 CFR Ch. II (10–1–17 Edition)

submitting the test data used to de- ary 2013 (‘‘API 2.2B’’), IBR approved for
velop performance specifications to the § 3174.5(c).
PMT to review. (3) API MPMS Chapter 2—Tank Cali-
(h) Meters used for allocation under a bration, Section 2C, Calibration of Up-
commingling and allocation approval right Cylindrical Tanks Using the Opti-
under § 3173.14 are not required to meet cal-triangulation Method; First Edi-
the requirements of this subpart. tion, January 2002; Reaffirmed May
2008 (‘‘API 2.2C’’), IBR approved for
§ 3174.3 Incorporation by reference § 3174.5(c).
(IBR).
(4) API MPMS Chapter 3, Section 1A,
(a) Certain material specified in this Standard Practice for the Manual
section is incorporated by reference Gauging of Petroleum and Petroleum
into this part with the approval of the Products; Third Edition, August 2013
Director of the Federal Register under (‘‘API 3.1A’’), IBR approved for
5 U.S.C. 552(a) and 1 CFR part 51. Oper- §§ 3174.5(b), 3174.6(b).
ators must comply with all incor- (5) API MPMS Chapter 3—Tank
porated standards and material, as
Gauging, Section 1B, Standard Prac-
they are listed in this section. To en-
tice for Level Measurement of Liquid
force any edition other than that speci-
Hydrocarbons in Stationary Tanks by
fied in this section, the BLM must pub-
Automatic Tank Gauging; Second Edi-
lish a rule in the FEDERAL REGISTER,
and the material must be reasonably tion, June 2001; Reaffirmed August 2011
available to the public. All approved (‘‘API 3.1B’’), IBR approved for
material is available for inspection at § 3174.6(b).
the Bureau of Land Management, Divi- (6) API MPMS Chapter 3—Tank
sion of Fluid Minerals, 20 M Street SE., Gauging, Section 6, Measurement of
Washington, DC 20003, 202–912–7162; at Liquid Hydrocarbons by Hybrid Tank
all BLM offices with jurisdiction over Measurement Systems; First Edition,
oil and gas activities; and is available February 2001; Errata September 2005;
from the sources listed below. It is also Reaffirmed October 2011 (‘‘API 3.6’’),
available for inspection at the National IBR approved for § 3174.6(b).
Archives and Records Administration (7) API MPMS Chapter 4—Proving
(NARA). For information on the avail- Systems, Section 1, Introduction;
ability of this material at NARA, call Third Edition, February 2005; Re-
202–741–6030 or go to http:// affirmed June 2014 (‘‘API 4.1’’), IBR ap-
www.archives.gov/federallregister/ proved for § 3174.11(c).
codeloflfederallregulations/ (8) API MPMS Chapter 4—Proving
ibrllocations.html. Systems, Section 2, Displacement
(b) American Petroleum Institute Provers; Third Edition, September 2003;
(API), 1220 L Street NW., Washington, Reaffirmed March 2011, Addendum Feb-
DC 20005; telephone 202–682–8000; API ruary 2015 (‘‘API 4.2’’), IBR approved
also offers free, read-only access to for §§ 3174.11(b) and (c).
some of the material at http://publica- (9) API MPMS Chapter 4, Section 5,
tions.api.org. Master-Meter Provers; Fourth Edition,
(1) API Manual of Petroleum Meas- June 2016, (‘‘API 4.5’’), IBR approved
urement Standards (MPMS) Chapter for § 3174.11(b).
2—Tank Calibration, Section 2A, Meas-
(10) API MPMS Chapter 4—Proving
urement and Calibration of Upright Cy-
Systems, Section 6, Pulse Interpola-
lindrical Tanks by the Manual Tank
tion; Second Edition, May 1999; Errata
Strapping Method; First Edition, Feb-
ruary 1995; Reaffirmed February 2012 April 2007; Reaffirmed October 2013
(‘‘API 2.2A’’), IBR approved for (‘‘API 4.6’’), IBR approved for
§ 3174.5(c). § 3174.11(c).
(2) API MPMS Chapter 2—Tank Cali- (11) API MPMS Chapter 4, Section 8,
Operation of Proving Systems; Second
pmangrum on DSK3GDR082PROD with CFR

bration, Section 2.2B, Calibration of


Upright Cylindrical Tanks Using the Edition, September 2013 (‘‘API 4.8’’),
Optical Reference Line Method; First IBR approved for § 3174.11(b).
Edition, March 1989, Reaffirmed Janu-

536

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00546 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
Bureau of Land Management, Interior § 3174.3

(12) API MPMS Chapter 4—Proving (21) API MPMS Chapter 9, Section 2,
Systems, Section 9, Methods of Cali- Standard Test Method for Density or
bration for Displacement and Volu- Relative Density of Light Hydro-
metric Tank Provers, Part 2, Deter- carbons by Pressure Hydrometer; Third
mination of the Volume of Displace- Edition, December 2012 (‘‘API 9.2’’),
ment and Tank Provers by the IBR approved for §§ 3174.6(b), 3174.8(b).
Waterdraw Method of Calibration; (22) API MPMS Chapter 9, Section 3,
First Edition, December 2005; Re- Standard Test Method for Density, Rel-
affirmed July 2015 (‘‘API 4.9.2’’), IBR ative Density, and API Gravity of
approved for § 3174.11(b). Crude Petroleum and Liquid Petroleum
(13) API MPMS Chapter 5—Metering, Products by Thermohydrometer Meth-
Section 6, Measurement of Liquid Hy- od; Third Edition, December 2012 (‘‘API
drocarbons by Coriolis Meters; First 9.3’’), IBR approved for §§ 3174.6(b),
Edition, October 2002; Reaffirmed No- 3174.8(b).
vember 2013 (‘‘API 5.6’’), IBR approved (23) API MPMS Chapter 10, Section 4,
for §§ 3174.9(e), 3174.11(h) and (i). Determination of Water and/or Sedi-
(14) API MPMS Chapter 6—Metering ment in Crude Oil by the Centrifuge
Assemblies, Section 1, Lease Auto- Method (Field Procedure); Fourth Edi-
matic Custody Transfer (LACT) Sys- tion, October 2013; Errata March 2015
tems; Second Edition, May 1991; Re- (‘‘API 10.4’’), IBR approved for
affirmed May 2012 (‘‘API 6.1’’), IBR ap- §§ 3174.6(b), 3174.8(b).
proved for § 3174.8(a) and (b). (24) API MPMS Chapter 11—Physical
(15) API MPMS Chapter 7, Tempera- Properties Data, Section 1, Tempera-
ture Determination; First Edition, ture and Pressure Volume Correction
June 2001, Reaffirmed February 2012 Factors for Generalized Crude Oils, Re-
(‘‘API 7’’), IBR approved for §§ 3174.6(b), fined Products and Lubricating Oils;
3174.8(b). May 2004, Addendum 1 September 2007;
(16) API MPMS Chapter 7.3, Tempera- Reaffirmed August 2012 (‘‘API 11.1’’),
ture Determination—Fixed Automatic IBR approved for §§ 3174.9(f), 3174.12(a).
Tank Temperature Systems; Second (25) API MPMS Chapter 12—Calcula-
Edition, October 2011 (‘‘API 7.3’’), IBR tion of Petroleum Quantities, Section
approved for § 3174.6(b). 2, Calculation of Petroleum Quantities
(17) API MPMS Chapter 8, Section 1, Using Dynamic Measurement Methods
Standard Practice for Manual Sam- and Volumetric Correction Factors,
pling of Petroleum and Petroleum Part 1, Introduction; Second Edition,
Products; Fourth Edition, October 2013 May 1995; Reaffirmed March 2014 (‘‘API
(‘‘API 8.1’’), IBR approved for 12.2.1’’), IBR approved for §§ 3174.8(b),
§§ 3174.6(b), 3174.11(h). 3174.9(g).
(18) API MPMS Chapter 8, Section 2, (26) API MPMS Chapter 12—Calcula-
Standard Practice for Automatic Sam- tion of Petroleum Quantities, Section
pling of Petroleum and Petroleum 2, Calculation of Petroleum Quantities
Products; Third Edition, October 2015 Using Dynamic Measurement Methods
(‘‘API 8.2’’), IBR approved for and Volumetric Correction Factors,
§§ 3174.6(b), 3174.8(b), 3174.11(h). Part 2, Measurement Tickets; Third
(19) API MPMS Chapter 8—Sampling, Edition, June 2003; Reaffirmed Sep-
Section 3, Standard Practice for Mix- tember 2010 (‘‘API 12.2.2’’), IBR ap-
ing and Handling of Liquid Samples of proved for §§ 3174.8(b), 3174.9(g).
Petroleum and Petroleum Products; (27) API MPMS Chapter 12—Calcula-
First Edition, October 1995; Errata tion of Petroleum Quantities, Section
March 1996; Reaffirmed, March 2010 2, Calculation of Petroleum Quantities
(‘‘API 8.3’’), IBR approved for Using Dynamic Measurement Methods
§§ 3174.8(b), 3174.11(h). and Volumetric Correction Factors,
(20) API MPMS Chapter 9, Section 1, Part 3, Proving Report; First Edition,
Standard Test Method for Density, Rel- October 1998; Reaffirmed March 2009
ative Density, or API Gravity of Crude (‘‘API 12.2.3’’), IBR approved for
pmangrum on DSK3GDR082PROD with CFR

Petroleum and Liquid Petroleum Prod- § 3174.11(c) and (i).


ucts by Hydrometer Method; Third Edi- (28) API MPMS Chapter 12—Calcula-
tion, December 2012 (‘‘API 9.1’’), IBR tion of Petroleum Quantities, Section
approved for §§ 3174.6(b), 3174.8(b). 2, Calculation of Petroleum Quantities

537

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00547 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
§ 3174.4 43 CFR Ch. II (10–1–17 Edition)

Using Dynamic Measurement Methods NOTE 1 TO § 3174.3(B): You may also be able
and Volumetric Correction Factors, to purchase these standards from the fol-
Part 4, Calculation of Base Prover Vol- lowing resellers: Techstreet, 3916 Ranchero
Drive, Ann Arbor, MI 48108; telephone 734–
umes by the Waterdraw Method; First 780–8000; www.techstreet.com/api/apigate.html;
Edition, December 1997; Reaffirmed IHS Inc., 321 Inverness Drive South, Engle-
March 2009; Errata July 2009 (‘‘API wood, CO 80112; 303–790–0600; www.ihs.com;
12.2.4’’), IBR approved for § 3174.11(b). SAI Global, 610 Winters Avenue, Paramus,
(29) API MPMS Chapter 13—Statis- NJ 07652; telephone 201–986–1131; http://
tical Aspects of Measuring and Sam- infostore.saiglobal.com/store/.
pling, Section 1, Statistical Concepts
§ 3174.4 Specific measurement per-
and Procedures in Measurements; First formance requirements.
Edition, June 1985 Reaffirmed February
2011; Errata July 2013 (‘‘API 13.1’’), IBR (a) Volume measurement uncertainty
approved for § 3174.4(a). levels. (1) The FMP must achieve the
(30) API MPMS Chapter 13, Section 3, following overall uncertainty levels as
Measurement Uncertainty; First Edi- calculated in accordance with statis-
tion, May, 2016 (‘‘API 13.3’’), IBR ap- tical concepts described in API 13.1, the
proved for § 3174.4(a). methodologies in API 13.3, and the
quadrature sum (square root of the
(31) API MPMS Chapter 14, Section 3,
sum of the squares) method described
Orifice Metering of Natural Gas and
in API 14.3.1, Subsection 12.3 (all incor-
Other Related Hydrocarbon Fluids—
porated by reference, see § 3174.3) or
Concentric, Square-edged Orifice Me-
other methods approved under para-
ters, Part 1, General Equations and Un- graph (d):
certainty Guidelines; Fourth Edition,
September 2012; Errata July 2013 (‘‘API TABLE 1 TO § 3174.4—VOLUME MEASUREMENT
14.3.1’’), IBR approved for § 3174.4(a). UNCERTAINTY LEVELS
(32) API MPMS Chapter 18—Custody
The overall
Transfer, Section 1, Measurement Pro- If the averaging period volume
cedures for Crude Oil Gathered From volume (see definition measurement
43 CFR 3170.3) is: uncertainty must be
Small Tanks by Truck; Second Edition, within:
April 1997; Reaffirmed February 2012
(‘‘API 18.1’’), IBR approved for 1. Greater than or equal to 30,000 bbl/ ±0.50 percent.
month.
§ 3174.6(b). 2. Less than 30,000 bbl/month ............ ±1.50 percent.
(33) API MPMS Chapter 18, Section 2,
Custody Transfer of Crude Oil from (2) Only a BLM State Director may
Lease Tanks Using Alternative Meas- grant an exception to the uncertainty
urement Methods, First Edition, July levels prescribed in paragraph (a)(1) of
2016 (‘‘API 18.2’’), IBR approved for this section, and only upon:
§ 3174.6(b). (i) A showing that meeting the re-
(34) API MPMS Chapter 21—Flow quired uncertainly level would involve
Measurement Using Electronic Meter- extraordinary cost or unacceptable ad-
ing Systems, Section 2, Electronic Liq- verse environmental effects; and
uid Volume Measurement Using Posi- (ii) Written concurrence of the PMT,
tive Displacement and Turbine Meters; prepared in coordination with the Dep-
First Edition, June 1998; Reaffirmed uty Director.
August 2011 (‘‘API 21.2’’), IBR approved (b) Bias. The measuring equipment
for §§ 3174.8(b), 3174.9(f), 3174.10(f). used for volume determinations must
(35) API Recommended Practice (RP) achieve measurement without statis-
12R1, Setting, Maintenance, Inspection, tically significant bias.
Operation and Repair of Tanks in Pro- (c) Verifiability. All FMP equipment
duction Service; Fifth Edition, August must be susceptible to independent
1997; Reaffirmed April 2008 (‘‘API RP verification by the BLM of the accu-
12R1’’), IBR approved for § 3174.5(b). racy and validity of all inputs, factors,
(36) API RP 2556, Correction Gauge and equations that are used to deter-
pmangrum on DSK3GDR082PROD with CFR

Tables For Incrustation; Second Edi- mine quantity or quality. Verifiability


tion, August 1993; Reaffirmed Novem- includes the ability to independently
ber 2013 (‘‘API RP 2556’’), IBR approved recalculate volume and quality based
for § 3174.5(c). on source records.

538

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00548 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
Bureau of Land Management, Interior § 3174.6

(d) Alternative equipment. The PMT and be maintained in a legible condi-


will make a determination under tion.
§ 3174.13 of this subpart regarding (c) Sales tank calibrations. The oper-
whether proposed alternative equip- ator must accurately calibrate each oil
ment or measurement procedures meet storage tank associated with an ap-
or exceed the objectives and intent of proved FMP that has a tank-gauging
this section. system using either API 2.2A, API 2.2B,
or API 2.2C; and API RP 2556 (all incor-
§ 3174.5 Oil measurement by tank porated by reference, see § 3174.3). The
gauging—general requirements. operator must:
(a) Measurement objective. Oil meas- (1) Determine sales tank capacities
urement by tank gauging must accu- by tank calibration using actual tank
rately compute the total net standard measurements;
volume of oil withdrawn from a prop- (i) The unit volume must be in bar-
erly calibrated sales tank by following rels (bbl); and
the activities prescribed in § 3174.6 and (ii) The incremental height measure-
the requirements of § 3174.4 of this sub- ment must match gauging increments
part to determine the quantity and specified in § 3174.6(b)(5)(i)(C);
quality of oil being removed. (2) Recalibrate a sales tank if it is re-
(b) Oil tank equipment. (1) Each tank located or repaired, or the capacity is
used for oil storage must comply with changed as a result of denting, damage,
the recommended practices listed in installation, removal of interior com-
API RP 12R1 (incorporated by ref- ponents, or other alterations; and
erence, see § 3174.3). (3) Submit sales tank calibration
(2) Each oil storage tank must be charts (tank tables) to the AO within
connected, maintained, and operated in 45 days after calibration. Tank tables
compliance with §§ 3173.2, 3173.6, and may be in paper or electronic format.
3173.7 of this part.
(3) All oil storage tanks, hatches, § 3174.6 Oil measurement by tank
connections, and other access points gauging—procedures.
must be vapor tight. Unless connected (a) The procedures for oil measure-
to a vapor recovery or flare system, all ment by tank gauging must comply
tanks must have a pressure-vacuum re- with the requirements outlined in this
lief valve installed at the highest point section.
in the vent line or connection with an- (b) The operator must follow the pro-
other tank. All hatches, connections, cedures identified in API 18.1 or API
and other access points must be in- 18.2 (both incorporated by reference,
stalled and maintained in accordance see § 3174.3) as further specified in this
with manufacturers’ specifications. paragraph to determine the quality and
(4) All oil storage tanks must be quantity of oil measured under field
clearly identified and have an oper- conditions at an FMP.
ator-generated number unique to the (1) Isolate tank. Isolate the tank for
lease, unit PA, or CA, stenciled on the at least 30 minutes to allow contents to
tank and maintained in a legible condi- settle before proceeding with tank
tion. gauging operations. The tank isolating
(5) Each oil storage tank associated valves must be closed and sealed under
with an approved FMP that has a tank- § 3173.2 of this part.
gauging system must be set and main- (2) Determine opening oil temperature.
tained level. Determination of the temperature of
(6) Each oil storage tank associated oil contained in a sales tank must com-
with an approved FMP that has a tank- ply with paragraphs (b)(2)(i) through
gauging system must be equipped with (iii) of this section, API 7, and API 7.3
a distinct gauging reference point, con- (both incorporated by reference, see
sistent with API 3.1A (incorporated by § 3174.3). Opening temperature may be
determined before, during, or after
pmangrum on DSK3GDR082PROD with CFR

reference, see § 3174.3). The height of


the reference point must be stamped on sampling.
a fixed bench-mark plate or stenciled (i) Glass thermometers must be
on the tank near the gauging hatch, clean, be free of fluid separation, have

539

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00549 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
§ 3174.6 43 CFR Ch. II (10–1–17 Edition)

a minimum graduation of 1.0 °F, and (A) The proper bob must be used for
have an accuracy of ±0.5 °F. the particular measurement method,
(ii) Electronic thermometers must i.e., either innage gauging or outage
have a minimum graduation of 0.1 °F gauging;
and have an accuracy of ±0.5 °F. (B) A gauging tape must be used. The
(iii) Record the temperature to the gauging tape must be made of steel or
nearest 1.0 °F for glass thermometers corrosion-resistant material with grad-
or 0.1 °F for portable electronic ther- uation clearly legible, and must not be
mometers. kinked or spliced;
(3) Take oil samples. Sampling oper- (C) Either obtain two consecutive
ations must be conducted prior to tak- identical gauging measurements for
ing the opening gauge unless auto- any tank regardless of size, or:
matic sampling methods are being (1) For tanks of 1,000 bbl or less in ca-
used. Sampling of oil removed from an pacity, three consecutive measure-
FMP tank must yield a representative ments that are within 1/4-inch of each
sample of the oil and its physical prop- other and average these three measure-
erties and must comply with API 8.1 or ments to the nearest 1⁄4 inch; or
API 8.2 (both incorporated by ref- (2) For tanks greater than 1,000 bbl in
erence, see § 3174.3). capacity, three consecutive measure-
(4) Determine observed oil gravity. ments within 1⁄8 inch of each other,
Tests for oil gravity must comply with averaging these three measurements to
paragraphs (b)(4)(i) through (iii) of this the nearest 1⁄8 inch.
section and API 9.1, API 9.2, or API 9.3 (D) A suitable product-indicating
(all incorporated by reference, see paste may be used on the tape to facili-
§ 3174.3). tate the reading. The use of chalk or
(i) The hydrometer or talcum powder is prohibited; and
thermohydrometer (as applicable) (E) The same tape and bob must be
must be calibrated for an oil gravity used for both opening and closing
range that includes the observed grav- gauges.
ity of the oil sample being tested and (ii) For automatic tank gauging
must be clean, with a clearly legible oil (ATG), comply with the requirements
gravity scale and with no loose shot of API 3.1B, API 3.6, and API 18.2 (all
weights. incorporated by reference, see § 3174.3)
(ii) Allow the temperature to sta- and the following:
bilize for at least 5 minutes prior to (A) The specific makes and models of
reading the thermometer. ATG that are identified and described
(iii) Read and record the observed at www.blm.gov are approved for use;
API oil gravity to the nearest 0.1 de- (B) The ATG must be inspected and
gree. Read and record the temperature its accuracy verified to within ±1⁄4 inch
reading to the nearest 1.0 °F. in accordance with API 3.1B, Sub-
(5) Measure the opening tank fluid section 9 (incorporated by reference,
level. Take and record the opening see § 3174.3) at least once a month or
gauge only after samples have been prior to sales, whichever is latest, or
taken, unless automatic sampling any time at the request of the AO. If
methods are being used. Gauging must the ATG is found to be out of toler-
comply with either paragraph (b)(5)(i) ance, the ATG must be calibrated prior
of this section, API 3.1A, and API 18.1 to sales; and
(both incorporated by reference, see (C) A log of field verifications must
§ 3174.3); or paragraph (b)(5)(ii) of this be maintained and available upon re-
section, API 3.1B, API 3.6, and API 18.2 quest. The log must include the fol-
(all incorporated by reference, see lowing information: The date of
§ 3174.3); or paragraph (b)(5)(iii) of this verification; the as-found manual
section for dynamic volume determina- gauge readings; the as-found ATG read-
tion. ings; and whether the ATG was field
pmangrum on DSK3GDR082PROD with CFR

(i) For manual gauging, comply with calibrated. If the ATG was field cali-
the requirements of API 3.1A and API brated, the as-left manual gauge read-
18.1 (both incorporated by reference, ings and as-left ATG readings must be
see § 3174.3) and the following: recorded.

540

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00550 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
Bureau of Land Management, Interior § 3174.8

(iii) For dynamic volume determina- (g) Automatic temperature com-


tion under API 18.2, Subsection 10.1.1, pensators and automatic temperature
(incorporated by reference, see § 3174.3), and gravity compensators are prohib-
the specific makes and models of in- ited.
line meters that are identified and de-
scribed at www.blm.gov are approved § 3174.8 LACT system—components
for use. and operating requirements.
(6) Determine S&W content. Using the (a) LACT system components. Each
oil samples obtained pursuant to para- LACT system must include all of the
graph (b)(3) of this section, determine equipment listed in API 6.1 (incor-
the S&W content of the oil in the sales porated by reference, see § 3174.3), with
tanks, according to API 10.4 (incor- the following exceptions:
porated by reference, see § 3174.3). (1) The custody transfer meter must
(7) Transfer oil. Break the tank load be a positive displacement meter or a
line valve seal and transfer oil to the Coriolis meter. The specific make,
tanker truck. After transfer is com- models, and sizes of positive displace-
plete, close the tank valve and seal the ment or Coriolis meter and associated
valve under §§ 3173.2 and 3173.5 of this software that are identified and de-
part. scribed at www.blm.gov are approved
(8) Determine closing oil temperature. for use.
Determine the closing oil temperature (2) An electronic temperature aver-
using the procedures in paragraph aging device must be installed.
(b)(2) of this section. (3) Meter back pressure must be ap-
(9) Take closing gauge. Take the clos- plied by a back pressure valve or other
ing tank gauge using the procedures in controllable means of applying back
paragraph (b)(5) of this section. pressure to ensure single-phase flow.
(10) Complete measurement ticket. Fol-
(b) LACT system operating require-
lowing procedures in § 3174.12.
ments. Operation of all LACT system
§ 3174.7 LACT system—general re- components must meet the require-
quirements. ments of API 6.1 (incorporated by ref-
erence, see § 3174.3) and the following:
(a) A LACT system must meet the
(1) Sampling must be conducted ac-
construction and operation require-
cording to API 8.2 and API 8.3 (both in-
ments and minimum standards of this
corporated by reference, see § 3174.3)
section, § 3174.8, and § 3174.4.
and the following:
(b) A LACT system must be proven as
prescribed in § 3174.11 of this subpart. (i) The sample extractor probe must
(c) Measurement tickets must be be inserted within the center half of
completed under § 3174.12(b) of this sub- the flowing stream;
part. (ii) The extractor probe must be hori-
(d) All components of a LACT system zontally oriented; and
must be accessible for inspection by (iii) The external body of the extrac-
the AO. tor probe must be marked with the di-
(e)(1) The operator must notify the rection of the flow.
AO, within 72 hours after discovery, of (2) Any tests conducted on oil sam-
any LACT system failures or equip- ples extracted from LACT system sam-
ment malfunctions that may have re- plers for determination of oil gravity
sulted in measurement error. and S&W content must meet the re-
(2) Such system failures or equip- quirements of either API 9.1, API 9.2,
ment malfunctions include, but are not or API 9.3, and API 10.4 (all incor-
limited to, electrical, meter, and other porated by reference, see § 3174.3).
failures that affect oil measurement. (3) The composite sample container
(f) Any tests conducted on oil sam- must be emptied and cleaned upon
ples extracted from LACT system sam- completion of sample withdrawal.
plers for determination of temperature, (4) The positive displacement or Cor-
pmangrum on DSK3GDR082PROD with CFR

oil gravity, and S&W content must iolis meter (see § 3174.10) must be
meet the requirements and minimum equipped with a non-resettable total-
standards in § 3174.6(b)(2), (4), and (6) of izer. The meter must include or allow
this subpart. for the attachment of a device that

541

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00551 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
§ 3174.9 43 CFR Ch. II (10–1–17 Edition)

generates at least 8,400 pulses per bar- the PMT, as provided in § 3174.13, ap-
rel of registered volume. proved by the BLM, and identified and
(5) The system must have a pressure- described at www.blm.gov are approved
indicating device downstream of the for use.
meter, but upstream of meter-proving (c) A CMS system must be proven at
connections. The pressure-indicating the frequency and under the require-
device must be capable of providing ments of § 3174.11 of this subpart.
pressure data to calculate the CPL cor- (d) Measurement tickets must be
rection factor. completed under § 3174.12(b) of this sub-
(6) An electronic temperature aver-
part.
aging device must be installed, oper-
ated, and maintained as follows: (e) A CMS at an FMP must be in-
(i) The temperature sensor must be stalled with the components listed in
placed in compliance with API 7 (incor- API 5.6 (incorporated by reference, see
porated by reference, see § 3174.3); § 3174.3). Additional requirements are as
(ii) The electronic temperature aver- follows:
aging device must be volume-weighted (1) The pressure transducer must
and take a temperature reading fol- meet the requirements of § 3174.8(b)(5)
lowing API 21.2, Subsection 9.2.8 (incor- of this subpart.
porated by reference, see § 3174.3); (2) Temperature determination must
(iii) The average temperature for the meet the requirements of § 3174.8(b)(6)
measurement ticket must be cal- of this subpart.
culated by the volumetric averaging (3) If nonzero S&W content is to be
method using API 21.2, Subsection used in determining net oil volume, the
9.2.13.2a (incorporated by reference, see sampling system must meet the re-
§ 3174.3); quirements of § 3174.8(b)(1) through (3)
(iv) The temperature averaging de- of this subpart. If no sampling system
vice must have a reference accuracy of is used, or the sampling system does
±0.5 °F or better, and have a minimum not meet the requirements of
graduation of 0.1 °F; and
§ 3174.8(b)(1) through (3) of this subpart,
(v) The temperature averaging device
the S&W content must be reported as
must include a display of instanta-
zero;
neous temperature and the average
temperature calculated since the meas- (4) Sufficient back pressure must be
urement ticket was opened. applied to ensure single phase flow
(vi) The average temperature cal- through the meter.
culated since the measurement ticket (f) Determination of API oil gravity.
was opened must be used to calculate The API oil gravity reported for the
the CTL correction factor. measurement ticket period must be de-
(7) Determination of net standard termined by one of the following meth-
volume: Calculate the net standard vol- ods:
ume at the close of each measurement (1) Determined from a composite
ticket following the guidelines in API sample taken pursuant to § 3174.8(b)(1)
12.2.1 and API 12.2.2 (both incorporated through (3) of this subpart; or
by reference, see § 3174.3). (2) Calculated from the average den-
sity as measured by the CMS over the
§ 3174.9 Coriolis measurement systems
(CMS)—general requirements and measurement ticket period under API
components. 21.2, Subsection 9.2.13.2a (incorporated
by reference, see § 3174.3). Density must
The following Coriolis measurement
be corrected to base temperature and
systems section is intended for Coriolis
measurement applications independent pressure using API 11.1 (incorporated
of LACT measurement systems. by reference, see § 3174.3).
(a) A CMS must meet the require- (g) Determination of net standard vol-
ments and minimum standards of this ume. Calculate the net standard volume
at the close of each measurement tick-
pmangrum on DSK3GDR082PROD with CFR

section, § 3174.4, and § 3174.10.


(b) The specific makes, models, and et following the guidelines in API 12.2.1
sizes of Coriolis meters and associated and API 12.2.2 (both incorporated by
software that have been reviewed by reference, see § 3174.3).

542

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00552 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
Bureau of Land Management, Interior § 3174.10

§ 3174.10 Coriolis meter for LACT and of the zero value verification procedure
CMS measurement applications— must be made available to the AO upon
operating requirements. request.
(a) Minimum electronic pulse level. The (e) Required on-site information. (1)
Coriolis meter must register the vol- The Coriolis meter display must be
ume of oil passing through the meter readable without using data collection
as determined by a system that con- units, laptop computers, or any special
stantly emits electronic pulse signals equipment, and must be on-site and ac-
representing the indicated volume cessible to the AO.
measured. The pulse per unit volume (2) For each Coriolis meter, the fol-
must be set at a minimum of 8,400 lowing values and corresponding units
pulses per barrel. of measurement must be displayed:
(b) Meter specifications. (1) The Cor-
(i) The instantaneous density of liq-
iolis meter specifications must identify
uid (pounds/bbl, pounds/gal, or degrees
the make and model of the Coriolis
meter to which they apply and must API);
include the following: (ii) The instantaneous indicated vol-
(i) The reference accuracy for both umetric flow rate through the meter
mass flow rate and density, stated in (bbl/day);
either percent of reading, percent of (iii) The meter factor;
full scale, or units of measure; (iv) The instantaneous pressure (psi);
(ii) The effect of changes in tempera- (v) The instantaneous temperature (
ture and pressure on both mass flow °F);
and fluid density readings, and the ef- (vi) The cumulative gross standard
fect of flow rate on density readings. volume through the meter (non-reset-
These specifications must be stated in table totalizer) (bbl); and
percent of reading, percent of full (vii) The previous day’s gross stand-
scale, or units of measure over a stated ard volume through the meter (bbl).
amount of change in temperature, pres-
(3) The following information must
sure, or flow rate (e.g., ‘‘±0.1 percent of
reading per 20 psi’’); be correct, be maintained in a legible
(iii) The stability of the zero reading condition, and be accessible to the AO
for volumetric flow rate. The specifica- at the FMP without the use of data
tions must be stated in percent of read- collection equipment, laptop com-
ing, percent of full scale, or units of puters, or any special equipment:
measure; (i) The make, model, and size of each
(iv) Design limits for flow rate and sensor; and
pressure; and (ii) The make, range, calibrated span,
(v) Pressure drop through the meter and model of the pressure and tempera-
as a function of flow rate and fluid vis- ture transducer used to determine
cosity. gross standard volume.
(2) Submission of meter specifica- (4) A log must be maintained of all
tions: The operator must submit Cor- meter factors, zero verifications, and
iolis meter specifications to the BLM zero adjustments. For zero adjust-
upon request. ments, the log must include the zero
(c) Non-resettable totalizer. The Cor-
value before adjustment and the zero
iolis meter must have a non-resettable
value after adjustment. The log must
internal totalizer for indicated volume.
(d) Verification of meter zero value be made available upon request.
using the manufacturer’s specifications. If (f) Audit trail requirements. The infor-
the indicated flow rate is within the mation specified in paragraphs (f)(1)
manufacturer’s specifications for zero through (4) of this section must be re-
stability, no adjustments are required. corded and retained under the record-
If the indicated flow rate is outside the keeping requirements of § 3170.7 of this
manufacturer’s specification for zero part. Audit trail requirements must
follow API 21.2, Subsection 10 (incor-
pmangrum on DSK3GDR082PROD with CFR

stability, the meter’s zero reading


must be adjusted. After the meter’s porated by reference, see § 3174.3). All
zero has been adjusted, the meter must data must be available and submitted
be proven required by § 3174.11. A copy to the BLM upon request.

543

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00553 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
§ 3174.11 43 CFR Ch. II (10–1–17 Edition)

(1) Quantity transaction record (QTR). mined by a minimum of five consecu-


Follow the requirements for a measure- tive prover runs within 0.0005 (0.05 per-
ment ticket in § 3174.12(b) of this sub- cent repeatability) as described in API
part. 4.5, Subsection 6.5 (incorporated by ref-
(2) Configuration log. The configura- erence, see § 3174.3). The master meter
tion log must comply with the require- must not be mechanically compensated
ments of API 21.2, Subsection 10.2 (in- for oil gravity or temperature; its read-
corporated by reference, see § 3174.3). out must indicate units of volume
The configuration log must contain without corrections. The meter factor
and identify all constant flow param- must be documented on the calibration
eters used in generating the QTR. certificate and must be calibrated at
(3) Event log. The event log must least once every 12 months. New mas-
comply with the requirements of API ter meters must be calibrated imme-
21.2, Subsection 10.6 (incorporated by diately and recalibrated in three
reference, see § 3174.3). In addition, the months. Master meters that have un-
event log must be of sufficient capacity dergone mechanical repairs, alter-
to record all events such that the oper- ations, or changes that affect the cali-
ator can retain the information under bration must be calibrated imme-
the recordkeeping requirements of diately upon completion of this work
§ 3170.7 of this part. and calibrated again 3 months after
(4) Alarm log The type and duration of this date under API 4.5, API 4.8, Sub-
any of the following alarm conditions section 10.2, and API 4.8, Annex B (all
must be recorded: incorporated by reference, see § 3174.3).
(i) Density deviations from accept- (2) Displacement provers must meet
able parameters; and the requirements of API 4.2 (incor-
(ii) Instances in which the flow rate porated by reference, see § 3174.3) and
exceeded the manufacturer’s maximum be calibrated using the water-draw
recommended flow rate or was below method under API 4.9.2 (incorporated
the manufacturer’s minimum rec- by reference, see § 3174.3), at the cali-
ommended flow rate.
bration frequencies specified in API 4.8,
(g) Data protection. Each Coriolis
Subsection 10.1(b) (incorporated by ref-
meter must have installed and main-
erence, see § 3174.3).
tained in an operable condition a
backup power supply or a nonvolatile (3) The base prover volume of a dis-
memory capable of retaining all data placement prover must be calculated
in the unit’s memory to ensure that under API 12.2.4 (incorporated by ref-
the audit trail information required erence, see § 3174.3).
under paragraph (f) of this section is (4) Displacement provers must be
protected. sized to obtain a displacer velocity
through the prover that is within the
§ 3174.11 Meter-proving requirements. appropriate range during proving under
(a) Applicability. This section speci- API 4.2, Subsection 4.3.4.2, Minimum
fies the minimum requirements for Displacer Velocities and API 4.2, Sub-
conducting volumetric meter proving section 4.3.4.1, Maximum Displacer Ve-
for all FMP meters. locities (incorporated by reference, see
(b) Meter prover. Acceptable provers § 3174.3).
are positive displacement master me- (5) Fluid velocity is calculated using
ters, Coriolis master meters, and dis- API 4.2, Subsection 4.3.4.3, Equation 12
placement provers. The operator must (incorporated by reference, see § 3174.3).
ensure that the meter prover used to (c) Meter proving runs. Meter proving
determine the meter factor has a valid must follow the applicable section(s) of
certificate of calibration on site and API 4.1, Proving Systems (incorporated
available for review by the AO. The by reference, see § 3174.3).
certificate must show that the prover, (1) Meter proving must be performed
identified by serial number assigned to under normal operating fluid pressure,
fluid temperature, and fluid type and
pmangrum on DSK3GDR082PROD with CFR

and inscribed on the prover, was cali-


brated as follows: composition, as follows:
(1) Master meters must have a meter (i) The oil flow rate through the
factor within 0.9900 to 1.0100 deter- LACT or CMS during proving must be

544

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00554 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
Bureau of Land Management, Interior § 3174.11

within 10 percent of the normal flow that range as the arithmetic average of
rate; all the meter factors within that range.
(ii) The absolute pressure as meas- The full range of normal operating con-
ured by the LACT or CMS during prov- ditions may be divided into segments
ing must be within 10 percent of the such that all the meter factors within
normal operating absolute pressure; each segment fall within a range of
(iii) The temperature as measured by 0.0020. In this case, a single meter fac-
the LACT or CMS during the proving tor for each segment may be calculated
must be within 10 °F of the normal op- as the arithmetic average of the meter
erating temperature; and factors within that segment; or
(iv) The gravity of the oil during (ii) The metering system may apply a
proving must be within 5° API of the dynamic meter factor derived (using,
normal oil gravity. e.g., linear interpolation, polynomial
(v) If the normal flow rate, pressure, fit, etc.) from the series of meter fac-
temperature, or oil gravity vary by tors determined over the range of nor-
more than the limits defined in para- mal operating conditions, so long as no
graphs (c)(i) through (c)(iv) of this sec- two neighboring meter factors differ by
tion, meter provings must be con- more than 0.0020.
ducted, at a minimum, under the three (7) The meter factor must be at least
following conditions: At the lower 0.9900 and no more than 1.0100.
limit of normal operating conditions, (8) The initial meter factor for a new
at the upper limit of normal operation or repaired meter must be at least
conditions, and at the midpoint of nor- 0.9950 and no more than 1.0050.
mal operating conditions. (9) For positive displacement meters,
(2) If each proving run is not of suffi- the back pressure valve may be ad-
cient volume to generate at least 10,000 justed after proving only within the
pulses, as specified by API 4.2, Sub- normal operating fluid flow rate and
section 4.3.2 (incorporated by reference, fluid pressure as described in paragraph
see § 3174.3), from the positive displace- (c)(1) of this section. If the back pres-
ment meter or the Coriolis meter, then sure valve is adjusted after proving,
pulse interpolation must be used in ac- the operator must document the as left
cordance with API 4.6 (incorporated by fluid flow rate and fluid pressure on the
reference, see § 3174.3). proving report.
(3) Proving runs must be made until (10) If a composite meter factor is
the calculated meter factor or meter calculated, the CPL value must be cal-
generated pulses from five consecutive culated from the pressure setting of
runs match within a tolerance of 0.0005 the back pressure valve or the normal
(0.05 percent) between the highest and operating pressure at the meter. Com-
the lowest value in accordance with posite meter factors must not be used
API 12.2.3, Subsection 9 (incorporated with a Coriolis meter.
by reference, see § 3174.3). (d) Minimum proving frequency. The
(4) The new meter factor is the arith- operator must prove any FMP meter
metic average of the meter generated before removal or sales of production
pulses or intermediate meter factors after any of the following events:
calculated from the five consecutive (1) Initial meter installation;
runs in accordance with API 12.2.3, (2) Every 3 months (quarterly) after
Subsection 9 (incorporated by ref- the last proving, or each time the reg-
erence, see § 3174.3). istered volume flowing through the
(5) Meter factor computations must meter, as measured on the non-reset-
follow the sequence described in API table totalizer from the last proving,
12.2.3 (incorporated by reference, see increases by 75,000 bbl, whichever
§ 3174.3). comes first, but no more frequently
(6) If multiple meters factors are de- than monthly;
termined over a range of normal oper- (3) Meter zeroing (Coriolis meter);
ating conditions, then: (4) Modification of mounting condi-
pmangrum on DSK3GDR082PROD with CFR

(i) If all the meter factors determined tions;


over a range of conditions fall within (5) A change in fluid temperature
0.0020 of each other, then a single that exceeds the transducer’s cali-
meter factor may be calculated for brated span;

545

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00555 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
§ 3174.11 43 CFR Ch. II (10–1–17 Edition)

(6) A change in pressure, density, or (3) The displayed reading of instanta-


flow rate that exceeds the operating neous temperature from the tempera-
proving limits; ture averager or the temperature
(7) The mechanical or electrical com- transducer must be compared with the
ponents of the meter have been reading from the test thermometer. If
changed, repaired, or removed; they differ by more than 0.5 °F, then
(8) Internal calibration factors have the difference in temperatures must be
been changed or reprogrammed; or noted on the meter proving report and:
(9) At the request of the AO. (i) The temperature averager or tem-
(e) Excessive meter factor deviation. (1) perature transducer must be adjusted
If the difference between meter factors to match the reading of the test ther-
established in two successive provings mometer; or
exceeds ±0.0025, the meter must be im- (ii) The temperature averager or
mediately removed from service, temperature transducer must be recali-
checked for damage or wear, adjusted brated, repaired, or replaced.
or repaired, and reproved before return- (g) Verification of the pressure trans-
ing the meter to service. ducer (if applicable). (1) As part of each
(2) The arithmetic average of the two required meter proving and upon re-
successive meter factors must be ap- placement, the pressure transducer
plied to the production measured must be compared with a test pressure
through the meter between the date of device (dead weight or pressure gauge)
the previous meter proving and the traceable to NIST and with a stated
date of the most recent meter proving. maximum uncertainty of no more than
(3) The proving report submitted one-half of the accuracy required from
under paragraph (i) of this section the transducer being verified.
must clearly show the most recent (2) The pressure reading displayed on
meter factor and describe all subse- the pressure transducer must be com-
quent repairs and adjustments. pared with the reading of the test pres-
(f) Verification of the temperature sure device.
transducer. As part of each required (3) The pressure transducer must be
meter proving and upon replacement, tested at the following three points:
the temperature averager for a LACT (i) Zero (atmospheric pressure);
system and the temperature transducer (ii) 100 percent of the calibrated span
used in conjunction with a CMS must of the pressure transducer; and
be verified against a known standard (iii) A point that represents the nor-
according to the following: mal flowing pressure through the Cor-
(1) The temperature averager or tem- iolis meter.
perature transducer must be compared (4) If the pressure applied by the test
with a test thermometer traceable to pressure device and the pressure dis-
NIST and with a stated accuracy of played on the pressure transducer vary
±0.25 °F or better. by more than the required accuracy of
(2) The temperature reading dis- the pressure transducer, the pressure
played on the temperature averager or transducer must be adjusted to read
temperature transducer must be com- within the stated accuracy of the test
pared with the reading of the test ther- pressure device.
mometer using one of the following (h) Density verification (if applicable).
methods: As part of each required meter proving,
(i) The test thermometer must be if the API gravity of oil is determined
placed in a test thermometer well lo- from the average density measured by
cated not more than 12″ from the probe the Coriolis meter (rather than from a
of the temperature averager or tem- composite sample), then during each
perature transducer; or proving of the Coriolis meter, the in-
(ii) Both the test thermometer and stantaneous flowing density deter-
probe of the temperature averager or mined by the Coriolis meter must be
temperature transducer must be placed verified by comparing it with an inde-
pmangrum on DSK3GDR082PROD with CFR

in an insulated water bath. The water pendent density measurement as speci-


bath temperature must be within 20 °F fied under API 5.6, Subsection 9.1.2.1
of the normal flowing temperature of (incorporated by reference, see § 3174.3).
the oil. The difference between the indicated

546

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00556 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
Bureau of Land Management, Interior § 3174.12

density determined from the Coriolis § 3174.12 Measurement tickets.


meter and the independently deter-
(a) Tank gauging. After oil is meas-
mined density must be within the spec- ured by tank gauging under §§ 3174.5
ified density reference accuracy speci- and 3174.6 of this subpart, the operator,
fication of the Coriolis meter. Sam- purchaser, or transporter, as appro-
pling must be performed in accordance priate, must complete a uniquely num-
with API 8.1, API 8.2, or API 8.3 (incor- bered measurement ticket, in either
porated by reference, see § 3174.3), as paper or electronic format, with the
appropriate. following information:
(i) Meter proving reporting require- (1) Lease, unit PA, or CA number;
ments. (1) The operator must report to (2) Unique tank number and nominal
the AO all meter-proving and volume tank capacity;
adjustments after any LACT system or (3) Opening and closing dates and
CMS malfunction, including excessive times;
meter-factor deviation, using the ap- (4) Opening and closing gauges and
propriate form in either API 12.2.3 or observed temperatures in °F;
API 5.6 (both incorporated by ref- (5) Observed volume for opening and
erence, see § 3174.3), or any similar for- closing gauge, using tank specific cali-
mat showing the same information as bration charts (see § 3174.5(c));
the API form, provided that the cal- (6) Total gross standard volume re-
culation of meter factors maintains the moved from the tank following API 11.1
proper calculation sequence and round- (incorporated by reference, see § 3174.3);
ing. (7) Observed API oil gravity and tem-
(2) In addition to the information re- perature in °F;
quired under paragraph (i)(1) of this (8) API oil gravity at 60 °F, following
section, each meter-proving report API 11.1 (incorporated by reference, see
must also show the: § 3174.3);
(i) Unique meter ID number; (9) S&W content percent;
(ii) Lease number, CA number, or (10) Unique number of each seal re-
unit PA number; moved and installed;
(iii) The temperature from the test (11) Name of the individual per-
thermometer and the temperature forming the tank gauging; and
from the temperature averager or tem- (12) Name of the operator.
perature transducer; (b) LACT system and CMS. (1) At the
(iv) For pressure transducers, the beginning of every month, and, unless
pressure applied by the pressure test the operator is using a flow computer
device and the pressure reading from under § 3174.10, before conducting prov-
the pressure transducer at the three ing operations on a LACT system, the
points required under paragraph (g)(3) operator, purchaser, or transporter, as
appropriate, must complete a uniquely
of this section;
numbered measurement ticket, in ei-
(v) For density verification (if appli- ther paper or electronic format, with
cable), the instantaneous flowing den- the following information:
sity (as determined by Coriolis meter), (i) Lease, unit PA, or CA number;
and the independent density measure- (ii) Unique meter ID number;
ment, as compared under paragraph (h)
(iii) Opening and closing dates;
of this section; and
(iv) Opening and closing totalizer
(vi) The ‘‘as left’’ fluid flow rate and readings of the indicated volume;
fluid pressure, if the back pressure (v) Meter factor, indicating if it is a
valve is adjusted after proving as de- composite meter factor;
scribed in paragraph (c)(9) of this sec- (vi) Total gross standard volume re-
tion. moved through the LACT system or
(3) The operator must submit the CMS;
meter-proving report to the AO no
pmangrum on DSK3GDR082PROD with CFR

(vii) API oil gravity. For API oil


later than 14 days after the meter prov- gravity determined from a composite
ing. The proving report may be either sample, the observed API oil gravity
in a hard copy or electronic format. and temperature must be indicated in

547

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00557 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
§ 3174.13 43 CFR Ch. II (10–1–17 Edition)

°F and the API oil gravity must be in- post the make, model, range or soft-
dicated at 60 °F. For API oil gravity de- ware version (as applicable), or method
termined from average density (CMS on the BLM Web site www.blm.gov as
only), the average uncorrected density being appropriate for use at an FMP
must be determined by the CMS; for oil measurement without further
(viii) The average temperature in °F; approval by the BLM, subject to any
(ix) The average flowing pressure in conditions of approval identified by the
psig; PMT and approved by the BLM.
(x) S&W content percent; (c) The procedures for requesting and
(xi) Unique number of each seal re- granting a variance under § 3170.6 of
moved and installed; this part may not be used as an avenue
(xii) Name of the purchaser’s rep- for approving new technology, meth-
resentative; and ods, or equipment. Approval of alter-
(xiii) Name of the operator. native oil measurement equipment or
(2) Any accumulators used in the de- methods may be obtained only under
termination of average pressure, aver- this section.
age temperature, and average density
must be reset to zero whenever a new § 3174.14 Determination of oil volumes
measurement ticket is opened. by methods other than measure-
ment.
§ 3174.13 Oil measurement by other (a) Under 43 CFR 3162.7–2, when pro-
methods. duction cannot be measured due to
(a) Any method of oil measurement spillage or leakage, the amount of pro-
other than tank gauging, LACT sys- duction must be determined by using
tem, or CMS at an FMP requires prior any method the AO approves or pre-
BLM approval. scribes. This category of production in-
(b)(1) Any operator requesting ap- cludes, but is not limited to, oil that is
proval to use alternate oil measure- classified as slop oil or waste oil.
ment equipment or measurement (b) No oil may be classified or dis-
method must submit to the BLM per- posed of as waste oil unless the oper-
formance data, actual field test results, ator can demonstrate to the satisfac-
laboratory test data, or any other sup- tion of the AO that it is not economi-
porting data or evidence that dem- cally feasible to put the oil into mar-
onstrates that the proposed alternate ketable condition.
oil equipment or method would meet or (c) The operator may not sell or oth-
exceed the objectives of the applicable erwise dispose of slop oil without prior
minimum requirements of this subpart written approval from the AO. Fol-
and would not affect royalty income or lowing the sale or disposal of slop oil,
production accountability. the operator must notify the AO in
(2) The PMT will review the sub- writing of the volume sold or disposed
mitted data to ensure that the alter- of and the method used to compute the
nate oil measurement equipment or volume.
method meets the requirements of this
subpart and will make a recommenda- § 3174.15 Immediate assessments.
tion to the BLM to approve use of the Certain instances of noncompliance
equipment or method, disapprove use warrant the imposition of immediate
of the equipment or method, or approve assessments upon the BLM’s discovery
use of the equipment or method with of the violation, as prescribed in the
conditions for its use. If the PMT rec- following table. Imposition of any of
ommends, and the BLM approves new these assessments does not preclude
equipment or methods, the BLM will other appropriate enforcement actions.
TABLE 1 TO § 3174.15—VIOLATIONS SUBJECT TO AN IMMEDIATE ASSESSMENT
Violations subject to an immediate assessment

Assessment
pmangrum on DSK3GDR082PROD with CFR

Violation: amount per


violation:

1. Missing or nonfunctioning FMP LACT system components as required by § 3174.8 of this subpart ................. $1,000

548

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00558 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198
Bureau of Land Management, Interior § 3175.10

TABLE 1 TO § 3174.15—VIOLATIONS SUBJECT TO AN IMMEDIATE ASSESSMENT—Continued


Violations subject to an immediate assessment

Assessment
Violation: amount per
violation:

2. Failure to notify the AO within 72 hours, as required by § 3174.7(e) of this subpart, of any FMP LACT system
failure or equipment malfunction resulting in use of an unapproved alternate method of measurement ............ 1,000
3. Missing or nonfunctioning FMP CMS components as required by § 3174.9 of this subpart ............................... 1,000
4. Failure to meet the proving frequency requirements for an FMP, detailed in § 3174.11 of this subpart ............ 1,000
5. Failure to obtain a written approval, as required by § 3174.13 of this subpart, before using any oil measure-
ment method other than tank gauging, LACT system, or CMS at a FMP ........................................................... 1,000

Subpart 3175—Measurement of Area ratio means the smallest unre-


Gas stricted area at the primary device di-
vided by the cross-sectional area of the
SOURCE: 81 FR 81609, Nov. 17, 2016, unless
meter tube. For example, the area
otherwise noted. ratio (Ar) of an orifice plate is the area
of the orifice bore (Ad) divided by the
§ 3175.10 Definitions and acronyms. area of the meter tube (AD). For an ori-
(a) As used in this subpart, the term: fice plate with a bore diameter (d) of
AGA Report No. (followed by a number) 1.000 inches in a meter tube with an in-
means a standard prescribed by the side diameter (D) of 2.000 inches the
American Gas Association, with the area ratio is 0.25 and is calculated as
number referring to the specific stand- follows:
ard.

As-found means the reading of a me- Bias means a systematic shift in the
chanical or electronic transducer when mean value of a set of measurements
compared to a certified test device, away from the true value of what is
prior to making any adjustments to being measured.
the transducer. British thermal unit (Btu) means the
As-left means the reading of a me- amount of heat needed to raise the
chanical or electronic transducer when temperature of one pound of water by 1
compared to a certified test device, °F.
after making adjustments to the trans- Component-type electronic gas measure-
ducer, but prior to returning the trans- ment system means an electronic gas
ducer to service. measurement system comprising trans-
Atmospheric pressure means the pres- ducers and a flow computer, each iden-
sure exerted by the weight of the at- tified by a separate make and model,
mosphere at a specific location. from which performance specifications
Beta ratio means the measured di- are obtained.
ameter of the orifice bore divided by
pmangrum on DSK3GDR082PROD with CFR

Configuration log means a list of all


the measured inside diameter of the fixed or user-programmable parameters
meter tube. This is also referred to as used by the flow computer that could
a diameter ratio.

549
ER17NO16.053</GPH>

VerDate Sep<11>2014 15:07 Nov 21, 2017 Jkt 241198 PO 00000 Frm 00559 Fmt 8010 Sfmt 8002 Y:\SGML\241198.XXX 241198

You might also like