Professional Documents
Culture Documents
Structures
AC AC
Power in Resistive Circuit True, Reactive & Apparent Power
Power dissipated by
rms
a load is referred to
as true power.
True power is
symbolized by the
the waveform for power is always positive, never negative letter P and is
for this resistive circuit measured in the
power is always being dissipated by the resistive load, and unit of Watts (W).
never returned to the source as it is with reactive loads
If the source were a mechanical generator, it would take
240 watts worth of mechanical energy (about 1/3
horsepower) to turn the shaft.
AC AC
Power in Reactive Circuit True, Reactive & Apparent Power
Power merely
rms
absorbed and
returned in load due
to its reactive
properties is
power is being alternately absorbed from and returned to referred to as
the source reactive power.
If the source were a mechanical generator, it would take
(practically) no net mechanical energy to turn the shaft,
because no power would be used by the load Reactive power is symbolized by the letter Q and is
The generator shaft would be easy to spin, and the measured in the unit of Volt-Amps-Reactive (VAR).
inductor would not become warm as a resistor would.
AC AC
Power in Resistive &Reactive Circuit True, Reactive & Apparent Power
Total power in an AC
circuit, both
rms
dissipated and
absorbed/returned
is referred to as
apparent power.
there will be more power dissipated by the load(s) than
returned, but some power will definitely be dissipated and
some will merely be absorbed and returned
If the source were a mechanical generator, the amount of
mechanical energy needed to turn the shaft would be the Apparent power is symbolized by the letter S and is measured
amount of power averaged between the positive and in the unit of Volt-Amps (VA).
negative power cycles.
AC AC
True, Reactive & Apparent Power True, Reactive & Apparent Power
These three types of
power are
trigonometrically
related to one rms
another.
AC AC
True, Reactive & Apparent Power True, Reactive & Apparent Power
rms
AC AC
True, Reactive & Apparent Power Power Factor
rms
AC AC
Power Factor Power Factor
AC AC
Power Factor Power Factor Correction
AC AC
Power Factor Power Factor Correction
AC AC
Power Factor Correction Practical Power Factor Correction
To correct power factor to 1.0,
If you have a wattmeter for measuring true power, whose
reading you can compare against a calculation of apparent
power (from multiplying total voltage and total current
measurements), you can determine reactive power and
power factor.
AC AC
Power Factor Correction Practical Power Factor Correction
rms
AC AC
Practical Power Factor Correction Practical Power Factor Correction
AC AC
Practical Power Factor Correction Power Factor Correction
Addition of capacitors for power factor improvement must
be based on an economic analysis of the particular
situation. The rate of return upon capacitor investment will
depend both on the structure of the power factor clause
and the present power factor.
AC AC
Practical Power Factor Correction Power Factor Correction
Assume your power company has a power factor charge
that increases the rate per kWh for any power factor
below 0.95 as follows:
AC AC
Power Factor Correction Power Factor Correction
The operation of electrical systems at low power factors
increases transmission costs and reduces capacity. The
higher current drawn by low power factor loads cause
greater line losses during transmission which then requires
that larger conductors be used.