No Item Description quotation Bidder’s Offer Specifications
compliant?
Required Specifications Bidder to Complete
a Complete set of Fire Fighting Pumps according to
NFPA 20, 14 (UL listed/FM approved) as follows
– Pumps Efficiency: Min 65%
– Operating Voltage: 3PH,380/400,50Hz
– Automatic Control Panel for each Pump: Min IP
65
Specifications includes the below items:
(1) End Suction Main Electric Fire Pump (FP-1): Min
Yes No Bidder to insert details
Flow 400 GPM @ 104PSI
(2) End Suction Standby Diesel Fire Pump (FP-2):
Min (Flow 400 GPM @ 104 PSI
(3) Vertical multistage Jockey pump (JP): Min Flow
8 GPM @ 114 PSI
Note: Bidder must provide datasheet based on Product
Schedule Selection by the manufacture includes
“Technical Documents, Controller and Accessories”.
b The bidder confirms the compliance of the proposed
equipment's with other specifications listed in the
Yes No Bidder to insert details
tender documents not mentioned above i.e., BoQs,
Drawings and Technical Specifications
Is
No Item Description quotation Bidder’s Offer Specifications
compliant?
Required Specifications Bidder to Complete
b Air Handling Units (AHU):
Refer to Drawing (DX-AHU-01)
– Horizontal DX AHU (Dx Expansion Coils 10% fresh
air including control Unit type
– Air Flow Rate: Min 2000 L/s
– Fresh Air Flow Rate: Min 250 L/s
– External Static Pressure: Min ESP 170 PA
– Insulation: Polyurethane Foam (Min 40 kg/m3)
– Double skin Panel Thickness: (Min 50 mm)
– Material: Galvanized Steel for External/Internal
Panel Sides, Screw/Bolts and Drain Pan
– Refrigerant Circuits: Units must have dual Yes No Bidder to insert details
refrigerant circuits. Each refrigerant circuit must be
controlled by a factory installed thermal expansion
valve
– Fan Type: Backward curve
– Installation Type: Outdoor with rainwater protection
– Sand Trap Louver
– Pre-Filter: MERV 7
– Intermediate Filter: MERV 13
– Smoke detector and pressure sensors included
– Blower differential pressure switch damper motor
actuator in supply, return & fresh air
c Temperature Thermostat
– Wall Mounted with internal control unit
– Accuracy: Max ±1.8C°
– Temperature Adjustment Range: Min 15 to 25°C
– Display: Touch-sensitive color screen Display
– Energy Savings: 365-Day programmable scheduling
standby setpoints
Yes No Bidder to insert details
– Network: Over a wired network
– Password protection capability
– Integral Humidity Sensor
– SD memory card or USB port
– Configurable alerts
– Customizable Reports
– Energy usage information
d – The bidder confirms the compliance of the proposed
equipment's with other specifications listed in the
Yes No Bidder to insert details
tender documents not mentioned above i.e., BoQs,
Drawings and Technical Specifications.