You are on page 1of 11

JCI VRF Selection Sabeen IU - Mech

JCI VRF Selection Software V2.99 System Report 29/04/2022

Project Name Sabeen IU - Mech

Client Name

Client Address sana'a

Memo

Selection parameters of the indoor units can be found under the official documents of Indoor unit details;
Selection parameters of the outdoor units can be found under the official documents of Outdoor unit details;

In any case of unclear problems, please contact with Johnson controls ,inc. Engineers for solutions, This software is just an
assistant tool for JCI VRF Selection, we suggest you contact with Johnson controls ,inc. Engineers for confirmation before you
adopt the solution given by this software.

1. Material List
Model Unit QTY Memo Price($) Sum Price($)
High Efficiency Standard Ambient VRF-
YV2VYH124KASFD-1 set 1 0 0
380V Outdoor unit
High Efficiency Standard Ambient VRF-
YV2VYH101KASFD-1 set 1 0 0
380V Outdoor unit
HZG-20B set 2 Outdoor branch pipe 0 0
YCZ-A004 set 2 Central controllor 0 0
Touch screen central controller translator
HA-MA164AD set 2 0 0
or BacNet Translator
Gas-38.1 m 3 Refrigerant gas pipe 0 0
Gas-31.8 m 3 Refrigerant gas pipe 0 0
Gas-28.58 m 6 Refrigerant gas pipe 0 0
Liquid-12.7 m 6 Refrigerant liquid pipe 0 0
Liquid-19.05 m 6 Refrigerant liquid pipe 0 0
Oil-9.52 m 4 Oil equalization pipe 0 0
CON-ZONE 1-18.08 CON-ZONE 2-11.08
R410A Kg 30.16 0 0

YAH1-560B set 2 AHU VB unit 0 0


YAH1-730B set 2 AHU VB unit 0 0
Total 0

2. Indoor/Outdoor Match
Outdoor unit Room Indoor unit
CON-ZONE 1--YV2VYH124KASFD-1 FAHU-ZONE 1--AHU-01

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 1
JCI VRF Selection Sabeen IU - Mech

CON-ZONE 2--YV2VYH101KASFD-1 FAHU-ZONE 2--FAHU-01-E1340

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 2
JCI VRF Selection Sabeen IU - Mech

3. Indoor Dip switch(0:OFF, 1:ON)


When YR-E17 used in group control system , the first unit of group control connection is set as master unit;

Name Name Model SW01 SW02/CN41 SW03 SW07 SW08 CN23/CN2 CN30/CN2 CN21/CN2
-44 7 9 8
CON- FAHU- AHU-01(YAH1- Plan A 0000 YAH1- YAH1- / / / / /
ZONE 1 ZONE 1 73*2B) Plan B 0100 730B: 730B:
Plan C 1000 00000000 00001111
Plan D 1100 YAH1- YAH1-
730B: 730B:
00000001 00011111
CON- FAHU- FAHU-01- Plan A 0000 YAH1- YAH1- / / / / /
ZONE 2 ZONE 2 E1340(YAH1- Plan B 0100 560B: 560B:
56*2B) Plan C 1000 00000000 00001111
Plan D 1100 YAH1- YAH1-
560B: 560B:
00000001 00011111

4. Outdoor Dip switch(0:OFF, 1:ON)


The 1st & 2nd bit of BM1 of master unit should be set 0(Off position) before power on , after power on and finishing searching indoor and
outdoor address ,set 1st & 2nd bit of BM1 to 1 (On position).

Name Model BM1 BM2 BM3 BM4 BM5


CON-ZONE 1-- YV2VYH068KASF 11000000 00000000 000001001 00000000 /
YV2VYH124KASFD-1 D-1
YV2VYH056KASF 00000001 00000000 000000111 00000000 /
D-1
The 1st & 2nd bit of BM1 of master unit should be set 0(Off position) before power on , after power on and finishing searching indoor and
outdoor address ,set 1st & 2nd bit of BM1 to 1 (On position).

Name Model BM1 BM2 BM3 BM4 BM5


CON-ZONE 2-- YV2VYH056KASF 11000000 00000000 000000111 00000000 /
YV2VYH101KASFD-1 D-1
YV2VYH045KASF 00000001 00000000 000000101 00000000 /
D-1

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 3
JCI VRF Selection Sabeen IU - Mech

5. Indoor units details


5.1 CON-ZONE 1----YV2VYH124KASFD-1
The outdoor unit's rated combination ratio is(98.8%),the details of connected indoor units are:

Name Model Cooling Heating Cooling Heating DB Airflow(H) Power Input Noise Size Weight
Capacity Capacity DB/WB
Tkw/Skw kW °C °C L/s W dB(A) mm Kg
FAHU- AHU-01 126.6/12 126.6 26.7/19.4 21.1 0 0 / 0
ZONE 1 6.6
Total 126.6/12 126.6
6.6

5.2 CON-ZONE 2----YV2VYH101KASFD-1


The outdoor unit's rated combination ratio is(98.1%),the details of connected indoor units are:

Name Model Cooling Heating Cooling Heating DB Airflow(H) Power Input Noise Size Weight
Capacity Capacity DB/WB
Tkw/Skw kW °C °C L/s W dB(A) mm Kg
FAHU- FAHU-01- 102.2/10 0 26.7/19.4 21.1 0 0 / 0
ZONE 2 E1340 2.2
Total 102.2/10 0
2.2

6. Outdoor units details


Name Model
Combinatio Cooling Heating Cooling Heating Cooling Heating Max pipe Size Weight
n(N) Capacity Capacity PI PI DB DB/WB Len
% kW kW kW kW °C °C m mm Kg
CON- YV2VYH124KAS 98.8 121.3 136.637 40.2 35.3 40 8.3/6.1 190 1350×720×2048 712
ZONE 1 FD-1 +1350×720×204
8
CON- YV2VYH101KAS 98.1 98.6 113.996 31 29.2 40 8.3/6.1 190 1350×720×1690 667
ZONE 2 FD-1 +1350×720×204
8

Name Model Refrigerant Power type Cooling Cooling Max Heating Heating Max
added running Cur Cur running Cur Cur
Kg A A A A
CON-ZONE YV2VYH124KASF 20 3N~,380~400V,50/60Hz 61.22 101.55 57.08 101.55
1 D-1
CON-ZONE YV2VYH101KASF 20 3N~,380~400V,50/60Hz 47.14 77.9 47.23 77.9
2 D-1

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 4
JCI VRF Selection Sabeen IU - Mech

7. Piping diagram
7.1 CON-ZONE 1

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 5
JCI VRF Selection Sabeen IU - Mech

7.2 CON-ZONE 2

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 6
JCI VRF Selection Sabeen IU - Mech

8. Wiring diagram
8.1 CON-ZONE 1

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 7
JCI VRF Selection Sabeen IU - Mech

8.2 CON-ZONE 2

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 8
JCI VRF Selection Sabeen IU - Mech

9. Central Controllers diagram

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 9
JCI VRF Selection Sabeen IU - Mech

10. Max pipe Len&Drop

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 10
JCI VRF Selection Sabeen IU - Mech

11. Refrigerant charging

The JCI VRF Selection Software is property of Johnson controls ,inc. Ltd. 11