Professional Documents
Culture Documents
7 Fig. 1 shows a ring distributor with interconnector BD. The supply is given at point A.
The resistances of go and return conductors of various sections are indicated in the 5
Figure. Calculate
i) Current in the interconnector
ii) Voltage drop in the interconnector
P.T.O
1
10 A
0.075 Ω
B
A
30 A
E
10 A C
20 A
Fig. 1
8 Determine the most economical size of a 3-phase line which supplies the following loads
at 10 kV 5
9 A 3-phase overhead line has per phase resistance and reactance of 6 Ω and 20 Ω 5
respectively. The sending end voltage is 66 kV while the receiving end voltage is
maintained at 66 kV by a synchronous phase modifier. Determine the KVAR of the
modifier when the load at receiving end is 75 MW at o.8 pf lagging.
--------------------**------------------