You are on page 1of 70

Technology and Solutions

Protection and Substation Automation

Learning Unit:

Generator Protection
in Power Plants
Philosophy
ID No.: PTU / T2309_V1b
Generator Protection in Power Plants
© ABB University Switzerland - 1 -

T2309 / T2309_Philo_V1b.ppt
© ABB University Switzerland 2 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Generator-Protection (1)

Why ?
Generator-Protection
© ABB University Switzerland 3 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
To avoid just THIS!
Generator-Protection (2)
Protection Philosophy Topics
1. Protection areas
2. Protection system
• Purpose
• Requirements

3. Generator protection
• Generator protection system
• Configuration of the power plant
• Type of generators / prime mover
• Grounding of the generator

4. Possible faults
© ABB University Switzerland 4 of 70
Generator Protection in Power Plants

5. Block diagram of a protection function


Single line diagram
T2309 / T2309_Philo_V1b.ppt

6.
7. Presentation of an example
8. Protection functions
Protection Philosophy Protection Areas
Line q Line protection
• Impedance protection (distance protection)

• Line differential protection


• requirement: - fast (40 – 80 ms)
- communication
- redundant
Busbar q Busbar protection
• Differential protection
• Directional comparison
• requirement: - fast
- selective
- security

Generator q Generator protection


• I∆ Differential protection
• I Current (overcurrent)
• U Voltage
© ABB University Switzerland 5 of 70

• Z Impedance
Generator Protection in Power Plants

• f Frequency
• P Power
T2309 / T2309_Philo_V1b.ppt

G • requirement: - multifunctional
- flexible, according to plant configuration
- fast but selective
T - redundant
RE
Protection Philosophy Tasks / purpose

As:
1. A security system
2. An ”insurance policy”

The purpose of a protection system is:


1. To protect the humans (security for personnel)
2. To protect the plant
3. To limit the damages
4. To keep the availability of energy at a high level

A protection system should protect against:


© ABB University Switzerland 6 of 70
Generator Protection in Power Plants

1. Abnormal service conditions


2. Faults
T2309 / T2309_Philo_V1b.ppt
Protection Philosophy Economical requirements
The following requirements should be taken into account:

1. Availability à of the protection


à of the protected object

2. Simplicity

3. Flexibility à Standard HW / SW modules


à standard concepts, Realisierungen,
documentations, training ⇒ quality
à Adaptation ability (i.e. Library of protection functions)

Protection = Insurance
⇓ ⇓
© ABB University Switzerland 7 of 70
Generator Protection in Power Plants

Investment = Premium
⇓ ⇓
T2309 / T2309_Philo_V1b.ppt

Damage costs = Riscs


§ Repair
§ Failure because of wrong handling
§ Outage times
Protection Philosophy Availability (MTBF)
Only with periodical testing:
Testing interval

MTTF MTTR

Relay
defect

With selfmonitoring (numerical relay) :


MTTF MTTR MTTF
© ABB University Switzerland 8 of 70
Generator Protection in Power Plants

Relay failure
T2309 / T2309_Philo_V1b.ppt

Availability:
Up Time (MTTF)
A = Up Time (MTTF) + Down Time (MTTR)

Up Time : Time in service in a healthy state - MTTF (Mean Time To Failure)


Down Time : Time out of service because of failure - MTTR (Mean Time To Repair)
© ABB University Switzerland 9 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt

AND
Protection Philosophy

OR

TRIP
AND
3

AND
2 out of 3
© ABB University Switzerland 10 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt

87G
Protection Philosophy

51
+
∆t
AND
Breaker failure protection
Protection Philosophy Functional requirements
The following requirements should be taken into account:

1. Reliability Quality of the system during the service time

q Dependability
q Security (stability)
q Consistency Always the same reaction for the same fault

2. Selectivity Evaluation (differential current I∆, unbalanced load I2)


Object → location → type of fault
3. Stability the same tripping behaviour today like yesterday
© ABB University Switzerland 11 of 70

No tripping when no fault happens


Generator Protection in Power Plants

4. Speed Not only the protection, also the power devices I>
T2309 / T2309_Philo_V1b.ppt

5. Avccuracy Evaluation of small fault currents


VT / CT failures (compensation)
6. Sensitivity
The final result will be a compromise related
to all these requirements
Generator protection Generator protection systems
The lay-out of a generator protection system depends on

1. Protected object
2. User

A generator protection system should provide:

1. Flexibility in the choice of protecton functions


2. Flexibility in the interface to the process
(alarm, signalling and tripping circuits)
3. Modular HW and SW
© ABB University Switzerland 12 of 70

4. Self supervision
Generator Protection in Power Plants

5. Connection of incoming signals


T2309 / T2309_Philo_V1b.ppt

With a generator protection system it should be possible


to match different configurations of powerplants without
any special additional engineering
Generator protection Configuration of a powerplant
- Configuration of the power plant
Busbar operation Block configuration Gasturbines, Pump storage plant
up to 15kV CombinedCycle
> 15kV > 15kV > 15 kV

T T T
Aux. Trafo
up to 20 MVA
G Aux. Trafo
~
Excit. Trafo Excit. Trafo

G G G
~ >20 MVA ~ ~

>20 MVA >20 MVA

- Number of generators in the power plant / in the network


Collecting bar with common Step-Up
Common Step-Up Transformer (Hydro)
© ABB University Switzerland 13 of 70

Transformer
Generator Protection in Power Plants

T T
T2309 / T2309_Philo_V1b.ppt

G G G G
~ ~ ~ ~ G G
~ ~

Stator earthfault protection!!!!


Generator protection Generator types / type of drives

1. Turbo generator (1-2 pairs of poles)

Steam
• To cover the base load
• Coal, nuclear, oil, process steam (industry)
• Different quantity of turbines
• Garbage burning plant
• Very big power (1500 MVA)

Gas
• To cover peak and middle load with steam turbine (Combined Cycle)
© ABB University Switzerland 14 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt

Diesel
• Emergency group (hospital)
• Small groups
Generator protection Generator types / type of drives
2. Salient pole generator (more than two pairs of poles)
Hydro – Pelton
• High height of fall
• High turning speed
• To cover the peak load together with
pump- storage operation

Hydro – Francis
• Middle height of fall
© ABB University Switzerland 15 of 70

• Middle turning speed


Generator Protection in Power Plants

• Coverage of middle and base load


T2309 / T2309_Philo_V1b.ppt
Generator protection Generator types / type of drives
Hydro – Kaplan
• River power plant
• Low turning speed
• Coverage of base load

Hydro – Straflo
• River power plant
• Low turning speed
© ABB University Switzerland 16 of 70
Generator Protection in Power Plants

• Coverage of base load


• Escher-Wyss & ABB development
T2309 / T2309_Philo_V1b.ppt

• The rotor winding is on the blades of the turbine

Turbine overview
Generator protection Grounding of the generator
Isolated Solid

Uo> I>

for small machines only because of shortcircuit

Resistor (primary) Resistance (secondary)


© ABB University Switzerland 17 of 70
Generator Protection in Power Plants

Re´ 64S
Re Uo> Uo>
T2309 / T2309_Philo_V1b.ppt

64R

I> I>

I0 = f(Re) 100% I0 = f(Re,U)

Grounding resistor calculated for approx. 10 Sec. and 5 – 15 A


Generator protection Grounding of the generator
Resistor (secondary) Resistance (secondary)
generator terminal and reactor

N1
Re´
N2
Re´ Uo>
Uo>
I>
Grounding
transformator
I>
Generator

Machines and blocktransformer with


Earthing on terminal side of generator high capacitive earth current which
Secondary resistor will be compensated by the reactor
© ABB University Switzerland 18 of 70

In case of inquiries In case of inquiries


Generator Protection in Power Plants

Earthing Transformer, Un/√3 / U2/3 On secondary side the transformer


very expensive must have also enough power for the
T2309 / T2309_Philo_V1b.ppt

resistor load
Special case in east European Special case in east European
countries countries
Generator protection Grounding of the generator
Reasons for using different earthing methods

ABB prefers the earthing methode with resistor because of


the following reasons:
§ VT is in normal conditions (without failure) without voltage, and in
case of an earthfault the VT is only short time loaded
§ In case of disconnected resistor protection will be still available,
only selectivity is no more achieved
§ Cheap earthing resistor and VT
§ Earthing on terminal side of the generator generats in the VT’s
continuous voltage
© ABB University Switzerland 19 of 70

§ In case of an earthfault the VT and resitors are loaded between 0 and


Generator Protection in Power Plants

phase-to-phase voltage and the resistors are shortly overloaded


T2309 / T2309_Philo_V1b.ppt

§ Costs for earthing transformer and seconary resistor are high


§ Resistor earthed methode with current measurement principle
will not be available in case of interruption of resistor
Generator protection Type of faults
Stresses:
1. Voltages (isolation)
2. Mechanical forces (machine side)
3. Heating of the iron parts

Possible faults:
Internal External
Stator Rotor Stator Rotor Turbine

Short-circuit Short-circuit Overload Overload Frequency


© ABB University Switzerland 20 of 70
Generator Protection in Power Plants

Ground-fault Ground-fault Überspannung NPS Reverse


T2309 / T2309_Philo_V1b.ppt

power

Interturn Overfluxing Loss of field


Generator protection Protection functions
Main- and back-up protection

Main protection Back-up protection


n Generator Differential n Block Differential
n Transformer Differential n Over- and undervoltage
n 95%- Earthfault protection n Minimum impedance
100%- Earthfault protection or Imax - Umin
n Rotor Earthfault protection n Overcurrent
n High impedance stator- n Over- and underfrequency
differential protection
n Reverse power
© ABB University Switzerland 21 of 70

n Overload
Generator Protection in Power Plants

n Unbalance I2>
T2309 / T2309_Philo_V1b.ppt

n Loss of excitation
n Pole slip protection
n Overfluxing (U/f)
Generator protection Protection functions
Main- and back-up protection for small power plants

Main protection Back-up protection


n Generator Differential n Block Differential
n Transformator Differential n Over- and undervoltage
n 95%- Earthfault protection n Minimum impedance
100%- Earthfault protection or Imax - Umin
n Rotor Earthfault protection n Overcurrent
n High impedance stator- n Over- and underfrequency
differential protection
n Reverse power
© ABB University Switzerland 22 of 70

n Overload
Generator Protection in Power Plants

n Unbalance I2>
T2309 / T2309_Philo_V1b.ppt

n Loss of excitation
n Pole slip protection
n Overfluxing (U/f)
Generator protection Possible faults
Location of the faults Undervoltage 27

Pole slip 78

ANSI-Code Overfluxing 24
G Generator
S Stator Overvoltage 59
R Rotor
Overload 49S

Ground Fault 64S


Invers I> 51
Overcurrent
Instant I>> 50
Winding failure

Min. Impedance 21

Differential 87G
© ABB University Switzerland 23 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt

+ -
Loss of field 40

Reverse power 32 Ground Fault 64R

Frequency 81 Negative phase sequence 46

Rotor overload 49R


Single line diagram Variant 1
Generator Differential 87G
Overcurrent 51G
Negative sequence 46
Imax / Umin 51/27
Loss of field 40
Rotor groundfault 64R
50/51E 49R Reverse power 32
Overvoltage 59
Frequency 81
Undervoltage 27
Stator earthfault 64S
Overcurrent field 50/51E
Rotor overload 49R
32 59 81 27

87G YWX111 64R


© ABB University Switzerland 24 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt

51G 46 51/27 40

64S
Single line diagram Variant 1
Generator Differential 87G
Overcurrent 51G
Negative sequence 46
Imax / Umin 51/27
Loss of field 40
Rotor groundfault 64R
50/51E 49R Reverse power 32
Overvoltage 59
Frequency 81
Undervoltage 27
Stator earthfault 64S
Overcurrent field 50/51E
Rotor overload 49R
32 59 81 27

87G YWX111 64R


© ABB University Switzerland 25 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt

51G 46 51/27 40

64S
Typical tripping examples Variant 1
PROTECTION FUNCTIONS Trippings

Excitation breaker
Generator breaker

Turbine TRIP

CO2 ON
Generator-Differential 87G X X X (X)
Imax / Umin 51/27 X X X
Rotor Groundfault (TRIP) 64R X X X
Stator Groundfault 64S X X X
Overvoltage (AVR) 59 X X X
Undervoltage (AVR) 27 X
Overcurrent (excitatation) 50/51E X X X
© ABB University Switzerland 26 of 70
Generator Protection in Power Plants

Overcurrent 51G X X X
Stator overload (TRIP) 64S X
T2309 / T2309_Philo_V1b.ppt

Rotor overload (TRIP) 49R X X X


NPS (TRIP) 46 X
Loss of field (min reactance) 40 X X X
Overfrequency 81> X X X
Underfrequency 81< X

Reverse power (protection) 32 X X X


Single line diagram Variant 2
Generator Differential 87G
Overcurrent 51G
Negative sequence 46
87N 51N
(64N) Imax / Umin 51/27
Loss of field 40
87T Rotor groundfault 64R
87A Reverse power 32.1
Overvoltage 59.1
87B Frequency 81>
Undervoltage 27
50/51E 49R Stator earthfault 64S
Overcurrent field 50/51E
Rotor overload 49R
81< Min. Impedance 21
60 24 81>
Pole slip 78
Stator overload 49S
32.1 32.2 59.1 27 Reverse power 32.2
59.2
Underfrequency 81<
Overvoltage 59.2
© ABB University Switzerland 27 of 70

Voltage comparison 60
Generator Protection in Power Plants

87G YWX111 64R Blockdifferential 87B


Aux. trafo Diff. 87A
T2309 / T2309_Philo_V1b.ppt

Transformer Diff. 87T


Trafo Groundfault 51N
51G 46 51/27 40 21 78 49S Restriced Earth Fault 87N (64N)

64S
Single line diagram Variant 2
Generator Differential 87G
Overcurrent 51G
Negative sequence 46
87N 51N
(64N) Imax / Umin 51/27
Loss of field 40
87T Rotor groundfault 64R
87A Reverse power 32.1
Overvoltage 59.1
87B Frequency 81>
Undervoltage 27
50/51E 49R Stator earthfault 64S
Overcurrent field 50/51E
Rotor overload 49R
81< Min. Impedance 21
60 24 81>
Pole slip 78
Stator overload 49S
32.1 32.2 59.1 27 Reverse power 32.2
59.2
Underfrequency 81<
Overvoltage 59.2
© ABB University Switzerland 28 of 70

Voltage comparison 60
Generator Protection in Power Plants

87G YWX111 64R Blockdifferential 87B


Aux. trafo Diff. 87A
T2309 / T2309_Philo_V1b.ppt

Transformer Diff. 87T


Trafo Groundfault 51N
51G 46 51/27 40 21 78 49S Restriced Earth Fault 87N (64N)

64S
Typische Auslösungen Variant 2
Schutzfunktionen Auslösungen

Eigenbedarfschalter
Erregerschalter
Turbine AUS
HS Schalter

CO2 EIN
Generator Differential 87G X X X X (X)
Transformer Differential 87T X X X X (X)
Block-Differential 87B X X X X
Imax / Umin 51/27 X X X X
Interturn Fault 59I X X X X
Rotor Groundfault (Trip) 64R X X X X
Stator Groundfault 64S X X X X
Restricted Earthfault 87N X X X X
Transformer Groundfault 51N X X X X
Overvoltage (AVR) 59 X X X X
Undervoltage (AVR) 27 Signal to AVR
© ABB University Switzerland 29 of 70

Overcurrent (Excitation) 50/51E X X X X


Generator Protection in Power Plants

Stator Overload (Trip) 49S X


Rotor Overload (Trip) 49R X X X X
X
T2309 / T2309_Philo_V1b.ppt

Negative Sequence (Trip) 46


Loss of Field ( Min Reak) 40 X X X X
Pole Slipe (Zone 1) 78 X X X X
Overfrequency 81> X X X X
Underfrequency 81< X
Overexcitation (AVR) 24 X X X X
Reverse Power (Protection) 32 X X X X
Under Impedance 21 X X X X
Voltage Comparison 60 - - - -
Blocking of 21, 27, 40
Single line diagram Variant 3
Generator-Differential 87G
Overcurrent 51G
Negative sequence 46
87N 51N Imax / Umin 51/27
(64N)
Loss of Field 40
Rotor groundfault 64R
87T Revers Power 32.1
87A
Overvoltage 59.1
Overfrequency 81>
87B Undervolatge 27
50/51E 49R Stator groundfault 64S
Overcurrent Excitation 50/51E
24 Rotor Overload 49R
59NB.1 Min. Impedance 21
60 81> 81< Pole Slipe 78
59NB.2 Stator Overload 49S
Revers Power 32.2
32.1 32.2 59.1 59.2 27 Underfrequency 81<
Overvoltage 59.2
Voltage comparission 60
© ABB University Switzerland 30 of 70

G Block-Differential 87B
Generator Protection in Power Plants

87G YWX111 64R Aux. Trafo Diff. 87A


~
Transformator-Diff. 87T
T2309 / T2309_Philo_V1b.ppt

Trafo Groundfault 51N


51G 46 51/27 40 21 78 49S Restriced Earth Fault 87N (64N)
Overexcitation 24
Busduct groundfault 59NB.1(64S)
Busduct groundfault 59NB.2(64S)
64S
Single line diagram Variant 3
Generator-Differential 87G
Overcurrent 51G
Negative sequence 46
87N 51N Imax / Umin 51/27
(64N)
Loss of Field 40
Rotor groundfault 64R
87T Revers Power 32.1
87A
Overvoltage 59.1
Overfrequency 81>
87B Undervolatge 27
50/51E 49R Stator groundfault 64S
Overcurrent Excitation 50/51E
24 Rotor Overload 49R
59NB.1 Min. Impedance 21
60 81> 81< Pole Slipe 78
59NB.2 Stator Overload 49S
Revers Power 32.2
32.1 32.2 59.1 59.2 27 Underfrequency 81<
Overvoltage 59.2
Voltage comparission 60
© ABB University Switzerland 31 of 70

G Block-Differential 87B
Generator Protection in Power Plants

87G YWX111 64R Aux. Trafo Diff. 87A


~
Transformator-Diff. 87T
T2309 / T2309_Philo_V1b.ppt

Trafo Groundfault 51N


51G 46 51/27 40 21 78 49S Restriced Earth Fault 87N (64N)
Overexcitation 24
Busduct groundfault 59NB.1(64S)
Busduct groundfault 59NB.2(64S)
64S
Typical Tripping examples Variant 3
Protection functions Trippings

Generator Breaker

Excitation Breaker

Aux. Trafo breaker


Turbine TRIP
HV Breaker

CO2 ON
Generator Differential 87G X X X (X)
Transformer Differential 87T X X X X X (X)
Block-Differential 87B X X X X X
Imax / Umin 51/27 X X X
Interturn Fault 59I X X X
Rotor Groundfault (TRIP) 64R X X X
Stator Groundfault 64S X X X
Selektiv Groundfault (REF) 87N X X X X X
Transformer Groundfault 51N X X X X
Overvoltage (AVR) 59 X X X
Undervoltage (AVR) 27 Signal to AVR
© ABB University Switzerland 32 of 70

Overcurrent (Excitation) 50/51E X X X


Generator Protection in Power Plants

Stator Overload (TRIP) 49S X


Rotor Overload (TRIP) 49R X X X
X X X
T2309 / T2309_Philo_V1b.ppt

Negative Sequence (TRIP) 46


Loss of Excitation, Min. Reactance 40 X X X
Pole Slip (Zone 1) 78 X X X
Overfrequency 81> X X X
Underfrequency 81< X
Overexcitation (AVR) 24 X X X X X
Reverse Power (Protection) 32 X X X
Underimpedance 21 X X X X X
Voltage comparison 60 - - - -
Blocking of 21, 27, 40
Generator protection Structure of the protection functions
Conventional
A B C D

E F G H I

Every protection function A, B, C, ... I is realized with one single


protective relay unit
© ABB University Switzerland 33 of 70
Generator Protection in Power Plants

I / O unit
T2309 / T2309_Philo_V1b.ppt

Signalling unit
Microprocessor unit
A/D converter
DC auxiliary supply unit

The structure of the protection system is based on


the signal processing
Generator protection Comparison conventional - numerical

Schutzrelais
Start
I>
51
Trip
Conventional
Schutzrelais
Start
G U<
27
Trip

HW SW HW

U<
27
© ABB University Switzerland 34 of 70

Start
Generator Protection in Power Plants

f<
81
Log
T2309 / T2309_Philo_V1b.ppt

ik Numerical
I>
G 51
Trip
I∆
87
Generator protection Protection function diagram
Block diagram of a protection function
Protection function

By means of external Signal


Blocking
Measurement value Start (starting)

analog A Signal-
input D processing Trigger t
Tripping
~ Algorithm: Tripping (of the function,
I> Yes / No delayed)
© ABB University Switzerland 35 of 70

Z<
Generator Protection in Power Plants

←P
T2309 / T2309_Philo_V1b.ppt
Function block Protection function

Frequency of the Function block example


processing
T/4 A I∆, I>>, U>>
T/2 B I>
T C, D I2, f, U>

Processing sequence

T = 1/fN
© ABB University Switzerland 36 of 70
Generator Protection in Power Plants

A B C, D A A B A B C, D
T2309 / T2309_Philo_V1b.ppt

T/4 T/2 3T/4 T time


Background processing (HMI, selfmonitoring, … )
Generator protection Configuration of a powerplant

Generator- Transformer- Block


without generator breaker

n Generator and transformer will


always be switched off in
common
© ABB University Switzerland 37 of 70
Generator Protection in Power Plants

G
T2309 / T2309_Philo_V1b.ppt
Generator protection Configuration of a powerplant

With generator- breaker

The generator can be


disconnected selectively,
the auxiliaries remain in
service
© ABB University Switzerland 38 of 70
Generator Protection in Power Plants

G
T2309 / T2309_Philo_V1b.ppt
Generator protection Configuration of a powerplant

Damdem arrangement
2 Generators on one
3-windings-transformer

Separate protection systems


for the transformer and for
each of the 2 generators
© ABB University Switzerland 39 of 70
Generator Protection in Power Plants

G1 G2
T2309 / T2309_Philo_V1b.ppt
Generator protection Configuration of a powerplant

Generators on a common
busbar

n smaller power plants with


some generators

n Stator- earthfault protection for


parallel operating generators
G1 Gn
© ABB University Switzerland 40 of 70

requires a grounding facility on


Generator Protection in Power Plants

the busbar side


T2309 / T2309_Philo_V1b.ppt
Powerplant Layout Combined Cycle
Exhaust
gas

boiler

Power Fuel Power


output input Steam output

Steam-turbine

Exhaust
© ABB University Switzerland 41 of 70

gas
Generator Protection in Power Plants

Generator Gas turbine Condenser Generator


T2309 / T2309_Philo_V1b.ppt

Cooling water
Types of turbines
© ABB University Switzerland 42 of 70 Gas Turbine

Effects:
Generator Protection in Power Plants

detection of emergency trip of turbine (flame off situation)


T2309 / T2309_Philo_V1b.ppt

Settings:
81< two steps (Alarm 49Hz, Trip 48 Hz)
32 machines >30MVA two steps with integrator, both steps in two different Systems (for gas turbine
5%Pn/0.5sec, 1%Pn/0.5sec measuring core in protection device
© ABB University Switzerland 43 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Powerplant Layout

Steam turbine
Steam turbine
Types of turbines Steam turbine

HP MP LP

Steam turbine:
HP High Pressure
MP Intermedate Pressure
LP Low Pressure
© ABB University Switzerland 44 of 70
Generator Protection in Power Plants

Settings:
81< two steps (Alarm 49Hz, Trip 48 Hz)
T2309 / T2309_Philo_V1b.ppt

for huge generators 2. Trip 47.5, t<200ms


32 machines >30MVA two steps with integrator, both steps in two different Systems (for steam turbine 0.5%Pn,
measuring core in protection device, in UK influenced areas additional Forward Power step

Effects:
overheating of turbine and turbines blades
Types of turbines Pelton- turbine
Pelton-Turbine (1880)

The Pelton-turbine represents a further


development of the push wheel which uses the
kinetic energy of the water from high heights
(water drops of more than 1000 m with
approximately 500 km/h). Out of one or more
jets the water flows into case shaped blades
which moves the turbine wheel. The Pelton-
turbine is used in water power plant with a high
height of fall and a less water stream.
The efficiency reaches about 90-95%.
© ABB University Switzerland 45 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Types of turbines
© ABB University Switzerland 46 of 70
Generator Protection in Power Plants
Pelton- turbine
T2309 / T2309_Philo_V1b.ppt

32R Reverse Power usually not required


81> Overfrequency as an backup protection for over speed (limit of turbine 60Hz / 2sec)
© ABB University Switzerland 47 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Pump storage lake
Pelton- turbine
Types of turbines Francis- turbine
Francis-Turbine (1849)

The Francis-Turbine is also called the “Power horse of


water exploitation", the turbine can be used in an wide
range (see attached table). In the turbine, the water
flows through an stand firm but adjustable wheel. In
comparison to a Kaplan-Turbine the water streams
vertical onto the wheel axis.
The efficiency of an Francis-Turbine is approx. 90%.
The range of use are from 20m up to 700m, in an
power range up to 700MW.
© ABB University Switzerland 48 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
© ABB University Switzerland 49 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Types of turbines
Francis- turbine
Types of turbines Kaplan-turbine
Kaplan-Turbine (1912)

The Kaplan-turbine is used where the


hydraulic pressure is low and the water flow
is extremely high and fluctuating, this
appears in all streams, rivers or small
creeks. The turbine/wheel looks like an ship
propeller which can turn/adjust the shovel
according the water flow of the river. The
water is forced through an adjustable guide-
apparatus which is parallel to the axis.
The efficiency of an Kaplan-Turbine reaches
80-95%. The turbine can be equipped with 3
or up to 8 blades with a power range up to
200 MW.
© ABB University Switzerland 50 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Types of turbines
© ABB University Switzerland 51 of 70
Generator Protection in Power Plants
Kaplan-turbine
T2309 / T2309_Philo_V1b.ppt

81> Overfrequency as an backup protection for over speed (limit of turbine 70Hz / 15sec)
32R Reverse Power for vertical axis in two steps in one system (appr. 2% Pn of turbine limit)
Reverse Power for horizontal axis in two steps in one system (appr. 25% Pn of turbine limit)
© ABB University Switzerland 52 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Types of turbines
Kaplan-turbine
Types of turbines Straflo- Turbine
Straflo-Turbine
A development of the Kaplan-Turbine is called
STRAFLO-Turbine (engl. „straight flow“). Turbine and
generator are forming in the STRAFLO-Turbine one
unit. Turbine and generator are not connected via an
driving axis. The generator is mounted in the same
level as the turning wheel/shovel. The water flows
through the generator and rotor. The support of the
turning wheel are on both sides of the turning wheel.
The water flows through the rotor of the machine. The
diameter of the rotor can be up to 8 m. The power can
very up to 50 MW.
© ABB University Switzerland 53 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Types of turbines Pump storage

In some cases it is helpful that the


pump can be separated from the
turbine/generator (different operation
tasks).
In this picture pump and turbine are
fixed together.
Pelton and Francis turbines are applied
in this sort of plants
© ABB University Switzerland 54 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Types of turbines Pump storage

A generator becomes an motor


1 from or to pressure pit
2 distribution pipe
3 Valve
4 Francis-turbine
5 choke tab
6 from or to submerged tunnel
7 Motor-Generator
8 Pump

blue arrow Turbine


red arrow Pump
© ABB University Switzerland 55 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
© ABB University Switzerland 56 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Types of turbines

Device in a pump storage powerplant


Pump storage
© ABB University Switzerland 57 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Types of turbines

Hydro power station with Francis turbine


Pump storage plant
Types of turbines Types of prime mower

Type Pelton turbine Francic turbine Kaplan turbine

Application area Pump Storage Pump Storage Hydro Power Plant

Fall height in m 200 - 2000 10 - 700 0 - 30


© ABB University Switzerland 58 of 70

Flow 4 - 15 m3/s 4 - 55 m3/s 4 - 350 m3/s


Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
© ABB University Switzerland 59 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Types of turbines
Application field of turbines
© ABB University Switzerland 60 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Types of turbines
Application field of turbines
© ABB University Switzerland 61 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Generator protection
GSX5e
© ABB University Switzerland 62 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Generator protection
REG216
Generator protection Selective Stator Earth fault

n Used for small machines or machines


running in parrallel on an common bus
n Earth fault Protection with with
measuring of U0 on an open delta v.t.
and I0 an cable-balance c.t.
n Protection with directional earth fault
T1

T2

T3
measuring principle

and transformer feeder


Zone of busbar
© ABB University Switzerland 63 of 70
Generator Protection in Power Plants

generator feeder
T2309 / T2309_Philo_V1b.ppt

Zone of
G2

G3
G1

G4
Generator protection Grounding of the generator

n Very rare way of grounding because of


high earth fault current

I> n Differential protection covers this fault or


I0 measuring within the earth connection

G~
I>
© ABB University Switzerland 64 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt
Generator protection Generator starpoint
Stator groundfault protection acc. to injection principle
R S T

generator

voltage transformer
N12 N11

REs Us
© ABB University Switzerland 65 of 70
Generator Protection in Power Plants

Uis RPs
T2309 / T2309_Philo_V1b.ppt

Injection voltage
Generator protection Generator starpoint
Stator groundfault protection acc. to secondary injection principle
R S T

generator

voltage transformer

N1 N2 N'12 N'11

R'Es Us
© ABB University Switzerland 66 of 70

grounding-
Generator Protection in Power Plants

transformer
R'Ps Uis
T2309 / T2309_Philo_V1b.ppt

Injection voltage
Generator protection Rotor
Rotor groundfault protection based on measurement bridge principle

C
rotor winding

shaft -

100 VAC
C1 C2 excitation system
© ABB University Switzerland 67 of 70
Generator Protection in Power Plants
T2309 / T2309_Philo_V1b.ppt

R R
tuning capacitor

U>
Generator protection YWX111
Rotor groundfault protection using the principle of wheatstone bridge

R R

(Wheatstone – bridge)

C1
C2
© ABB University Switzerland 68 of 70

C
Generator Protection in Power Plants

C2 has to be tuned to the


T2309 / T2309_Philo_V1b.ppt

capacity of the rotor


circuit
Generator protection Generator starpoint
100% Stator- und Rotor- Earthfault protection

For generators in block configuration


RP RE n Applicable for stator- and rotor
groundfault protection
RE RP n Also useful for grounding
transformers on terminal side
n Continuous supervison of leakage
REX 011
WU30Z resistance, and calculation of
P8 resistance to earth.
© ABB University Switzerland 69 of 70

95%-E/F Stator Rotor Ui n Continuous supervision of injection


Generator Protection in Power Plants

110
[V]

unit and primary earthing


T2309 / T2309_Philo_V1b.ppt

-110
A
Inj ecti on Test

D
[ms]

Coded 12.5H z i njec tion Signal

95% StEF 100% StEF100% RoEF

U DC CPU
110V REX 010 REG 216
Generator protection Generator starpoint
100% Stator- and rotor- earthfault protection
with current- injection REX 010
Injection signal
V

t
Injection test

320ms 640ms

n I0 < 20A; recommended 5A


n Supply of the system by station battery
© ABB University Switzerland 70 of 70
Generator Protection in Power Plants

n Settings and measuring in kΩ


T2309 / T2309_Philo_V1b.ppt

n with mode for self-calibration


n Injection of a coded current signal with pulse and periodic breaks
for evaluation and suppression of disturbance signals
n Injection frequency: 12,5Hz

You might also like