DIGSI 4 / SIPROTEC 4

Overcurrent Protection
Restricted © Siemens 2020 siemens.com/PowerAcademy
Content

• Time-overcurrent protection
• Function
• Characteristics
• Application

• Directional time-overcurrent protection


• Function
• Application

• Direction Comparison
• Principle
• Application

Restricted © Siemens 2020


Page 2 Siemens Power Academy TD
Time-overcurrent protection
Function

two criteria

• Criteria for fault: overcurrent

• Criteria for selectivity: time

Restricted © Siemens 2020


Page 3 Siemens Power Academy TD
Time-overcurrent protection
Function

I> t TRIP
IL1

I>> t
IL2

IL3

IE> t

IE
IE>> t

Valid for all devices with 4 CT inputs

Restricted © Siemens 2020


Page 4 Siemens Power Academy TD
Time-overcurrent protection
Characteristics

Tripping characteristic of a two stage time-overcurrent


protection device - definite time (DMT, ANSI 50, 50N)

t [sec]
2.0

1.5 Tripping area

1.0

0.5

0.5 1.0 1.5 2.0 2.5 x IN

I> I>>

Restricted © Siemens 2020


Page 5 Siemens Power Academy TD
Time-overcurrent protection
Characteristics

Tripping characteristic of a time-overcurrent protection device -


inverse time (IDMT, ANSI 51,51N)

t [sec]
2.0 Characteristics:
• IEC
1.5 • ANSI
• user defined

1.0

0.5

0.5 1.0 1.5 2.0 2.5 x IN

Restricted © Siemens 2020


Page 6 Siemens Power Academy TD
Setting opportunities for IDMT

Restricted © Siemens 2020


Page 7 Siemens Power Academy TD
Time-overcurrent protection
Application

As main protection Used as:

1 feeder line protection


Selectivity by time-grading
x

x
x

O/C O/C O/C 2 Motor protection


with short circuit- and
overload protection,
start protection,
x

restart inhibit

O/C M
3 Transformer protection
for network transformers
with short circuit- and
1 2 3 overload protection,
Inrush-stabilisation

Restricted © Siemens 2020


Page 8 Siemens Power Academy TD
Time-overcurrent protection
Application

Main protection as line protection

x x x x

O/C O/C O/C O/C

t = 900ms t = 600ms t = 300ms t = 0ms

Advantage: simple device,


only current transformers are necessary
Disadvantage: near infeed higher tripping time

Restricted © Siemens 2020


Page 9 Siemens Power Academy TD
Time-overcurrent protection
Application

x x x x
Main protection
as line protection
O/C 1 O/C 2 O/C 3 O/C 4
wrong time grading
t = 150ms t = 100ms t = 50ms t = 0ms

Devices 1 2 3 4 are picking up


t CB = 60 msec,(3 cycles)
Device 4 trips instantaneously t drop off = 20 msec
safety margin = 20 msec
Device 3 trips after 50 msec grading time >= 100 ms
Device 2 risk of trip after 100 msec

Device 1 drops off after 150 msec

Restricted © Siemens 2020


Page 10 Siemens Power Academy TD
Circuit breaker operating times

Restricted © Siemens 2020


Page 11 Siemens Power Academy TD
Time-overcurrent protection
Application

Main protection as distribution transformers protection

<800kVA >800kVA >1600kVA

Short circuit and Short circuit Short circuit (Inrush Stab)


overload protection (Inrush Stab) and overload protection

x
HV-fuse
Typ: GTr
O/C O/C
2
I t
x
x

x
Restricted © Siemens 2020
Page 12 Siemens Power Academy TD
Time-overcurrent protection
Application

As back-up protection

Used for:

x
x

1 Line differential-
I O/C O/C protection

I
2 Transformer-
differential protection
I O/C
x
x

1 2

Restricted © Siemens 2020


Page 13 Siemens Power Academy TD
Time-overcurrent protection
Application
Back-up protection of transformers
two stages are used:
high voltage
• I>>: faults on the high-voltage side
x

uk = short-circuit voltage of the transformer


IN = nominal current of high-voltage side
O/C
100[%]
I>> > * IN[A], t=0
uk[%]
I therefore I>> responds only to faults on
high-voltage side of transformer

• I>: faults on the low-voltage side


x

- pickup value for faults of the low-voltage side


- the value must be higher than the total
of all nominal currents of all feeders, converted
low voltage to the high-voltage side.
- t = 200ms + highest grading time in the feeders

Restricted © Siemens 2020


Page 14 Siemens Power Academy TD
Time-overcurrent protection
Application

setting example: back-up protection of transformers


110 kV
I>>, t = 0 Settings:
300 / 1A
I> , t = xs

40 MVA = 210 A I>> > 100[%] * IN[A]


IN-HV = 110 kV Ö3 uk[%]

uk = 10% = 100[%] * 210 A


40 MVA 10[%]
= 10 * 210 A
40 MVA
IN-LV = 20 kV Ö3
= 1154 A
= 2100 A
1200 / 1A
I>> chosen to 2300 A
20 kV

I> > 1.5 * IN[A] note:


= 1.5 * 210 A setting
refers to
I> chosen to 315 A 110kV-side
200 A 200 A 200 A
400 A 400 A 400 A

Restricted © Siemens 2020


Page 15 Siemens Power Academy TD
Breaker failure protection
Application

Power direction

TRIP breaker failure

TRIP overcurrent prot.

OC function I>
&
t1

BF function &
t2
CB I>
t2= t CB + t BFdrop off + t safety
= 150 - 300 ms

Restricted © Siemens 2020


Page 16 Siemens Power Academy TD
Time-overcurrent protection
SIPROTEC 4

• Time overcurrent Protection (50/51, 50N/51N)


• Thermal overload Protection (49)
7SJ61 • Inrush blocking
• Motor Protection (14, 37, 48, 66/68)
• Negative Sequence Protection (46)
• Trip Circuit Monitoring (74TC)
• Lock-out (86)
• Circuit Breaker Failure Protection (50BF)
• Auto reclosing (79M)
• Fault Recording

• Synchronised Real Time


• User programmable Logic Functions (CFC)
• Measured Value processing
• metered Values, demand values (max, min)
• 3 serial Communications Interfaces
• (RTD: Remote temperature detection interface)
• CB Control Function (Interlocking)

Restricted © Siemens 2020


Page 17 Siemens Power Academy TD
Dir. time-overcurrent protection
Introduction

Directional
time-overcurrent
protection

Restricted © Siemens 2020


Page 18 Siemens Power Academy TD
Dir. time-overcurrent protection
Function

three criteria

• Criteria for fault: overcurrent

• Criteria for selectivity: direction + time

Restricted © Siemens 2020


Page 19 Siemens Power Academy TD
Dir. time-overcurrent protection
Function

I>
IL1 & t

I>>
& t
TRIP

Power
Direction
UL1

Restricted © Siemens 2020


Page 20 Siemens Power Academy TD
Non-Dir. time-overcurrent protection
Application

Power direction
As main protection
of parallel lines

x
x

t = 400 ms t = 400 ms
O/C 1 O/C 2

Devices 1 2 3 4 are picking up

Devices 3 4 are tripping after 200 ms


t = 200 ms t = 200 ms
O/C 4
Device 1 trips after 400 ms
O/C 3
x
x

Device 2 drops off

fault free line 2 has been interrupted


à unselective tripping
x

t = 0 ms à Non-dir. OC protection is not sufficient


O/C 5

Restricted © Siemens 2020


Page 21 Siemens Power Academy TD
Dir. time-overcurrent protection
fault on one of two parallel lines
Power direction
As main protection

x
x

of parallel lines
t = 200 ms t = 200 ms
O/C 1 O/C 2
Devices 1 2 3 are picking up

Device 4 blocks (‘reverse’ direction)

Device 3 trips instantaneously


t = 0 ms t = 0 ms
Directional O/C O/C 4 Device 2 drops off
3
O/C
x
x

Device 1 trips after 300 ms

à power supply is maintained via line 2


x

t = 0 ms
O/C 5

Restricted © Siemens 2020


Page 22 Siemens Power Academy TD
Dir. time-overcurrent protection
fault beyond parallel lines
Power direction
As main protection

x
x

of parallel lines

O/C 1 O/C 2

Devices 1 2 5 are picking up

Devices 3 4 blocking (‘reverse’ direction)

Device 5 trips instantaneously


O/C 3 O/C 4
x

1 2 are dropping off


x

Devices
x

O/C 5

Restricted © Siemens 2020


Page 23 Siemens Power Academy TD
Dir. time-overcurrent protection
Application

x x x x x x
O/C O/C O/C O/C O/C O/C

t = 400ms t = 0ms t = 200ms t = 200ms t = 0ms t = 400ms


1 2 3 4 5 6

Devices 1 2 4 6 are picking up

As main protection Device 2 trips instantaneously


of lines with
two side infeed Devices 4 6 are dropping off

Device 1 trips after 400ms

Restricted © Siemens 2020


Page 24 Siemens Power Academy TD
Dir. time-overcurrent protection
Application

x x x x x x
O/C O/C O/C O/C O/C O/C

t = 400ms t = 0ms t = 200ms t = 200ms t = 0ms t = 400ms


1 2 3 4 5 6

Devices 1 3 4 6 are picking up

As main protection Devices 3 4 are tripping in 200ms


of lines with
two side infeed Devices 1 6 are dropping off

Restricted © Siemens 2020


Page 25 Siemens Power Academy TD
Directional comparison
Introduction

Directional comparison -

an alternative protection concept

Restricted © Siemens 2020


Page 26 Siemens Power Academy TD
Directional comparison
Introduction

HV infeed

20kV
20kV

20kV 400V 400V 20kV

400V 400V
20kV

400V

Restricted © Siemens 2020


Page 27 Siemens Power Academy TD
Directional comparison
Principle

TRIP TRIP
R R
A I>
S I> B
& S &
Data link
t1 t1

I> Start time-overcurrent stage


detect “forward direction”
t1 Time delay
R Receive information “reverse” -> blocking
detect “reverse direction”
S Send information “reverse direction”

Restricted © Siemens 2020


Page 28 Siemens Power Academy TD
Directional comparison
Application

fault in the network part B–C with two end infeed

A B C D

I>,t I>,t I>,t I>,t I>,t I>,t


I>,t I>,t I>,t I>,t I>,t I>,t
I>,t I>,t I>,t I>,t I>,t I>,t
I>,t I>,t I>,t I>,t I>,t I>,t
R 1.1 R 1.2 R 2.1 R 2.2 R 3.1 R 3.2

R 1.1 forward, R 1.2 reverse è R 1.2 blocks R 1.1


R 3.1 reverse, R 3.2 forward è R 3.1 blocks R 3.2
R 2.1 forward, R 2.2 forward è high speed trip in t1 (100ms)

Restricted © Siemens 2020


Page 29 Siemens Power Academy TD
Directional comparison
Application

fault in the network part C–D with single end infeed

A B C D

I>,t I>,t I>,t I>,t I>,t I>,t


I>,t I>,t I>,t I>,t I>,t I>,t
I>,t I>,t I>,t I>,t I>,t I>,t
I>,t I>,t I>,t I>,t I>,t I>,t
R 1.1 R 1.2 R 2.1 R 2.2 R 3.1 R 3.2

R 1.1 forward, R 1.2 reverse è R 1.2 blocks R 1.1


R 2.1 forward, R 2.2 reverse è R 2.2 blocks R 2.1
R 3.1 forward, R 3.2 no pickup è high speed trip in t1 (100ms),
because no block signal is received

Restricted © Siemens 2020


Page 30 Siemens Power Academy TD
Binary signal transmitter

Transmission of 2 binary signals via fibre optic


(in case of protection devices are not equipped with
built-in optical protection data interface)

Störmelde- Störmelde-
kontakt kontakt

Binäreingange
Binäreingange

FSMA-Anschlüße für den LWL


FSMA-Anschlüße für den LWL

Fibre-optic,
Multimode,820nm
Kommando
Kontakte Kommando
SV Kontakte
SV

Binary signal transmitter


7XV5653

Restricted © Siemens 2020


Page 31 Siemens Power Academy TD
Directional comparison
Application

Principle “reverse interlocking”

Power direction
O/C
I>>, t=100ms
Blocking
2 I>, t = 900ms
Bus bar 1 Outgoing protection
picks up and blocks
the infeed protection
stage within 100 ms

O/C O/C O/C


Infeed protection
I>, t = 600ms
pickup pickup 2 gives a trip after
I> I>
pickup M 100 ms since no
I> outgoing feeder has
1 picked up and blocked
the infeed protection

Restricted © Siemens 2020


Page 32 Siemens Power Academy TD
Time-overcurrent protection SIPROTEC 4

• Directional time-overcurrent Protection (67/67N)


7SJ62 7SJ64 • Time overcurrent Protection (50/50N, 51/51N)
• Thermal overload Protection (49)
• Inrush blocking
• Sensitive Ground Fault Protection (64, 50Ns, 67Ns)
• Motor Protection (14, 37, 48, 66/68)
• Under / Over voltage (27, 59)
• Under / Over frequency (81)
• Negative Sequence Protection (46)
• Trip Circuit Monitoring (74TC)
• Lock-out (86)
• Circuit Breaker Failure Protection (50BF)
• Synchronisation (25), only 7SJ64
• Auto reclosing (79M)
• Fault Recording
• Synchronised Real Time
• User programmable Logic Functions
• Measured Value processing
Max demand, metered Values
• 3 serial Communications Interfaces
(Remote temperature device interface)
• CB Control Function (Interlocking)

Restricted © Siemens 2020


Page 33 Siemens Power Academy TD
Disclaimer

Subject to changes and errors. The information given in this document only
contains general descriptions and/or performance features which may not always
specifically reflect those described, or which may undergo modification in the
course of further development of the products. The requested performance
features are binding only when they are expressly agreed upon in the concluded
contract.

All product designations, product names, etc. may contain trademarks or other
rights of Siemens AG, its affiliated companies or third parties. Their unauthorized
use may infringe the rights of the respective owner.

Restricted © Siemens 2020


Page 34 Siemens Power Academy TD
Siemens Power Academy
Contact

Published by Siemens AG For the U.S. published by


Siemens Industry Inc.
Siemens Power Academy TD
SI DG EA-CS PA 100 Technology Drive
Alpharetta, GA 30005
Humboldtstraße 59
90459 Nuremberg
Germany

Phone: +49 911 9852-7100

E-mail:
poweracademy@siemens.com
siemens.com/poweracademy

Restricted © Siemens 2020


Page 35 Siemens Power Academy TD

You might also like