You are on page 1of 1

1 LOAD COMPUTATIONS

E 5 SCALE SCALE NTS

CAFE
MINI GROCERY TOTAL FLOOR AREA: 94 SQM
TOTAL FLOOR AREA: 144 SQM AND EQUIPPED WITH THE FOLLOWING LOADS:
AND EQUIPPED WITH THE FOLLOWING LOADS:
1 - 2KW, 230V REFRIGERATOR
4 - 2KW, 230V REFRIGERATOR 2 - 1.5KW, 230V EXHAUST
1 - 1.5KW, 230V EXHAUST
A.) NONCONTINUOUS LOADS
A.) NONCONTINUOUS LOADS 8 RECEPTACLES AT 180VA 8 × 180VA =1440VA
7 RECEPTACLES AT 180VA 7 × 180VA =1260VA FIRST 10000VA @100% =1440VA
FIRST10000VA @100% =1260VA NET TOTAL NONCONTINUOUS LOADS =1440VA.....................................=1440VA
NET TOTAL NONCONTINUOUS LOADS =1260VA.....................................=1260VA
B.) CONTINUOUS LOAD
B.) CONTINUOUS LOAD GLCRL 94 SQM × 16 VA / SQM =1504VA
GLCRL 144 SQM × 24 VA / SQM =3456VA 1 - 2KW, 230V REFRIGERATOR 1 × 2000VA =2000VA
4 - 2KW, 230V REFRIGERATOR 4 × 2000VA =8000VA 2 - 1.5KW, 230V EXHAUST 2 × 1500VA =3000VA
1 - 1.5KW, 230V EXHAUST 1 × 1500VA =1500VA GROSS TOTAL CONTINUOUS LOAD =6504VA
GROSS TOTAL CONTINUOUS LOADS =12956VA NET TOTAL CONTINUOUS LOADS 125% × 6504VA =8130VA.................................=8130VA
NET TOTAL CONTINUOUS LOADS 125% × 12956VA =16195VA.................................=16195VA
NET TOTAL COMPUTED LOAD =9570VA
NET TOTAL COMPUTED LOAD =16195VA
COMPUTATION FOR MAIN DISCONNECTION MEANS AND SIZE OF SUBFEEDER
COMPUTATION FOR MAIN DISCONNECTION MEANS AND SIZE OF SUBFEEDER IOCPD = ISF = 9570VA / 230 V = 41.6087A ≈ 42A
IOCPD = ISF = 16195 VA / 230 V = 70.4131A ≈ 71A USE 45AT IN 50AF, 2 POLE, 250V ITCB (MCCB)
USE 80AT IN 100AF, 2 POLE, 250V ITCB (MCCB) USE 14 mm² THHN COPPER WIRE (70 A AMPACITY) IN 32 mm² RIGID METTALIC CONDUIT
USE 30 mm² THHN COPPER WIRE (115 A AMPACITY) IN 32 mm² RIGID METTALIC CONDUIT

SALON
TOTAL FLOOR AREA: 42 SQM
AND EQUIPPED WITH THE FOLLOWING LOADS:

1- 1.5KW, 230V EXHAUST

A.) NONCONTINUOUS LOADS


9 RECEPTACLES AT 180VA 9 × 180VA =1620VA
FIRST 10000VA @100% =1620VA
NET TOTAL NONCONTINUOUS LOADS =1620VA.....................................=1620VA

B.) CONTINUOUS LOAD


GLCRL 42 SQM × 24 VA / SQM =1008VA
1 - 1.5KW, 230V EXHAUST 1 × 1500VA =1500VA
GROSS TOTAL CONTINUOUS LOADS =2508VA
NET TOTAL CONTINUOUS LOADS 125% × 2508VA =3135VA.....................................=3135VA

NET TOTAL COMPUTED LOAD =4755VA

COMPUTATION FOR MAIN DISCONNECTION MEANS AND SIZE OF SUBFEEDER


IOCPD = ISF = 4755 VA / 230 V = 20.6740A ≈ 21A
USE 30AT IN 50AF, 2 POLE, 250V ITCB (MCCB)
USE 8.0 mm² THHN COPPER WIRE (55 A AMPACITY) IN 32 mm² RIGID METTALIC CONDUIT