OPzV2-200(2V200Ah)

OPzV series is Valve Regulated Lead Acid battery that adopts immobilized
GEL and Tubular Plate technology to offer high reliability and performance.
The Battery is designed and manufactured according to DIN standards and
with die-casting positive grid and patented formula of active material OPzV
series exceeds DIN standard values with more than 20 years floating design
life at 25 ℃ and It is the best solution for cyclic use under extreme operating
conditions.
Specification
Cells Per Unit 1
ISO 9001 ISO 14001 OHSAS 18001
Voltage Per Unit 2
Nominal Capacity 200Ah@10hr-rate to 1.80V per cell @25℃
Weight Approx. 16.0Kg (Tolerance±3.0%) MH 28539 G4M20206-0910-E-16

Internal Resistance Approx. 1.0 mΩ


Terminal F10(M8)
Dimensions Unit: mm
Max. Discharge Current 1000A (5 sec)
Design Life 20 years (floating charge) 206 103 108

Max. Charging Current 40.0 A

C3 153.6AH
C5 173.7AH
Reference Capacity
C10 200.0AH
C20 213.2AH
Φ20

390
355
2.25 V~2.30 V @ 25℃ M8
Float Charging Voltage
Temperature Compensation: -3mV/℃/Cell

5
2.37 V~2.40 V @ 25℃
Cycle Use Voltage Temperature Compensation: -4mV/℃/Cell
Discharge: -40℃~60℃
Operating Temperature Range Charge: -20℃~50℃
Storage: -40℃~60℃
F10 TERMINAL
Normal Operating Temperature Range 25℃±5℃
RITAR Valve Regulated Lead Acid (VRLA) batteries can Length 103±2mm (4.06 inches)
be stored for up to 6 months at 25℃ and then recharging
Self Discharge Width 206±2mm (8.11 inches)
is recommended. Monthly Self-discharge ratio is less
than 2% at 20℃.Please charged batteries before using. Height 355±2mm (14.0 inches)
Total Height 390±2mm (15.4 inches)
Container Material A.B.S. UL94-HB, UL94-V0 Optional. Torque Value 10~12 N*m

Constant Current Discharge Characteristics : A(25 ℃)


F.V/ Time 10min 15min 30min 1h 2h 3h 5h 8h 10h 20h
1.60V 314.6 251.8 171.3 113.2 72.21 53.77 36.12 24.95 20.90 10.97
1.65V 300.5 242.7 167.3 111.5 71.11 53.17 35.82 24.75 20.70 10.87
1.70V 280.4 230.7 161.3 108.6 69.92 52.18 35.22 24.45 20.60 10.82
1.75V 249.2 210.6 152.3 104.1 68.23 51.19 34.73 24.15 20.30 10.66
1.80V 211.1 188.6 142.3 100.1 65.94 50.10 34.03 23.75 20.00 10.50
1.85V 171.9 155.5 122.2 89.31 60.16 46.03 31.54 22.16 18.70 9.818

Constant Power Discharge Characteristics : WPC(25℃)


F.V/ Time 10min 15min 30min 1h 2h 3h 5h 8h 10h 20h
1.60V 534.7 440.3 311.6 212.2 137.0 102.9 69.95 48.90 41.30 21.68
1.65V 521.6 431.3 307.6 209.9 135.9 102.3 69.45 48.70 41.00 21.53
1.70V 494.5 414.2 298.6 205.9 133.6 100.6 68.85 48.20 40.70 21.37
1.75V 448.2 385.2 284.6 199.1 130.7 98.90 67.76 47.70 40.30 21.16
1.80V 385.9 349.0 269.5 192.8 127.9 97.22 66.57 47.01 39.70 20.84
1.85V 319.6 292.9 233.5 172.3 116.9 89.78 61.99 44.01 37.30 19.58
(Note) The above characteristics data are average values obtained within three charge/discharge cycle not the minimum values.
The battery must be fully charged before the capacity test. The C 10 should reach 95% after the first cycle and 100% after the third cycle.
OPzV2-200(2V200Ah)
Discharge Characteristics Curve Charge Characteristic Curve for Cycle Use(IU)
Temperature:25℃(77℉) Temperature:25℃(77℉)
(V/cell)
120 0.14 2.50
Charge Volume
2.16

Charge Voltage (VPC)


Charge Current (CA)
Terminal Voltage (v )

100 0.12 2.40

Charge Volume (%)


2.00 Charge Voltage
80 0.10 2.30
1.84
0.1C 0.05C
0.25C 0.17C 60 0.06 2.20
1.68 After 50% Discharge
0.50C
After 100% Discharge
1C 40 0.04 2.10
1.52

1.36 20 0.02 2.00


Charge Current
0
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 0 0.00 1.90
min h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28

Discharge Time Charging Time(h)

Cycle Life in Relation to Depth of Discharge Relationship Between Charging Voltage and Temperature
120 2.60

100
2.50

Charge Voltage (v )
Cycle use
80
2.37~2.40VPC@25℃
Capacity(%)

2.40

60
100% 80% 50% 30%
DOD DOD DOD DOD 2.30
Float charging
40
2.25~2.30VPC@25℃
2.20
20

2.10
0 -20 -10 0 10 20 30 40 50
1000 2000 3000 4000 5000 6000 7000
Number of Cycles Temperature (℃)

Temperature Effects on Capacity Storage Characteristics


120 100

100 0℃
0 .1 C A 80
Capacity (% )
Capacity (% )

80 0 .2 C A
60 10℃

60
20℃
1 .0 C A 40
40℃ 30℃
40

20
20

0 0
-20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24
Temperature (℃) Storage Time(months)

Effect of Temperature on Long Term Life Relationship of OCV And State of Charge(20℃)
25 2.20

2.15
Battery Voltage (V)
Lift Expectancy (y ears)

20
2.10

2.05
15

2.00

10
1.95

1.90
5
1.85

0 1.80
0 10 20 30 40 50 0 10 20 30 40 50 60 70 80 90 100
Temperature(℃) State Of Capacity (%)

(Note) All above information shall be changed without prior notice, Ritar reserves the right to explain and update the latest information.

HENGYANG RITAR POWER CO.,LTD. Add: No.1 Huagong Road, Songmu Industrial Park, Shigu District, Hengyang, Hunan, China 421001