SUB : AUTOMATIC TRANSFER SWITCHES

With reference to your request, please find attached our Technical and
Commercial offer.

We hope our offer meets your requirement and look forward to receiving
your valued order.

Best Regards,

Anila Mathew
AL FAJR AL JADID CO. W.L.L.

CONT...2

P.O.BOX-42084 SHUWAIKH, 70651 KUWAIT


TEL: 24679195, 24674326, 24674327 FAX: 24679460
Email: alfajr@fajraljadid.com
ISO 9001:2015 C280 CB-039-MS/1
MGMT. SYS. CERTIFIED
AL FAJR 102 2 04/09
AL FAJR AL JADID CO. W.L.L
FOR MANUFACTURE OF ELECTRICAL CONTROL SWITCHGEAR & ELECTRO-AUTOMATION SERVICES

FAX MESSAGE
**************************
15TH OCT. 19 2.

OUR REF: FJ/29691/F19

COMMERCIAL OFFER

OPTION EACH DISCOUNT NET


DESCRIPTION QTY
NO. (KD) (KD) (KD)
1 Supply of ASCO 300 Series Automatic
Transfer Switches without manual
bypass / isolation facility as per
attached description
a) 400Amps 4 Pole 1 1,990.000 210.000 1,780.000
b) 600Amps 4 Pole 1 3,300.000 350.000 2,950.000
2 Supply of ASCO 300 Series Automatic
Transfer Switches with 1 way manual
bypass / isolation facility as per
attached description
a) 400Amps 4 Pole 1 2,630.000 280.000 2,350.000

b) 600Amps 4 Pole 1 4,200.000 450.000 3,750.000


3 Supply of ASCO 300 Series Automatic
Transfer Switches with 2 way manual
bypass / isolation facility as per
attached description
a) 400Amps 4 Pole 1 3,190.000 340.000 2,850.000
b) 600Amps 4 Pole 1 5,200.000 550.000 4,650.000
4 Supply of ASCO 7000 Series
Automatic Transfer Switches with two
way no-break manual bypass /
isolation facility as per attached
description

a) 400Amps 4 Pole 1 5,350.000 570.000 4,780.000


b) 600Amps 4 Pole 1 7,060.000 760.000 6,300.000

CONT...3

P.O.BOX-42084 SHUWAIKH, 70651 KUWAIT


TEL: 24679195, 24674326, 24674327 FAX: 24679460
Email: alfajr@fajraljadid.com
ISO 9001:2015 C280 CB-039-MS/1
MGMT. SYS. CERTIFIED
AL FAJR 102 2 04/09
AL FAJR AL JADID CO. W.L.L
FOR MANUFACTURE OF ELECTRICAL CONTROL SWITCHGEAR & ELECTRO-AUTOMATION SERVICES

FAX MESSAGE
**************************
15TH OCT. 19 3.

OUR REF: FJ/29691/F19

OPTION :

Sl. EACH DISCOUNT NET TOTAL


DESCRIPTION QTY
NO. (KD) (KD) (KD) (KD)
1 Supply of Remote 2 760.000 80.000 680.000 1,360.000
Communication Modules
for ATSs

TERMS & CONDITIONS :

1) Price Inclusive of : Supply of the ATSs.


: Testing & Commissioning.

2) Validity : 30 days from the date of our offer.

3) Delivery : To be agreed upon.

4) Warranty : 1 year for the System.

Exclusions : Any Installation works at site.


: Any bus duct connections.
: Supply, installation or termination of any cables.

Notes : Delivery up to Site is only included in our offer.


Unloading and Transportation to the location at
Site is not included.

: Our prices are exclusive of value added tax (VAT).


Any applicable VAT will be charged in addition to
quoted/agreed prices and is payable by the buyer in
addition to, and at the same time as, the price
quoted/agreed for the supply of any goods or
services.

CONT...4

P.O.BOX-42084 SHUWAIKH, 70651 KUWAIT


TEL: 24679195, 24674326, 24674327 FAX: 24679460
Email: alfajr@fajraljadid.com
ISO 9001:2015 C280 CB-039-MS/1
MGMT. SYS. CERTIFIED
AL FAJR 102 2 04/09
AL FAJR AL JADID CO. W.L.L
FOR MANUFACTURE OF ELECTRICAL CONTROL SWITCHGEAR & ELECTRO-AUTOMATION SERVICES

FAX MESSAGE
**************************
15TH OCT. 19 4.

OUR REF: FJ/29691/F19

OPTION NO. 1 : ASCO 300 SERIES ATSs WITHOUT MANUAL BYPASS /


ISOLATION FACILITY

Supply of Automatic Transfer Switches without manual bypass /


isolation facility, each to include:
- 1 no. Transfer Switch (ASCO 300 SERIES - USA).
 True double throw, inherently interlocked.
 Single, electrically operated, momentarily energized
solenoid operator.
 Mechanically held.
 One sixth of second retransfer time.
 Neutral pole switching, make before break.
(Protection against floating neutral).
 Off load single handle manual operator.

- 1 no. Microprocessor based, plug in control unit for:


 Mains three phase voltage monitoring.
 Transfer and retransfer controls with necessary
adjustable time delays.
 In-phase voltage monitor for motor load transfers.
 Generator voltage, frequency monitoring.
 Generator start / stop signal with necessary adjustable
time delays.

- Set of Indication lights for:


 Mains voltage normal.
 Mains connected to load.
 Generator voltage normal.
 Generator connected to load.

- 1 no. Test switch for simulation of mains failure for testing


of Generator and ATS.

- 1 no. Wall mounting Enclosure.


CONT...5

P.O.BOX-42084 SHUWAIKH, 70651 KUWAIT


TEL: 24679195, 24674326, 24674327 FAX: 24679460
Email: alfajr@fajraljadid.com
ISO 9001:2015 C280 CB-039-MS/1
MGMT. SYS. CERTIFIED
AL FAJR 102 2 04/09
AL FAJR AL JADID CO. W.L.L
FOR MANUFACTURE OF ELECTRICAL CONTROL SWITCHGEAR & ELECTRO-AUTOMATION SERVICES

FAX MESSAGE
**************************
15TH OCT. 19 5.

OUR REF: FJ/29691/F19

OPTION NO. 2 : ASCO 300 SERIES ATSs WITH 1 WAY MANUAL


BYPASS/ ISOLATION FACILITY

Supply of Automatic Transfer Switches with 1 way manual bypass /


isolation facility, each to include:
- 1 no. Transfer Switch (ASCO 300 SERIES).
 True double throw, inherently interlocked.
 Single, electrically operated, momentarily energized
solenoid operator.
 Mechanically held.
 One sixth of second retransfer time.
 Neutral pole switching, make before break.
(Protection against floating neutral).
 Off load single handle manual operator.

- 1 no. Microprocessor based, plug in control unit for:


 Mains three phase voltage monitoring.
 Transfer and retransfer controls with necessary
adjustable time delays.
 Generator voltage, frequency monitoring.
 Generator start / stop signal with necessary adjustable
time delays.

- Set of Indication lights for:


 Mains voltage normal.
 Mains connected to load.
 Generator voltage normal.
 Generator connected to load.

- 1 no. Test switch for simulation of mains failure for testing


of Generator and ATS.

CONT...6

P.O.BOX-42084 SHUWAIKH, 70651 KUWAIT


TEL: 24679195, 24674326, 24674327 FAX: 24679460
Email: alfajr@fajraljadid.com
ISO 9001:2015 C280 CB-039-MS/1
MGMT. SYS. CERTIFIED
AL FAJR 102 2 04/09
AL FAJR AL JADID CO. W.L.L
FOR MANUFACTURE OF ELECTRICAL CONTROL SWITCHGEAR & ELECTRO-AUTOMATION SERVICES

FAX MESSAGE
**************************
15TH OCT. 19 6.

OUR REF: FJ/29691/F19

- 1 no. One way manual bypass / isolation facility (MEW


SIDE) to supply power to the load from the MEW supply
during maintenance and repair of the system, to include:
 1 no. Manual change over switch.
 1 no. Load break isolation switch.
 Set of interconnecting Bus bars.

- Set of Incoming / Outgoing termination, bus bars, labels,


wiring and accessories.

- 1 no. Wall mounting Enclosure.

OPTION NO. 3 : ASCO 300 SERIES ATSs WITH 2 WAY MANUAL


BYPASS/ ISOLATION FACILITY

Supply of Automatic Transfer Switches with 2 way manual bypass /


isolation facility, each to include:
- 1 no. Transfer Switch (ASCO 300 SERIES - USA).
 True double throw, inherently interlocked.
 Single, electrically operated, momentarily energized
solenoid operator.
 Mechanically held.
 One sixth of second retransfer time.
 Neutral pole switching, make before break.
(Protection against floating neutral).
 Off load single handle manual operator.

- 1 no. Microprocessor based, plug in control unit for:


 Mains three phase voltage monitoring.
 Transfer and retransfer controls with necessary
adjustable time delays.
 Generator voltage, frequency monitoring.
 Generator start / stop signal with necessary adjustable
time delays.
CONT...7

P.O.BOX-42084 SHUWAIKH, 70651 KUWAIT


TEL: 24679195, 24674326, 24674327 FAX: 24679460
Email: alfajr@fajraljadid.com
ISO 9001:2015 C280 CB-039-MS/1
MGMT. SYS. CERTIFIED
AL FAJR 102 2 04/09
AL FAJR AL JADID CO. W.L.L
FOR MANUFACTURE OF ELECTRICAL CONTROL SWITCHGEAR & ELECTRO-AUTOMATION SERVICES

FAX MESSAGE
**************************
15TH OCT. 19 7.

OUR REF: FJ/29691/F19

- Set of Indication lights for:


 Mains voltage normal.
 Mains connected to load.
 Generator voltage normal.
 Generator connected to load.

- 1 no. Test switch for simulation of mains failure for testing


of Generator and ATS.

- 1 no. Two way manual bypass / isolation facility (MEW and


GENERATOR SIDE) to supply power to the load from the
MEW or GENERATOR supply during maintenance and
repair of the system, to include:
 2 nos. Manual change over switches.
 2 nos. Load break isolation switches.
 Set of interconnecting Bus bars.

- Set of Incoming / Outgoing termination, bus bars, labels,


wiring and accessories.

- 1 no. Wall mounting Enclosure.

CONT...8

P.O.BOX-42084 SHUWAIKH, 70651 KUWAIT


TEL: 24679195, 24674326, 24674327 FAX: 24679460
Email: alfajr@fajraljadid.com
ISO 9001:2015 C280 CB-039-MS/1
MGMT. SYS. CERTIFIED
AL FAJR 102 2 04/09
AL FAJR AL JADID CO. W.L.L
FOR MANUFACTURE OF ELECTRICAL CONTROL SWITCHGEAR & ELECTRO-AUTOMATION SERVICES

FAX MESSAGE
**************************
15TH OCT. 19 8.

OUR REF: FJ/29691/F19

OPTION NO. 4 : ASCO 7000 SERIES ATSs WITH 2 WAY NO - BREAK


MANUAL BYPASS/ ISOLATION FACILITY

Supply of Automatic Transfer Switches with two way no-break


manual bypass / isolation facility, each to include:
- 1 no. Automatic Transfer Switch (ASCO 7000 SERIES).
 True double throw inherently interlocked.
 Single electrically operated, momentarily energized
solenoid operator.
 Mechanically held.
 One sixth of a second retransfer time.
 Neutral pole switching, make before break.
(Protection against floating neutral).
 Off load single handle manual operator.

- 1 no. Digital Microprocessor with touch pad programming


display, plug in control unit for:
 3-Phase under and over voltage settings on normal and
emergency sources.
 Under and over frequency settings on normal and
emergency.
 True RMS Voltage sensing with +/- 1% accuracy;
Frequency Sensing Accuracy is +/- 0.2%.
 Phase sequence sensing for phase sensitive loads.
 Voltages unbalance detection between phases.
 Advanced in phase algorithm which automatically
measures the frequency difference between the two
sources and initiates transfer at appropriate phase
angles to minimize disturbances from transferring
motor loads.
 Event log displays 99 logged events with the time and
date of the event, event type and event reason.
 Output signals for remote indication of normal and
emergency source acceptability.
CONT...9

P.O.BOX-42084 SHUWAIKH, 70651 KUWAIT


TEL: 24679195, 24674326, 24674327 FAX: 24679460
Email: alfajr@fajraljadid.com
ISO 9001:2015 C280 CB-039-MS/1
MGMT. SYS. CERTIFIED
AL FAJR 102 2 04/09
AL FAJR AL JADID CO. W.L.L
FOR MANUFACTURE OF ELECTRICAL CONTROL SWITCHGEAR & ELECTRO-AUTOMATION SERVICES

FAX MESSAGE
**************************
15TH OCT. 19 9.

OUR REF: FJ/29691/F19

 Statistical ATS / System monitoring data screens


which provide:
 Total number of ATS transfers.
 Number of ATS transfers caused by power
source failure.
 Total number of days ATS has been in
operation.
 Total number of hours that the normal and
emergency sources have been available.
 Engine start time delay.
 Transfer to emergency time delay.
 Emergency source failure time delay.
 Retransfer to normal time delay.
 Unloaded running time delay for engine cools down.
 Pre and post transfer signal time delay for selective
load disconnect.
 Fully programmable engine exerciser.

- Set of Indication lights for:


 Mains voltage normal.
 Mains connected to load.
 Generator voltage normal.
 Generator connected to load.
 Bypass position indication.
 ATS connected/Test / Disconnected position
indication.

- 1 no. Two way no break bypass / isolation arrangement.


 Two handle operation.
 Auto / Test disconnect.
 Normal / Emergency.

CONT...10

P.O.BOX-42084 SHUWAIKH, 70651 KUWAIT


TEL: 24679195, 24674326, 24674327 FAX: 24679460
Email: alfajr@fajraljadid.com
ISO 9001:2015 C280 CB-039-MS/1
MGMT. SYS. CERTIFIED
AL FAJR 102 2 04/09
AL FAJR AL JADID CO. W.L.L
FOR MANUFACTURE OF ELECTRICAL CONTROL SWITCHGEAR & ELECTRO-AUTOMATION SERVICES

FAX MESSAGE
**************************
15TH OCT. 19 10.

OUR REF: FJ/29691/F19

 Bypass can be achieved without interruption of power


to the load.
 In test position all ATS function can be tested without
power interruption.
 In disconnected position the complete ATS can be
draw-out removed for maintenance.
 During bypass the load can be fed from either the
normal or emergency source.

- Set of Mimic line diagram with LED indications.

- 1 no. Test switch for simulation of mains failure for testing


of Generator and ATS.

- Set of Incoming / Outgoing termination, labels, wiring and


accessories.

- 1 no. Floor mounting Enclosure.

OPTION :