Professional Documents
Culture Documents
The following article was published in ASHRAE Journal, September 2004. © Copyright 2004 American Society of Heating, Refrigerating and Air-
Conditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in
paper form without permission of ASHRAE.
By William Ryan, Ph.D., P.E., Member ASHRAE is more acute as there often are few other
practical applications for waste heat.
In the long run, developing countries cogeneration systems. Engine generators Absorber Types
(where electric demand is growing and are the most commonly used drives for The first issue is the selection of the
electric distribution is strained) can ben- cogeneration systems in commercial best type of absorption chiller to apply
efit most from cogeneration. Every co- buildings and campuses. For most prac- to engine heat rejection. Engine genera-
generation system built reduces the need tical application sizes, this means that a tors reject heat in the exhaust, the jacket
for central generation and transmission portion of the summer cooling load must water, the oil cooler, one or more turbo-
system construction, and decentralizes be met by an absorption chiller operat- charger intercoolers, and directly to the
power production, potentially increasing ing on waste heat from an industrial en- engine room. The last three often are too
the security of the electric system. gine. In the developing world, which low in temperature to be practically used.
Aggressive year-round heat recovery tends to be more tropical, the need for Temperature limits govern how much
is important in economically justifying cogeneration systems to supply cooling can be recovered. Engine jacket outlet
S30 Building for the Future | A Supplement to ASHRAE Journal September 2004
ABSORPTION CHILLERS
September 2004 Building for the Future | A Supplement to ASHRAE Journal S31
Cooling Percent Cost
Heat Absorber Available, Above
Production, Hot Water
COP tons/kW Electric
Btu/kWh
Gen. (At 500 tons)
Water Absorber
Single Effect
Min. 3,800 0.22 Cooled Chilled
0.7
Low Temp. 25% Silencer Water to
System Single Effect
Max. 6,000 0.35 Cooling
0.7 Exhaust
Load
Double
Min. 1,500 Effect 0.15
High Temp. 1.2
100%
System Double
Max. 2,000 Effect 0.2
1.2
Table 1 (left): Comparison of low and high temperature approaches. Figure 1 (right): Ideal engine absorber interconnection.
Figure 2 (left): Absorption chiller at GTI cogeneration facility. Figure 3 : Exhaust heat recovery heat exchanger at GTI facility.
S32 Building for the Future | A Supplement to ASHRAE Journal September 2004
ABSORPTION
HEAT RECOVERY
CHILLERS
280 280
90% 90% %
Figure 5 (left): Derating charts for two American manufacturers. Figure 6 (right): Operating points to achieve 207°F (97°C)
return to jacket temperature.
temperatures), whereas the single pass allows only a tor is to engine jacket entering water temperature, and also
13°F (7°C) range. The larger range of the multipass the value of using multipass machines. Both absorber derat-
means that less water has to be pumped to and through the ing, requiring installation of a larger absorber, and the larger
absorber to supply a given hot water flows, requiring
heat input. This helps to 280 larger piping and pumps,
compensate for the higher can make a significant dif-
260 100%
pressure drop of a multipass 1 0 0% ference in first cost.
arrangement. 90% % There are situations
Inlet Temp. (°F)
240 0
or 9
If the maximum return wa- act % where single-pass arrange-
yF 80% 80
ter temperature to the engine 220 acit 70% % ments will make sense,
p 7 0
Ca
jacket was 190°F (88°C), 212°F
60% 6 0 % specifically where tempera-
%
as quoted by some engine 200 198°F 50 ture ranges must be kept low
%
manufacturers, the situation 40 or the water flow rate must
180 190°F
becomes appreciably worse, Multipass be high for some other sys-
Single-Pass
as shown in Figure 8. 160
tem-related reason. How-
With a 190°F (88°C) maxi- 140 150 160 170 180 190 200 210 220 230 240 ever, with engine coolant,
mum engine jacket entering Outlet Temp. (°F) the limited return tempera-
temperature (and therefore a Figure 7: Operating points to achieve 190°F (88°C) return to ture to the engine and the
190°F [88°C] absorber leav- jacket temperature. ability for an engine to
ing water temperature) the generate high (250°F or
maximum entering water temperature for a multipass absorber more [121°C or more]) leaving water temperatures suggest
is 212°F (100°C), with a capacity factor of ~65%. that engine heat recovery is a problem best solved with a
Table 2 illustrates how sensitive the absorber capacity fac- multipass chiller.
Table 2: Resulting derating situation and water flows for 100 tons (350 kW) of heat recovery cooling.
September 2004 Building for the Future | A Supplement to ASHRAE Journal S33
How Heat Exchangers Make the Situation Worse pump to be in separate circuits, other ways exist of handling
Designers often place a heat exchanger between the ab- this, as described in the next section.
sorber and the engine jacket. Engine manufacturers may ac-
tually recommend this as it relieves them of any concerns Pumping Issues
about the capability of the engine water pump to handle the Moving jacket water through the absorption chiller directly
pressure drop through the absorber. Unfortunately, this is not involves overcoming the pressure drop within the hot water
desirable from an overall sys- piping that runs through the
tem standpoint. generator. The longer the flow
If the heat exchanger has a path, the greater the pressure
10°F (5.5°C) drop, as is typi- Absorber loss. Therefore the pressure
cal of shell and tube arrange- Water drop increases with the num-
Cooled
ments, and the maximum Silencer ber of passes used.
return temperature of the en- 180°F As shown in Table 3, mov-
Exhaust
gine is 190°F (88°C), the ing from single to multipass
maximum output temperature machines both raises the pres-
from the absorber becomes sure drop and lowers the water
180°F (82°C). As shown in 190°F 190°F flow rate, resulting in similar
Table 2, this results in a fur- power consumption. Pumping
ther derating of the absorber, Figure 8: Commonly used heat exchanger worsens situation. power does rise with lower
increasing the design size of water temperatures in either
the absorber from 143 to 200 tons 20 pass arrangement. However, it remains
ss
(503 to 703 kW) just to effectively a small quantity compared to the cool-
Pa
produce 100 tons (352 kW). ing derived. The values in Table 3 do
3
10
Some designers also voice con- not include pumping needed to send
Pressure Drop, ft of water
cerns about any leakage in the ab- the hot water from the engine to the
ss
Pa
5
potentially contaminating the engine distance between the engine and the
coolant system. However, even when absorber will consume more power.
ss
Pa
tor operates below atmospheric pres- equipped with a pump on the engine.
2
sure, whereas the jacket coolant However, this pump will have been
system is at or above atmospheric. sized to move jacket water through
When the absorber is shut down, the 1
a radiator and back to and through
generator is far below atmospheric 90 100 200 300 400 500 the engine. It may not be sufficient
Gallons Per Minute
pressure. Any leakage in generator to handle pumping through the ab-
tubing would admit jacket water to Figure 9: Pressure drop in a 160 ton (563 kW) sorber. An additional pump may
the absorber, rather than leak bro- (nominal rating) hot water absorption chiller. need to be added to circulate cool-
mide solution to the jacket water. ant through the absorber. Also, the
Finally, although a heat exchanger dividing the two water pressure drops shown in Figure 9 are for water and will be
flows allows the absorber’s hot water flow pump and engine higher than for the ethylene glycol water mixtures generally
S34 Building for the Future | A Supplement to ASHRAE Journal September 2004
ABSORPTION
HEAT RECOVERY
CHILLERS
Peak Electric Cogen Size Absorber Size, tons Peak Cooling Cost of Installed Cost of System
Building Size, ft2
Load at 50% Load, tons System Per ft2 of Building
100,000 700 kW 350 kW 87 250 $1,400/kW $5.50
500,000 3,500 kW 1,750 kW 438 1250 $1,200/kW $3.33
1,000,000 7,000 kW 3,500 kW 875 2500 $800/kW $2.80
September 2004 Building for the Future | A Supplement to ASHRAE Journal S35
the boiling point of the hottest water in
From
the system. CWR Cooling
A water-cooled silencer (for exhaust Load
Low-Temperature Absorption Chillers William Ryan, Ph.D., P.E., is a research engineer at the Uni-
Single-effect absorption chillers also can be built that op- versity of Illinois Chicago.
S36 Building for the Future | A Supplement to ASHRAE Journal September 2004