PMS-LVSG 1 & 2 PMS of Low Voltage Switchgear 1 & 2
Record as-found details Inspect mechanical and physical condition Conduct cleaning and removal of dirt and residue
Apply contact grease to terminals
Perform test on components
Reconnect and retighten terminal connections Record as-left details Components:
2 Unit Air Circuit Breaker [IR,CR]
15 Unit MCCB [IR, CR]
PMS-CB 1 & 2 PMS of Capacitor Bank 1 & 2 Record as-found details Inspect mechanical and physical condition Conduct cleaning and removal of dirt and residue Perform Insulation Resistance Tests on breakers and contactors
Perform Capacitance Tests on
capacitor cells Verify and check power factor controller Reconnect and retighten terminal connections Verify tightness of control connections Record as-left details PMS of Medium Voltage PMS-MVSG Switchgear Record as-found details Inspect mechanical and physical condition Conduct cleaning and removal of dirt and residue
Apply contact grease to terminals
Perform test on components
Reconnect and retighten terminal connections Record as-left details Components: 6 Unit Vacuum Circuit Breaker [IR, CR] 3 Unit MicomP122(Protection Relay) 1 Unit Siemens & SJ6005(Protection Relay)
2 unit Siemens brand Reyrolle 7SR10 Argus (New
Protection Relay) Note: for installation testing & commissioning
1 Unit LS DPRI000(Protection Relay)
PMS of SF6 Power Circuit Breaker
PMS-PCB [Live Tank]
Record as-found details
Inspect mechanical and physical condition Conduct cleaning and removal of dirt and residue
Apply contact grease to terminals
Perform Insulation Resistance Test
Perform Contact Resistance Test
Reconnect and retighten terminal
connections Record as-left details INS-TRB Troubleshooting of Charging motore of Livetank Circuit breaker. Charging motor is not functional MOB-R8 Mobilization/Demobilization