2014-SEP-01 REV. 11 PAGE 6-1
After the system has been completely installed, and BEFORE TESTING MECHANICAL GAS VALVES
INSTALLING THE CARTRIDGE, the system must be tested at To test each mechanical gas shut-off valve complete the
the regulated release assembly. The testing information listed following steps:
in this section deals with the limitations and parameters of this
! WARNING
pre-engineered system. Those individuals responsible for the 1.
testing of the R-102 system must be trained and hold a current
ANSUL certificate in an R-102 training program. To reduce the risk of explosion due to leaking gas, before
Note: AUTOMAN Release must be in the cocked position the gas line is turned on, make certain to extinguish any
before testing manual pull station. Make certain to remove lock open flames and turn off all burners and any electrical
pin before performing pull station testing. or mechanical devices that are capable of igniting gas.
Failure to comply may result in serious personal injury or
TESTING MANUAL PULL STATION death.
To test each remote manual pull station, complete the following
steps: Turn gas line on.
1. W
ith the expellant gas cartridge removed, remove lock pin 2. M
anually push each air cylinder rod to full ‘‘DOWN’’ posi-
from regulated release assembly cable lever. tion. The gas valve should close. If mechanical gas valve
does not trip, remove each pulley elbow cover to make
2. On pull station, remove break rod from the pull station by certain wire rope is resting on each pulley elbow sheave.
inserting a small screwdriver into slot at bottom of pull knob If this does not correct the problem there may be too much
to facilitate turning the pull knob. Push slightly on the screw- slack in the line and it should be retightened.
driver and turn pull knob clockwise, then the pull knob can
be removed without breaking the glass rod. 3.
Test for gas leaks by painting connections with a soap
solution. Bubbles indicate a gas leak. Tighten connections
NOTICE where leaks appear and repeat test again to make certain
no other gas leaks exist.
Take care in removing the break rod from
4. If no gas leak is found, pull air cylinder rod to full ‘‘UP’’
the pull station side shields while rotating
position.
the break rod/pull knob assembly.
5. Recock mechanical gas valve.
3.
Pull ring handle on pull station. If the regulated release 6.
Check burners for gaseous odor. IF GASEOUS ODOR
assembly is tripped easily, the remote manual pull station EXISTS, MANUALLY PUSH THE AIR CYLINDER ROD
is properly installed. If the regulated release assembly does TO THE FULL ‘‘DOWN’’ POSITION IMMEDIATELY. This
not trip, remove pulley tee (if provided) and each pulley will cause the mechanical gas valve to shut the gas line off.
elbow cover to make certain wire rope is resting on the
Open any doors and/or windows to clear the area of
pulley sheave. If this does not correct the problem, there is gaseous fumes, then correct the gas leak before proceeding
too much slack in the line and it must be retightened. any further.
4.
Recock regulated release assembly using cocking lever 7. If no gaseous odor exists, pilot light may be ignited at this
(Part No. 441042 or 441041) and reinstall lock pin (Part No. time.
438031).
8. Reinstall side covers to gas valve housing. Make certain roll
5.
On pull station, insert the break rod into the two holes pin is positioned within both sides of the valve housing slot.
toward the top of the pull knob. Rotate the pull knob coun- Connect visual inspection seals (Part No. 197) on ANSUL
terclockwise. type valves. See Figure 6-1 (next page).
9. Make certain the regulated release mechanism is cocked
NOTICE with lock pin in place.
Take care in snapping in the ends of the
break rod into the pull station side shields NOTICE
while rotating the entire assembly.
If no other devices are being attached,
proceed to Page 6-3, Step No. 1, and test
the detection system.
NOTICE
If no other devices are being attached,
proceed to Page 6-3, Step No. 1, and test
the detection system.
SECTION 6 – TESTING AND PLACING IN SERVICE R-102 Restaurant Fire Suppression Manual
UL EX3470 ULC EX3470
PAGE 6-2 REV. 11 2014-SEP-01
TESTING MECHANICAL GAS VALVES (Continued) valve, thus shutting off the gas line. If this does not happen,
turn power source off. Then re-examine all wiring connec-
tions for proper hookup. Refer to Figures 5-122, 5-123,
5-124, and 5-125 in ‘‘Installation Instructions’’ section for
typical wiring diagrams.
8. If test is successful, recock regulated release mechanism
using cocking lever (Part No. 441042 or 441041) and rein-
stall lock pin (Part No. 438301). Depress reset button on
manual reset relay (RED LIGHT ON).
9.
Check burners for gaseous odor. IF GASEOUS ODOR
VISUAL INSPECTION
SEAL (PART NO. 197) EXISTS, TURN OFF POWER SOURCE IMMEDIATELY.
This will cause the electric gas valve to shut the gas line off.
Open any doors and/or windows to clear the area of
gaseous fumes, then correct the gas leak before proceeding
any further.
10. If no gaseous odor exists, pilot light may be ignited at this
time.
FIGURE 6-1
NOTICE
000359
! WARNING
1.
TESTING ELECTRIC SWITCH
To reduce the risk of explosion due to leaking gas, before The procedure for testing a field installed electric (snap-action)
the gas line is turned on, make certain to extinguish any switch is as follows:
open flames and turn off all burners and any electrical
or mechanical devices that are capable of igniting gas. NOTICE
Failure to comply may result in serious personal injury or
death. If an electrical gas shut-off valve is attached
to system, perform proper test procedure
Turn gas line on. for the gas valve first, before completing the
following steps.
2. Make certain electric (snap-action) switch is properly wired.
3.
Make certain all other devices connected to the manual
1. Turn power source on and if installed, depress reset button
reset relay are properly wired. Refer to typical wiring
on manual reset relay (RED LIGHT ON). All electrical
diagrams in Figures 5-122, 5-123, 5-124, and 5-125 in
devices should be operating at this time.
“Installation Instructions” section.
2. Remove lock pin.
4.
Test for gas leaks by painting connections with a soap
solution. Bubbles indicate a gas leak. Tighten connections
where leaks appear. Repeat test again to make certain no
CAUTION
other gas leaks exist. Do not install cartridge at this time or system may be
5. If no gas leaks are found, turn power source on and depress actuated.
the reset button on the manual reset relay (RED LIGHT ON)
to energize (OPEN) electric gas valve. 3. Manually actuate the system by operating the remote pull
6. Remove lock pin from regulated release mechanism. station. It may be necessary to remove the glass break rod
prior to operating pull station. (If installed, the manual reset
CAUTION relay will de-energize the electric gas valve, thus shutting
off the gas line.) All electrically-operated devices prede-
Do not install cartridge at this time or system may be termined to shut off or turn on should do so. If this does
actuated. not occur, turn power source off and make sure all wiring
is properly connected and retest. Refer to Figures 5-122,
7. Manually actuate the system by operating the remote pull 5-123, 5-124, and 5-125 in “Installation Instructions” section
station. (It may be necessary to remove the glass break for typical wiring diagrams.
rod prior to operating pull station.) Manual reset relay (RED
LIGHT OUT) will de-energize (CLOSE) the electric gas
R-102 Restaurant Fire Suppression Manual SECTION 6 – TESTING AND PLACING IN SERVICE
UL EX3470 ULC EX3470
2014-SEP-01 REV. 11 PAGE 6-3
CAUTION
Before installing cover, make certain detection tension
lever is secured in the “DOWN” position to enable
automatic detection and operation of the AUTOMAN
Regulated Release.