MERIDIAN, ID 83642
9 (TYP.) 3. CONCRETE COMPRESSIVE STRENGTH AT 28 DAYS TO BE:
2'-0"
#208-283-3775
WALLS NOT EXPOSED TO WEATHER 2500 PSI
WALLS EXPOSED TO WEATHER 3000PSI
8 (TYP.) PORCHES, STEPS & GARAGE SLAB 3500PSI
4. EXTEND FOOTING BELOW FROST LINE, (24" MIN. INTO NATURAL
94'-10" SOIL FOR 1 STORY AND 2 STORY CONSTRUCTION
8'-6"
4'-6"
5. THE GRADE AWAY FROM THE FOUNDATION WALLS TOF ALL A MIN.
6'-0" 15'-0" 20'-11" 13'-5" 18'-0" 5'-6" 16'-0" 6' WITHIN THE FIRST 10 FEET.
SIMPSON JOIST HANGER 6. 1/2" DIA. X 10" ANCHOR BOLTS TO BE USED @ 6'-0" O.C. & 7" MIN.
OR EQUAL (TYP.) INTO CONC. & 12" MAX FROM ANY CORNER W/ 2" DIA. WASHERS
START JOIST 4 & 1/2" DIA. NUTS (CONC. STEM WALLS).
16"x6" FOUNDATION 7. 18" MIN. CRAWL SPACE W 6MIL. BLACK W/6 MIL. BLACK VAPOR BARRIER
LAYOUT HERE (TYP.) THROUGHOUT LAP JOINTS 12" MIN. EXTEND UP STEM WALL & STAPLE TO
MUD SILL.
8. SUGGESTED REBAR PLACEMENT TO BE: 2- #4 HORIZONTAL REBAR
5'-6"
IN FOOTING AND VERTICAL REBAR @ 6'-0" O.C. IN ALL 2' EXTERIOR
3 CONCRETE STEM WALLS. ACTUAL REBAR INSTALLATION TO FOLLOW
VENT WELL (TYP.) LOCAL REQUIREMENTS.
9'-6"
9. SUGGESTED REBAR PLACEMENT TO BE: 2- #4 HORIZONTAL REBAR
7'-0"
IN FOOTING AND 2-#4 HORIZONTAL REBAR IN STEM WALL EQUALLY SPACED
12'-0"
AND VERTICAL REBAR @ 6'-0" O.C. IN ALL 2' EXTERIOR CONCRETE STEM
10'-0"
WALLS. ACTUAL REBAR INSTALLATION TO FOLLOW LOCAL REQUIREMENTS.
3'-6"
4" REBAR@ 2'-0"o.c. (TYP.) 10. BASEMENT CONCRETE WALLS TO FOLLOW LOCAL REQUIREMENTS AND
OR PER APPROVED STRUCTURAL ENGINEERING DRAWINGS.
of Risen Home Design. These drawings are NOT to be reproduced, copied whole or in part, disclosed,
used for construction or any other purpose without prior written permission from Risen Home Design.
11. ALL CONCRETE PORCHES TO BE DOWELED TO EXTERIOR STEM WALL
FIE
14'-0"
These Drawings contain confidential proprietary information and are the property
2X4 PONY WALL OVER BUILDING DEPARTMENT.
CONTINUOUS ALONG 16"X8" CONCRETE
LENGTH OF BRACED WALL FOOTING (TYP.)
PANEL AS REQ'D.
SHEET NOTES
9'-0"
9'-0"
18'-0"
WALKER RESIDENCE
2'-0" ACCESS
3 (TYP.)
2 CONTINUOUS FOUNDATION WALL BLOCK OUT
AS REQUIRED.
1 1 1 1 1
3 CRAWL SPACE ACCESS.
40'-6"
FOUNDATION PLAN
JOIST@24"o.c. GLUE AND NAIL SHEATHING 4 4" CONCRETE SLAB ON 4" COMPACT GRAVEL
(TYP.) BASE W/ 6" THICKENED SLAB EDGE TO
1'-0" 1'-10" 1'-0" 2'-0" FROSTLINE W/ 4" x 18" BAR @ 24" O.C.
7
7'-0"
(TYP.) 2'-0" 1'-0" 2'-0" WH
18'-6"
1'-3"
6 ANCHOR BOLTS PER R403.1.6 AS REQUIRED
1'-3"
is iii
PER PORTAL FRAMING AT GARAGE DOORS
3'-8 1/4"
6" x 24" CONC. STEM WALL OVER 2
16" x 8" CONC. FOOTING (TYP.) 7 CONC. STOOP.
1 1 1
I
8 SIMPSON POST BASE OR EQUAL.
-
7'-9"
9 24"Ø x 24" MIN. DEEP CONC. SUPPORT
2'-6" 5'-11 1/4" 3'-9 1/2" 28'-9 1/4" PIER@CONC. SLAB.
16" x 8" CONC. FOOTING (TYP.)
REVISIONS
2'-0"
2'-0"
T
12/28/2023
11'-11 1/2"
DATE
5
2'-11" 14'-0 1/2" 13'-0"
8'-0"
5'-7 1/4"
BEAM
6'-0"
adhote
4
GARAGE FLOOR
4" CONC. SLAB OVER 4" COMPACTED GRANULAR & FILL.
36''x36''x10'' CONC. FOOTING
28'-6"
APPROVED POST CAP
PROVIDE 1/2" FIBERBOARD EXPANSION JOINTS & SLAB
7
PERMITER AND CONTROL JOINTS AT 10" O.C. BOTH
2'-4 3/4"
2'-0"
29'-3"
6x6 POST
1'-11" 12'-4"
SLOPE
8'-0" 15'-4 1/2" 29'-11 1/2"
22'-0"
E
53'-4"
HideLargepost
6 2 6
SIMPSON POST BAST OR
EQUAL
6 2 6
2'-6"
24" Ø x 24" CONCRETE
2'-0"
3'-5" 18'-2" 3'-5" 3'-0" 10'-2" 3'-4"
25'-0" 16'-6"
41'-6"
DESCRIPTION
2'-0"
site
FOUNDATION PLAN POST DETAIL
1 2
In Folder
1/4" = 1'-0" 1/2" = 1'-0"
NO.
0
Add
SHEET TITLE
FOUNDATION
plan Walthracing
PLAN
All
GENERAL CONDITIONS
DRAWINGS & SPECIFICATIONS RHD PROJECT NUMBER: RHD-1027
IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS TO BE GUIDELINES
NOTE: RISEN HOME DESIGN PLANS DO NOT CARRY AN FOR CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING DRAWN BY: RMC DATE:12/28/2023
ENGINEER'S AND/OR ARCHITECT'S STAMP(S) SOME ANY QUESTIONS AND MEANINGS IN THE WORKING DRAWINGS AND
CONDITIONS MAY ARISE DURING DESIGN. AND/OR CHECKED BY: MM DATE:12/28/2023
SPECIFICATIONS AND THE CONTRACTOR SHALL NOTIFY THE DESIGNER IN
CONSTRUCTION THAT MAY REQUIRE AN ARCHITECT'S AND/OR WRITING OF ANY ERRORS, OMISSIONS, OR UNSUITABLE DETAILING WHICH MAY DRAWING NUMBER: REV:
ENGINEER'S STAMP TO COMPLY WITH LOCAL BUILDING CAUSE CONSTRUCTION PROBLEMS. THE DESIGNER'S LIABILITY REGARDING
CODES. THE CONTRACTOR IS TO VERIFY THESE CONDITIONS
AND SECURE REQUIRED STAMPS PRIOR TO CONSTRUCTION
ERRORS AND/OR OMMISSIONS WILL BE LIMITED TO THE CORRECTION OF THE
ORIGINAL DRAWINGS. CONSULTANT'S LITABILITY IS THE SAME. A2.0 0
390 E CORPORATE DRIVE STE 112
FLOOR PLAN NOTES
MERIDIAN, ID 83642
1. ALL STRUCTURAL LUMBER SIDED FOR #2 OR BETTER
#208-283-3775
DOUG FIR LARCH.
2. 2x EXTERIOR STUD FRAMING @ 16' O.C. W/ SINGLE BOTTOM
PLATE AND DOUBLE TOP PLATE.
94'-10" 3. 4x8 HEADERS IN ALL BEARING WALL OPENING UNLESS
OTHERWISE NOTED.
6'-0" 15'-0" 20'-11" 13'-5" 18'-0" 5'-6" 16'-0" 4. ALLOW FOR A 22' x 30' (MIN) ATTIC AND CRAWL SPACE
ACCESS.
6x6 P.T. POST (TYP.)
l
5. ALL METAL CONNECTIONS TO BE SIMPSON CO. OR BETTER
6. 5/8" TYPE 'X' GYP BOARD @ ALL GARAGE COMMON
l l l l
WALLS AND CEILINGS APPLIED TO GARAGE SIDE AND
ALL WALLS, BEAMS, POSTS AND OTHER STRUCTURAL
MEMBERS SUPPORTING FIRE PROTECTED HORIZONTAL
STRUCTURAL MEMBERS.
(2)1 3/4"x11 7/8" 7. DOORS BETWEEN GARAGE AND DWELLING ARE TO BE SELF
CLOSING AND TIGHT FITTING SOLID WOOD DOOR 1 3/8" THICK
OR A DOOR W/ A FIRE PROTECTION RATING OF NOT LESS
8'-6"
4'-6"
(2)1 3/4"x11 7/8"
THAN 20 MINUTES.
12'-0"
HOUSE.
5'-10 3/4" 3'-4" 5'-9 1/4" COVERED PATIO A4.1 30/60 SH 30/60 SH 9. ALL WINDOWS TO HAVE BREATHER TUBES INSTALLED.
VAULTED CEILING 10. ROOF SYSTEM TO BE PRE-ENGINEERED MANUFACTURED
W.I.C.
15'-6"
1 ROOF TRUSSES UNLESS OTHERWISE NOTED.
30/60 SH 30/60 SH 11. ALL CONSTRUCTION PRACTICES USED IN THE CONSTRUCTION
of Risen Home Design. These drawings are NOT to be reproduced, copied whole or in part, disclosed,
26
5'-5 1/2"
used for construction or any other purpose without prior written permission from Risen Home Design.
OF THIS DWELLING SHALL BE DONE IN ACCORDANCE W/ THE
5'-6"
5'-0"
(2) 2x10 (2) 2x10 2018 WHERE APPLICABLE.
2'-6"
R&S
11'-9 1/2" 2 1 12. VENT RANGE HOOD, FANS, AND DRYER TO OUTSIDE AIR.
30/20 PW
9'-6"
30 BEDROOM#3 R&S PRIOR TO COMMENCING WORK.
30/60 SH 30/60 SH
7'-0"
7'-0"
10' CEILING 13. ALL RESCUE WINDOWS FROM SLEEPING AREAS MUST MEET
11'-8"
EQ EQ THE FOLLING REQUIREMENTS:
MASTER (2) 2x10 (2) 2x10 5'-0" 1. SHALL HAVE A NET CLEAR OPENING OF 5.1 SQ. FT.
5'-5 1/2" 5'-0" 5'-0" 5'-5 1/2"
26/60 SH
BEDROOM
These Drawings contain confidential proprietary information and are the property
2. MINIMUM HEIGHT OF 24".
3'-6"
10' CEILING 3. MINIMUM WIDTH OF 20".
5'-11"
30/60 SH 30/60 SH 4. FINISHED SILL HEIGHT OF NOT MORE THAN 44".
14'-0"
9'-7 1/2"
14'-2"
9'-7 1/2"
14'-1" 60/80 BATH#3 15. ALL FURNACE SWITCHES, PILOTS, AND BURNERS TO BE MINIMUM
9'-5"
DINING 10' CEILING R&S 18" ABOVE FINISHED FLOOR.
BUILT-IN
5'-3 1/2"
10' CEILING
30
5'-11 1/2"
W.I.C.
WALKER RESIDENCE
R&S
IFF
5'-2 1/2"
3'-9 1/2"
7'-4"
3'-6"
2'-0"
30/20 PW
28
(2) 2x8
VAULT LINE
1'-10 1/2"
26
Fireplace
30 5S 7'-3" 5'-8"
GREAT ROOM
1'-0"
5'-0"
26
1 2 VAULTED CEILING 30
18'-5 1/2"
6'-9 1/4" 3'-6" 6'-7 1/4" 3'-8" 2'-3 1/2" 17'-0" 3'-1" 3'-6" 3'-6" 5'-11" 6'-7" 3'-6" 12'-11"
5'-11 1/2"
7'-10 1/2"
R&S
5'-9"
4'-3 1/2"
5'-7"
8'-0"
W.I.C.
5'-0"
W.I.C.
5S
26
DW
STAIRS UP
A4.1 2 BEDROOM#4 DOOR/WINDOW TAG EXAMPLE
7'-4"
12'-0 1/2"
12'-9 1/2"
50/40 SL
BUILT-IN
(2) 2x10
40'-6"
Rangetop
6'-1"
3'-0'' OPENING
6'-0"
5'-7 1/2"
4'-2 1/2"
FURN
4'-11"
4'-0"
30/60 SH
12'-2"
-
8'-2" 3'-5" 5'-3 1/2" 5'-9" 10'-4" 4'-2" 15'-0 1/2" BELOW
4"
(2) 2x10
1'-3 1/2"
56'-0"
24
20 7'-0'' OPENING 3'-10 1/2" Refrigerator 50
REVISIONS
1'-3"
28
ENTRY
R&S
3'-7"
28 24
12/12/2023
12/19/2023
12/20/2023
12/28/2023
3'-7"
3'-0"
3'-7"
DATE
5S 5'-0" BATH#2
7'-0 1/2"
FD
10' CEILING
8'-7"
30
1 30 5'-0" UTILITY
3'-5 1/2"
7'-3 1/2"
7'-0"
7'-9"
24
A7.1
36/80 5S
10' CEILING 3 A4.0 SQ/FT.
(2) 2x10
1st FLOOR 2275 SF
40/20 SL Dryer Washer BONUS ROOM 327 SF
BEDROOM#2
2'-0"
2'-0"
ABOVE
6'-5 1/2"
R&S
28'-6"
(2)1 3/4"x11 7/8"
(2)1 3/4"x11 7/8"
30'-6 1/2"
30/60 SH 30/60 SH
2'-0"
9 1/2"
22'-0"
22'-1"
8'-0" 15'-4 1/2" 1'-11" 1'-7" 9'-2" 1'-7" 15'-8 1/2"
2
A4.0
29'-11 1/2"
DESCRIPTION
1 1/4" = 1'-0"
(2) 1 3/4'' x 11 7/8''
2'-6"
180/80 OVERHEAD DR.
NO.
3'-6" 18'-0" 3'-6" 3'-1" 10'-0" 3'-5"
C
A
B
0
SHEET NOTES 25'-0" 16'-6"
GENERAL CONDITIONS
TABLE R402.1.1 DRAWINGS & SPECIFICATIONS
INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT RHD PROJECT NUMBER: RHD-1027
SEE 2018 IRC IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS TO BE GUIDELINES
NOTE: RISEN HOME DESIGN PLANS DO NOT CARRY AN FOR CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING DRAWN BY: MM DATE:12/12/2023
CLIMATE ZONE FENESTRATION SKYLIGHT GLAZED CEILING WOOD FRAM MASS FLOOR BASEMENT SLAB CRAWLSPACE ENGINEER'S AND/OR ARCHITECT'S STAMP(S) SOME ANY QUESTIONS AND MEANINGS IN THE WORKING DRAWINGS AND
R302.7 PROVIDE UNDERSTAIR PROTECTION AS REQUIRED CHECKED BY: DATE:12/12/2023
U-FACTOR U-FACTOR FENESTRATION R-VALUE WALL R-VALUE WALL R-VALUE WALL R-VALUE WALL CONDITIONS MAY ARISE DURING DESIGN. AND/OR SPECIFICATIONS AND THE CONTRACTOR SHALL NOTIFY THE DESIGNER IN -
R302.11 PROVIDE FIREBLOCKING AS REQUIRED
SHGC R-VALUE R-VALUE R-VALUE R303.7 PROVIDE SWITCHING AND ILLUMINATION AS REQUIRED CONSTRUCTION THAT MAY REQUIRE AN ARCHITECT'S AND/OR WRITING OF ANY ERRORS, OMISSIONS, OR UNSUITABLE DETAILING WHICH MAY DRAWING NUMBER: REV:
NOTE: VERIFY ALL WINDOW/DOOR ROUGH OPENING AND R305 PROVIDE SUFFICIENT CEILING HEIGHTS ENGINEER'S STAMP TO COMPLY WITH LOCAL BUILDING CAUSE CONSTRUCTION PROBLEMS. THE DESIGNER'S LIABILITY REGARDING
5 AND
MARINE 4 0.35 0.60 NR 38 20 OR 13+5 h 13/17 30 g 10/13 10, 2 ft 10/13 HEADER HEIGHT AND THE SAME FOR TRIM PACKAGE. VERIFY
STANDARD HEIGHTS WITH CONTRACTOR BEFORE FRAMING.
R311.7 MEET STAIRWAY REQUIREMENTS
R312 MEET GUARD REQUIREMENTS
CODES. THE CONTRACTOR IS TO VERIFY THESE CONDITIONS
AND SECURE REQUIRED STAMPS PRIOR TO CONSTRUCTION
ERRORS AND/OR OMMISSIONS WILL BE LIMITED TO THE CORRECTION OF THE
ORIGINAL DRAWINGS. CONSULTANT'S LITABILITY IS THE SAME. A3.0 0
all
MERIDIAN, ID 83642
#208-283-3775
74
1-1 2-1 3-1 4-1
an
COVERED PATIO
WSP
A4.1
C-1
of Risen Home Design. These drawings are NOT to be reproduced, copied whole or in part, disclosed,
1
used for construction or any other purpose without prior written permission from Risen Home Design.
WSP WSP
WSP
WSP
CS-WSP W.I.C.
t.FI I
These Drawings contain confidential proprietary information and are the property
BEDROOM#3
i
MASTER WSP
BEDROOM
DINING BATH#3
WALKER RESIDENCE
WSP
GB GB W.I.C.
WSP
Forefext
A4.1 2
BEDROOM#4
MASTER KITCHEN
WH
BATHROOM
-
WSP REVISIONS
43
WSP WSP
12/28/2023
DATE
WSP
B
ENTRY
FD BATH#2
UTILITY
WSP
3 A4.0
BEDROOM#2 CS-WSP
ABW
WSP WSP
WSP
WSP
COVERED PORCH
WSP
3-CAR GARAGE
A4.0
DESCRIPTION
A-1
WSP
PFG PFG
NO.
0
PFG PFG
SHEET TITLE
shearwalt
SHEAR WALL
PLAN
12
12 10
10
(APPROX. HEIGHT)
23'-10 3/4"
of Risen Home Design. These drawings are NOT to be reproduced, copied whole or in part, disclosed,
used for construction or any other purpose without prior written permission from Risen Home Design.
These Drawings contain confidential proprietary information and are the property
WALKER RESIDENCE
FRONT VIEW
2 1/4" = 1'-0"
ELEVATIONS
-
STAIRS DN.
REVISIONS
12/12/2023
12/19/2023
12/20/2023
12/28/2023
DATE
2'-7" 3'-6" 5'-11"
2'-4 1/2"
CLOSET
24
BONUS ROOM 12
6
12
6
27'-2 1/2"
27'-2 1/2"
12'-0"
C
A
B
0
30/50 SH 30/50 SH
4'-4" 3'-4" 4'-4"
RIGHT VIEW
12'-0" 3 1/4" = 1'-0"
SHEET TITLE
ELEVATIONS
BONUS ROOM
1 1/4" = 1'-0"
GENERAL CONDITIONS
DRAWINGS & SPECIFICATIONS RHD PROJECT NUMBER: RHD-1027
IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS TO BE GUIDELINES
NOTE: RISEN HOME DESIGN PLANS DO NOT CARRY AN FOR CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING DRAWN BY: MM DATE:12/12/2023
ENGINEER'S AND/OR ARCHITECT'S STAMP(S) SOME ANY QUESTIONS AND MEANINGS IN THE WORKING DRAWINGS AND
CONDITIONS MAY ARISE DURING DESIGN. AND/OR CHECKED BY: - DATE:12/12/2023
SPECIFICATIONS AND THE CONTRACTOR SHALL NOTIFY THE DESIGNER IN
CONSTRUCTION THAT MAY REQUIRE AN ARCHITECT'S AND/OR WRITING OF ANY ERRORS, OMISSIONS, OR UNSUITABLE DETAILING WHICH MAY DRAWING NUMBER: REV:
ENGINEER'S STAMP TO COMPLY WITH LOCAL BUILDING CAUSE CONSTRUCTION PROBLEMS. THE DESIGNER'S LIABILITY REGARDING
CODES. THE CONTRACTOR IS TO VERIFY THESE CONDITIONS
AND SECURE REQUIRED STAMPS PRIOR TO CONSTRUCTION
ERRORS AND/OR OMMISSIONS WILL BE LIMITED TO THE CORRECTION OF THE
ORIGINAL DRAWINGS. CONSULTANT'S LITABILITY IS THE SAME. A4.0 0
390 E CORPORATE DRIVE STE 112
MERIDIAN, ID 83642
#208-283-3775
12 12
10 10
of Risen Home Design. These drawings are NOT to be reproduced, copied whole or in part, disclosed,
used for construction or any other purpose without prior written permission from Risen Home Design.
These Drawings contain confidential proprietary information and are the property
BACK VIEW
1
WALKER RESIDENCE
1/4" = 1'-0"
12
6
ELEVATIONS
12
-
6
REVISIONS
12/19/2023
12/20/2023
12/28/2023
DATE
LEFT VIEW
2 1/4" = 1'-0"
3D VIEW
3 GENERAL CONDITIONS
DRAWINGS & SPECIFICATIONS RHD PROJECT NUMBER: RHD-1027
IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS TO BE GUIDELINES
NOTE: RISEN HOME DESIGN PLANS DO NOT CARRY AN FOR CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING DRAWN BY: MM DATE:12/19/2023
ENGINEER'S AND/OR ARCHITECT'S STAMP(S) SOME ANY QUESTIONS AND MEANINGS IN THE WORKING DRAWINGS AND
CONDITIONS MAY ARISE DURING DESIGN. AND/OR CHECKED BY: - DATE:12/19/2023
SPECIFICATIONS AND THE CONTRACTOR SHALL NOTIFY THE DESIGNER IN
CONSTRUCTION THAT MAY REQUIRE AN ARCHITECT'S AND/OR WRITING OF ANY ERRORS, OMISSIONS, OR UNSUITABLE DETAILING WHICH MAY DRAWING NUMBER: REV:
ENGINEER'S STAMP TO COMPLY WITH LOCAL BUILDING CAUSE CONSTRUCTION PROBLEMS. THE DESIGNER'S LIABILITY REGARDING
CODES. THE CONTRACTOR IS TO VERIFY THESE CONDITIONS
AND SECURE REQUIRED STAMPS PRIOR TO CONSTRUCTION
ERRORS AND/OR OMMISSIONS WILL BE LIMITED TO THE CORRECTION OF THE
ORIGINAL DRAWINGS. CONSULTANT'S LITABILITY IS THE SAME. A4.1 0
ROOF NOTES
MERIDIAN, ID 83642
2. ALL ROOF AND SOFFIT VENTS TO BE INSTALLED ACCORDING TO U.B.C. AND
#208-283-3775
APPLICABLE LOCAL CODES.
3. ALL TOTAL SPANS MAY VARY DEPENDING ON GIRDER TRUSS PLACEMENT. (IF
NEEDED)
21'-10" 4. ALL WINDOW HEADERS, GARAGE DOOR HEADER AND MICRO-LAM BEAMS UNDER
ROOF LOAD TO BE SPECIFIED BY LOCAL TRUSS COMPANY.
5. TRUSS COMPANY TO CONFIRM DESIGN ROOF SNOW LOAD SHOWN WITH COUNTY
REQUIREMENTS OF THIS HOUSE LOCATION.
DESIGN CRITERIA
CALDWELL
LOCATION: (CITY)_______________ (COUNTY)______________
CANYON
18'-0"
e
• 30PSF
DESIGN ROOF SNOW LOAD: ______________
• 115MPH
DESIGN WIND SPEED:___________
• --
DESIGN WIND EXPOSURE TYPE:____________
• DESIGN EARTH QUAKE ZONE:______________
D1
• 24"
FROST DEPTH:____________
10:12 10:12
3:12
of Risen Home Design. These drawings are NOT to be reproduced, copied whole or in part, disclosed,
Middleton
used for construction or any other purpose without prior written permission from Risen Home Design.
10:12
10:12
6:12
These Drawings contain confidential proprietary information and are the property
6:12
WALKER RESIDENCE
6:12
10:12
lane
6:12
32'-6"
6:12
ROOF PLAN
0
6:12
18'-6"
-
REVISIONS
12/28/2023
6:12
DATE
6:12
10:12
10:12
10:12 10:12
3:12
28'-6"
15'-4 1/2"
6:12
12'-3 1/2"
frIii
DESCRIPTION
oI62
NO.
89
0
25'-0"
1
ROOF PLAN SHEET TITLE
1/4" = 1'-0"
ROOF PLAN
GENERAL CONDITIONS
DRAWINGS & SPECIFICATIONS RHD PROJECT NUMBER: RHD-1027
IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS TO BE GUIDELINES
NOTE: RISEN HOME DESIGN PLANS DO NOT CARRY AN FOR CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING DRAWN BY: RMC DATE:12/28/2023
ENGINEER'S AND/OR ARCHITECT'S STAMP(S) SOME ANY QUESTIONS AND MEANINGS IN THE WORKING DRAWINGS AND
CONDITIONS MAY ARISE DURING DESIGN. AND/OR CHECKED BY: MM DATE:12/28/2023
SPECIFICATIONS AND THE CONTRACTOR SHALL NOTIFY THE DESIGNER IN
CONSTRUCTION THAT MAY REQUIRE AN ARCHITECT'S AND/OR WRITING OF ANY ERRORS, OMISSIONS, OR UNSUITABLE DETAILING WHICH MAY DRAWING NUMBER: REV:
ENGINEER'S STAMP TO COMPLY WITH LOCAL BUILDING CAUSE CONSTRUCTION PROBLEMS. THE DESIGNER'S LIABILITY REGARDING
CODES. THE CONTRACTOR IS TO VERIFY THESE CONDITIONS
AND SECURE REQUIRED STAMPS PRIOR TO CONSTRUCTION
ERRORS AND/OR OMMISSIONS WILL BE LIMITED TO THE CORRECTION OF THE
ORIGINAL DRAWINGS. CONSULTANT'S LITABILITY IS THE SAME. A5.0 0
ELECTRICAL LEGEND
MERIDIAN, ID 83642
3
#208-283-3775
4-WAY SWITCH GD GARAGE DOOR
4 BUTTON
3
FLOOD
of Risen Home Design. These drawings are NOT to be reproduced, copied whole or in part, disclosed,
used for construction or any other purpose without prior written permission from Risen Home Design.
CASTER CLOSET CASTER LIGHT UC UNDER CABINET
S LIGHT
These Drawings contain confidential proprietary information and are the property
CS GFI RECTANGULAR
FR
ROUND
3 3
3
S
CF
S
CEILING FAN LIGHT w/ FAN
ROUGH
3
LCF LCF
WALKER RESIDENCE
ROUGH
GFI GFI
220V GFI
WH
220V
I
3
CS
GFI CS 3
GFI GFI
3
FD
GFI
-
4 REVISIONS
220V GFI
GFI GFI
12/28/2023
DATE
I GFI
3
CS
GFI
GFI
GFI
DESCRIPTION
1/4" = 1'-0"
NO.
0
SHEET TITLE
BONUS ROOM ELECTRICAL PLAN ELECTRICAL
2 1/4" = 1'-0"
PLAN
GENERAL CONDITIONS
DRAWINGS & SPECIFICATIONS RHD PROJECT NUMBER: RHD-1027
IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS TO BE GUIDELINES
NOTE: RISEN HOME DESIGN PLANS DO NOT CARRY AN FOR CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING DRAWN BY: RMC DATE:12/28/2023
ENGINEER'S AND/OR ARCHITECT'S STAMP(S) SOME ANY QUESTIONS AND MEANINGS IN THE WORKING DRAWINGS AND
CONDITIONS MAY ARISE DURING DESIGN. AND/OR CHECKED BY: MM DATE:12/28/2023
SPECIFICATIONS AND THE CONTRACTOR SHALL NOTIFY THE DESIGNER IN
CONSTRUCTION THAT MAY REQUIRE AN ARCHITECT'S AND/OR WRITING OF ANY ERRORS, OMISSIONS, OR UNSUITABLE DETAILING WHICH MAY DRAWING NUMBER: REV:
ENGINEER'S STAMP TO COMPLY WITH LOCAL BUILDING CAUSE CONSTRUCTION PROBLEMS. THE DESIGNER'S LIABILITY REGARDING
CODES. THE CONTRACTOR IS TO VERIFY THESE CONDITIONS
AND SECURE REQUIRED STAMPS PRIOR TO CONSTRUCTION
ERRORS AND/OR OMMISSIONS WILL BE LIMITED TO THE CORRECTION OF THE
ORIGINAL DRAWINGS. CONSULTANT'S LITABILITY IS THE SAME. A6.0 0
390 E CORPORATE DRIVE STE 112
FASTEN BRCING
7/16" OSB SHEATHING ≤10FT. FROM EDGE OF MATERIAL AS REQUIRED
BRACED WALL TO START BY TABLE R602.3(3)
MERIDIAN, ID 83642
OF WALL BRACE ≤20 FT. BETWEEN CLOSET
#208-283-3775
30 YR. COMP. ROOFING EDGES OF WALL BRACES
OVER #15 BLDG. FELT
1'-4"
of Risen Home Design. These drawings are NOT to be reproduced, copied whole or in part, disclosed,
used for construction or any other purpose without prior written permission from Risen Home Design.
BOXED SOFFET WITH
REQUIRED VENTING
These Drawings contain confidential proprietary information and are the property
NOTES:
WALKER RESIDENCE
3 SPECIAL REBAR PLACEMENT TO BE: 2-#4 REBAR IN FOOTING AND 2-#4 HORZ. REBAR IN
STEM WALL EQUALLY SPACED AND VERTICAL #4 REBAR@ 4'o.c. IN ALL 2' EXTERIOR
CONCRETE STEM WALLS. REFERENCE FOUNDATION PLAN A3.0 FOR COUNTY
REQUIREMENTS AND NOTES.
WSP DETAIL
2 3/4" = 1'-0"
2 x 6 STUDS @ 16" o.c.
R-21 EXT. WALL INSULATION
SIDING AS NOTED ON ELEVATIONS (TYP.)
1/2" SHEETROCK
7/16 WAFERBOARD SHEATHING
DETAILS
3/4" OSB T& G FLOOR EXTENT OF HEADER
P.T. 2 X 6 FIR MUD-SILL GLUE & NAIL TO FLOOR JOISTS
SINGLE PORTAL FRAME(ONE BRACED WALL PANEL)
SIMPSON OR EQUAL JOIST HANGER (TYP.)
1/2"x 10" LG. CONCRETE
BOLTS @ 6'-0" O.C. EXTENT OF HEADER
SINGLE PORTAL FRAME(ONE BRACED WALL PANEL)
X"min. 1
-
2% Grade 9 1/2" TJI-150 @ 24" o.c. 11-1/4" DEEP HEADER (MIN)
12/28/2023
6" THICK STEM WALL PER PLAN 1000lb STRAP
DATE
TYPICAL PORTAL FRAME
SPECIAL REBAR PLACEMENT & REQUIEMENTS SEE NOTE 3 2 x 4 PONY WALL STACKED ON 1000lb STRAP OPPOSITE SHEATHING CONSTRUCTION
8" CONT. CONC. FOOTING.
(Stack 2x4 cripple under each Joist)
STANDARD REBAR PLACEMENT & REQUIREMENTS
2
SEE NOTE 2
8"
8"
.006 VISQUEEN GROUND COVER
MAX. HEIGHT
MIN. 2x4 FRAMING 5
MIN. DOUBLE
10'-0"
2x4 POST
3
1'-4" 1'-4"
WALL SECTION
1 1" = 1'-0" 3/8" MIN. THICKNESS
WOOD STRUCTURAL
PANEL SHEATHING
4
MIN. 1000lb TIE-DOWN
DEVICE
1'-4" 1'-4" 1'-4" 1'-4" 1'-4" 1'-4" 1'-4" 1'-4" 1'-4" SEE SECTION R602.10.3.3
2'-0"
DOUBLE TOP
HEADROOM
PLATE
6'-8" Min.
LOAD BEARING HEADER
2 FASTEN SHEATHING TO HEADER WITH 8d COMMON OR GALVANIED BOX NAILS IN 3in. GRID
PATTERN AS SHOWN AND 3in. o.c. IN ALL FRAMING (STUDS, BLOCKING, AND SILLS) (TYP.)
DESCRIPTION
TYPICAL WINDOW 4" Min.
3 MIN. LENGTH = 16in. FOR ONE STORY, MIN. LENGHT = 24in FOR USE IN THE FIRST OF TWO
ROUGH OPENING
STORY STRUCTURES.
4 MIN 4200lb TIE-DOWN (EBEDDED INTO CONCRETE AND NAILED INTO FRAMING).
DOOR
2'-10"
WINDOW SILL
7 3/4" Max.
(ROUGH OPENIGN) 5 FOR A PANEL SPLICE (IF NEEDED), PANEL EDGES SHALL OCCUR OVER AND BE NAILED TO
NO.
FRAMING
0
COMMON BLOCKING AND OCCUR WITHIN MIDDLE 24in. OF WALL HEIGHT. ONE ROW OF 3in. o.c.
NAILING IS REQUIRED IN EACH PANEL EDGE.
10" Min.
SHEET TITLE
CRIPPLE TRIMMER STUD
STUD STAIR DETAIL PORTAL FRAME HOLD-DOWN DETAIL DETAILS
4 1/4" = 1'-0"
5 1/2" = 1'-0"
GENERAL CONDITIONS
FRAMING DETAIL DRAWINGS & SPECIFICATIONS RHD PROJECT NUMBER: RHD-1027
3 1/2" = 1'-0" NOTE: RISEN HOME DESIGN PLANS DO NOT CARRY AN
IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS TO BE GUIDELINES
FOR CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING DRAWN BY: RMC DATE:12/28/2023
ENGINEER'S AND/OR ARCHITECT'S STAMP(S) SOME ANY QUESTIONS AND MEANINGS IN THE WORKING DRAWINGS AND
CONDITIONS MAY ARISE DURING DESIGN. AND/OR CHECKED BY: MM DATE:12/28/2023
SPECIFICATIONS AND THE CONTRACTOR SHALL NOTIFY THE DESIGNER IN
CONSTRUCTION THAT MAY REQUIRE AN ARCHITECT'S AND/OR WRITING OF ANY ERRORS, OMISSIONS, OR UNSUITABLE DETAILING WHICH MAY DRAWING NUMBER: REV:
ENGINEER'S STAMP TO COMPLY WITH LOCAL BUILDING CAUSE CONSTRUCTION PROBLEMS. THE DESIGNER'S LIABILITY REGARDING
CODES. THE CONTRACTOR IS TO VERIFY THESE CONDITIONS
AND SECURE REQUIRED STAMPS PRIOR TO CONSTRUCTION
ERRORS AND/OR OMMISSIONS WILL BE LIMITED TO THE CORRECTION OF THE
ORIGINAL DRAWINGS. CONSULTANT'S LITABILITY IS THE SAME. A7.0 0
390 E CORPORATE DRIVE STE 112
MERIDIAN, ID 83642
#208-283-3775
of Risen Home Design. These drawings are NOT to be reproduced, copied whole or in part, disclosed,
used for construction or any other purpose without prior written permission from Risen Home Design.
P.E. ROOF TRUSSES
QHis.gg qulatn
MIN. R-49 INSULATION
These Drawings contain confidential proprietary information and are the property
MIN. R-21 INSULATION
WALKER RESIDENCE
Hide
BUILDING SECTION 1
1 1/4" = 1'-0"
-
REVISIONS
12/28/2023
DATE
P.E. ROOF TRUSSES
NO.
0
SHEET TITLE
BUILDING SECTION 2
2 1/4" = 1'-0"
CUT SECTION
VIEWS
GENERAL CONDITIONS
DRAWINGS & SPECIFICATIONS RHD PROJECT NUMBER: RHD-1027
IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS TO BE GUIDELINES
NOTE: RISEN HOME DESIGN PLANS DO NOT CARRY AN FOR CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING DRAWN BY: RMC DATE:12/28/2023
ENGINEER'S AND/OR ARCHITECT'S STAMP(S) SOME ANY QUESTIONS AND MEANINGS IN THE WORKING DRAWINGS AND
CONDITIONS MAY ARISE DURING DESIGN. AND/OR CHECKED BY: MM DATE:12/28/2023
SPECIFICATIONS AND THE CONTRACTOR SHALL NOTIFY THE DESIGNER IN
CONSTRUCTION THAT MAY REQUIRE AN ARCHITECT'S AND/OR WRITING OF ANY ERRORS, OMISSIONS, OR UNSUITABLE DETAILING WHICH MAY DRAWING NUMBER: REV:
ENGINEER'S STAMP TO COMPLY WITH LOCAL BUILDING CAUSE CONSTRUCTION PROBLEMS. THE DESIGNER'S LIABILITY REGARDING
CODES. THE CONTRACTOR IS TO VERIFY THESE CONDITIONS
AND SECURE REQUIRED STAMPS PRIOR TO CONSTRUCTION
ERRORS AND/OR OMMISSIONS WILL BE LIMITED TO THE CORRECTION OF THE
ORIGINAL DRAWINGS. CONSULTANT'S LITABILITY IS THE SAME. A7.1 0