2. CONSTRUCTION TESTING
YES NO Remarks:
3. AS-BUILT DRAWINGS
YES NO Remarks:
Company
Signature
Print name
Date
General Comments:
Conforme
Item No. Descriptions Comments
Yes No
Is the LVS conform in accordance with the approved plans,
1
shopdrawing/submittals, and specification. ü
Are the bus bar joint connection/bolts has been tighthen base
2
on their required torqued. ü
3 Inspect anchorage, alignment, grounding, and required area clearances
ü
Verify that the current and voltage transformer ratios corresponds to drawing.
4
ü
Verify that fuse and/or circuit breaker sizes and type corresponds to the drawings.
5
ü
I s the equipment grounding has been check and tested.
6
ü
Lubrication requirements:
7 •
•
Verify appropriate lubrication on moving current-carrying parts.
Verify appropriate lubrication on moving and sliding surfaces.
ü
Are LVS Interlocks operational.
8 •
•
Mechanical Interlock
Electrical Interlock
ü
Is the LVS Control Interface to Generator Sychronizing Panel
9
Control has been completed. ü
Check if the all the contruction punchlist has been completed, the
10
euipment are clean and the area are secured. ü
LEGEND: P - YES / NO N/A - Not Applicable
Noted by:
Owner Representative Signature Date
Remarks :
Conforme
Item No. Descriptions Comments
Yes No
ü
Verify correct functioning of drw-out disconnecting and grounding contacts and
15 interlocks.
ü
Verify / Check if LVS load schedule and wiring diagram are attached inside the panel
16 enclosure
ü
Verify if insulation resistance test for main bus and sections are performed or
17 conducted
Noted by:
Owner Representative Signature Date
Remarks :
GENERAL DATA
Feeder Description System Voltage
Breaker Type Short Circuit (KAIC) RATING
Ampere Trip (AT) (rms or symmetrical)
Ampere Frame Serial Number
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting x ln
trip
(G) setting x ln
Earth Fault (G) trip
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism
Breaker closing mecahnism
Breaker tripping mechanism
Mechanical interlocking
Breaker withdrawing facilities
Breaker on and off indication
Padlocking facilities
LEGEND: P - YES / NO N/A - Not Applicable
Noted by:
Owner Representative Signature Date
Remarks :
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
WINDING RESISTANCE TESTER METREL/MI 3200 15031185 03-230253-H001
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
Line Side Load Side Load Side Line Side (Volts) (Amps) (Hz)
LINE 1 - LINE 2
LINE 2 - LINE 3
LINE 1 - LINE 3
LINE 1 - NEUTRAL
LINE 2 - NEUTRAL
LINE 3 - NEUTRAL
LINE 1 - GROUND
LINE 2 - GROUND
LINE 3 - GROUND
NEUTRAL - GROUND
B. TRANSFER SWITCH OPERATIONAL / FUNCTIONAL TEST
1. Auto Mode :
Yes No Remarks
1.1 Normal Power to Emergency Power (Timer Setting :_________secs.)
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
Date: Time: Dry Bulb Temp.: Wet Bulb Temp.: Relative Humidity:
LEGEND: P - YES / NO N/A - Not Applicable
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
ENCLOSURE TYPE :
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
Noted by:
Owner Representative Signature Date
Remarks :
TEST RESULT
DESCRIPTION STATUS
REMARKS
MANUAL OPERATIONS Functioning Mal-Functioning
1. Normal Breaker On and Off
2. Emergency Breaker On and Off
ELECTRICAL OPERATIONS
1. Normal Breaker On and Off
2. Emergency Breaker On and Off
BREAKER INTERLOCKING
1. Normal Breaker On-Emergency Breaker Interlock
2. Normal Breaker Off-Emergency Breaker Operates
3. Emergency Breaker On-Normal Breaker Interlock
4. Emergency Breaker Off-Normal Breaker Operates
AUTOMATIC TRANSFER
1. Normal - Emergency
2. Emergency - Normal
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
Noted by:
Owner Representative Signature Date
Remarks :
EQUIPMENT DATA
MANUFACTURER / BRAND :
LVS NAME :
ENCLOSURE TYPE :
VOLTAGE / PHASE / FREQUENCY :
Timer : Ammeter :
Switches : Others :
Noted by:
Owner Representative Signature Date
Remarks :
Location :
Site : Carmona, Cavite
Area Served :
Description :
Project : TIM DATA CENTER Equipment Tag No. :
System ID :
ITEM COMPLIANCE
PUNCHLIST DESCRIPTION REMARKS
No. YES NO
EQUIPMENT RELATED
WORKMANSHIP
DOCUMENTS RELATED
Noted by:
Owner Representative Signature Date
Remarks :