LVSG REV004

You might also like

You are on page 1of 65

TIM DATA CENTER

GENCON OR
PM LOGO
Carmona, Cavite

TESTING AND COMMISSIONING

SYSTEMS NUMBERING INFORMATION ATTACHMENTS

DESCRIPTION : Low Voltage Switch Board — PRE-FUNCTIONAL TESTS (PFT)


SYSTEM I.D. : EL-008 — FUNCTIONAL PERFORMANCE TESTS (FPT)
SYSTEM No. : TIM-CTR-045 — ISSUES LOG
EQUIPMENT TAG : LVSB ME-A

CONSTRUCTION TEST RECORDS

1. EQUIPMENT SUBMITTAL APPROVAL


YES NO Remarks:

2. CONSTRUCTION TESTING
YES NO Remarks:

3. AS-BUILT DRAWINGS
YES NO Remarks:

VERIFICATION / VALIDATION AND SIGN OFF

Test carried-out by Attested & Witnessed by Accepted by Accepted by

Company

Signature

Print name

Date

General Comments:

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR
Location : GROUND FLOOR
Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008
PRE-FUNCTIONAL CHECKLIST
PRIOR TO ENERGIZATION OF LOW VOLTAGE SWITCHGEAR
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : LVSB ME-A
MAIN BUS RATING : 5000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

Conforme
Item No. Descriptions Comments
Yes No
Is the LVS conform in accordance with the approved plans,
1
shopdrawing/submittals, and specification. ü
Are the bus bar joint connection/bolts has been tighthen base
2
on their required torqued. ü
3 Inspect anchorage, alignment, grounding, and required area clearances
ü
Verify that the current and voltage transformer ratios corresponds to drawing.
4
ü
Verify that fuse and/or circuit breaker sizes and type corresponds to the drawings.
5
ü
I s the equipment grounding has been check and tested.
6
ü
Lubrication requirements:
7 •

Verify appropriate lubrication on moving current-carrying parts.
Verify appropriate lubrication on moving and sliding surfaces.
ü
Are LVS Interlocks operational.
8 •

Mechanical Interlock
Electrical Interlock
ü
Is the LVS Control Interface to Generator Sychronizing Panel
9
Control has been completed. ü
Check if the all the contruction punchlist has been completed, the
10
euipment are clean and the area are secured. ü
LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date
Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
PRE-FUNCTIONAL CHECKLIST
PRIOR TO ENERGIZATION OF LOW VOLTAGE SWITCHGEAR
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : LVSB ME-B
MAIN BUS RATING : 5000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

Conforme
Item No. Descriptions Comments
Yes No

1
Is the LVS conform in accordance with the approved plans,
shopdrawing/submittals, and specification. ü
2
Are the bus bar joint connection/bolts has been tighthen base
on their required torqued. ü
3 Inspect anchorage, alignment, grounding, and required area clearances ü
4
Verify that the current and voltage transformer ratios corresponds to drawing.
ü
5
Verify that fuse and/or circuit breaker sizes and type corresponds to the drawings.
ü
6
I s the equipment grounding has been check and tested.
ü
Lubrication requirements:
7 • Verify appropriate lubrication on moving current-carrying parts.
• Verify appropriate lubrication on moving and sliding surfaces.
ü
Are LVS Interlocks operational.
8 • Mechanical Interlock
• Electrical Interlock
ü
9
Is the LVS Control Interface to Generator Sychronizing Panel
Control has been completed. ü
10
Check if the all the contruction punchlist has been completed, the
euipment are clean and the area are secured. ü
LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : SECOND FLOOR


Site : Carmona, Cavite
Area Served : SECOND FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-047 (ATS LVSG DC 2F-A)
System ID : EL-0010
PRE-FUNCTIONAL CHECKLIST
PRIOR TO ENERGIZATION OF LOW VOLTAGE SWITCHGEAR
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 2F-A
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

Conforme
Item No. Descriptions Comments
Yes No

1
Is the LVS conform in accordance with the approved plans,
shopdrawing/submittals, and specification. ü
2
Are the bus bar joint connection/bolts has been tighthen base
on their required torqued. ü
3 Inspect anchorage, alignment, grounding, and required area clearances ü
4
Verify that the current and voltage transformer ratios corresponds to drawing.
ü
5
Verify that fuse and/or circuit breaker sizes and type corresponds to the drawings.
ü
6
I s the equipment grounding has been check and tested.
ü
Lubrication requirements:
7 • Verify appropriate lubrication on moving current-carrying parts.
• Verify appropriate lubrication on moving and sliding surfaces.
ü
Are LVS Interlocks operational.
8 • Mechanical Interlock
• Electrical Interlock
ü
9
Is the LVS Control Interface to Generator Sychronizing Panel
Control has been completed. ü
10
Check if the all the contruction punchlist has been completed, the
euipment are clean and the area are secured. ü
LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : SECOND FLOOR


Site : Carmona, Cavite
Area Served : SECOND FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-048 (ATS LVSG DC 2F-B)
System ID : EL-0011
PRE-FUNCTIONAL CHECKLIST
PRIOR TO ENERGIZATION OF LOW VOLTAGE SWITCHGEAR
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 2F-B
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

Conforme
Item No. Descriptions Comments
Yes No

1
Is the LVS conform in accordance with the approved plans,
shopdrawing/submittals, and specification. ü
2
Are the bus bar joint connection/bolts has been tighthen base
on their required torqued. ü
3 Inspect anchorage, alignment, grounding, and required area clearances ü
4
Verify that the current and voltage transformer ratios corresponds to drawing.
ü
5
Verify that fuse and/or circuit breaker sizes and type corresponds to the drawings.
ü
6
I s the equipment grounding has been check and tested.
ü
Lubrication requirements:
7 • Verify appropriate lubrication on moving current-carrying parts.
• Verify appropriate lubrication on moving and sliding surfaces.
ü
Are LVS Interlocks operational.
8 • Mechanical Interlock
• Electrical Interlock
ü
9
Is the LVS Control Interface to Generator Sychronizing Panel
Control has been completed. ü
10
Check if the all the contruction punchlist has been completed, the
euipment are clean and the area are secured. ü
LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : THIRD FLOOR


Site : Carmona, Cavite
Area Served : THIRD FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-049 (ATS LVSG DC 3F-A)
System ID : EL-0012
PRE-FUNCTIONAL CHECKLIST
PRIOR TO ENERGIZATION OF LOW VOLTAGE SWITCHGEAR
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 3F-A
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

Conforme
Item No. Descriptions Comments
Yes No

1
Is the LVS conform in accordance with the approved plans,
shopdrawing/submittals, and specification. ü
2
Are the bus bar joint connection/bolts has been tighthen base
on their required torqued. ü
3 Inspect anchorage, alignment, grounding, and required area clearances ü
4
Verify that the current and voltage transformer ratios corresponds to drawing.
ü
5
Verify that fuse and/or circuit breaker sizes and type corresponds to the drawings.
ü
6
I s the equipment grounding has been check and tested.
ü
Lubrication requirements:
7 • Verify appropriate lubrication on moving current-carrying parts.
• Verify appropriate lubrication on moving and sliding surfaces.
ü
Are LVS Interlocks operational.
8 • Mechanical Interlock
• Electrical Interlock
ü
9
Is the LVS Control Interface to Generator Sychronizing Panel
Control has been completed. ü
10
Check if the all the contruction punchlist has been completed, the
euipment are clean and the area are secured. ü
LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : THIRD FLOOR


Site : Carmona, Cavite
Area Served : THIRD FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-050 (ATS LVSG DC 3F-B)
System ID : EL-0013
PRE-FUNCTIONAL CHECKLIST
PRIOR TO ENERGIZATION OF LOW VOLTAGE SWITCHGEAR
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 3F-B
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

Conforme
Item No. Descriptions Comments
Yes No

1
Is the LVS conform in accordance with the approved plans,
shopdrawing/submittals, and specification. ü
2
Are the bus bar joint connection/bolts has been tighthen base
on their required torqued. ü
3 Inspect anchorage, alignment, grounding, and required area clearances ü
4
Verify that the current and voltage transformer ratios corresponds to drawing.
ü
5
Verify that fuse and/or circuit breaker sizes and type corresponds to the drawings.
ü
6
I s the equipment grounding has been check and tested.
ü
Lubrication requirements:
7 • Verify appropriate lubrication on moving current-carrying parts.
• Verify appropriate lubrication on moving and sliding surfaces.
ü
Are LVS Interlocks operational.
8 • Mechanical Interlock
• Electrical Interlock
ü
9
Is the LVS Control Interface to Generator Sychronizing Panel
Control has been completed. ü
10
Check if the all the contruction punchlist has been completed, the
euipment are clean and the area are secured. ü
LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR
Location : GROUND FLOOR
Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008
PRE-FUNCTIONAL CHECKLIST
PRIOR TO ENERGIZATION OF LOW VOLTAGE SWITCHGEAR
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : LVSB ME-A
MAIN BUS RATING : 5000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

Conforme
Item No. Descriptions Comments
Yes No

11 Inspect insulators for evidence of physical damage or contaminated and surfaces.


ü
12 Exercise all active components
ü
ü
Perform visual and mechanical inspection of instruments transformers in accordance
13 with applicable standards.

Inspect control power transformer.

Inspect for physical damge, cracked insulation, broken leads, tightness of



14 connections, defective wiring and overall general condition.
ü
Verify that primary and secondary fuse or circuit breakers rating match the

drawings

ü
Verify correct functioning of drw-out disconnecting and grounding contacts and
15 interlocks.

ü
Verify / Check if LVS load schedule and wiring diagram are attached inside the panel
16 enclosure

ü
Verify if insulation resistance test for main bus and sections are performed or
17 conducted

LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date
Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
PRE-FUNCTIONAL CHECKLIST
PRIOR TO ENERGIZATION OF LOW VOLTAGE SWITCHGEAR
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : LVSB ME-B
MAIN BUS RATING : 5000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

Conforme
Item No. Descriptions Comments
Yes No
11 Inspect insulators for evidence of physical damage or contaminated and surfaces. ü
12 Exercise all active components ü
13
Perform visual and mechanical inspection of instruments transformers in accordance
with applicable standards. ü
Inspect control power transformer.
Inspect for physical damge, cracked insulation, broken leads, tightness of
14 •


connections, defective wiring and overall general condition.
Verify that primary and secondary fuse or circuit breakers rating match the
ü
drawings
15
Verify correct functioning of drw-out disconnecting and grounding contacts and
interlocks. ü
16
Verify / Check if LVS load schedule and wiring diagram are attached inside the panel
enclosure ü
17
Verify if insulation resistance test for main bus and sections are performed or
conducted ü

LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : SECOND FLOOR


Site : Carmona, Cavite
Area Served : SECOND FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-047 (ATS LVSG DC 2F-A)
System ID : EL-0010
PRE-FUNCTIONAL CHECKLIST
PRIOR TO ENERGIZATION OF LOW VOLTAGE SWITCHGEAR
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 2F-A
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

Conforme
Item No. Descriptions Comments
Yes No
11 Inspect insulators for evidence of physical damage or contaminated and surfaces. ü
12 Exercise all active components ü
13
Perform visual and mechanical inspection of instruments transformers in accordance
with applicable standards. ü
Inspect control power transformer.
Inspect for physical damge, cracked insulation, broken leads, tightness of
14 •


connections, defective wiring and overall general condition.
Verify that primary and secondary fuse or circuit breakers rating match the
ü
drawings
15
Verify correct functioning of drw-out disconnecting and grounding contacts and
interlocks. ü
16
Verify / Check if LVS load schedule and wiring diagram are attached inside the panel
enclosure ü
17
Verify if insulation resistance test for main bus and sections are performed or
conducted ü

LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : SECOND FLOOR


Site : Carmona, Cavite
Area Served : SECOND FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-048 (ATS LVSG DC 2F-B)
System ID : EL-0011
PRE-FUNCTIONAL CHECKLIST
PRIOR TO ENERGIZATION OF LOW VOLTAGE SWITCHGEAR
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 2F-B
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

Conforme
Item No. Descriptions Comments
Yes No
11 Inspect insulators for evidence of physical damage or contaminated and surfaces. ü
12 Exercise all active components ü
13
Perform visual and mechanical inspection of instruments transformers in accordance
with applicable standards. ü
Inspect control power transformer.
Inspect for physical damge, cracked insulation, broken leads, tightness of
14 •


connections, defective wiring and overall general condition.
Verify that primary and secondary fuse or circuit breakers rating match the
ü
drawings
15
Verify correct functioning of drw-out disconnecting and grounding contacts and
interlocks. ü
16
Verify / Check if LVS load schedule and wiring diagram are attached inside the panel
enclosure ü
17
Verify if insulation resistance test for main bus and sections are performed or
conducted ü

LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : THIRD FLOOR


Site : Carmona, Cavite
Area Served : THIRD FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-049 (ATS LVSG DC 3F-A)
System ID : EL-0012
PRE-FUNCTIONAL CHECKLIST
PRIOR TO ENERGIZATION OF LOW VOLTAGE SWITCHGEAR
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 3F-A
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

Conforme
Item No. Descriptions Comments
Yes No
11 Inspect insulators for evidence of physical damage or contaminated and surfaces. ü
12 Exercise all active components ü
13
Perform visual and mechanical inspection of instruments transformers in accordance
with applicable standards. ü
Inspect control power transformer.
Inspect for physical damge, cracked insulation, broken leads, tightness of
14 •


connections, defective wiring and overall general condition.
Verify that primary and secondary fuse or circuit breakers rating match the
ü
drawings
15
Verify correct functioning of drw-out disconnecting and grounding contacts and
interlocks. ü
16
Verify / Check if LVS load schedule and wiring diagram are attached inside the panel
enclosure ü
17
Verify if insulation resistance test for main bus and sections are performed or
conducted ü

LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : THIRD FLOOR


Site : Carmona, Cavite
Area Served : THIRD FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-050 (ATS LVSG DC 3F-B)
System ID : EL-0013
PRE-FUNCTIONAL CHECKLIST
PRIOR TO ENERGIZATION OF LOW VOLTAGE SWITCHGEAR
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 3F-B
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

Conforme
Item No. Descriptions Comments
Yes No
11 Inspect insulators for evidence of physical damage or contaminated and surfaces. ü
12 Exercise all active components ü
13
Perform visual and mechanical inspection of instruments transformers in accordance
with applicable standards. ü
Inspect control power transformer.
Inspect for physical damge, cracked insulation, broken leads, tightness of
14 •


connections, defective wiring and overall general condition.
Verify that primary and secondary fuse or circuit breakers rating match the
ü
drawings
15
Verify correct functioning of drw-out disconnecting and grounding contacts and
interlocks. ü
16
Verify / Check if LVS load schedule and wiring diagram are attached inside the panel
enclosure ü
17
Verify if insulation resistance test for main bus and sections are performed or
conducted ü

LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR
Location : GROUND FLOOR
Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008

CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST


EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : MAIN-NORMAL
MAIN BUS RATING : 5000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100KA
Ampere Trip (AT) 5000 AT (rms or symmetrical)
Ampere Frame 5000 AF Serial Number SN22510067
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.9 1.040 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
6 0.427 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.4 0.401 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Breaker closing mecahnism ü PASSED
Breaker tripping mechanism ü PASSED
Mechanical interlocking ü PASSED
Breaker withdrawing facilities ü PASSED
Breaker on and off indication ü PASSED
Padlocking facilities ü PASSED
LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date
Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
LGB ECBS INC.
Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : MAIN-EMERGENCY
MAIN BUS RATING : 5000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100KA
Ampere Trip (AT) 5000 AT (rms or symmetrical)
Ampere Frame 5000 AF Serial Number SN22510076
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.9 1.047 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
6 0.428 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.4 0.402 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : TIE-LVSB-ME-B
MAIN BUS RATING : 5000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100KA
Ampere Trip (AT) 5000 AT (rms or symmetrical)
Ampere Frame 5000 AF Serial Number SN22510090
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.9 1.179 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
6 0.428 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.4 0.401 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : CHILLER-1
MAIN BUS RATING : 1200A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22410345
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.488 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.105 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.046 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.261 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : CHILLER-2
MAIN BUS RATING : 1200A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22410329
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.478 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.105 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.047 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.266 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : CHILLER-3
MAIN BUS RATING : 1200A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22410362
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.497 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.106 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.046 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.261 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : CHILLER-4
MAIN BUS RATING : 1200A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22410353
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.529 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.106 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.045 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : MCC-A
MAIN BUS RATING : 3000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 3000 AT (rms or symmetrical)
Ampere Frame 3200 AF Serial Number SN23150949
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.496 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
10 0.287 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : DPP-1A
MAIN BUS RATING : 800A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 800 AT (rms or symmetrical)
Ampere Frame 1000 AF Serial Number SN23150899
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.8 3.215 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
3 0.121 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 3 x ln 0.045 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : 4PPAC-A
MAIN BUS RATING : 600A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 600 AT (rms or symmetrical)
Ampere Frame 1000 AF Serial Number SN23150982
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.6 3.255 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
3 0.105 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 3 x ln 0.045 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.259 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : 4PPAC-B
MAIN BUS RATING : 600A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 600 AT (rms or symmetrical)
Ampere Frame 1000 AF Serial Number SN22150416
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.6 3.321 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
3 0.105 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 3 x ln 0.046 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Breaker closing mecahnism ü PASSED
Breaker tripping mechanism ü PASSED
Mechanical interlocking ü PASSED
Breaker withdrawing facilities ü PASSED
Breaker on and off indication ü PASSED
Padlocking facilities ü PASSED
LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045 (LVSB ME-A)
System ID : EL-008
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : MCC-B
MAIN BUS RATING : 3000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 3000 AT (rms or symmetrical)
Ampere Frame 3200 AF Serial Number SN23520298
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.450 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
10 0.287 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : MAIN-NORMAL
MAIN BUS RATING : 5000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100KA
Ampere Trip (AT) 5000 AT (rms or symmetrical)
Ampere Frame 5000 AF Serial Number SN22510079
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.9 1.023 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
6 0.428 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.4 0.397 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : MAIN-EMERGENCY
MAIN BUS RATING : 5000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100KA
Ampere Trip (AT) 5000 AT (rms or symmetrical)
Ampere Frame 5000 AF Serial Number SN22510080
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.9 1.043 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
6 0.431 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.4 0.401 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : TIE-LVSB-ME-A
MAIN BUS RATING : 5000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100KA
Ampere Trip (AT) 5000 AT (rms or symmetrical)
Ampere Frame 5000 AF Serial Number SN22510104
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.9 1.779 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
6 0.428 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.4 0.401 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : CHILLER-1
MAIN BUS RATING : 1200A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22410339
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.522 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.105 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.047 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.258 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : CHILLER-2
MAIN BUS RATING : 1200A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22410397
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.473 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.097 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.036 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.269 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : CHILLER-3
MAIN BUS RATING : 1200A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN22150633
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.439 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.097 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.039 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : CHILLER-4
MAIN BUS RATING : 1200A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 1200 AT (rms or symmetrical)
Ampere Frame 1600 AF Serial Number SN80952629
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.529 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
5 0.106 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 10 x ln 0.045 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : MCC-A
MAIN BUS RATING : 3000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 3000 AT (rms or symmetrical)
Ampere Frame 3200 AF Serial Number SN22150782
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.498 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
10 0.287 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : DPP-1B
MAIN BUS RATING : 800A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 800 AT (rms or symmetrical)
Ampere Frame 1000 AF Serial Number SN23150899
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.8 3.229 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
3 0.120 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 3 x ln 0.046 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.260 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : 4PPAC-A
MAIN BUS RATING : 600A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 600 AT (rms or symmetrical)
Ampere Frame 1000 AF Serial Number SN23150882
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.6 3.244 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
3 0.103 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 3 x ln 0.045 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.265 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : 4PPAC-B
MAIN BUS RATING : 600A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 600 AT (rms or symmetrical)
Ampere Frame 1000 AF Serial Number SN23150976
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.6 3.339 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
3 0.109 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting 3 x ln 0.045 sec PASSED
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.257 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED
Breaker closing mecahnism ü PASSED
Breaker tripping mechanism ü PASSED
Mechanical interlocking ü PASSED
Breaker withdrawing facilities ü PASSED
Breaker on and off indication ü PASSED
Padlocking facilities ü PASSED
LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046 (LVSB ME-B)
System ID : EL-009
CIRCUIT BREAKER INSPECTION AND TESTING CHECKLIST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : MCC-B
MAIN BUS RATING : 3000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

GENERAL DATA
Feeder Description 4W+G System Voltage 400V/230 V 60HZ
Breaker Type ACB MASTERPACT H1 Short Circuit (KAIC) RATING 100
Ampere Trip (AT) 3000 AT (rms or symmetrical)
Ampere Frame 3200 AF Serial Number SN22150782
BREAKER OPERATING SYSTEMS - ELECTRICAL
Description Volts Condition / Remarks
Spring charge motor
Shunt opening release
Shunt closing release
Undervoltage release
Protection As found setting Test Current / Time Condition / Remarks
Overload protection with (L) setting x ln
0.7 2.446 sec PASSED
inverse long-time delay (L) trip time setting time
Short Circuit protection with (S) setting x ln
10 0.288 sec PASSED
short-time delay (S) trip time setting time
Short Circuit protection with
adjustable instanteneous (I) (I) setting OFF x ln OFF NA
trip
(G) setting x ln
Earth Fault (G) trip 0.3 0.259 sec PASSED
time setting time
Test equipment Serial Number
BREAKER OPERATING SYSTEMS - MECHANICAL
Description Checked Remarks
Spring charger mechanism ü PASSED

Breaker closing mecahnism ü PASSED

Breaker tripping mechanism ü PASSED

Mechanical interlocking ü PASSED

Breaker withdrawing facilities ü PASSED

Breaker on and off indication ü PASSED

Padlocking facilities ü PASSED


LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR
Location : GROUND FLOOR
Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045
System ID : EL-008

CIRCUIT BREAKER CONTACT RESISTANCE TEST


EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : LVSB ME-A
MAIN BUS RATING : 5000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

CONTACT RESISTANCE MICRO-OHMS


SERIAL
BREAKER INFORMATION COMMENTS
NUMBER
PHASE A PHASE B PHASE C NEUTRAL

SN22510067 MAIN-NORMAL 0.0188 mΩ 0.0199 mΩ 0.0187 mΩ 0.01842 mΩ Passed


SN22510076 MAIN-EMERGENCY 0,0106 mΩ 0.0110 mΩ 0.0114 mΩ 0.0111 mΩ Passed
SN23150982 4PPAC-A 0.0095 mΩ 0.0093 mΩ 0,0094 mΩ 0.0088 mΩ Passed
SN22150416 4PPAC-B 0.0089 mΩ 0.0088 mΩ 0.0093 mΩ 0.0103 mΩ Passed
SN23150899 DPP-1A 0,0096 mΩ 0.0098 mΩ 0.0098 mΩ 0.0111 mΩ Passed
SN22410353 CHILLER-4 0.0093 mΩ 0.0100 mΩ 0.0098 mΩ 0.0101 mΩ Passed
SN22410362 CHILLER-3 0.0096 mΩ 0.0085 mΩ 0.0090 mΩ 0.0121 mΩ Passed
SN23150948 SPARE 0.0089 mΩ 0.0088 mΩ 0,0104 mΩ 0.0094 mΩ Passed
SN23150949 MCC-A 0.0104 mΩ 0.0091 mΩ 0.0092 mΩ 0.0106 mΩ Passed
SN22410329 CHILLER-2 0.0090 mΩ 0.0081 mΩ 0.0096 mΩ 0.0091 mΩ Passed
SN23151018 SOLAR PROVISION 0.0093 mΩ 0.0090 mΩ 0.0082 mΩ 0.0092 mΩ Passed
SN23520298 MCC-B 0.0089 mΩ 0.0084 mΩ 0.0086 mΩ 0.0096 mΩ Passed
SN22410345 CHILLER-1 0.0096 mΩ 0.0092 mΩ 0.0098 mΩ 0.0101 mΩ Passed
SN23151045 CAPACITOR BANK 0.0095 mΩ 0.0086 mΩ 0.0090 mΩ 0.0114 mΩ Passed
SN22510090 TIE CIRCUIT BREAKER 0.0104 mΩ 0.0100 mΩ 0.0116 mΩ 0.0103 mΩ Passed

LEGEND: P - YES / NO N/A - Not Applicable

INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
WINDING RESISTANCE TESTER TELDAR/TRM-1OP 15310041 3K0594

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date
Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
LGB ECBS INC.
Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046
System ID : EL-009
CIRCUIT BREAKER CONTACT RESISTANCE TEST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : LVSB ME-B
MAIN BUS RATING : 5000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

SERIAL CONTACT RESISTANCE MICRO-OHMS


BREAKER INFORMATION COMMENTS
NUMBER PHASE A PHASE B PHASE C NEUTRAL
SN22510079 MAIN-NORMAL 0.0146 mΩ 0.0120 mΩ 0.0147 mΩ 0.0126 mΩ Passed
SN22510080 MAIN-EMERGENCY 0.0134 mΩ 0.141 mΩ 0.0129 mΩ 0.0120 mΩ Passed
SN23150882 4PPAC-A 0.0165 mΩ 0.0164 mΩ 0.0111 mΩ 0.0106 mΩ Passed
SN23150976 4PPAC-B 0.0088 mΩ 0.0087 mΩ 0.0093 mΩ 0.0092 mΩ Passed
SN23151019 DPP-1B 0.0085 mΩ 0.0090 mΩ 0.0092 mΩ 0.0088 mΩ Passed
SN22410339 CHILLER-1 0.0102 mΩ 0.0098 mΩ 0.0094 mΩ 0.0095 mΩ Passed
SN22410397 CHILLER-2 0.0096 mΩ 0.0085 mΩ 0.0090 mΩ 0.0121 mΩ Passed
SN23151043 SPARE 0.0089 mΩ 0.0088 mΩ 0,0104 mΩ 0.0094 mΩ Passed
SN22150824 MCC-A 0.0087 mΩ 0.0090 mΩ 0.0087 mΩ 0.0102 mΩ Passed
SN22150633 CHILLER-3 0.0089 mΩ 0.0091 mΩ 0.0117 mΩ 0.0096 mΩ Passed
SN23150910 SOLAR PROVISION 0.0094 mΩ 0.0091 mΩ 0.0088 mΩ 0.0092 mΩ Passed
SN22150782 MCC-B 0.0083 mΩ 0.0081 mΩ 0.0079 mΩ 0.0089 mΩ Passed
SN80952629 CHILLER-4 0.0152 mΩ 0.0106 mΩ 0.0133 mΩ 0.0132 mΩ Passed
SN23150915 CAPACITOR BANK 0.0095 mΩ 0.0086 mΩ 0.0090 mΩ 0.0092 mΩ Passed
SN22510104 TIE CIRCUIT BREAKER 0.0127 mΩ 0.0098 mΩ 0.0107 mΩ 0.0101 mΩ Passed

LEGEND: P - YES / NO N/A - Not Applicable


INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
WINDING RESISTANCE TESTER TELDAR/TRM-1OP 15310041 3K0594

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : SECOND FLOOR


Site : Carmona, Cavite
Area Served : SECOND FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-047
System ID : EL-0010
CIRCUIT BREAKER CONTACT RESISTANCE TEST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 2F-A
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

SERIAL CONTACT RESISTANCE MICRO-OHMS


BREAKER INFORMATION COMMENTS
NUMBER PHASE A PHASE B PHASE C NEUTRAL
SN23510969 MAIN-NORMAL 0.0105 mΩ 0.0096 mΩ 0.0116 mΩ 0.0098 mΩ Passed
SN23520270 MAIN-EMERGENCY 0.0101 mΩ 0.0098 mΩ 0.0089 mΩ 0.0097 mΩ Passed
SN23510956 TIE CIRCUIT BREAKER 0.0097 mΩ 0.0092 mΩ 0,0090 mΩ 0.0097 mΩ Passed
SN24330375 MDP UPS 2FA-1 (BYPASS-A) 0.0091 mΩ 0.0088 mΩ 0.0091 mΩ 0.0092 mΩ Passed
SN24331021 MDP UPS STS 2FA-1 (INPUT-A) 0,0085 mΩ 0.0087 mΩ 0.0096 mΩ 0.0090 mΩ Passed
SN23420294 SPARE 0.0098 mΩ 0.0097 mΩ 0.0091 mΩ 0.0094 mΩ Passed
SN24330473 MDP UPS 2FA-2 (BYPASS-B) 0.0087 mΩ 0.0084 mΩ 0.0094 mΩ 0.0086 mΩ Passed
SN23520259 WAB 2F-A (BYPASS) 0.0095 mΩ 0.0092 mΩ 0.0097 mΩ 0.0093 mΩ Passed
SN24331109 MDP UPS STS 2FA-2 (INPUT-B) 0.0094 mΩ 0.0087 mΩ 0.0090 mΩ 0.0085 mΩ Passed

LEGEND: P - YES / NO N/A - Not Applicable


INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

WINDING RESISTANCE TESTER TELDAR/TRM-1OP 15310041 3K0594

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : SECOND FLOOR


Site : Carmona, Cavite
Area Served : SECOND FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-048
System ID : EL-0011
CIRCUIT BREAKER CONTACT RESISTANCE TEST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 2F-B
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

SERIAL CONTACT RESISTANCE MICRO-OHMS


BREAKER INFORMATION COMMENTS
NUMBER PHASE A PHASE B PHASE C NEUTRAL
SN23520263 MAIN-NORMAL 0.0097 mΩ 0.0095 mΩ 0.0090 mΩ 0.104 mΩ Passed
SN23520309 MAIN-EMERGENCY 0.0090 mΩ 0.0097 mΩ 0.0095 mΩ 0.0095 mΩ Passed
SN23510970 TIE CIRCUIT BREAKER 0.0088 mΩ 0.0081 mΩ 0,0085 mΩ 0.0098 mΩ Passed
SN24330363 MDP UPS 2FB-1 0.0092 mΩ 0.0092 mΩ 0.0091 mΩ 0.0101 mΩ Passed
SN24461122 MDP UPS STS 2FB-1 0.0107 mΩ 0.0085 mΩ 0.0088 mΩ 0.0088 mΩ Passed
SN23520301 SPARE 0.0091 mΩ 0.0094 mΩ 0.0085 mΩ 0.0091 mΩ Passed
SN24330432 MDP UPS 2FB-2 0.0089 mΩ 0.0094 mΩ 0.0091 mΩ 0.0095 mΩ Passed
SN23520259 WAB 2F-B (BYPASS) 0.0084 mΩ 0.0078 mΩ 0.0093 mΩ 0.0085 mΩ Passed
SN24331012 MDP UPS STS 2FB-2 0.0086 mΩ 0.0085 mΩ 0.0086 mΩ 0.0084 mΩ Passed

LEGEND: P - YES / NO N/A - Not Applicable


INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

WINDING RESISTANCE TESTER TELDAR/TRM-1OP 15310041 3K0594

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : THIRD FLOOR


Site : Carmona, Cavite
Area Served : THIRD FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-049
System ID : EL-0012
CIRCUIT BREAKER CONTACT RESISTANCE TEST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 3F-A
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

SERIAL CONTACT RESISTANCE MICRO-OHMS


BREAKER INFORMATION COMMENTS
NUMBER PHASE A PHASE B PHASE C NEUTRAL
SN14651533 MAIN-NORMAL 0.0101 mΩ 0.0091 mΩ 0.0083 mΩ 0.0093 mΩ Passed
MAIN-EMERGENCY 0.0091 mΩ 0.0094 mΩ 0.0094 mΩ 0.0091 mΩ Passed
SN23520310 TIE CIRCUIT BREAKER 0.0091 mΩ 0.0091 mΩ 0.0091 mΩ 0.0085 mΩ Passed
SN24331001 MDP UPS 3FA-1 0.0080 mΩ 0.0076 mΩ 0.0080 mΩ 0.0080 mΩ Passed
SN24331107 MDP UPS STS 3FA-1 0.0096 mΩ 0.0090 mΩ 0.0099 mΩ 0.0090 mΩ Passed
SN15010109 SPARE 0.0094 mΩ 0.0094 mΩ 0.0085 mΩ 0.0084 mΩ Passed
SN21861005 MDP UPS 3FA-2 0.0089 mΩ 0.0089 mΩ 0.0094 mΩ 0.0089 mΩ Passed
WAB 3F-A (BYPASS) 0.0092 mΩ 0.0085 mΩ 0.0088 mΩ 0.0086 mΩ Passed
MDP UPS STS 3FA-2 0.0086 mΩ 0.0112 mΩ 0.0098 mΩ 0.0089 mΩ Passed

LEGEND: P - YES / NO N/A - Not Applicable


INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

WINDING RESISTANCE TESTER METREL/MI 3200 15031185 03-230253-H001

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : THIRD FLOOR


Site : Carmona, Cavite
Area Served : THIRD FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-050
System ID : EL-0013
CIRCUIT BREAKER CONTACT RESISTANCE TEST
EQUIPMENT DATA
MANUFACTURER / BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 3F-B
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING
VOLTAGE / PHASE / FREQUENCY : 400V/3Ø/60HZ

SERIAL CONTACT RESISTANCE MICRO-OHMS


BREAKER INFORMATION COMMENTS
NUMBER PHASE A PHASE B PHASE C NEUTRAL
SN15010196 MAIN-NORMAL 0.0082 mΩ 0.0088 mΩ 0.0083 mΩ 0.0079 mΩ Passed
MAIN-EMERGENCY 0.0095 mΩ 0.00100 mΩ 0.0082 mΩ 0.0086 mΩ Passed
TIE CIRCUIT BREAKER 0.0089 mΩ 0.0082 mΩ 0.0088 mΩ 0.0102 mΩ Passed
SN24331004 MDP UPS 3FB-1 0.0103 mΩ 0.0115 mΩ 0.0103 mΩ 0.109 mΩ Passed
MDP UPS STS 3FB-1 0.0108 mΩ 0.0110 mΩ 0.0103 mΩ 0.0135 mΩ Passed
SN24330426 SPARE 0.0094 mΩ 0.0094 mΩ 0.0085 mΩ 0.0084 mΩ Passed
MDP UPS 3FB-2 0.0087 mΩ 0.0085 mΩ 0.0102 mΩ 0.0082 mΩ Passed
WAB 3F-A (BYPASS) 0.0128 mΩ 0.0105 mΩ 0.0096 mΩ 0.0103 mΩ Passed
MDP UPS STS 3FA-2 0.0094 mΩ 0.0085 mΩ 0.0094 mΩ 0.0091 mΩ Passed

LEGEND: P - YES / NO N/A - Not Applicable


INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

WINDING RESISTANCE TESTER TELDAR/TRM-1OP 15310041 3K0594

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR
Location :
Site : Carmona, Cavite
Area Served :
Description :
Project : TIM DATA CENTER Equipment Tag No. :
System ID :
VISUAL & FUNCTIONAL TEST
EQUIPMENT - GROUNDING SYSTEM
Ground Connection (Grounding Bus Bar to Equipment) Continuity
Grd. Wire
Item No. Floor Level Notes
Size (mm²)
From To Y N

To conforme with the following :


1 The grounding wires and grounding bar are properly connected with appropriate terminal lugs and bolts.
2 The grounding bar and wire size connected to the equipment are as per approved drawing/ specification.
3 Check if there is ground continuity between Main Ground System and equipment frame.

LEGEND: P - YES / NO N/A - Not Applicable

INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date
Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR
Location :
Site : Carmona, Cavite
Area Served :
Description :
Project : TIM DATA CENTER Equipment Tag No. :
System ID :

LVS - VOLTAGE / PHASE READING & FUNCTIONAL TEST


Switch Gear Name : Phase :
System Voltage / Frequency : Enclosure :
Rating : No. of Pole :

INSTRUMENT READING READING ON METERING: MN __________ SN __________

Terminal Connection Voltage Reading Phase Sequence /


Voltage Current Frequency
(Volts) Rotation Results KWHR Reading

Line Side Load Side Load Side Line Side (Volts) (Amps) (Hz)
LINE 1 - LINE 2
LINE 2 - LINE 3
LINE 1 - LINE 3
LINE 1 - NEUTRAL
LINE 2 - NEUTRAL
LINE 3 - NEUTRAL
LINE 1 - GROUND
LINE 2 - GROUND
LINE 3 - GROUND
NEUTRAL - GROUND
B. TRANSFER SWITCH OPERATIONAL / FUNCTIONAL TEST
1. Auto Mode :
Yes No Remarks
1.1 Normal Power to Emergency Power (Timer Setting :_________secs.)

1.2 Emergency Power to Normal Power (Timer Setting :_________mins.)

2. Manual Mode : Yes No Remarks

1.1 Normal Power to Emergency Power

1.2 Emergency Power to Normal Power

LEGEND: P - YES / NO N/A - Not Applicable

INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date
Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
Sub Contractor
GENCON OR PM LOGO Logo
LOW VOLTAGE SWITCHGEAR
Location : GROUND FLOOR
Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045
System ID : EL-008
PRE-FUNCTIONAL
INSULATION RESISTANCE TEST

MANUFACTURER / BRAND : SCHNEIDER ELECTRIC MAIN BUS RATING : 5000A


EQUIPMENT NAME : LVSB ME-A ENCLOSURE TYPE : NEMA 1, FREE STANDING

Phase Connection - Reading ( M-Ohm's ) Conforme


Continuity Mega Ohms
Item No. Equipment Name
Test Required
A-B B-C A-C A-N B-N C-N A-G B-G C-G N-G Y N

TIM-CTR-
045
LVSB ME-A (MAIN NORMAL) ü 4.71 GΩ 4.65 GΩ 610 GΩ 1,59 GΩ 2.11 GΩ 439 GΩ 731 GΩ 1.95 GΩ 4.49 GΩ 129 GΩ 100 MΩ ü
TIM-CTR-
045
LVSB ME-A (EMERGENCY) ü 44.1 GΩ >1.00 TΩ >1.00 TΩ 560 GΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ 100 MΩ ü
TIM-CTR-
045
LVSB ME-A (TIE BREAKER) ü >1.00 TΩ >1.00 TΩ 916 GΩ 965 GΩ >1.00 TΩ 239 GΩ 962 GΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ 100 MΩ ü
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
Date: Time: Dry Bulb Temp.: Wet Bulb Temp.: Relative Humidity:
LEGEND: P - YES / NO N/A - Not Applicable

INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:
INSULATION RESISTANCE TESTER METREL/MI 3200 15031185 03-230253-H001

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date
Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
Sub Contractor
GENCON OR PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046
System ID : EL-009
PRE-FUNCTIONAL
INSULATION RESISTANCE TEST

MANUFACTURER / BRAND : SCHNEIDER ELECTRIC MAIN BUS RATING : 5000A


EQUIPMENT NAME : LVSB ME-B ENCLOSURE TYPE : NEMA 1, FREE STANDING

Continuity Phase Connection - Reading ( M-Ohm's ) Mega Ohms Conforme


Item No. Equipment Name
Test A-B B-C A-C A-N B-N C-N A-G B-G C-G N-G Required Y N
TIM-CTR-
046
LVSB ME-B (MAIN NORMAL) ü 485 GΩ >1.90 GΩ 8.02 GΩ 169 GΩ 414 GΩ >1.00 TΩ 3.34 GΩ 1.20 GΩ 1.45 GΩ 64.1 GΩ 100 MΩ ü
TIM-CTR-
046
LVSB ME-B (EMERGENCY) ü 18.0 GΩ >1.00 TΩ 6.45 GΩ 560 GΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ 100 MΩ ü
TIM-CTR-
046
LVSB ME-B (TIE BREAKER) ü >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ 100 MΩ ü
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
Date: Time: Dry Bulb Temp.: Wet Bulb Temp.: Relative Humidity:
LEGEND: P - YES / NO N/A - Not Applicable
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

INSULATION RESISTANCE TESTER METREL/MI 3200 15031185 03-230253-H001

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
Sub Contractor
GENCON OR PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : SECOND FLOOR


Site : Carmona, Cavite
Area Served : SECOND FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-047
System ID : EL-010
PRE-FUNCTIONAL
INSULATION RESISTANCE TEST

MANUFACTURER / BRAND : SCHNEIDER ELECTRIC MAIN BUS RATING : 4000A


EQUIPMENT NAME : ATS LVSG DC 2F-A ENCLOSURE TYPE : NEMA 1, FREE STANDING

Continuity Phase Connection - Reading ( M-Ohm's ) Mega Ohms Conforme


Item No. Equipment Name
Test A-B B-C A-C A-N B-N C-N A-G B-G C-G N-G Required Y N
LVSB ME-A COMMON BUS
TIM-CTR-
047 (CLOSE POSITION) ü 478 GΩ 368 GΩ 247 GΩ 166 GΩ 356 GΩ >1.00 TΩ 893 GΩ 508 GΩ 107 GΩ >1.00 TΩ 100 MΩ ü
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
Date: Time: Dry Bulb Temp.: Wet Bulb Temp.: Relative Humidity:
LEGEND: P - YES / NO N/A - Not Applicable
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

INSULATION RESISTANCE TESTER METREL/MI 3200 15031185 03-230253-H001

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
Sub Contractor
GENCON OR PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : SECOND FLOOR


Site : Carmona, Cavite
Area Served : SECOND FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-048
System ID : EL-011
PRE-FUNCTIONAL
INSULATION RESISTANCE TEST

MANUFACTURER / BRAND : SCHNEIDER ELECTRIC MAIN BUS RATING : 4000A


EQUIPMENT NAME : ATS LVSG DC 2F-B ENCLOSURE TYPE : NEMA 1, FREE STANDING

Continuity Phase Connection - Reading ( M-Ohm's ) Mega Ohms Conforme


Item No. Equipment Name
Test A-B B-C A-C A-N B-N C-N A-G B-G C-G N-G Required Y N
ATS LVSG DC 2F-B
TIM-CTR-
048
COMMON BUS (CLOSE
POSITION)
ü 119 GΩ 189 GΩ 221 GΩ 284 GΩ 283 GΩ 317 GΩ 77.0 GΩ 77.5 GΩ 82.8 GΩ 81.8 GΩ 100 MΩ ü
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
Date: Time: Dry Bulb Temp.: Wet Bulb Temp.: Relative Humidity:
LEGEND: P - YES / NO N/A - Not Applicable
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

INSULATION RESISTANCE TESTER METREL/MI 3200 15031185 03-230253-H001

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
Sub Contractor
GENCON OR PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : THIRD FLOOR


Site : Carmona, Cavite
Area Served : THIRD FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-049
System ID : EL-012
PRE-FUNCTIONAL
INSULATION RESISTANCE TEST

MANUFACTURER / BRAND : SCHNEIDER ELECTRIC MAIN BUS RATING : 4000A


EQUIPMENT NAME : ATS LVSG DC 3F-A ENCLOSURE TYPE : NEMA 1, FREE STANDING

Continuity Phase Connection - Reading ( M-Ohm's ) Mega Ohms Conforme


Item No. Equipment Name
Test A-B B-C A-C A-N B-N C-N A-G B-G C-G N-G Required Y N
ATS LVSG DC 3F-A
TIM-CTR-
049
COMMON BUS (CLOSE
POSITION)
ü >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ 100 MΩ ü
100 MΩ

100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
Date: Time: Dry Bulb Temp.: Wet Bulb Temp.: Relative Humidity:
LEGEND: P - YES / NO N/A - Not Applicable
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

INSULATION RESISTANCE TESTER METREL/MI 3200 15031185 03-230253-H001

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
Sub Contractor
GENCON OR PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : THIRD FLOOR


Site : Carmona, Cavite
Area Served : THIRD FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-050
System ID : EL-013
PRE-FUNCTIONAL
INSULATION RESISTANCE TEST

MANUFACTURER / BRAND : SCHNEIDER ELECTRIC MAIN BUS RATING : 4000A


EQUIPMENT NAME : ATS LVSG DC 3F-B ENCLOSURE TYPE : NEMA 1, FREE STANDING

Continuity Phase Connection - Reading ( M-Ohm's ) Mega Ohms Conforme


Item No. Equipment Name
Test A-B B-C A-C A-N B-N C-N A-G B-G C-G N-G Required Y N
ATS LVSG DC 3F-B
TIM-CTR-
050
COMMON BUS (CLOSE
POSITION)
ü >1.00 TΩ 7.04 GΩ 38.4 GΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ >1.00 TΩ 138 GΩ 19.4 GΩ 140 GΩ 100 MΩ ü
100 MΩ

100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
100 MΩ
Date: Time: Dry Bulb Temp.: Wet Bulb Temp.: Relative Humidity:
LEGEND: P - YES / NO N/A - Not Applicable
INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

INSULATION RESISTANCE TESTER METREL/MI 3200 15031185 03-230253-H001

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR
Location : GROUND FLOOR
Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-045
System ID : EL-008
PRE-FUNCTIONAL
TIGHTENING / TORQUING OF LVSG BOLTS
: SCHNEIDER ELECTRIC
MANUFACTURER /BRAND
LVS NAME : LVSB ME-A

MAIN BUS RATING : 5000A

ENCLOSURE TYPE : NEMA 1, FREE STANDING

SIZE / DIAMETER Conforme


PHASE BUS BAR Torque Required COMMENTS /
LVS NO. OF BOLTS BOLT SPECIFICATION
CONNECTION (ft-lbs) PUNCHLIST
(in) Yes No

TIM-CTR-
045
ABCN 3/8 SAE Grade 8.8 30 ü
TIM-CTR-
045
ABCN 1/2 SAE Grade 8.9 74 ü

LEGEND: P - YES / NO N/A - Not Applicable

INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date
Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-046
System ID : EL-009
PRE-FUNCTIONAL
TIGHTENING / TORQUING OF LVSG BOLTS
MANUFACTURER /BRAND : SCHNEIDER ELECTRIC
LVS NAME : LVSB ME-B
MAIN BUS RATING : 5000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING

SIZE / DIAMETER Conforme


PHASE BUS BAR Torque Required COMMENTS /
LVS NO. OF BOLTS BOLT SPECIFICATION
CONNECTION (ft-lbs) Yes No PUNCHLIST
(in)
TIM-CTR-
046
ABCN 3/8 SAE Grade 8.8 30 ü
TIM-CTR-
046
ABCN 1/2 SAE Grade 8.8 74 ü

LEGEND: P - YES / NO N/A - Not Applicable


INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-047
System ID : EL-010
PRE-FUNCTIONAL
TIGHTENING / TORQUING OF LVSG BOLTS
MANUFACTURER /BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 2F-A
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING

SIZE / DIAMETER Conforme


PHASE BUS BAR Torque Required COMMENTS /
LVS NO. OF BOLTS BOLT SPECIFICATION
CONNECTION (ft-lbs) Yes No PUNCHLIST
(in)
TIM-CTR-
047
ABCN 3/8 SAE Grade 8.8 30 ü
TIM-CTR-
047
ABCN 1/2 SAE Grade 8.8 74 ü
TIM-CTR-
047
ABCN 1/4 SAE Grade 8.8 8 ü

LEGEND: P - YES / NO N/A - Not Applicable

INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-048
System ID : EL-011
PRE-FUNCTIONAL
TIGHTENING / TORQUING OF LVSG BOLTS
MANUFACTURER /BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 2F-B
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING

SIZE / DIAMETER Conforme


PHASE BUS BAR Torque Required COMMENTS /
LVS NO. OF BOLTS BOLT SPECIFICATION
CONNECTION (ft-lbs) Yes No PUNCHLIST
(in)
TIM-CTR-
048
ABCN 3/8 SAE Grade 8.8 30 ü
TIM-CTR-
048
ABCN 1/2 SAE Grade 8.8 74 ü
TIM-CTR-
048
ABCN 1/4 SAE Grade 8.8 8 ü

LEGEND: P - YES / NO N/A - Not Applicable

INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-049
System ID : EL-012
PRE-FUNCTIONAL
TIGHTENING / TORQUING OF LVSG BOLTS
MANUFACTURER /BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 3F-A
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING

SIZE / DIAMETER Conforme


PHASE BUS BAR Torque Required COMMENTS /
LVS NO. OF BOLTS BOLT SPECIFICATION
CONNECTION (ft-lbs) Yes No PUNCHLIST
(in)
TIM-CTR-
049
ABCN 3/8 SAE Grade 8.8 30 ü
TIM-CTR-
049
ABCN 1/2 SAE Grade 8.8 74 ü
TIM-CTR-
049
ABCN 1/4 SAE Grade 8.8 8 ü

LEGEND: P - YES / NO N/A - Not Applicable

INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR

Location : GROUND FLOOR


Site : Carmona, Cavite
Area Served : GROUND FLOOR TO 4TH FLOOR
Description : Low Voltage Switch Gear
Project : TIM DATA CENTER Equipment Tag No. : TIM-CTR-050
System ID : EL-013
PRE-FUNCTIONAL
TIGHTENING / TORQUING OF LVSG BOLTS
MANUFACTURER /BRAND : SCHNEIDER ELECTRIC
LVS NAME : ATS LVSG DC 3F-B
MAIN BUS RATING : 4000A
ENCLOSURE TYPE : NEMA 1, FREE STANDING

SIZE / DIAMETER Conforme


PHASE BUS BAR Torque Required COMMENTS /
LVS NO. OF BOLTS BOLT SPECIFICATION
CONNECTION (ft-lbs) Yes No PUNCHLIST
(in)
TIM-CTR-
050
ABCN 3/8 SAE Grade 8.8 30 ü
TIM-CTR-
050
ABCN 1/2 SAE Grade 8.8 74 ü
TIM-CTR-
050
ABCN 1/4 SAE Grade 8.8 8 ü

LEGEND: P - YES / NO N/A - Not Applicable

INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR
Location :
Site : Carmona, Cavite
Area Served :
Description :
Project : TIM DATA CENTER Equipment Tag No. :
System ID :

SYSTEM OPERATION TEST

LOW VOLTAGE SWITCH GEAR INFORMATION


Breaker Type : System Voltage :
Breaker Rating/Brand : Control Voltage :
Enclosure Type : Others :

MAJOR COMPONENTS OF ATS CONTROLLER


Control C.B. : Normal Power Source :
Control Switches : Protection Relay :
Control P.T. : Others :

PROTECTIONS AND PARAMETERS


SETTING Operating Time Delay
FUNCTION REMARKS
Normal Emergency Normal Emergency
Normal Checking
Abnormal Checking
Closed Time
Open Time
Transfer Interval
Genset Start
Genset Stop
Rated Voltage
Over Voltage
Over Voltage Return
Under Voltage
Under Voltage Return
System Type Select
Breaking Position
Select AC System
Set Priority
Aux. Output 1
Aux. Output 2
Aux. Output 3
Aux. Output 4
Aux. Output 5
Aux. Input 1
Aux. Input 2

LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date
Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
LGB ECBS INC.
Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR
Location :
Site : Carmona, Cavite
Area Served :
Description :
Project : TIM DATA CENTER Equipment Tag No. :
System ID :

SYSTEM OPERATION TEST

TEST RESULT

DESCRIPTION STATUS
REMARKS
MANUAL OPERATIONS Functioning Mal-Functioning
1. Normal Breaker On and Off
2. Emergency Breaker On and Off
ELECTRICAL OPERATIONS
1. Normal Breaker On and Off
2. Emergency Breaker On and Off
BREAKER INTERLOCKING
1. Normal Breaker On-Emergency Breaker Interlock
2. Normal Breaker Off-Emergency Breaker Operates
3. Emergency Breaker On-Normal Breaker Interlock
4. Emergency Breaker Off-Normal Breaker Operates
AUTOMATIC TRANSFER
1. Normal - Emergency
2. Emergency - Normal

LEGEND: P - YES / NO N/A - Not Applicable

INSTRUMENTATION
Instrument used: Brand/Model: Serial No.: Calibration Cert. No.:

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date
Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
LOW VOLTAGE SWITCHGEAR
Location :
Site : Carmona, Cavite
Area Served :
Description :
Project : TIM DATA CENTER Equipment Tag No. :
System ID :

SWITCHGEAR ACCESSORIES TEST REPORT

EQUIPMENT DATA
MANUFACTURER / BRAND :
LVS NAME :
ENCLOSURE TYPE :
VOLTAGE / PHASE / FREQUENCY :

MAJOR COMPONENTS OF PANEL/SWITCHGEAR

Control C.B. : Multi-meter :

Timer : Ammeter :

Contactor Relay : Voltmeter :

Control P.T. : Current Transformer :

Pilot Light : Protection Relay :

Switches : Others :

FUNCTION TEST RESULT

OPERATING TIME STATUS


DEVICES SETTING REMARKS
DELAY GOOD NO GOOD

LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by:


Project Management Representative Signature Date

Test witnessed and


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date
Remarks :

LGB ECBS INC.


Project: TIM DATA CENTER
LGB ECBS INC.
Project: TIM DATA CENTER
TEST RECORD
GENCON OR Sub Contractor
PM LOGO Logo
PUNCHLIST

Location :
Site : Carmona, Cavite
Area Served :
Description :
Project : TIM DATA CENTER Equipment Tag No. :
System ID :

MVAC System Telephone System

Plumbing/Sanitary & Drainage System Fire Detection & Alarm System

Fire Protection System Door Access

Electrical System CCTV System

Lift System Other System Please Specify _________________

ITEM COMPLIANCE
PUNCHLIST DESCRIPTION REMARKS
No. YES NO
EQUIPMENT RELATED

WORKMANSHIP

DOCUMENTS RELATED

LEGEND: P - YES / NO N/A - Not Applicable

Test carried out by:


Sub Con Representative Signature Date

Test witnessed by;


Project Management Representative Signature Date

Test witnessed and Engr Christian Marc Tabios


accepted by: Exquis Electrical Services & Supplies Co Signature Date

Noted by:
Owner Representative Signature Date

Remarks :