FCI-24-001 - C9 - 480x100 Plate
FCI-24-001 - C9 - 480x100 Plate
The design results must be checked for plausibility and fulfill the conditions of local standards and approvals. Page 1 of 4
1/12/2024 DesignFiX 3.5.8747.193
Tension load
Steel failure
h
N Ed < N Rk,s / γ Ms
The fastening consists of 2 groups which do not affect each other for concrete cone failure
because their spacing is larger than the characteristic value scr,N.
Group 1: Anchor no. 1
N Rk,c = 56.75 · (108900 / 108900 ) · 1.000 · 1.000 · 1.000 · 1.000 · 1.000 = 56.75 kN
30.85 < 56.75 / 1.50 = 37.84 kN
Utilization: βN,c = 81.5%
Group 2: Anchor no. 2
N Rk,c = 56.75 · (108900 / 108900 ) · 1.000 · 1.000 · 1.000 · 1.000 · 1.000 = 56.75 kN
30.85 < 56.75 / 1.50 = 37.84 kN
Utilization: βN,c = 81.5%
The fastening consists of 2 groups which do not affect each other for concrete cone failure
because their spacing is larger than the characteristic value scr,N.
Group 1: Anchor no. 1
N Rk,p = 105.05 · (108900 / 108900 ) · 1.000 · 1.000 · 1.000 · 1.000 · 1.000 = 105.05 kN
30.85 < 105.05 / 1.50 = 70.03
Utilization: βN,p = 44.0%
Group 2: Anchor no. 2
N Rk,p = 105.05 · (108900 / 108900 ) · 1.000 · 1.000 · 1.000 · 1.000 · 1.000 = 105.05 kN
30.85 < 105.05 / 1.50 = 70.03
Utilization: βN,p = 44.0%
The design results must be checked for plausibility and fulfill the conditions of local standards and approvals. Page 2 of 4
1/12/2024 DesignFiX 3.5.8747.193
Splitting
According to design method no splitting proof is required!
Shear loads
The fastening consists of 2 groups which do not affect each other for pry-out failure because their spacing is larger than
the characteristic value scr,N.
Group 1: Anchor no. 1
V Rk,cp = 2.0 · 56.75 · (108900 / 108900 ) · 1.000 · 1.000 · 1.000 · 1.000 = 113.51 kN
15.50 < 113.51 / 1.50 = 75.67
Utilization: βV,cp = 20.5%
Group 2: Anchor no. 2
V Rk,cp = 2.0 · 56.75 · (108900 / 108900 ) · 1.000 · 1.000 · 1.000 · 1.000 = 113.51 kN
15.50 < 113.51 / 1.50 = 75.67
Utilization: βV,cp = 20.5%
Basic value of the characteristic resistance for combined pull-out and concrete failure
0 0
V Rk,cp = k · N Rk,p · (A p,N / A p,N ) · ψ s,Np · ψ re,Np · ψ ec,Np,x · ψ ec,Np,y · ψ g,Np
g
V Sd < V Rk,cp / γ Mcp
The fastening consists of 2 groups which do not affect each other for pry-out failure because their spacing is larger than
the characteristic value scr,N.
Group 1: Anchor no. 1
V Rk,cp = 2.0 · 105.05 · (108900 / 108900 ) · 1.000 · 1.000 · 1.000 · 1.000 · 1.000 = 210.10 kN
15.50 < 210.10 / 1.50 = 140.07
Utilization: βV,cp = 11.1%
Group 2: Anchor no. 2
V Rk,cp = 2.0 · 105.05 · (108900 / 108900 ) · 1.000 · 1.000 · 1.000 · 1.000 · 1.000 = 210.10 kN
15.50 < 210.10 / 1.50 = 140.07
Utilization: βV,cp = 11.1%
Interaction:
1.5 1.5
β N + β V < 1.0
0.8151.5 + 0.2051.5 = 0.829 < 1.0
The design results must be checked for plausibility and fulfill the conditions of local standards and approvals. Page 3 of 4
1/12/2024 DesignFiX 3.5.8747.193
Notes:
The design results are based essentially on the conditions defined by the user of the software and on the data entered by
them. However, the end-user bears the sole responsibility for the absence of errors and their completeness. Furthermore,
the end-user is solely responsible for having the results of the calculation checked and cleared by an expert prior to using
them for the specific application. This is especially true with regard to the compliance with applicable standards and
approvals. DesignFiX serves only as an aid to interpret the standards and approvals without any guarantee to the
absence of errors. All conditions of the approval (ETA-21/0354) are to be observed.
As a pre-condition it is assumed that the anchor plate does not deform under the design actions. The DesignFiX anchor
plate design is based on a proof of stresses and does not allow a statement about the stiffness of the plate. The proof of
the necessary stiffness is not carried out by DesignFiX.
To ensure the structural component's capacity, the proofs in accordance with EN 1992-4:2018, Annex A must be
observed.
The design results must be checked for plausibility and fulfill the conditions of local standards and approvals. Page 4 of 4