BHEL Project: 2x660 MW Udangudi Supercritical TPS, Stage I

Application: Base Plate Connection - B8 - 550x100

1/12/2024 DesignFiX 3.5.8747.195

Supplier: Fosroc International Ltd.


P.O.Box 12276 | Dubai | +971 4 403 7643
Product: Fosroc International Ltd.
Lokfix E77 threaded rod (50 year) - Material: Zinc-plated
8.8
M20
Threaded rod: l = 220 + 10 + 21 + 5 = 256 mm
Design method: EN 1992-4:2018, method A
Approval: ETA-21/0354 | 5/12/2021
Base material: Uncracked concrete C20/25
No or normal reinforcement
Temperature: Short term = 40°C | Long term = 24°C
Installation: Pre-positioned | Hammer drilling | Compressed Air Cleaning | Annular gap not filled |
Dry or wet
Embedment depth: hef = 220 mm | Drill hole depth min. = 220 mm
Base plate: Rectangular 550 • 100 • 10
Profile: none selected
Load: Static / quasi-static | αsus = 0.60 | ψsus = 1.00
Units: Load [kN, kNm] | Dimensions [mm], * Not drawn to scale

The design results must be checked for plausibility and fulfill the conditions of local standards and approvals. Page 1 of 4
1/12/2024 DesignFiX 3.5.8747.195

Anchor forces [kN]: Concrete:


Anchor N V Vx Vy Max. compression 0.74 [‰]
1 87.40 10.08 10.05 0.75 Max. compressive 22.32 N/mm²
2 87.40 10.08 10.05 0.75 stress:
Resultant tension load: 174.79 kN
xZ / yZ: 0 / 0 mm
Resultant compression 93.49 kN
force:
xD / yD: 0 / 45 mm

Tension load
Steel failure
h
N Ed < N Rk,s / γ Ms

87.40 < 196.00 / 1.50 = 130.67 kN


Utilization: β N,s = 66.9%

Concrete cone failure


0 0
N Rk,c = N Rk,c · (A c,N / A c,N ) · ψ s,N · ψ re,N · ψ ec,N,x · ψ ec,N,y · ψ M,N
g
N Ed < N Rk,c / γ Mc

The fastening consists of one group.


Anchor no. 1, 2
N Rk,c = 160.52 · (732600 / 435600 ) · 1.000 · 1.000 · 1.000 · 1.000 · 1.000 = 269.97 kN
174.79 < 269.97 / 1.50 = 179.98 kN
Utilization: βN,c = 97.1%

Combined pull-out and concrete failure


0 0
N Rk,p = N Rk,p · (A p,N / A p,N ) · ψ s,Np · ψ g,Np · ψ ec,Np,x · ψ ec,Np,y · ψ re,Np
g
N Ed < N Rk,p / γ Mp

The fastening consists of one group.


Anchor no. 1, 2
N Rk,p = 248.81 · (662429 / 383688 ) · 1.000 · 1.000 · 1.000 · 1.000 · 1.000 = 429.56 kN
174.79 < 429.56 / 1.50 = 286.37
Utilization: βN,p = 61.0%

Splitting
According to design method no splitting proof is required!

Shear loads

Steel Resistance (without lever arm)


h
V Ed < V Rk,s / γ Ms

10.08 < 98.00 / 1.25 = 78.40 kN


Utilization: β V,s = 12.9%

The design results must be checked for plausibility and fulfill the conditions of local standards and approvals. Page 2 of 4
1/12/2024 DesignFiX 3.5.8747.195

Concrete pry-out failure at the side opposite to load direction:


Basic value of the characteristic resistance for concrete cone failure
0 0
V Rk,cp = k · N Rk,c · (A c,N / A c,N ) · ψ s,N · ψ re,N · ψ ec,N,x · ψ ec,N,y
g
V Sd < V Rk,cp / γ Mcp

The fastening consists of one group.


Anchor no. 1, 2
V Rk,cp = 2.0 · 160.52 · (732600 / 435600 ) · 1.000 · 1.000 · 1.000 · 1.000 = 539.95 kN
20.16 < 539.95 / 1.50 = 359.96
Utilization: βV,cp = 5.6%

Basic value of the characteristic resistance for combined pull-out and concrete failure
0 0
V Rk,cp = k · N Rk,p · (A p,N / A p,N ) · ψ s,Np · ψ re,Np · ψ ec,Np,x · ψ ec,Np,y · ψ g,Np
g
V Sd < V Rk,cp / γ Mcp

The fastening consists of one group.


Anchor no. 1, 2
V Rk,cp = 2.0 · 248.81 · (662429 / 383688 ) · 1.000 · 1.000 · 1.000 · 1.000 · 1.000 = 859.12 kN
20.16 < 859.12 / 1.50 = 572.75
Utilization: βV,cp = 3.5%
Interaction:
βN + βV > 1.2
0.971 + 0.056 = 1.027 < 1.2

Summary of the design results:


Failure mode Utilization
Tension load Steel failure 66.9%
Concrete failure 97.1%
Combined pull-out and concrete 61.0%
failure
Shear loads Steel failure 12.9%
Concrete pry-out failure at the side 5.6%
opposite to load direction
Interaction 85.6%
Proof of anchor was successful!

The design results must be checked for plausibility and fulfill the conditions of local standards and approvals. Page 3 of 4
1/12/2024 DesignFiX 3.5.8747.195

Notes:
The design results are based essentially on the conditions defined by the user of the software and on the data entered by
them. However, the end-user bears the sole responsibility for the absence of errors and their completeness. Furthermore,
the end-user is solely responsible for having the results of the calculation checked and cleared by an expert prior to using
them for the specific application. This is especially true with regard to the compliance with applicable standards and
approvals. DesignFiX serves only as an aid to interpret the standards and approvals without any guarantee to the
absence of errors. All conditions of the approval (ETA-21/0354) are to be observed.

As a pre-condition it is assumed that the anchor plate does not deform under the design actions. The DesignFiX anchor
plate design is based on a proof of stresses and does not allow a statement about the stiffness of the plate. The proof of
the necessary stiffness is not carried out by DesignFiX.

To ensure the structural component's capacity, the proofs in accordance with EN 1992-4:2018, Annex A must be
observed.

The design results must be checked for plausibility and fulfill the conditions of local standards and approvals. Page 4 of 4