BHEL Project: 2x660 MW Udangudi Supercritical TPS, Stage I

Application: Base Plate Connection - C9 - 480x100 - Seismic

1/12/2024 DesignFiX 3.5.8747.194

Supplier: Fosroc International Ltd.


P.O.Box 12276 | Dubai | +971 4 403 7643
Product: Fosroc International Ltd.
Lokfix E77 threaded rod (50 year) - Material: Zinc-plated
8.8
M16
Threaded rod: l = 110 + 10 + 18 + 5 = 143 mm
Design method: EN 1992-4:2018, method A
Approval: ETA-21/0354 | 5/12/2021
Seismic loading: C2:Capacity design according to ETAG 001, TR 45, Section 5.3 a1
DLS displacement: δ N,req(DLS) = -1.0 mm , δ V,req(DLS) = 3.4 mm
Base material: Cracked concrete C20/25
No or normal reinforcement / Straight reinforcement (Ø ≥ 12 mm) + hanger (a ≤ 100
mm)
Splitting reinforcement according EN 1992-4, Section 7.2.1.7 available
Temperature: Short term = 40°C | Long term = 24°C
Installation: Pre-positioned | Hammer drilling | Compressed Air Cleaning | Annular gap not filled |
Dry or wet
Embedment depth: hef = 110 mm | Drill hole depth min. = 110 mm
Base plate: Rectangular 480 • 100 • 10
Profile: none selected
Load: Seismic load (see Notes on the last page) | αsus = 0.60 | ψsus = 1.00
Units: Load [kN, kNm] | Dimensions [mm], * Not drawn to scale

The design results must be checked for plausibility and fulfill the conditions of local standards and approvals. Page 1 of 5
1/12/2024 DesignFiX 3.5.8747.194

The design results must be checked for plausibility and fulfill the conditions of local standards and approvals. Page 2 of 5
1/12/2024 DesignFiX 3.5.8747.194

Anchor forces [kN]: Concrete:


Anchor N V Vx Vy Max. compression - [‰]
1 0.00 2.75 -2.75 -0.05 Max. compressive -
2 0.00 2.75 -2.75 -0.05 stress:
Resultant tension load: -
xZ / yZ: -/-
Resultant compression -
force:
xD / yD: -/-

Shear loads

Steel Resistance (without lever arm)


h
V Ed,seis < δ V,req(DLS) / δ V,seis(DLS) · α gap · α seis · V Rk,s,seis,C2 / γ Ms,seis

2.75 < 1.00 · 0.50 · 0.85 · 44.10 / 1.25 = 14.99 kN


Utilization: β V,s = 18.3%

The design results must be checked for plausibility and fulfill the conditions of local standards and approvals. Page 3 of 5
1/12/2024 DesignFiX 3.5.8747.194

Concrete pry-out failure at the side opposite to load direction:


Basic value of the characteristic resistance for concrete cone failure
0 0
V Rk,cp,seis = k · N Rk,c · (A c,N / A c,N ) · ψ s,N · ψ re,N · ψ ec,N,x · ψ ec,N,y
g
V Sd,seis < δ V,req(DLS) / δ V,seis(DLS) · α gap · α seis · V Rk,cp,seis / γ Mcp,seis

The fastening consists of 2 groups which do not affect each other for pry-out failure because their spacing is larger than
the characteristic value scr,N.
Group 1: Anchor no. 1
V Rk,cp,seis = 2.0 · 39.73 · (108900 / 108900 ) · 1.000 · 1.000 · 1.000 · 1.000 = 79.46 kN
2.75 < 1.00 · 0.50 · 0.75 · 79.46 / 1.50 = 19.86
Utilization: βV,cp = 13.8%
Group 2: Anchor no. 2
V Rk,cp,seis = 2.0 · 39.73 · (108900 / 108900 ) · 1.000 · 1.000 · 1.000 · 1.000 = 79.46 kN
2.75 < 1.00 · 0.50 · 0.75 · 79.46 / 1.50 = 19.86
Utilization: βV,cp = 13.8%

Basic value of the characteristic resistance for combined pull-out and concrete failure
0 0
V Rk,cp,seis = k · N Rk,p · (A p,N / A p,N ) · ψ s,Np · ψ re,Np · ψ ec,Np,x · ψ ec,Np,y · ψ g,Np
g
V Sd,seis < δ V,req(DLS) / δ V,seis(DLS) · α gap · α seis · V Rk,cp,seis / γ Mcp,seis

The fastening consists of 2 groups which do not affect each other for pry-out failure because their spacing is larger than
the characteristic value scr,N.
Group 1: Anchor no. 1
V Rk,cp,seis = 2.0 · 26.54 · (108900 / 108900 ) · 1.000 · 1.000 · 1.000 · 1.000 · 1.000 = 53.08 kN
2.75 < 1.00 · 0.50 · 0.75 · 53.08 / 1.50 = 13.27
Utilization: βV,cp = 20.7%
Group 2: Anchor no. 2
V Rk,cp,seis = 2.0 · 26.54 · (108900 / 108900 ) · 1.000 · 1.000 · 1.000 · 1.000 · 1.000 = 53.08 kN
2.75 < 1.00 · 0.50 · 0.75 · 53.08 / 1.50 = 13.27
Utilization: βV,cp = 20.7%

Summary of the design results:


Failure mode Utilization
Shear loads Steel failure 18.3%
Concrete pry-out failure at the side 20.7%
opposite to load direction
Proof of anchor was successful!

The design results must be checked for plausibility and fulfill the conditions of local standards and approvals. Page 4 of 5
1/12/2024 DesignFiX 3.5.8747.194

Notes:
The design results are based essentially on the conditions defined by the user of the software and on the data entered by
them. However, the end-user bears the sole responsibility for the absence of errors and their completeness. Furthermore,
the end-user is solely responsible for having the results of the calculation checked and cleared by an expert prior to using
them for the specific application. This is especially true with regard to the compliance with applicable standards and
approvals. DesignFiX serves only as an aid to interpret the standards and approvals without any guarantee to the
absence of errors. All conditions of the approval (ETA-21/0354) are to be observed.

You have selected the design option "Capacity design" according to ETAG 001, TR 045, Section 5.3a1. The entered
loads correspond to the maximum tension- and/or shear loads that can be transmitted to the fastening based on the
development of a ductile yield mechanism in the attached element welded to the anchor plate or to the capacity of a non-
yielding attached element.
As a pre-condition it is assumed that the anchor plate does not deform under the design actions. The DesignFiX anchor
plate design is based on a proof of stresses and does not allow a statement about the stiffness of the plate. The proof of
the necessary stiffness is not carried out by DesignFiX.

To ensure the structural component's capacity, the proofs in accordance with EN 1992-4:2018, Annex A must be
observed.

The design results must be checked for plausibility and fulfill the conditions of local standards and approvals. Page 5 of 5