CSC-211

Multifunction Protection IED

Product guide
CSC-211 Multifunction Protection IED

Version:V1.01

Issued Date:2019.01

Copyright owner: Beijing Sifang Automation Co., Ltd

Note: the company keeps the right to perfect the instruction. If equipment does not agree
with the instruction at anywhere, please contact our company in time. We will provide you
with corresponding service.

®
is registered trademark of Beijing Sifang Automation Co., Ltd.

We reserve all rights to this document, even in the event that a patent is issued and a different commercial
proprietary right is registered. Improper use, in particular reproduction and dissemination to third parties, is
not permitted.

This document has been carefully checked. If the user nevertheless detects any errors, he is asked to notify
us as soon as possible.

The data contained in this manual is intended solely for the product description and is not to be deemed to
be a statement of guaranteed properties. In the interests of our customers, we constantly seek to ensure
that our products are developed to the latest technological standards as a result; it is possible that there
may be some differences between the hardware/software product and this information product.

Manufacturer:
Beijing Sifang Automation Co., Ltd.
Email: support@sf-auto.com
Website: http://www.sf-auto.com
Add: No.9, Shangdi 4th Street, Haidian District, Beijing, P.R.C.100085

2 / 40
CSC-211 Multifunction Protection IED

CSC-211 is selective, reliable and high speed protection IED with rich functions to cover following
applications:

 Protection, bay control unit, MU(Merging Unit), and SCU(Smart control Unit) in one IED;

 Work as feeder or capacitor bank protection IED;

 Work as backup protection IED for transmission lines, transformer;

 Fully proven protection functions library;

 Powerful scalable hardware capability, for present and future application

 Mixable CT&VT inputs / SV(Sampling Value) input /output;

 Mixable Binary inputs & output relays / GOOSE inputs /outputs;

 Robust hardware with excellent EMC performance and IP54 protection under -40℃ to 70℃
operating temperature;

3 / 40
Application

46NU

50 3I >>> MEASUREMENT
PIOC 46NI

51/67 3I> 3I>>


PTOC 59 3U>
MONITORING
PTOV
50N I0>>>
PIEF 27 3U<
PTUV INTERLOCK
51N/67N I0> I0>>
50Ns
&
PTEF 3INE>>

50BF 3I>BF
RBRF 51Ns/67Ns 3INE>
CONTROL

49 Ith
PTTR 32

ENERGY METER
37 CALCULATED
55

46
Disturbance
64 UE> recording
STATION
COMMUNICATION

- RS232/485
79 O→I 25
- RJ45/FO
RREC RSYN - IEC61850
- IEC60870-5-103

4 / 40
Function
Function ANSI Code Qty. Description
Directional overcurrent protection 50,51,67 1 4 stages; Directional/unidirectional; Definite time/inverse
time characteristic; 5 IEC curves, 7 ANSI curves and 1
user defined inverse time curve; Inrush block;
Directional earth fault protection 50N, 51N, 1 4 stages; Directional/Unidirectional; Definite time /
67N Inverse time characteristic; 5 IEC curves, 7 ANSI curves
and 1 user defined inverse time curve; 3 phase current
inputs/Single current input;
Sensitive directional earth fault 50Ns, 51Ns, 1 4 stages; Directional/Unidirectional; Definite time /
protection 67Ns Inverse time characteristic; 5 IEC curves, 7 ANSI curves
and 1 user defined inverse time curve; 3 phase current
inputs/Single current input;
Negative sequence overcurrent 46 1 4 stages; Definite time/Inverse time characteristic; 5 IEC
curves, 7 ANSI curves and 1 user defined inverse time
curve;
Switch onto fault protection 50SOTF 1 1 stage

Thermal overload 49 1 2 stages for alarm; 1 stage for tripping

Under current protection 37 1 1 stage

Overvoltage 59 1 4 stages; Definite time / Inverse time characteristic;

Undervoltage 27 1 4 stages; Definite time / Inverse time characteristic;

Zero sequence overvoltage 59N 1 4 stages; Definite time / Inverse time characteristic;

Negative sequence overvoltage 59NS 1 4 stages; Definite time / Inverse time characteristic;

Unbalanced voltage protection 46UV 1 For capacitor bank; 1 stage;

Unbalanced current protection 46UC 1 For capacitor bank;1 stage

Power protection 32 1 2 stage

Under frequency protection 81U 1 4 stages;

Over frequency protection 81O 1 4 stages;

Frequency change of rate 81DF 1 4 stages;


protection
Breaker failure protection 51BF 1 2 stages;

Dead zone protection 51DZ 1 1 stage

Poles discordance protection 51PD 1 1 stage

Broken conduct detection 46BC 1 1 stage

Synchro-check & Energizing 25 1


check

5 / 40
Function
Auto-reclosing 79 2 4 shots;

Load shedding by underfrequency 81U-LS 1 4 stages;

Load shedding by undervoltage 27LS 1 4 stages;

Load shedding by overload 50LS 1 4 stages;

VT secondary circuit supervision 97FF 1

Disturbance recording 1 Max.16 records; Max. 20s in 1 recording;

Fault locator 1

Self-supervision Self-diagnose status of hardware and software of IED

Trip circuit supervision 2

Lockout 86

Programmable logic

Measurement V, I, f, P, Q, Wp, Wq;

Control CB and isolators control; Remote/local control:

Monitoring Status of primary equipment;

Communication Ethernet communication; serial communication; Printer;

Time synchronization IRIG-B; IEEE1588;SNTP;

Note 1: the number in “Qty.” column is the maximum quantity of function module is able to
offer.

50, 51, 67 Overcurrent protection


 4 stages relevantly;

 Definite time/invers time characteristic  Work as emergency overcurrent, depend


selectable. on VT secondary circuit supervision

 11 kinds of IEC and ANSI inverse time


characteristic curves as well as optional
user defined characteristic

 Directional/non-directional set for each


stage relevantly;

 Forward / Reverse direction set for each


stage relevantly;

 Inrush restraint set for each stage

6 / 40
Function
Characteristic of overcurrent directional element
Forward 90° IA

ΦPh_Char

U BC_Ref

IA Reverse

50N, 51N, 67N Earth fault protection


 3 phase currents inputs or single current relevantly;
inputs work as transformer neutral
overcurrent protection, Bisector 90° Reverse
-3I 0
 4 stages;

 Definite time/invers time characteristic


selectable for each stage;.

 11 kinds of IEC and ANSI inverse time
3U 0_Ref
characteristic curves as well as optional
Φ0_Char
user defined characteristic

 Directional/non-directional set for each


stage relevantly;
Forward Bisector
 Forward / Reverse direction set for each -3I 0

stage relevantly;
Characteristic of zero sequence directional
 Inrush restraint set for each stage element.

50Ns, 51Ns, 67Ns Sensitive earth


fault protection
 For power system non-earthed or earthed  Single current input, from cable type CT
through resistor or reactor;

7 / 40
Function
 4 stages; Characteristic of the sensitive earth fault directional
element by U0/I0-Φ
 Definite time/invers time characteristic set
for each stage;.  Sensitive earth fault directional element with
Cos Φ principle
 11 kinds of IEC and ANSI inverse time
characteristic curves as well as optional 90°
IS
user defined characteristic

 Directional/non-directional set for each


stage relevantly;

 Sensitive earth fault directional element


Forward 0°
with 3U0/3I0-Φ principle
3U0_Ref

90° - I NS
Forward

Bisector
- IS

ΦNS_Char 0°
Characteristic of the sensitive earth fault directional
3U0_Ref element by Cos Φ

 Forward / Reverse direction set for each


stage relevantly;

I NS  Inrush restraint set for each stage


relevantly;

50NS, 51NS Negative sequence


overcurrent protection
 4 stages;  11 kinds of IEC and ANSI inverse time
characteristic curves as well as optional
 Definite time/invers time characteristic
user defined characteristic.
selectable for each stage;.

49 Thermal overload protection


 1 stage for alarm and 2 stages for tripping; Curve) of IEC60255-8 standard.

 Based on thermal models (Cold or Hot

8 / 40
Function
59 Overvoltage protection
 4 stages  Phase-earth voltage or phase-phase
voltage inputs
 definite time/inverse time characteristic
selectable for each stage;

27 Undervoltage protection
 4 stages voltage inputs

 definite time/inverse time characteristic  Current criteria supervision


selectable for each stage;
 Circuit breaker aux. contact supervision
 Phase-earth voltage or phase-phase
 VT secondary circuit supervision

59N(64) Zero sequence overvoltage


protection
 3 stages  3U0 based on calculated summation of 3
phase voltages or measured injected
 definite time/inverse time characteristic
residual voltage
selectable for each stage;

59NS Negative sequence overvoltage


protection
 4 stages  Phase-earth voltage or phase-phase
voltage inputs
 definite time/inverse time characteristic
settable for each stage;

50BF Breaker failure protection


 Two trip stages (local CB and surrounding breaker tripping)

9 / 40
Function
 Transfer trip command to the remote line  Settable CB Aux contacts checking
end in second stage
 Current criteria checking (including phase
 Internal/ external initiation current, zero and negative sequence
current)
 Single/three phase CBF initiation

50DZ Dead zone protection


 Protected area is between circuit breaker and
CT in the case that CB is open.

 Situation 1: With one bus side CT of feeder


Inter trip
Bus
The IED trips the relevant busbar zone, shown
as below.

Legend:

Opened CB IFAULT
Closed CB

Trip
Bus Line1 Line2 LineN

Legend:
IFAULT Trip
Relay Opened CB
Closed CB

Line1 Line2 LineN  Internal/ external initiation

 Self-adaptive for bus side CT or line side CT

 Situation 2: With one line side CT.

Protection relay sends a transfer trip to


remote end relay to isolate the fault.
Tripping logic is illustrated below.

51STUB STUB protection


 Condition 1: The line side disconnector is of service..
open;
 The protected zone is between the CTs and
 Condition 2: Main line protection IED is out the open disconnector.

10 / 40
Function
 The STUB protection is enabled when the
open position of the disconnector;

 1 definite time stage, which related concept


is shown below.

Legend:

Closed CB

Bus A Delay trip Bus B

IFAULT IFAULT

Line Line
A B

25 Synchro-check and energizing check


 Available for automatic reclosing (internally  Override
or externally)
 Modes of energizing check:
 Based on voltage/ angle/ frequency
 Dead line and dead bus
difference
 Dead line and live bus
 Synchro-check conditions:
 Live line and dead bus
 Synch-check
 Synchro-check reference voltage
 Energizing check, and synch-check
supervision
after energizing check failure

79 Auto-reclosing

11 / 40
Function
 Up to 2 AR modules to support 2 CBs in  Internal/external AR initiation
one IED
 Single/three phase AR operation
 4 shots automatic reclosing (selectable)
 CB ready supervision
 Individually settable dead time for three
 CB Aux. contact supervision
phase and single phase fault and for each
shot  Cooperation with internal synch-check
function for reclosing command

46UC Unbalanced overcurrent protection


 Dedicated to capacitor bank  1 stages;

 3 independent current inputs;

46UV Unbalanced overvoltage protection


 Dedicated to protection of capacitor bank  1 stages;

 3 independent voltage inputs;

37 Undercurrent protection
 To avoid capacitor bank charging the bus  3 phase current inputs;
when bus voltage falling down.
 1 stages;

81U-LS load shedding by Under


frequency
 4 stages  CB position checking

 Under voltage checking  Load current checking

 Rate of frequency (df/dt) checking  VT secondary circuit supervision

27LS Under voltage load shedding

12 / 40
Function
 4 stages  CB position checking

 Under voltage checking  Load current checking

 Negative sequence voltage checking  VT secondary circuit supervision

 Rate of voltage (du/dt) checking

51LS Overload load shedding


 4 stages  Rate of frequency (df/dt) checking (in the
case of voltage connection)
 Under voltage checking
 VT secondary circuit supervision (in the
 Rate of voltage (du/dt) checking (in the
case of voltage connection)
case of voltage connection)

50BB Fast busbar protection scheme


 Based on coordination among protection
IED of all feeders connected with the A
Relay A
busbar;

 Based on GOOSE interlocking between the


protection IEDs or incoming feeders and

GOOSE message-Block
outgoing feeders in accordance with
IEC61850;

 Clear busbar fault in short time if without


dedicated busbar protection IED Relay B

B
Trip

Relay C

Operating principle when fault on the outgoing feeder

13 / 40
Function
Operating principle when fault on the Busbar

A
Relay A

Trip

Relay B

Relay C

14 / 40
Automation
 Support SV, GOOSE service of process  DNP 3.0;
layer application in accordance with
 MODBUS
IEC61850-8-1, -9-2, -9-2LE,
 Support several time synchronizing way,
 Support MMS, GOOSE service of station
include:
layer and bay layer application in
accordance with IEC61850-8-1,  IRIG-B electrical/optical;

 Seamless communication by PRP.  Pulse;

 Adaption to the existing automation system  SNTP;


with several Ethernet ports or serial
 IEEE 1588;
communication ports in one module
 Proven technology from thousands of
 Support all main protocols, include:
operated digital substations;
 IEC 60870-5-103 serial or TCP/IP;

HMI

Switch

Protection
IED

Switch Switch
Indoor

Outdoor
SCU AMU+SCU AMU+SCU

Bay A Bay B Bay A Bay B Bay A Bay B Bay A Bay B

Station layer: MMS/GOOSE; PRP; Station layer: MMS/GOOSE; PRP; Station layer: MMS/GOOSE; PRP; Station layer: MMS/GOOSE; PRP;
Bay layer: GOOSE; PRP; Bay layer: GOOSE; PRP; Bay layer: GOOSE; PRP; Bay layer: GOOSE; PRP;
Process layer: Process bus, GOOSE; PRP; Process layer: SV/GOOSE; PRP; Process layer: Process bus, SV/GOOSE; PRP;

15 / 40
Tools
AESP tools is the user-friendly software tool bar, and protection characteristic diagram
sets. AESP covers all works for the whole life graphically and precise data in pointed
cycle of protection IEDs, include, instant.
 Setting and parameter
 Disturbance analysis by Fisewave
 Monitoring
 Logic programming by Nuclide
 IED configuration by IO master;
 Single line diagram painter;
 IEC 61850 system engineering manager
Its features are as follows:

 Oriented to IEDs management of whole


substation with freely configurable
hierarchies based on the substation
topology in real project.
 With integrated logic, the user can set, via a
 Intelligent validity checks and shadow avoid graphic interface, specific functions for the
incorrect input when setting and automation of switchgear or substation.

 Fault analysis with fault records in curves,  Password-protected access for different
circle diagrams, vector diagrams, harmonic operation and different roles;

16 / 40
Hardware
 Up to 12 AC Current Inputs and 6 Voltage  Up to 3 RJ45 Ethernet ports );
Inputs;  Up to 2 RS485 ports;
 Up to 42 Binary Inputs, include independent  1 IRIG-B / Pulse time synchronization port;
BIs;  1 RJ45 front test port
 Up to40 Output relays, with 4 switchable  22 programmable LED
NO/NC contacts;  Up to 4 customer defined function key;
 Up to 7 Ethernet optical ports, for SV,  4U 19” or 4U 1/2 19” case;
GOOSE, MMS and other automation
services;

Available Transformer input modules

Transformer input module 177

Current inputs for protection 259.2

Current input for measurement 232.7

Voltage inputs 226

DC input for measurement mm

Front view
Rear view

17 / 40
Hardware
D

A 177

B 259.2
A
C 232.7

D 226

C Unit mm

Dimension of case

18 / 40
Specification
IEC60255-27 110V
AC current measurement
DL/T478-2013
Item Data Thermal overload 180V, continuously;
Rated current Ir 1A and 5A capacity Vph-e 400V for 60s.
Operating range of (0 ~ 100) Ir IEC60255-27
protection CT DL/T478-2013

Measuring range of (0.05 ~ 40) Ir


protection CT Other measurement
Reading Accuracy for ±1%I at I> Ir
Item Data
protection CT ±0.5%Ir at I≤Ir
Rated frequency 50Hz / 60Hz, settable
Thermal overload 4 Ir Continuously;
capacity of protection CT 30 Ir for 10s Measuring range of
±10% Fn
IEC60255-27 100 Ir for 1s frequency
Reading accuracy of
Range for measuring CT (0.01 ~ 2) Ir ±0.02Hz
frequency
Reading accuracy for ±0.5%I at I>In
Reading accuracy of ±1°, at rated AC voltage and
measuring CT ±0.5%In at I≤In
angle AC current
Thermal overload 4 Ir Continuously;
Reading accuracy of
capacity of measuring CT 30 Ir for 10s 1%, at rated voltage and
power and reactive
IEC60255-27 100 Ir for 1s current
power
Measurement range for 0.005A ~ 1.2A
high sensitive CT
Reading accuracy for ±0.5%I at I>10%In Binary inputs
high sensitive CT ±0.5%In at I≤10%In
Item Data
Thermal overload 3A continuously
Rated voltage Vr.aux 110V/125V/220V/250V DC,
capacity of high sensitive 100A for 1s
IEC60255-1 settable;
CT
Or 24V/48V DC settable;
IEC60255-27
Max. permissible 300V, at rated 110V/ 125V/
DL/T478-2013
voltage 220V/ 250V DC;
Power consumption (per ≤0.15VA at In=1A;
IEC60255-1 62V, at rated 24V/ 48V;
phase) ≤0.3VA at In=5A
Operating Threshold ≥70% Vr.aux, guarantee
Dynamic thermal 250 Ir for 1.5 cycle
IEC60255-1 operating
overload capacity
≤55% Vr.aux, guarantee not to
operating
AC voltage measurement Pickup time Approx. 1ms, intrinsic
Dropout time Approx. 2ms, intrinsic
Item Data
Power consumption ≤0.1 W/input, at Vr.aux=110V DC
Rated voltage Vr.ph-ph 100V ~ 120V, settable;
IEC60255-1 ≤0.5 W/input, at Vr.aux=220V DC
IEC60255-1
Measuring range Vph-e 0.1V ~ 180V
Reading accuracy Vph-e ±1% at >10%Vr.ph-e.
Output relay
0.03V at ≤10% Vr.ph-e Item Data
Power consumption ≤ 0.05VA/Phase, at Vr. ph-ph = Rated contact voltage 24V, 48V, 110V, 220V DC

19 / 40
Specification
IEC60255-1 100V, 220V AC Static power consumption ≤ 18W
Maximum contact voltage 250V AC/DC IEC60255-1
IEC60255-1 Maximum load power ≤ 20W
Current carrying capacity General relay:
consumption
IEC60255-1 5A continuous,
IEC60255-1
10A, 1s on,15s off
30A, 200ms on,15s off
Power output relay:
Ethernet communication
10A continuous, Item Data
30A, 200ms on,15s off Max. ports number 3
Making capacity General relay: Electrical Ethernet port type RJ45
IEC60255-1 1100W(DC) at L/R>40ms Maximum transmission 100M
1000VA(AC) distance of Ethernet cable
Power output relay: Optical Ethernet port type LC
1250W (DC)
Fiber optic cable type Multi-mode
2000VA(AC)
Optic wavelength 1310 nm
Breaking capacity General relay:
Optic received sensitivity -34 dBm
IEC60255-1 0.2A, at Vr.aux=220V,
Emitter electric level >-11 dBm;
L/R≤40ms;
Maximum transmission 2kM
0.4A, at Vr.aux=110V,
distance of optical fiber
L/R≤40ms;
Transmission rate for 100Mbit/s
1000VA, at Vr.AC;
IEC61850
Power output relay:
Transmission rate for DNP 100Mbit/s
0.25A, at Vr.aux=220V,
3.0
L/R≤40ms;
0.45A, at Vr.aux=110V,
L/R≤40ms; Serial communication
1200VA, at Vr.AC;
Item Data
Pick up time General relay: Number 2
IEC60255-1 ≤5ms
Port type Extract twisted pair
Power output relay:
Maximum transmission 1.0km
≤5ms
distance
Drop off time ≤10ms
Voltage withstand test 500V earthing AC voltage
IEC60255-1
Transmission rate for Default setting 9600 bps;
IEC60870-5-103 Minimum: 1200bps;
Auxiliary power maximum: 19200bps

Item Data
Time synchronization
Rated voltage Vr.aux 100V to 250V DC/AC
IEC60255-1 24/48V DC Item Data

Input voltage range ±%20 Vr.aux Synchronization mode SNTP

IEC60255-1 IRIG-B time sync


Minute or second Pulse

20 / 40
Specification
IRIG-B signal format IRIG-B000 IEC60255-5  Auxiliary power
IRIG-B Port type Twisted-pair connection or EN60255-5 supply port;
optical fibers ANSIC37.90  Enclosure port;
IRIG-B signal voltage level Differential signal input GB/T15145-2001  Input and output
DL/T478-2013 ports;

Inter-substation communication Functional earth
port;
Item Data 500V, 50Hz, at rated
Ports number 1~2 voltage ≤63V, Tested on:
Fiber optic cable type Single-mode  Communication port;
Optic wavelength 1310 nm, when the Impulse voltage 5kV, at rated voltage>60V,
transmission distance <60 km IEC60255-5 Tested on:
1550 nm, when the IEC60255-27  Auxiliary power
transmission distance >60 km EN60255-5 supply port;
Optic received -34 dBm ANSIC37.90  Enclosure port;
sensitivity GB/T15145-2001  Input and output
Emitter electric level >-11 dBm, at length <40 kM DL/T478-2013 ports;
>-4 dBm, at length 40~60 kM  Functional earth
>-5 dBm, at length 60~80 kM port;
>-3 dBm, at length 80~100 kM 1kV, at rated voltage≤60V,
>-0 dBm, at length 100~120 tested on:
kM  Communication port;
Fiber optic connector LC Insulation resistance ≥100MΩ,500V,
type IEC60255-5
Data transmission rate 64 kbit/s, G703 IEC60255-27
2,048 kbit/s, G703-E1 EN60255-5
Max. transmission 120 kM ANSIC37.90
distance GB/T15145-2001
DL/T478-2013

Product safety test Protective bonding ≤0.1Ω


resistance
Item Data IEC60255-27
Over voltage category Category III Fire withstand/flammability Class V2
IEC60255-27 IEC60255-27
Pollution degree Degree 2

EMC test
IEC60255-27
Insulation Basic insulation
IEC60255-27 Item Data

Degree of protection (IP) Front plate: IP54 Electrostatic discharge Criteria A;


IEC60255-27 Side plate:IP52 immunity test Level IV;
IEC60529 Rear plate: IP30 IEC60255-26:2013 ±6kV contact discharge;

Power frequency high 2KV, 50Hz, at rated IEC61000-4-2 ±8kV air gap discharge;

voltage withstand test voltage > 63V, Tested on: Radiated, Criteria A;

21 / 40
Specification
radio-frequency Class IV;  Communication ports;
electromagnetic field 10 V/m(r.m.s.), 80%,AM (1 Power frequency Class V
immunity test kHz) magnetic field immunity 30A / m Continuous;
IEC60255-26:2013 Frequency sweep: test 300A/m, from 1s to 3s; Test
IEC61000-4-3 80 MHz – 1 GHz; 1.4 GHz – 2.7 IEC60255-26:2013 on:
GHz IEC61000-4-8  Enclosure ports;
spot frequencies (MHz): Power frequency Zone A
80; 160; 380; 450; 900; 1850; immunity test 300V, CM; 150V, DM;
2150. IEC60255-26:2013; Test on:
Electrical fast Class A IEC61000-4-16  Binary input ports;
transient/burst immunity 4KV peak voltage; Slow damped oscillatory Class III
test Tested on: wave immunity test 2.5 kV CM ; 1 kV DM;
IEC60255-26:2013,  Auxiliary power supply (1MHz) IEC60255-26: Tested on:
IEC61000-4-4 port; 2013  Auxiliary power supply
ANSI/IEEE C37.90.1  Enclosure port; IEC61000-4-18 port;
 Input and output ports; ANSI/IEEEC37.90.1  Input and output ports;
 Functional earth port; 1 kV CM ; 0 kV DM;
2KV peak voltage; Tested on:
Tested on:  Communication ports
 Communication port; Fast damped oscillatory Level 4
Surge (impact) immunity Class A,Level IV wave immunity test 4 kV, at 3MHz, 10MHz,
test 4.0kV, Line-to-earth; IEC61000-4-18 30MHz.
IEC60255-26:2013, 2.0kV, Line-to-line; Tested on:
IEC61000-4-5 Tested on:  Auxiliary power supply
 Auxiliary power supply port;
port;  Input and output ports;
 Enclosure port; Pulse magnetic field Class V
 Input and output ports; immunity 1000A/m
 Functional earth port; IEC61000-4-9
4.0kV, Line-to-earth; Damped oscillation Class V
Tested on: magnetic field immunity 100A/m
 Communication ports; test
Test for Immunity to 10 V/m(r.m.s.), 80%,AM (1 IEC61000-4-10
conducted disturbances, kHz) Conducted emission Class A;
induced by Frequency sweep: 150kHz– IEC60255-26:2013 0.15MHz to 0.50MHz;
radio-frequency fields 80MHz CISPR22 0.50MHz to 30MHz;
IEC60255-26:2013 Spot frequencies: 27MHz and Tested on:
IEC61000-4-6 68MHz;  Auxiliary power supply
Tested on: port;
 Auxiliary power supply Radiated emission Class A;
port; IEC60255-26:2013 30MHz to 230MHz;
 Input and output ports; CISPR11 230MHz to 1GHz;
 Functional earth port;
DC voltage dips 20 ms at 0% residual voltage;

22 / 40
Specification
IEC60255-26:2013 200 ms at 40% residual Mechanical endurance, Unloaded, 10,000 times
IEC 61000-4-11 voltage; Unloaded (switching frequency is 3Hz);
IEC 61000-4-29 500 ms at 70% residual IEC60255-1 Making, ≥1000;
voltage; Breaking, ≥1000
AC voltage dips At 60Hz: Current carrying capacity 5A continuous,
IEC60255-26:2013 1.0 cycle at 0% residual IEC60255-1 30A, 200ms on,15s off
IEC 61000-4-11 voltage; Making capacity 1000W(DC) at Vr.aux,
IEC 61000-4-29 12 cycle at 40% residual IEC60255-1 L/R>40ms
voltage,; 1000VA(AC)
30 cycle at 70% residual Breaking capacity 30W, at Vr.aux, L/R≤40ms;
voltage; IEC60255-1 1000VA, at Vr.AC;
At 50Hz:
Contact circuit resistance 30mΩ
1.0 cycle at 0% residual
IEC60255-1
voltage;
Contact insulation test AC1000V,1min
10 cycle at 40% residual
(AC dielectric strength )
voltage,;
IEC60255-1
25 cycle at 70% residual
Maximum temperature 70℃
voltage;
that operation allows
DC voltage interruptions 5 s, at 0% residual voltage;
IEC60255-1
IEC60255-26:2013

Contact performance test of power


IEC 61000-4-11
IEC 61000-4-29
output relay
AC voltage interruptions At 60Hz:
IEC60255-26:2013 300 cycle at 0% residual Item Data
IEC 61000-4-11 voltage; Mechanical endurance, Unloaded, 10,000 times
IEC 61000-4-29 At 50Hz: Unloaded (switching frequency is 3Hz);
250 cycle at 0% residual IEC60255-1 Making, ≥1000;
voltage; Breaking, ≥1000
A.C. component in 15%, at 100Hz, twice rated Current carrying capacity 10A continuous,
d.c. (ripple) frequency; IEC60255-1 30A, 200ms on,15s off
IEC60255-26:2013 15%, at 120Hz, twice rated Making capacity 1250W(DC) at Vr.aux,
IEC 61000-4-17 frequency; IEC60255-1 L/R>40ms
Gradual shutdown/ 60 s shut down ramp 2000VA(AC)
start-up (for d.c. power 5 min power off Breaking capacity 0.25A, at Vr.aux=220V,
supply) 60 s start-up ramp IEC60255-1 L/R≤40ms;
IEC60255-26:2013 0.45A, at Vr.aux=110V,
DC voltage reverse 1 min L/R≤40ms;
polarity 1200VA, at Vr.AC;
Contact circuit resistance 30mΩ
Contact performance test of general IEC60255-1

relay Contact insulation test AC1000V,1min


(AC dielectric strength )
Item Data
IEC60255-1

23 / 40
Specification
Maximum temperature 70℃ 8-35 Hz: 1g acceleration
that operation allows (horizontal axis)
IEC60255-1 8-35 Hz: 0,5g acceleration
(vertical axis)
Mechanical test Frequency sweep 1
octave/min
Item Data
1 sweep cycle in each axis
Sinusoidal vibration Class 1
Relay energized
response test 10-60 Hz: ± 0.035 mm
IEC60255-21-1 amplitude
EN60255-21-1 60-150 Hz: 0,5g acceleration
Environmental test
Frequency sweep: 1 Item Data
octave/min Cold test - Operation -40°C, 96 hours, rated load
1 sweep cycle in each axis IEC60255-27
Relay energized IEC60068-2-1
Sinusoidal vibration Class 1 Cold test – Storage -40°C, 96 hours
endurance test 10 Hz to 150 Hz: 1 g IEC60255-27
IEC60255-21-1 20 sweep cycle in each axis IEC60068-2-1
EN60255-21-1 Relay non-energized Dry heat test – Operation +70°C, 96 hours, rated
Shock response test Class 1 IEC60255-27 load
IEC60255-21-2 Acceleration 5g, duration 11 IEC60068-2-2
EN 60255-21-2 ms. Dry heat test – Storage +70°C, 96 hours
3 shocks in each direction (6 IEC60255-27
shocks in each axis) IEC60068-2-2
Relay energized
Change of temperature Test Nb, figure 2, 5 cycles
Shock withstand test Class 1 IEC60255-27 -40°C / +70°C
IEC60255-21-2 Acceleration 15g, duration 11 IEC60068-2-14
EN 60255-21-2 ms.
Damp heat static test +40°C, 95% r.h. 10 days,
3 shocks in each direction (6 IEC60255-27 rated load
shocks in each axis)
IEC60068-2-78
Relay non-energized
Damp heat cyclic test +55°C, 97% r.h. 6 cycles,
Bump test Class 1
IEC60255-27 rated load
IEC60255-21-2 Acceleration 10g, duration 16
IEC60068-2-30
EN 60255-21-2 ms
1000 bumps in each direction
CE Certification
(2000 bumps in each axis)
Relay non-energized Item Data
Seismic test Class 1 EMC EN61000-6-2 and
IEC60255-21-3 1-8 Hz: ± 3.5 mm amplitude EN61000-6-4(EMC steering
(horizontal axis) committee 2004/108/EC)
1-8 Hz: ± 1.5 mm amplitude LVD EN60255-27(LVD2006/95EC)
(vertical axis)

24 / 40
Specification
50, 51, 67, Directional overcurrent Angle range of Operating 170°

protection area
Characteristic angle 0°to 90°, step 1°
Item Data ≤ ±1°, at phase to phase
voltage >2V
Definite time characteristic
Inrush current blocking element
0.05 Ir to 40.00 Ir
Current Max. current setting 0.05 In to 40.00 In
≤ ±2% setting or ±0.02Ir
≤ ±2% setting or ±0.02In
0.00s to 100.00s, step 0.01s without inrush current
Time delay of definite
≤ ±1% setting or ≤ +40ms, at
time characteristic blocking
200% operating setting
Reset ratio ≥ 0.95 Ratio of second 0.07 to 0.50, step 0.01
Reset time ≤ 40ms harmonics to
Inverse time characteristic fundamental current
0.05 Ir to 40.00 Ir
Current
≤ ±2% setting or ±0.02Ir
Inverse time Normal inverse; 50N, 51N, 67N Directional earth fault
characteristic in Very inverse; protection
accordance with Extremely inverse;
Item Data
IEC60255-151 Long inverse Three phase currents or
Current inputs
≤ ±5% or ≤ +50ms , at 2 single current
<I/ISETTING < 20 Definite time characteristic
0.05 Ir to 40.00 Ir
Inverse time Inverse; Current
≤ ±2% setting or ±0.02Ir
characteristic in Short inverse; 0.00s to 100.00s, step 0.01s
Time delay ≤ ±1% setting or ≤ +40ms, at
accordance with Long inverse; 200% operating setting
ANSI/IEEE C37.112 Moderately inverse; Reset ratio ≥ 0.95
Very inverse; Reset time ≤ 40ms
Extremely inverse; Inverse time characteristic
Definite inverse 0.05 Ir to 40.00 Ir
Current
≤ ±2% setting or ±0.02Ir
≤ ±5% setting or ≤ +50ms, at
Inverse time Normal inverse;
2 <I/ISETTING < 20,
characteristic in Very inverse;
User-defined A
T=( i + B) k accordance with Extremely inverse;
characteristic in ( )P −1
I_SET
IEC60255-151 Long inverse
accordance with ≤ ±5% setting or ≤ + 50ms, at
IEC60255-151
IEC60255-151 2 <I/ISETTING < 20
≤ ±5% setting or ≤ + 50ms, at 2
Time factor of 0.001 to 1000.000, step 0.001
<I/ISETTING < 20
characteristic, A
Inverse time Inverse;
Tine Delay of 0.00s to 100.00s, step 0.01s characteristic in Short inverse;
characteristic, B
accordance with Long inverse;
Index of characteristic, P 0.01 to 10.00, step 0.01 ANSI/IEEE C37.112 Moderately inverse;
Time constant of 0.025 to 1.500, step 0.001 Very inverse;
characteristic, T Extremely inverse;
Reset mode of inverse
Instantaneous Definite inverse
time characteristic
Reset ratio ≥ 0.95 ANSI/IEEE C37.112,
Reset time ≤ 40ms ≤ ±5% setting or ≤ + 50ms, at 2
Directional element <I/ISETTING < 20

25 / 40
Specification
User-defined A Current for sensitive CT 0.005 to 1.000 A , step 0.001
T=( i + B) k
characteristic in ( )P −1 input A
I_SET

accordance with IEC60255-151 ≤ ±2 % setting or 1 mA


IEC60255-151 ≤ ±5% setting or ≤ + 50ms, at 2 Inverse time Normal inverse;
<I/ISETTING < 20 characteristic in Very inverse;
Time factor of 0.001 to 1000.000, step 0.001 accordance with Extremely inverse;
characteristic, A IEC60255-151 Long inverse
Tine Delay of 0.00s to 100.00s, step 0.01s ≤ ±5% setting or ≤ + 50ms, at
characteristic, B 2 <I/ISETTING < 20
Index of characteristic, 0.01 to 10.00, step 0.01 Inverse time Inverse;
P characteristic in Short inverse;
Time constant of 0.025 to 1.500, step 0.001 accordance with Long inverse;
characteristic, T ANSI/IEEE C37.112 Moderately inverse;
Reset mode of inverse Very inverse;
instantaneous
time characteristic
Extremely inverse;
Reset ratio ≥ 0.95
Definite inverse
Reset time ≤ 40ms
≤ ±5% setting or ≤ + 50ms, at
Zero sequence directional element
2 <I/ISETTING < 20
160°;
Operating area range User-defined A
≤ ±1°, at 3U0≥1V T=( i + B) k
characteristic in ( )P −1
I_SET
0°to 90°, step 1°
Characteristic angle
≤ ±1°, at 3U0≥1V accordance with ≤ ±5% setting or ≤ + 50ms, at
Negative sequence directional element IEC60255-151 2 <I/ISETTING < 20
160° Time factor of 0.001 to 1000.000, step 0.001
Operating area range
≤ ±1°, at 3U2≥2V characteristic, A
0°to 90°, step 1°
Characteristic angle Tine Delay of 0.00s to 100.00s, step 0.01s
≤ ±1°, at 3U2≥2V
characteristic, B
50Ns, 51Ns, 67Ns, Sensitive Index of characteristic, P 0.01 to 10.00, step 0.01

directional earth fault protection Time constant of 0.025 to 1.500, step 0.001
characteristic, T
Item Data Reset mode of inverse
instantaneous
Current input From sensitive CT or cable time characteristic
Reset ratio ≥ 0.95
type CT
Reset time ≤ 40ms
Definite time characteristic
Directional element
Current for sensitive CT 0.005 to 1.000 A , step 0.001
principles I cos Φ and Φ (V0 / I0)”
input A
Direction measurement IE and VE measured
≤ ±2 % setting or 1 mA
or 3V0 calculated
Time delay of definite 0.00s to 100.00, step 0.01 s
3U0 Minimum voltage 2.00 to 100.00 V, step 0.01 V
time characteristic ≤ ±1 % setting value or ≤
threshold ≤ ±2 % setting for measured
+40ms, at 200% operating
voltage;
setting
≤ ±2 % setting for calculated
Reset ratio ≥ 0.95
voltage
Reset time ≤ 40ms
Characteristic angle 0°to 90°, step 1°
Inverse time characteristic

26 / 40
Specification
Φ_SEFChar ≤ ±1° characteristic, T
Operating area range 160°, Reset mode of inverse
instantaneous
time characteristic
≤ ±1°
Reset ratio ≥ 0.95
Reset time ≤ 40ms
50NS, 51NS, 67NS,
Negative-sequence overcurrent 37, Undercurrent protection
protection
Item Data
Item Data Current
0.05 Ir to 40.00 Ir
≤ ±2% setting or ±0.02Ir
Definite time characteristic
0.00s to 100.00s, step 0.01s
0.05 Ir to 40.00 Ir Time delay of definite
Current ≤ ±1% setting or ≤ +40ms, at
≤ ±2% setting or ±0.02Ir time characteristic
200% operating setting
0.00s to 100.00s, step 0.01s Reset ratio ≤ 1.05
Time delay of definite
≤ ±1% setting or ≤ +40ms, at
time characteristic Reset time ≤ 40ms
200% operating setting
Reset ratio ≥ 0.95
Reset time ≤ 40ms 49, Thermal overload protection
Inverse time characteristic
0.05 Ir to 40.00 Ir Item Data
Current
≤ ±2% setting or ±0.02Ir 0.05 Ir to 40.00 Ir
Current
Inverse time Normal inverse; ≤ ±2% setting or ±0.02Ir
Heating time constant 1-9999s
characteristic in Very inverse;
Cooling time constant 0.1-10
accordance with Extremely inverse;
IEC60255-151 Long inverse  I eq2 
IEC low temperature t   ln  2 2
≤ ±5% or ≤+ 50ms, at 2 curve  I eq  I  
<I/ISETTING < 20 ≤ ±5% setting or ≤+50ms
Inverse time Inverse;
 I eq2  I P2 
characteristic in Short inverse; IEC high temperature t   ln  2 2
accordance with Long inverse;
curve  I eq  I  
ANSI/IEEE C37.112 Moderately inverse; ≤ ±5% setting or ≤+50ms

Very inverse;
Extremely inverse;
24, Overexcitation protection
Definite inverse Item Data
≤ ±5% setting or ≤ +50ms, at
Reference voltage Un 10V/120V
2 <I/ISETTING < 20, ≤ ±2% setting or ±1V
User-defined A
T=( + B) k Definite time characteristic
i
characteristic in ( )P −1
I_SET
V/F 1.00 to 1.70
accordance with ≤ ±5% setting or ≤ + 50ms, at
≤ ±2% setting or ±0.01
IEC60255-151 2 <I/ISETTING < 20
Time delay 0.00s to 9999.00s, step 0.01s
Time factor of 0.001 to 1000.000, step 0.001
≤ ±5% setting or +80ms
characteristic, A
Reset ratio ≥0.96
Tine Delay of 0.00s to 100.00s, step 0.01s
Reset time ≤80ms
characteristic, B
Inverse time characteritic
Index of characteristic, P 0.01 to 10.00, step 0.01
V/F 1.00 to 1.70
Time constant of 0.025 to 1.500, step 0.001
≤ ±2% setting or ±0.01

27 / 40
Specification
Time delay 0.00s to 9999.00s, step 0.01s ≤ ±5% setting or ≤ +50ms, at
≤ ±5% setting or ≤ +80ms 2 <U/Uset < 20.
V/F characteristic value 1.05 /1.10 /1.15 /1.20 /1.25 User-defined curve ≤ ±5% setting or ≤ +50ms, at
/1.30 /1.35 /1.40 /1.45 /1.50 2 <U/Uset < 20.
/1.55 /1.60 /1.65 /1.7 Time factor of 0.001 to 10.000, step 0.001
≤ ±5% setting or ≤ ±80ms characteristic, A
Reset mode of inverse Tine Delay of 0.00s to 100.00s, step 0.01s
instantaneous
time characteristic
Reset ratio ≥ 0.96 characteristic, B

Reset time ≤ 80ms Index of characteristic, P 0.01 to 10.00, step 0.01


Time constant of 0.025 to 1.500, step 0.001
59, Overvoltage protection characteristic, T
Reset mode of inverse
instantaneous
Item Data time characteristic
Reset ratio ≥ 0.95
Voltage input Phase to phase voltage or
Reset time ≤ 50ms
phase to earth voltage
Definite time characteristic
59N/64, Zero-sequence overvoltage
phase-to-earth voltages 40.0V to 100.0 V, step 0.1 V
protection
≤ ±2% setting or ± 0.1V
Phase to phase voltage 80.0V to 200.0 V, step 0.1 V Item Data
≤ ±2% setting or ± 0.1V Voltage input Calculated from 3 Phase to
Reset ratio 0.90 to 0.99, step 0.01 phase voltages or phase to
Time delay 0.00s to 120.00s, step 0.01s earth voltages
≤ ±1 % setting or ≤ +50ms Definite time characteristic
at 120% voltage setting Voltage 2 to 100 V, step 0.1 V
Reset time ≤ 50ms ≤ ±2% setting or ± 0.1V
Inverse time characteristic Time delay 0.00s to 120.00s, step 0.01s
phase-to-earth voltages 40.0V to 100.0 V, step 0.1 V ≤ ±1 % setting or ≤ +50ms
≤ ±2% setting or ± 0.1V at 120% voltage setting
Phase to phase voltage 80.0V to 200.0 V, step 0.1 V Reset ratio ≥ 0.95
≤ ±2% setting or ± 0.1V Reset time ≤ 50ms
IEC standard curve Normal inverse time; Inverse time characteristic
Abnormal inverse time; Voltage 2 to 100 V, step 0.1 V
Extreme inverse time; ≤ ±2% setting or ± 0.1V
Long inverse time; IEC standard curve Normal inverse time;
≤ ±5% setting or ≤ + 70ms, at Abnormal inverse time;
2 <U/Uset < 20. Extreme inverse time;
ANSI standard curve Standard inverse time; Long inverse time;
Short inverse time ≤ ±5% setting or ≤+50ms, at 2
Long inverse time; <U0/U0set < 20.
Normal inverse time; ANSI standard curve Standard inverse time;
Abnormal inverse time; Short inverse time
Extreme inverse time; Long inverse time;
User-defined inverse time;

28 / 40
Specification
Normal inverse time; 2 <U2/U2set < 20.
Abnormal inverse time; ANSI standard curve Standard inverse time;
Extreme inverse time; Short inverse time
User-defined inverse time; Long inverse time;
≤ ±5% setting or ≤ +50ms, at Normal inverse time;
2 <U0/U0set < 20. Abnormal inverse time;
User-defined curve ≤ ±5% setting or ≤ +50ms, at Extreme inverse time;
2 <U0/U0set < 20. User-defined inverse time;
Time factor of 0.001 to 10.000, step 0.001 ≤ ±5% setting or ≤ +50ms, at
characteristic, A 2 <U2/U2set < 20.
Tine Delay of 0.00s to 100.00s, step 0.01s User-defined curve ≤ ±5% setting or +50ms, at 2
characteristic, B <U2/U2set < 20.
Index of characteristic, P 0.01 to 10.00, step 0.01 Time factor of 0.001 to 10.000, step 0.001
Time constant of 0.025 to 1.500, step 0.001 characteristic, A
characteristic, T Tine Delay of 0.00s to 100.00s, step 0.01s
Reset mode of characteristic, B
instantaneous
characteristic
Index of characteristic, P 0.01 to 10.00, step 0.01
Reset ratio ≥ 0.95
Time constant of 0.025 to 1.500, step 0.001
Reset time ≤ 50ms
characteristic, T
Reset mode of inverse
47, Negative-sequence overvoltage time characteristic
instantaneous

protection Reset ratio ≥ 0.95


Reset time ≤ 50ms
Item Data
Voltage input Calculated from 3 Phase to
27, Undervoltage protection
phase voltages or phase to
earth voltages Item Data
Definite time characteristic Voltage input Phase to phase voltages or
Voltage 0.0V to 100 V, step 0.1 V phase to earth voltages
≤ ±2% setting or ± 0.1V Permitted current setting 0.08-2.00 Ir, step 0.01A
Time delay 0.00s to 100.00s, step 0.01s ≤ ±2% setting or ±0.02Ir
≤ ±1 % setting or ≤ +50ms, at Definite time characteristic
120% voltage setting phase-to-earth voltages 5.0 to 150.0 V, step 0.1 V
Reset ratio ≥ 0.95 ≤ ±2% setting or ± 0.1V
Reset time ≤ 50ms Phase to phase voltage 10.0 to 150.0 V, step 0.1 V
Inverse time characteritic ≤ ±2% setting or ± 0.1V

Voltage 0.0V to 100 V, step 0.1 V Reset ratio 1.00 to 2.00, step 0.01
≤ ±2% setting or ± 0.1V Time delay 0.00s to 120.00s, step 0.01s
IEC standard curve Normal inverse time; ≤ ±1 % setting or ≤ +50ms
Abnormal inverse time; at 80% voltage setting
Extreme inverse time; Reset time ≤ 50ms
Long inverse time; Inverse time characteritic
≤ ±5% setting or ≤ +50ms, at phase-to-earth voltages 5.0 to 150.0 V, step 0.1 V

29 / 40
Specification
≤ ±2% setting or ± 0.1V Voltage input Phase to phase voltage
Phase to phase voltage 10.0 to 150.0 V, step 0.1 V voltage 1.00 to 100.00 V, step 0.1V
≤ ±2% setting or ± 0.1V ≤ ±2% setting or ± 0.1V
Invers time characteristic ≤ ±5% setting or ≤ +50ms, at Time delay 0.00s to 100.00s, step 0.01s
in accordance with 0.05 <U2/U2set < 0.5. ≤ ±1% setting or ≤ +50ms, at
IEC60255-127 200% operating setting
User-defined curve ≤ ±5% setting or ≤ +50ms, at Reset ratio ≥ 0.95
0.05 <U2/U2set < 0.5 Reset time ≤ 50ms
Time factor of 0.001 to 10.000, step 0.001
characteristic, A 51UC, Unbalance current protection
Tine Delay of 0.00s to 100.00s, step 0.01s
Item Data
characteristic, B
Current 0.05 Ir to 40.00 Ir
Index of characteristic, P 0.010 to 10.000, step 0.005
≤ ±2% setting or ±0.02Ir
Time constant of 0.025 to 1.500, step 0.001
Time setting 0.00s to 100.00s, step 0.01s
characteristic, T
≤ ±1% setting or ≤ +40 ms, at
Reset mode instantaneous
200% operating setting
Reset ratio ≥ 0.95 Reset ratio ≥ 0.95
Reset time ≤ 50ms
Reset time ≤ 40ms

59N-NS, Zero-sequence voltage


32, Power protection
protection with negative-sequence
directional element Item Data
Power 1W to 500W
Item Data
≤ ±3% setting or ±0.5Pn
Zero sequence voltage of 3.00 to 100.00 V
Time delay 0.00s to 100.00s, step 0.01s
stage 1 ≤ ±2.5% setting or ±0.05V
≤ ±1 % setting or ≤ +40ms
Zero-sequence voltage of 1.00 to 100.00 V at 120% operating setting
stage 2 ≤ ±2.5% setting or ±0.05V
Reset time ≤ 40ms
Time delay of stage 1 0.00s to 30.00s, step 0.01s
≤ ±1% setting or ≤ +50ms, at
Time delay of stage 2
50BF, Breaker failure protection
200% operating setting
The most sensitive angle 82.5°±5° Item Data
of negative sequence  Phase current 0.05 Ir to 40.00 Ir
directional element  Negative sequence ≤ ±2% setting or ±0.02Ir
Operating range of 0°~165° current
negative sequence  Zero sequence
directional element current

Filtering ratio of the 3rd >100 Time delay of stage 1 0.00s to 100.00 s, step 0.01s
harmonic ≤ ±1% setting or ≤ +40 ms, at
200% operating setting

59UV, Unbalance voltage protection Time delay of stage 2 0.00s to 100.00 s, step 0.01s
≤ ±1% setting or ≤ +40 ms, at
Item Data 200% operating setting

30 / 40
Specification
Reset ratio ≥ 0.95 Reset ratio ≥ 0.95
Reset time ≤ 15ms Reset time ≤ 40ms

50DZ, Dead zone protection 81U, Underfrequency protection

Item Data Item Data


Current 0.05 Ir to 40.00 Ir 45.00 to 50.00Hz, step
≤ ±2% setting or ±0.02Ir 0.01Hz at Fr=50Hz
Time setting 0.00s to 100.00s, step 0.01s 54.00 to 60.00Hz, step
≤ ±1% setting or ≤ +40 ms, at Frequency 0.01Hz at Fr=60Hz
200% operating setting ≤±20mHz, at 3 symmetric
Reset ratio ≥ 0.95 phase voltages in the
Reset time ≤ 40ms operating range
0.00s to 600.00 s, step 0.01s
50STUB, STUB protection Time setting ≤ ±1% setting or ≤+100 ms,
at 80% setting
Item Data
Reset Δf =︱fset - freset︱ Approx. 20mHz
Current 0.05 Ir to 40.00 Ir
0.1 to 20Hz/s
≤ ±2% setting or ±0.02Ir Change of rate Δf/Δt
≤±0.5Hz/s
Time setting 0.00s to 100.00s, step 0.01s
30 to 100V, step 0.1V
≤ ±1% setting or ≤ +40 ms, at Voltage
≤±2% setting or ± 0.1V
200% operating setting
0 to 10In
Reset ratio ≥ 0.95 Current
≤±2% setting or +0.01In
Reset time ≤ 40ms

81O, Overfrequency protection


50PD, Phase discordance protection
Item Data
Item Data
50.00 to 55.00Hz, step
Current 0.05 Ir to 40.00 Ir
0.01Hz at Fr=50Hz
≤ ±2% setting or ±0.02Ir
Frequency 60.00 to 66.00Hz, step
Time setting 0.00s to 100.00s, step 0.01s
0.01Hz at Fr=60Hz
≤ ±1% setting or ≤ +40 ms, at
≤±20mHz
200% operating setting
0.00s to 600.00 s, step 0.01s
Reset ratio ≥ 0.95
Time setting ≤ ±1% setting or ≤ +100 ms,
Reset time ≤ 40ms
at 80% setting
Reset Δf =︱fset - freset︱ Approx. 20mHz
46BC, Broken conductor protection
0.1 to 20Hz/s
Change of rate Δf/Δt
Item Data ≤±0.5Hz/s
Current 0.05 Ir to 40.00 Ir 30 to 100V, step 0.1V
Voltage
≤ ±2% setting or ±0.02Ir ≤±2% setting or ± 0.1V
Time setting 0.00s to 100.00s, step 0.01s
≤ ±1% setting or ≤ +40 ms, at
200% operating setting

31 / 40
Specification
81DF, Frequency change rate ≤±20mHz
protection Δα- angle difference 1 °to 80 °, step of 1 °
(α2>α1; α2<α1)
Minimum measuring 0.05s to 100.00 s, step 0.01s
Item Data time
≤ ±1% setting or ≤ +40 ms
0.1 to 20Hz/s
Change of rate Δf/Δt Maximum synchronous 0.00s to 60.00 s, step 0.01s
≤±0.5Hz/s check broadening time
0.00s to 60.00s, step 0.01s ≤ ±1% setting or ≤ +40 ms
Constant time
≤ ±1% setting or ≤ +100 ms
Upper limit of frequency 0.1 to 20Hz/s 79, Autoreclosing
change rate ≤±0.5Hz/s
Item Data
Lower limit of frequency 0.1 to 20Hz/s 1 to 4
Shots of reclosing
change rate ≤±0.5Hz/s
Reclosing initiated Internal protection startups
10 to 100V, step 0.1V inputs External binary input
voltage
≤±2% setting or ± 0.1V
Time for each shot of 0.00s~100.00s, step of 0.01 s
reclosing ≤ ±1% setting or ≤ +100 ms
50SOTF, Switch onto fault protection Reclosing confirmation 0.50 s~100.00s, step of 0.01 s

Item Data time ≤ ±1% setting or ≤ +40 ms

Current 0.05 Ir to 40.00 Ir Reclosing blocking 0.50 s~100.00s, step of 0.01 s

≤ ±2% setting or ±0.02Ir time ≤ ±1% setting or +40 ms

Time 0.00s to 100.00s, step 0.01s Equal breaking time 0.50 s~100.00s, step of 0.01 s

≤ ±1% setting or ≤ +40 ms, at ≤ ±1% setting or ≤ +40 ms

200% operating setting Synchronization 0.50 s~100.00s, step of 0.01 s

Reset ratio ≥ 0.95 waiting time ≤ ±1% setting or ≤ +40 ms


Reset time ≤ 40ms
27LS, Load shedding by
25, Synchro-check & energizing undervoltage
check
Item Data

Item Data Voltage input Phase to phase voltages or


Modes of Synchro-check  Synchro-check phase to earth voltages
 synchronous check after
Permitted current setting 0.08-2.00 Ir, step 0.01A
energizing check
failure ≤ ±2% setting or ±0.02Ir
 Override
Definite time characteristic
Modes of Energizing  Dead line & dead bus
check  Live line & dead bus phase-to-earth voltages 5.0 to 150.0 V, step 0.1 V
 Live line & live bus
 Dead line & live bus ≤ ±2% setting or ± 0.1V
Undervoltage setting 10V to 50 V, step 0.1 V Phase to phase voltage 10.0 to 150.0 V, step 0.1 V
(Phase to earth voltage)
≤ ±2% setting or ± 0.1V ≤ ±2% setting or ± 0.1V
Overvoltage setting 30V to 65 V, step 0.1 V Time delay 0.00s to 120.00s, step 0.01s
(Phase to earth voltage)
≤ ±2% setting or ± 0.1V ≤ ±1 % setting or ≤ +50ms
∆V- voltage difference 1V to 40 V, step 0.1 V Voltage change rate, 2V/s~200V/s, step 0.01V/s
(Phase to earth voltage)
≤ ±2% setting or ± 0.1V Δu/Δt ≤ ±3% setting or ±1V/s
Δf- frequency difference 0.02 to 2.00Hz, step 0.01Hz Reset time ≤ 50ms
(f2>f1; f2<f1)

32 / 40
Specification
51LS, Load shedding by overload ≤ ±1% setting or ≤ +100 ms,
at 80% setting
Item Data
Reset Δf =︱fset - freset︱ Approx. 20mHz
0.05 Ir to 40.00 Ir
Current
≤ ±2% setting or ±0.02Ir 0.1 to 20Hz/s
0.00s to 100.00s, step 0.01s Change of rate Δf/Δt
Time delay of definite ≤±0.5Hz/s
≤ ±1% setting or ≤ +40ms, at
time characteristic
200% operating setting 10V to 120V, step 0.1V
Voltage
Reset ratio ≥ 0.95 ≤±2% setting or ± 0.1V
Reset time ≤ 40ms
Blocking element 97FF, VT secondary circuit
Frequency changing rate 0.3Hz/s~20Hz/s,step supervision
Δf/Δt 0.01Hz/s
Voltage change rate, 2V/s~200V/s, step 0.01V/s Item Data
Δu/Δt ≤ ±3% setting or ±1V/s Phase current 0.05Ir to 0.20Ir, step 0.01A
≤ ±2% setting or ±0.02Ir

81LS, Load shedding underfrequency Zero or negative 0.05Ir to 0.20Ir, step 0.01A

protection sequence current ≤ ±2% setting or ±0.02Ir


Phase to earth voltage 7.0V to 20.0V, step 0.1V
Item Data ≤ ±2% setting or ± 0.1 V
45.00 to 50.00Hz, step Phase to phase voltage 10.0V to 30.0V, step 0.1V
0.01Hz at Fr=50Hz ≤ ±2% setting or ± 0.1 V
Frequency 54.00 to 60.00Hz, step
Operating phase to 40.0V to 65.0V, step 0.1V
0.01Hz at Fr=60Hz
earth voltage ≤ ±2% setting or ± 0.1V
≤±20mHz
Time setting 0.00s to 100.00 s, step 0.01s

33 / 40
Ordering Code
Ordering code Description

Product Family

CSC-211-EB CSC product family

Hardware architecture

AR CT/VT Input / BIO

DA SV Input / GOOSE IO

AG CT/VT Input / GOOSE IO

AD CT/VT Input / BIO / SV OUT / GOOSE IO

Language

EC English + Chinese

RE Russian + English + Chinese;

FE French + English + Chinese;

PE Portuguese + English + Chinese;

SE Spain + English + Chinese;

Protocols

X Null

A IEC61850

B IEC61870-5-103

C MODBUS

D DNP 3.0

Typical function groups of CSC-211

For 66KV-10KV earthed power grid, Feeder protection IED;


50, 51&67: Directional Overcurrent Protection, 4 stages, DT/INVT, Inrush block;
50N,51N&67N: Directional Earth-Fault Protection, 4 stages, DT/INVT, Inrush block;
46: Negative-Sequence Overcurrent Protection, 4 stages, DT/INVT;
49: Thermal Overload Protection, 3 Stages, 2 of 3 stages for alarm, 1 of 3 stages for tripping, for cable;
50SOTF: Switch-Onto-Fault Protection, 1 stage, DT;
A
46BC: Broken Conductor, 1 stage;
97FF: Symmetrical and asymmetrical VT Fuse Fail Detection;
CTFF: CT-Secondary Current Supervision ;
DR: Disturbance recorder;
FP: Faulty phase indication;
94-3: Three-pole tripping logic;

For 35KV-10KV, Feeder protection IED;


50, 51&67: Directional Overcurrent Protection, 4 stages, DT/INVT, Inrush block;
50Ns, 51Ns&67Ns: Directional Sensitive Earth-Fault protection, 4 stages, DT/INVT;
B 46: Negative-Sequence Overcurrent Protection, 4 stages, DT/INVT;
49: Thermal Overload Protection, 3 Stages, 2 of 3 stages for alarm, 1 of 3 stages for tripping, for cable;
50SOTF: Switch-Onto-Fault Protection, 1 stage, DT;
46BC: Broken Conductor, 1 stage;

34 / 40
Ordering Code
97FF: Symmetrical and asymmetrical VT Fuse Fail Detection;
CTFF: CT-Secondary Current Supervision ;
DR: Disturbance recorder;
FP: Faulty phase indication;

For ≥66KV transmission line, Backup protection IED;


50, 51&67: Directional Overcurrent Protection, 4 stages, DT/INVT, Inrush block;
50N,51N&67N: Directional Earth-Fault Protection, 4 stages, DT/INVT, Inrush block;
46: Negative-Sequence Overcurrent Protection, 4 stages, DT/INVT;
49: Thermal Overload Protection, 3 Stages, 2 of 3 stages for alarm, 1 of 3 stages for tripping, for cable;
50SOTF: Switch-Onto-Fault Protection, 1 stage, DT;
C
46BC: Broken Conductor, 1 stage;
97FF: Symmetrical and asymmetrical VT Fuse Fail Detection;
CTFF: CT-Secondary Current Supervision ;
DR: Disturbance recorder;
FP: Faulty phase indication;
94-3: Three-pole tripping logic;

For ≥66KV transformer, Backup protection IED;


50, 51&67: Directional Overcurrent Protection, 4 stages, DT/INVT, Inrush block;
50N,51N&67N: Directional Earth-Fault Protection, 4 stages, DT/INVT, Inrush block;
46: Negative-Sequence Overcurrent Protection, 4 stages, DT/INVT;
49: Thermal Overload Protection, 3 Stages, 2 of 3 stages for alarm, 1 of 3 stages for tripping, for transformer;
50SOTF: Switch-Onto-Fault Protection, 1 stage, DT;
D
46BC: Broken Conductor, 1 stage;
97FF: Symmetrical and asymmetrical VT Fuse Fail Detection;
CTFF: CT-Secondary Current Supervision ;
DR: Disturbance recorder;
FP: Faulty phase indication;
94-3: Three-pole tripping logic;

For 35KV-10KVearhted power grid, capacitor protection IED;


50, 51&67: Directional Overcurrent Protection, 4 stages, DT/INVT, Inrush block;
50N,51N&67N: Directional Earth-Fault Protection, 4 stages, DT/INVT, Inrush block;
46: Negative-Sequence Overcurrent Protection, 4 stages, DT/INVT;
37I: Under current protection, 1 stage, DT;
E 59: Overvoltage Protection, 4 stages, DT/INVT;
59N/64: Zero sequence overvoltage protection, 3 stages, DT/INVT;
27: Undervoltage Protection, 4 stages, DT/INVT;
46: Negative-Sequence Overvoltage Protection, 4 stages, DT/INVT;
DR: Disturbance recorder;
FP: Faulty phase indication;

For ≥66KV, Independent Breaker protection IED;


50BF: Circuit-Breaker Failure Protection, 2 stages, single/three-pole operating;
F
50DZ: Dead Zone Protection/End-fault protection, 1 stage, DT;
62PD: Pole-Discrepancy Protection, 1 stage, DT;

35 / 40
Ordering Code
DR: Disturbance recorder;
FP: Faulty phase indication;
94-1/3: Single- and/or three-pole tripping logic;

For ≥66KV, Independent autoreclosing IED;


25: Synchro-Check with Live/Dead Line/Bus Measurement ;
79: Single and/or Three-Pole AutoReclosing, 4 shots;
G
DR: Disturbance recorder;
FP: Faulty phase indication;
94-3: Three-pole tripping logic;
For ≥66KV,Bus coupler or bus sectionalizer protection IED

50&51: Overcurrent Protection, 2 stages, DT;


50N&51N: Earth-Fault Protection, 2 stages, DT;
H 50&51: Overcurrent Protection, 1 stages, Enable in short time, for bus coupler;
DR: Disturbance recorder;
FP: Faulty phase indication;
94-3: Three-pole tripping logic;

Current protection function group

X Null-Current protection function group

A 50N&51N: Earth-Fault Protection, 4 stages, DT/INVT, Inrush block;

50&51: Overcurrent Protection, 4 stages, DT/INVT, Inrush block;


B 50N&51N: Earth-Fault Protection, 4 stages, DT/INVT, Inrush block;
46: Negative-Sequence Overcurrent Protection, 4 stages, DT/INVT;

50, 51&67: Directional Overcurrent Protection, 4 stages, DT/INVT, Inrush block;


C 50N,51N&67N: Directional Earth-Fault Protection, 4 stages, DT/INVT, Inrush block;
46: Negative-Sequence Overcurrent Protection, 4 stages, DT/INVT;

Voltage protection function group

X Null-Voltage protection function group

59: Overvoltage Protection, 4 stages, DT/INVT;


59N/64: Zero sequence overvoltage protection, 3 stages, DT/INVT;
A
27: Undervoltage Protection, 4 stages, DT/INVT;
46: Negative-Sequence Overvoltage Protection, 4 stages, DT/INVT;

Overexcitation protection function

X Null-Overexcitation protection function

A 24: Over-excitation Protection, 4 stages, 3 of 4 stages in DT, 1 of 4 stages in INVT ;

Frequency protection function group

X Null-Frequency protection function group

81O: Overfrequency, 4 stages;


A 81U: Underfrequency, 4 stages;

81DF: df/dt Protection, 4 stages;;

Power protection function group

X Null-Power protection function group

A 32D: Directional overpower protection, 2 stages;;

Breaker protection function group

36 / 40
Ordering Code
X Null-Breaker protection function group

A 50BF: Circuit-Breaker Failure Protection, 2 stages, single/three-pole operating;

50BF: Circuit-Breaker Failure Protection, 2 stages, single/three-pole operating;


B
50DZ: Dead Zone Protection/End-fault protection, 1 stage, DT;

50BF: Circuit-Breaker Failure Protection, 2 stages;


C 50DZ: Dead Zone Protection/End-fault protection, 1 stage, DT;
50STB: STUB protection, 1 stage, DT;

50BF: Circuit-Breaker Failure Protection, 2 stages, single/three-pole operating;


D
50STB: STUB protection, 1 stage, DT;

Autoreclosing & Synchronization function group

X NULL-Autoreclosing & Synchronization function group

A 79: Single and/or Three-Pole AutoReclosing, 4 shots;

25: Synchro-Check with Live/Dead Line/Bus Measurement ;


B
79: Single and/or Three-Pole AutoReclosing, 4 shots;

C 25: Synchro-Check with Live/Dead Line/Bus Measurement ;

Control function

X NULL-Control function

CB control;
Isolator control;
A
Programmable Interlock logic;
Remote/local control switch;

Capacitor protection function group

X NULL-Capacitor protection function group

A 60U: Unbalance voltage capacitor protection, 2 stages;

B 60I: Unbalance current capacitor protection, 2 stages;

Case & Front plate

Width of CASE :1/2 19";


LCD: Medium;
Qty. of LEDs:24;
A
Qty. CB operating buttons:2;
Qty. Configurable buttons:4;
Type of front test Port:RJ45;

Power Supply

A Voltage range of auxiliary power supply: DC 24-48V;

B Voltage range of auxiliary power supply: DC/AC250-110V;

Communication port

Qty. RJ45 for SAS:1;


Qty. of RS485/IRIG-B:1;
A Qty. of RS485:1;
RS232-Printer port:1;
Qty. of optical Ethernet port for SAS:2;

B Qty. RJ45 for SAS:3;

37 / 40
Ordering Code
Qty. of RS485/IRIG-B:1;
Qty. of RS485:1;
RS232-Printer port:1;

Transformer inputs & Analog inputs/outputs

XX NULL-Transformer inputs module

Qty. of modules:1;
Ip (1A&5A, 40Ir):4;
AA
Is (1A&5A, 1.2Ir):1;
U (180V,star):4;

Qty. of modules:2;
Ip (1A&5A, 40Ir):4;
AB Is (1A&5A, 1.2Ir):1;
Im(2Ir) :3;
U (180V,star):4;

Qty. of modules:1;
AC
Ip (1A&5A, 40Ir):3;

Qty. of modules:2;
Ip (1A&5A, 40Ir):5;
Is (1A&5A, 1.2Ir):1;
AD
Im(2Ir) :3;
U (180V,star):7;
AI (4-20mA):2;

Qty. of modules:2;
Ip (1A&5A, 40Ir):7;
Is (1A&5A, 1.2Ir):1;
AE
Im(2Ir) :3;
U (180V,star):5;
AI (4-20mA):2;

Binary inputs & output relays

XX NULL-Binary input & output module

Qty. of modules(Include Power Supply module):2;


Qty. of BIs with common terminal:17;
Qty. of General output relay C, 1 NO: 11;
AA Qty. of General output relay D, 1 NO/NC: 1;
Signal relay, 2 NO with common terminal: 2;
General relay alarm relay, 2 NO:1;
Internal Failure alarm relay, 2 NC:1;

Qty. of modules(Include Power Supply module):3;


Qty. of BIs with common terminal:23;
Qty. of General output relay C, 1 NO: 22;
AB
Qty. of General output relay D, 1 NO/NC: 2;
Signal relay, 2 NO with common terminal: 2;
General relay alarm relay, 2 NO:1;

38 / 40
Ordering Code
Internal Failure alarm relay, 2 NC:1;

Qty. of modules(Include Power Supply module):4;


Qty. of BIs with common terminal:29;
Qty. of General output relay C, 1 NO: 33;
AC Qty. of General output relay D, 1 NO/NC: 3;
Signal relay, 2 NO with common terminal: 2;
General relay alarm relay, 2 NO:1;
Internal Failure alarm relay, 2 NC:1;

Qty. of modules(Include Power Supply module):5;


Qty. of BIs with common terminal:35;
Qty. of General output relay C, 1 NO: 44;
AD Qty. of General output relay D, 1 NO/NC: 4;
Signal relay, 2 NO with common terminal: 2;
General relay alarm relay, 2 NO:1;
Internal Failure alarm relay, 2 NC:1;

Qty. of modules(Include Power Supply module):2;


Qty. of BIs with common terminal:11;
Qty. of Power output relay, 1 NO + TCS: 1;
Qty. of Power output relay, 1 NO: 1;
AE Qty. of General output relay A, 2 NO: 1;
Qty. of General output relay B, 1 NO + 1 NC: 1;
Signal relay, 2 NO with common terminal :2;
General relay alarm relay, 2 NO:1;
Internal Failure alarm relay, 2 NC:1;

Qty. of modules(Include Power Supply module):3;


Qty. of BIs with common terminal:17;
Qty. of Power output relay, 1 NO + TCS: 1;
Qty. of Power output relay, 1 NO: 1;
Qty. of General output relay A, 2 NO: 1;
AF Qty. of General output relay B, 1 NO + 1 NC: 1;
Qty. of General output relay C, 1 NO: 11;
Qty. of General output relay D, 1 NO/NC: 1;
Signal relay, 2 NO with common terminal: 2;
General relay alarm relay, 2 NO:1;
Internal Failure alarm relay, 2 NC:1;

Qty. of modules(Include Power Supply module):4;


Qty. of BIs with common terminal:23;
Qty. of Power output relay, 1 NO + TCS: 1;
Qty. of Power output relay, 1 NO: 1;
AG
Qty. of General output relay A, 2 NO;
Qty. of General output relay B, 1 NO + 1 NC: 1;
Qty. of General output relay C, 1 NO: 22;
Qty. of General output relay D, 1 NO/NC: 2;

39 / 40
Ordering Code
Signal relay, 2 NO with common terminal: 2;
General relay alarm relay, 2 NO:1;
Internal Failure alarm relay, 2 NC:1;

Qty. of modules(Include Power Supply module):5;


Qty. of BIs with common terminal:23;
Qty. of Power output relay, 1 NO + TCS: 2;
Qty. of Power output relay, 1 NO: 2;
Qty. of General output relay A, 2 NO: 2;
AH Qty. of General output relay B, 1 NO + 1 NC: 2;
Qty. of General output relay C, 1 NO: 22;
Qty. of General output relay D, 1 NO/NC: 2;
Signal relay, 2 NO with common terminal: 2;
General relay alarm relay, 2 NO:1;
Internal Failure alarm relay, 2 NC:1;

Accessories

X Null

A Width of protection front cover:1/2 19";

B Accessories of mounted 2 1/2 19"cases in parallel;

Width of protection front cover:1/2 19";


C
Accessories of mounted 2 1/2 19"cases in parallel;

40 / 40