Professional Documents
Culture Documents
Paper - USE OF A GLOBAL EARTHING SYSTEM TO IMPLEMENT THE SAFETY REQUIREMENTS FOR PROTECTING AGAINST INDIRECT CONTACTS IN HV SYSTEMS
Paper - USE OF A GLOBAL EARTHING SYSTEM TO IMPLEMENT THE SAFETY REQUIREMENTS FOR PROTECTING AGAINST INDIRECT CONTACTS IN HV SYSTEMS
USTp in V
Ground Not defined gravel – ballast brick – tiles tarmac – asphalt
Duration of the Ra = 1 kΩ Ra = 2.5 kΩ Ra = 4 kΩ Ra = 8 kΩ
fault current
in s
0.5 500 700 1 000 1 500
1 200 300 400 550
It is necessary here to make the relation between If we assume that there is a voltage drop (as a
USTp and UE (i.e. the increase in potential of the part of UE) at the earth surface with increasing
local earthing system with respect to a neutral distance from the location of the earth electrodes,
earth, as a result of the expected maximum fault then values of UE higher than USTp can be
current). permitted.
According to Cenelec HD637-S1 it is assumed The cases where the permissible potential rise
that the voltage drop with respect to an earth point was exceeded concerned stand alone cabins
1 m away from the earth electrode amounts to (interruption of the continuity of the protection
50% of UE. The maximum permissible value of UE conductor, cabin in antenna or situated at a long
may then amount to the double of USTp. distance from other cabins), which couldn’t be
considered as involved in a GES.
GLOBAL EARTHING SYSTEM (GES) Remarkable was also the fact that the value of the
local earthing resistance at the place where the
Definition of the concept of “global earthing fault occurred was not decisive for the
system” computation of the potential rise.
This confirms the assumption that a global
According to HD 637, a global earthing system is earthing system is effectively present in areas with
defined as “an equivalent earthing system created a high residential density and in areas with highly
by the interconnection of local earthing systems developed industrial activity.
that ensures, by the proximity of the earthing On the other hand, by means of calculations, a
systems, that there are no dangerous touch procedure was developed to identify cabins that
voltages. Such systems permit the division of the might present a risk. The study showed that
earth fault current in a way that results in a installations located near the power source
reduction of the earth potential rise at the local (HV/MV substation) enjoy some advantage since
earthing system. Such a system could be said to the fault current returns to the source mainly via
form a quasi equipotential surface.” the protective conductor and doesn’t contribute a
lot to the earth potential rise. Remote installations
Application of the GES concept in the also enjoy some advantage since the fault
duration is always lower than 0.5 s and in many
Electrabel network
cases even lower than 0.3 s. Furthermore, the
fault current is then limited by the impedance of
On basis of the above criteria, Laborelec was
the loop.
asked in 1999 to investigate how a distribution
This is highlighted in figure 1, where for a
network with a relatively high density of local
maximum fault current of 2 kA and a potential rise
earthing systems behaves. The study investigated
UE limited to 800 V, the maximum value of the
the behaviour of about 16,000 MV/LV transformer
local earth resistance RE (for a MV/LV cabin) has
cabins under real fault conditions.
been calculated in function of the distance to the
Assuming a maximum fault current Imax of 1 or
source, taking into account the number of cabins
2 kA (limitation by an impedance near to the
upstream the considered installation (lowest curve
source) and a maximum fault duration of
1 cabin, next curves representing
1 second, a possible exceeding of the permissible
2,3,5,7,9,13,21,29 cabins).
touch voltage USTp (2 UE with Ra=2.5 kΩ) was Two cases have been considered: figure 1a
found in only 1 % of the cases (see table 3). 2
applies to a single feeder involving 150 aluminium
This calculation was done in a conservative way paper-lead cables with the lead sheath in contact
because for each of the local earth resistance a
with a soil of 1000 Ωm resistivity, whereas figure
value of 10 Ω was arbitrary chosen. In fact this 1b applies to a feeder equipped with the same
value is in most cases lower than 10 Ω or even kind of cables but with an outside PE insulated
than 5 Ω. sheath.
Even with a relatively high value of the soil
UE Number of Number of resistivity, the earthing effect of the paper-lead
in V cabins for cabins for cables leading to higher permissible values for the
Imax = 1 kA Imax = 2 kA local resistances is clearly visible in these figures.
0-199 10522 3.716
200-399 1749 7.755
450-599 59 664
600-799 4 105
800-999 1 12
1000-1199 0 3
1600-1799 1 0
2600-2799 0 1
Figure 1a Figure 1b
h = 0,5 m
L = 1,5 m Figure 3b – Equivalent circuit for ZE
L=8m
LL = 10 m LL = 8 m
d = 0,02 m
RE
Figure 2 - Examples of local earthing systems
ZEB ZB’ ZB’’
achieving compliance
REFERENCES
These conditions (the latter in case of a low RE
value) are necessary for staying independent of
RE variations due to different earth moistness [1] Criteria for determining the efficiency of a
conditions. global earthing
If ZEB doesn’t fit these conditions, RE has to be D. Halkin, J. Hoeffelman
measured again together with an additional check CIRED 1997 Record of discussion S2
of the continuity by the measurement of ZEB. [2] How to ensure the efficiency of a global
earthing in MV networks
D. Halkin, J. Hoeffelman
CIRED 1999 – Paper 2.20