Design and Application of Water Piping System: - Cold Water Supply - Hot Water Supply - Drinking Water
Design and Application of Water Piping System: - Cold Water Supply - Hot Water Supply - Drinking Water
1
Standard and
Code reference
of Water
Piping System
E.I.T. Standard 1004-16
(Standard for piping
installation in building)
E.I.T. Standard 3004-40
(Standard for piping in
building)
2
Standard and Code
Reference on
Water Piping System
National plumbing codes
National fire protection
association code (NFPA)
3
Criteria to Design of
Copper Tube in
Hot water supply
system
Estimating Hot-Water
Demand
Storage type heaters
Instantaneous type heaters
4
Criteria to Design of
Copper Tube in
Hot water supply
system
Estimating the Demand in
Hot-Water System
See Table 1
5
Table 1 Probable Hot-Water
Demand and Use for
Various Types of Building
Occupancies
6
Criteria to Design of
Copper Tube in
Hot water supply
system
Estimating of Hot-Water
Requirements with
Storage Type Water
Heaters
See Table 2
7
Table 2 Estimates of Hot-
Water Requirements in
Various Types of Buildings
with Storage-Type Water
Heaters
8
Criteria to Design of
Copper Tube in
Hot water supply
Procedure system
for Estimating
Step 1 Tabulate the
number of fixtures
Step 2 Multiply the number of
fixtures by demand figure
Step 3 Summarize the total
demand
Step 4 Obtain
9 the Hourly
Criteria to Design of
Copper Tube in
Hot water supply
Procedure system
for Estimating
Step 5 Obtain the Required
Capacity of The Storage
Tank by multiplying the
figure in step 4 by the
storage capacity factor
Step 6 Obtain the Total
Capacity of The Storage
Tank by dividing the figure
10 5 by 0.6-0.8
in step
Criteria to Design of
Copper Tube in
Hot water supply
Estimate ofsystem
Hot Water
Requirements with
Instantaneous and Semi-
Instantaneous Type Water
Heater
See table 3
11
Table 3 Probable Hot-Water
Demand in Terms of Number of
Fixture Units for Various Types of
Fixtures in Buildings
For use with semi-instantaneous
heaters, calculated oat a final
temperature of 140 F (60oC)
12
Criteria to Design of
Copper Tube in
Hot water supply
Sizing of Hot Water piping
system
System
Determine the total demand
in water supply
- see Demand load fixture in
Table 4
- see Demand water supply
in Table 5
13
Table 4 Demand Load of
Fixtures
14
Table 5 Table for Estimating the
Demand in a Water Supply
System
15
WATER SUPPLY
SERVICES
21
Table 7 Sizing Table Based on
Velocity Limitation-U.S.
Customary Units Copper water
tube, type L
22
Criteria to Design of
Copper Tube in
Hot water supply
Sizing of Hot Water piping
system
System
Pipe friction chart
- see Figure 2, (Copper tube,
type K)
- see Figure 3, (Copper tube,
type L)
23
24
25
Criteria to Design of
Copper Tube in
Hot water supply
Sizing of Hot Water piping
system
System
Pipe Insulation
- see Table 8
26
27
Criteria to Design of
Copper Tube in
Hot water supply
Sizing of Hot Water piping
system
System
Hot water circulating system
- Total length of pipe
between hot water source an
d
the fixture is more than 100 f
t.
28
Criteria to Design of
Copper Tube in
Hot water supply
Sizing of Hot Water piping
system
System
Hot water circulating rate
- 1 gpm. For every 20
fixtures
- 0.5 gpm. For 3/4-1 inch
diameters of supply pipe
- 1 gpm.29For 1 1/4 - 1 1/2
Criteria to Design of
Copper Tube in
Hot water supply
Sizing of Hot Water piping
system
System
Hot water circulating rate
- 2 gpm. For 2 - 2 1/2 inch
diameters of supply pipe
- 3 gpm. For 3 inch
diameters and larger of suppl
y pipe
30
Criteria to Design of
Copper Tube in
Drinking water system
Sizing of Drinking Water
piping System
Determine the maximum
drinking water demand
- 5 gph for drinking fountain
- 1 gph for every 20 people
31