Professional Documents
Culture Documents
Tertiary Pumping
In Air-conditioning Systems
Grundfos FLOW THINKING
Pressure
holding
Cooling surface
M
Primary Buffer
pump tank
Chiller Secondary
pumps
Grundfos FLOW THINKING
H
Max. Buffer
tank
Dp
Dp: connection point
Dp Dp: pipes,
secondary control valves
fan coils etc.
pump
Qmax. Q
Distance/pressure profile
Tertiary pumps
H
M M M M M
Buffer
tank
Max.
Dp: connection point
Dp
Dp
Dp:
secondary
Q pump
control valve
Qmax.
Distance/pressure profile
Grundfos FLOW THINKING
Tertiary pumps
H
M M M M M
Buffer
tank
Max.
Dp: connection point
Dp
Dp
Dp:
secondary
Q pump
control valve
Qmax.
Distance/pressure profile
Grundfos FLOW THINKING
Mixing Loops
In Air-conditioning Systems
Grundfos FLOW THINKING
Mixing loops
Pressure
profile Dp Dp Dp Dp Dp
Grundfos FLOW THINKING
Will adapt to
weather conditions:
Sun
Wind
Floor divided
There could be seperate tertiary pumps for diferent buildings, which are catered by a
common chilled water plant. Then each building will have its own mixing loop
Grundfos FLOW THINKING
Dt Dt Dt Dt Dt
5oC 5oC 5oC 5oC 5oC
Dt
5oC
Other rooms
Sun radiation
Light Light
Electrical People
Wind equipment
Other rooms
Grundfos FLOW THINKING
Tertiary side tf tf tf tf
tr tr tr
tr
M M M
ts M M
Secondary side
System 1
Tertiary side
Function
tO
Tertiary side:
Load The load will normally be an exchanger, where the
temperature out of the exchanger is the set point. The
flow is decreasing when the valve is closing. The valve can
be placed either in the flow pipe or in the return pipe. The
pressure lost in the bypass has to close to same as the
M
pressure loss in the system.
Secondary side:
Connection The flow is constant or variable, but the differential
point
temperature will change when the valve is adjusting.
Secondary side
Grundfos FLOW THINKING
System 2
System 3
Tertiary side
Function
tO
Tertiary side:
The load will normally be a heat surface or a radiator
Load
system, where there is a demand for a variable tem-
tf perature. The flow in the secondary side will normally be
higher, due to a reduction in the flow temperature. The flow
tr can be constant or variable depending on the system. The
valve can be placed either in the flow pipe or in the return
M pipe.
Secondary side:
The flow is decreasing when the valve is closing. If an
uncontrolled pump is installed on the primary side,the
Connection differential pressure in the connection point will increase
point
when the flow is decreasing.
Secondary side
Grundfos FLOW THINKING
System 4
Secondary side:
The flow is constant, but the differential temperature will
Connection change when the valve is adjusting.
point
Secondary side
Grundfos FLOW THINKING
System 5
Secondary side:
The flow is constant, but the differential temperature will
Connection change when the valve is adjusting.
point
Secondary side
Grundfos FLOW THINKING
Design
Out-door
temperature sensor to
Loop Flow
controller temperature sensor
Thermometer
Tf
Return
Control valve temperature sensor
Grundfos FLOW THINKING
By adding more or less chilled water to the tertiary side the Loop Controller is
adjusting the flow temperature based on outdoor, zone supply and return
temperature.
to Loop
controller
ts tf
M
tr
Grundfos FLOW THINKING
Conclusion:
1. Full hydraulic balance in the system:
It will also be possible to change the cooling/heating system in one of the
buildings without disturbing the balance in in the other buildings.
THANK YOU