W301 & SF01 W001 LLVD & BLBD Settings

Rectifier Para setting (CMPAK HQ Requirement for


Shoto AGM 600AH)
Rectifier Para setting (CMPAK HQ Requirement for
Narada EOS 600AH)
Urban Areas/DG sites Rural Areas (LS>12 hours)
Details Platinum/Gold Site Silver/Bronze/Strategic Platinum/Gold Site Silver/Bronze/Strategic
Rectifier Settings Site Rectifier Settings Rectifier Settings Site Rectifier Settings
** Single Site up to
Single Site 46.356V Single Site 46.356V Single Site 46.356V
LVLD 46.356V
Hub Site 47.0V Hub Site 47.0 Hub Site 47.0V
Hub Site 46.356V
LVBD 46.356V 46.356V ** 46.356V 46.356V
DG Operation 48.2V 48.2V 48.2V 48.2V
Float Charge 54.0V 54.0V 54.0V 54.0V
Equalize Charge 56.4V 56.4V 56.4V 56.4V
Up to 0.2C (Dependent Up to 0.2C (Dependent Up to 0.2C (Dependent Up to 0.2C (Dependent
Battery Charging
on rectifier capacity on rectifier capacity on rectifier capacity on rectifier capacity
Coefficient
installed) installed) installed) installed)
Temperature
Compensation Co-eff. 3mV/Cell/°C 3mV/Cell/°C 3mV/Cell/°C 3mV/Cell/°C
(mV/Cell/C)
Temperature Alarm 40 °C 40 °C 40 °C 40 °C
High Temperature
50 °C 50 °C 50 °C 50 °C
Disconnect
Battery disconnection
Battery Voltage Battery Voltage Battery Voltage Battery Voltage
Method
High Voltage Disconnect >=59V >=59V >=59V >=59V
Equalize duration 10 Hours once in 15 days 10 Hours once in 15 days 10 Hours once in 15 days 10 Hours once in 15 days
Bat Parameter Verify
Parameter Rectifier setting Purpose
Battery capacity(Battery capacity 1: 300Ah+Battery
600AH As per Battery Capacity
Capacity 2: 300AH)
LLVD1 Enable (default value) BTS load will disconnect if enable
LLVD1 value 46.8 (use 47.2 for Hub site) BTS load will disconnect at 46.8 to save battery from deep discharging
LLVD2 Enable RTN or PTN load will disconnect if Enable
BLVD Enable RTN or PTN load will disconnect if Enable

LLVD2 & BLVD value 46.8 RTN & PTN load will disconnect at 46.8 to save battery from deep discharging

Float charging value 54 as written on batteries

Equalize charging Enable Must be enable otherwise battery will loose life due to sulfation & acid stratification

Equalize charging value 56.4 as written on batteries


Battery type Fast Charging batteries As batteries are high charging

.300(Shoto &.200 narada) for non DG For charging batteries at fast rate. Must ensure at least 5 SMR if batteries are at .300
Battery charging co
sites only.(for DG sites use only .150) Charging coefficient

Use for minimize battery charging current at rate of 3mV if battery temperature increases
Temperature compensation cooficent(mV/Cell/C) 3mV/Cell/C (default value)
25 degree
Battery high temperature alarm 40 Degree High temperature alarm will report at 40 degree

BHTD (Battery High Temperature disconnect) Enable If not enable then Battery will remain on charging if temperature is higher then 50 C

BHTD Value 50 C At this temperature battery will disconnect from system until cool down

Equalization Period 15 days After 15 days Equalization period will start


Relation of Parameters Value:
LLVD1+1<=Minimum(Test Stop Volt, Battery voltage Low, DC volt. Low)
BLVD<=LLVD1
BLVD+1<=DG Start Volt<=Mains start voltage-1

No Parametre Name Default Value in CSU

1 Mains start volt 48


2 DG Start Volt 47
3 Test Stop Volt 46
4 Battery volt. Low 46

5 DC volt. Low 46
6 LLVD 45
7 BLVD 44
W301 LLVD1 ,LLVD2 & BLVD setting(V1.03.00.00 &
V1.0N.00.00 &V1.11.00.00 & V1.12.00.00)
How to increase W301 LLVD1 & BLVD (for those sites where Software is not upgraded)

Menu List Parameter Value

Battery Para
Test stop Voltage 49
Alarm Para
DC Voltage Low 48.2

Alarm Para Battery Voltage Low 48.2

Battery Para
LLVD1 46.8
Battery Para
LLVD2/BLVD 46.8
W301 & W001 LLVD1 ,LLVD2 & BLVD setting (V2.01.00.00,V2.05.02.00,
V2.05.02.01,V2.06.00.03)

How to increase LLVD1 & BLVD value at SF01 or W301 (Where software upgraded)

Menu List Parameter Value


System Para AC in Scenario Mains
System Para Battery type Fast charging Batteries
Battery Para Float Charge 54
Battery Para BHTD Enabled Enable
Battery Para Equalized Charge duration 15 Days
Alarm Para Battery temperature High Thr 40
Battery Para Test stop Voltage 49
Alarm Para DC Voltage Low 48.2
Alarm Para Battery Voltage Low 48.2
DG Mains Para Mains Start Voltage 49.2
Battery Para Equalized charge threshold voltage 48.7
DG Mains Para DG Start Voltage 48.2
Battery Para LLVD1 Enabled Enable
Battery Para LLVD1 value 46.8
Battery Para TLLVD1 # 1 47.8
Battery Para TLLVD1 # 2 47.8
Battery Para TLLVD1 # 3 47.8
Battery Para TLLVD1 # 4 47.8
Battery Para LLVD2 Enabled Enable
Battery Para LLVD2 Value 46.8 (47.2 for Hub site)
Battery Para BLVD Enabled Enable

Battery Para 46.8 (47.2 for Hub site)


BLVD
Where to install Temp Sensor in different Rectifiers

Rectifier Model Battery Bank Temp 1 Battery Bank Temp 2

ZXDU 68 W301 X6 X7

ZXDU 58 W121,w201 X4 X5

ZXDU 68 W201 X6 X7

T451 (Solar) X2 X3

ZXDU 300 (Indoor) X7 X8

W001 C914,C917,C922 Phase-9 X13 X14

W001 MMN601 Phase-10 X10 X11


Thank you