Professional Documents
Culture Documents
By
A. Sharath Kumar
14071D8302
Power Systems
14071D8302 06/29/2020 1
CONTENTS
● Introduction
● Distribution system
● What is congestion
14071D8302 06/29/2020 2
CONTENTS
14071D8302 06/29/2020 3
Introduction
14071D8302 06/29/2020 4
2
Congestion Management Techniques
14071D8302 06/29/2020 5
Distribution system
14071D8302 06/29/2020 6
2
Radial distribution system
14071D8302 06/29/2020 7
2
● Due to such system, if the fault occurs either on feeder or a
distributor, all the consumers connected to that distributor will
get affected. There would be an interruption of supply to all
such consumers.
● The consumers at the distant end of the distributor would be
subjected to the voltage variations and fluctuations, as the load
on the distributor changes and is because of congestion of the
branch.
● So that it is very important to over come these problems in
Radial distribution systems by considering without violation
of generator limits as an objective.
14071D8302 06/29/2020 8
Reactive Loading Index
A distribution system consists of 2 numbers of nodes. Normally, a number of
branches are series connected to form a radial feeder in low voltage distribution
system which is shown in Figure 1. Consider branch i in Figure 1 which is
connected between buses 1 and 2(where 1 is closer to the source or generator
bus).
14071D8302 06/29/2020 9
The load reactive power becomes maximum when the following condition
becomes satisfied.
Hence, 4
Hence the LHS of equation (6) may be considered as reactive loading index of the system that varies
between sinα at no load and zero at maximum reactive power. Thus
14071D8302 06/29/2020 10
By considering we can write from equation (7)
Here , 9
The reactive loading index is a proposed method for determining the congested branch of
a radial distribution system. The receiving end node of the congested line will be the
optimal node for capacitor placement .
14071D8302 06/29/2020 11
Reactive Power Compensation using shunt capacitor
14071D8302 06/29/2020 12
Problem Identification And Procedure
advantages of capacitor placement depends on how capacitors
are allocated and controlled under possible loading conditions.
This means that the optimization problem, namely, capacitor
placement problem should be formulated with the desired
objective function (such as loss minimization) and various
technical constraints (e.g. the limits of voltage levels and
power flow).
In this project I used the reactive loading index values in order
to find the location of the capacitor placement. And the size of
the capacitor depends on the reactive power compensation.
14071D8302 06/29/2020 13
Flow Chart
Start
No
Is congestion
minimized?
Yes
End
14071D8302 06/29/2020 14
Step By Step Procedure
14071D8302 06/29/2020 15
Cont…
Step 5: Incorporate a shunt capacitor at the receiving end of the each weakest
branch with random ratings.
Step 6: The capacitor value will be optimal where the reactive power
compensation is maximum by satisfying voltage and generating limits.
Step 7: Tabulate the corresponding values of all bus voltages, losses and KVA
flow of each line in the network by placing optimal capacitor.
Step 8: Compare the results from step 2 and step 7.
Step 9: Before placement of capacitor and after placement of capacitor results
for voltage, line flows and losses are compared and shown in figures 3&4.
14071D8302 06/29/2020 16
IEEE 12 Bus Radial Distribution System
14071D8302 06/29/2020 17
Line and load data
14071D8302 06/29/2020 18
Simulation Results
● Consider a IEEE 12 bus radial distribution network having one generator of11KV,100
MVA, 90% efficiency,0.85 P.F. Using ETAP 14 software simulation results are tabulated.
Simulation Results
14071D8302 06/29/2020 19
REACTIVE LOADING INDEX AND ITS MAXIMUM RANGE FOR
DIFFERENT BRANCHES
Reactive Loading Index and Its Maximum Range for Different Branches
14071D8302 06/29/2020 20
Capacitor Placement
● From the Table.3, it is observed that branches 4,3,7,8 are congested and ranked 1,2,3,4 respectively.
Here first four congested lines are considered and the congested branches in rank wise are listed below.
14071D8302 06/29/2020 21
Case 1: Optimal Capacitor for Branch 4 at Node 5
Power Flow Without
Node C=0.25MVAR C=0.253MVAR C=0.255MVAR C=0.256MVAR
Capacitor
From To P(KW) Q(KVAR) P(KW) Q(KVAR) P(KW) Q(KVAR) P(KW) Q(KVAR) P(KW) Q(KVAR)
1 2 426.2 387.6 425 149.8 425 146.9 425.1 145 425.1 144.1
2 3 363.9 326.9 363.7 89.5 363.7 86.7 363.8 84.8 363.8 83.8
3 4 322.3 296.6 323 59.5 323 56.6 323.1 54.7 323 53.7
4 5 265.9 242.1 267.6 5.24 267.7 2.35 267.7 0.464 267.7 -0.522
5 6 234 212.3 237 215 237 215 237.1 215.1 237.1 215.1
6 7 214.3 197.8 217 200.3 217 200.4 217.1 200.4 217.1 200.4
7 8 162.1 146.1 164.2 148 164.2 148 164.3 148 164.2 148
8 9 118.9 104.2 120.4 105.5 120.4 105.6 120.5 105.6 120.4 105.6
9 10 81.4 67.6 82.4 68.5 82.4 68.5 82.5 68.5 82.4 68.5
11 12 13.5 13.5 13.7 13.7 13.7 13.7 13.7 13.7 13.7 13.7
14071D8302 06/29/2020 22
C=0.255 MVAR at Node 5
14071D8302 06/29/2020 23
Case 2: Optimal Capacitor for Branch 3 at Node 4
Power Flow
Node C=0.31MVAR C=0.305MVAR C=0.306MVAR C=0.307MVAR
Without Capacitor
From To P(KW) Q(KVAR) P(KW) Q(KVAR) P(KW) Q(KVAR) P(KW) Q(KVAR) P(KW) Q(KVAR)
1 2 426.2 387.6 425.5 87.3 425.6 92.1 425.6 91.2 425.6 89.2
3 4 322.2 296.6 323.7 -3.06 323.6 1.81 323.6 0.837 323.7 -1.11
4 5 265.9 242.1 268.3 244.3 268.3 244..3 268.3 244.3 268.3 244.3
5 6 234 212.3 236.1 214.2 236.1 214.2 236.1 214.2 236.1 214.2
6 7 214.3 197.8 216.2 199.6 216.2 199.6 216.2 199.6 216.2 199.6
7 8 162.1 146.1 163.6 147.4 163.6 147.4 163.6 147.6 163.6 147.4
8 9 118.9 104.2 120 105.2 120 105.1 120 105.1 120 105.2
9 10 81.4 67.6 82.1 68.2 82.1 68.2 82.1 68.2 82.1 68.2
11 12 13.5 13.5 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6
14071D8302 06/29/2020 24
Capacitor C=0.306 MVAR At Node 4
POWER FLOWS LINE LOSS
FROM TO KVA AMP V(P.U)
KW KVAR KW KVAR
14071D8302 06/29/2020 25
Case 3: Optimal Capacitor for Branch 7 at Node 8
Power Flow
Node C=0.16MVAR C=0.159MVAR C=0.158MVAR C=0.157MVAR
Without Capacitor
From To P(KW) Q(KVAR) P(KW) Q(KVAR) P(KW) Q(KVAR) P(KW) Q(KVAR) P(KW) Q(KVAR)
1 2 426.2 387.6 424.1 239.4 424.1 240.4 424.1 241.3 424.1 242.2
3 4 322.3 296.6 321.6 148.9 321.6 149.9 321.6 150.8 321.6 181.9
4 5 265.9 242.1 266.1 94.7 266.1 95.7 266.1 96.6 266.1 151.7
6 7 214.3 197.8 215.8 50.8 215.8 51.7 215.8 52.7 215.8 52.9
7 8 162.1 146.1 163.5 -1.31 163.4 -0.375 163.4 0.557 163.4 1.457
8 9 118.9 104.2 120.5 105.6 120.5 105.6 120.5 105.6 120.5 105.6
9 10 81.4 67.6 82.5 68.5 82.5 68.5 82.5 68.5 82.5 68.5
11 12 13.5 13.5 13.7 13.7 13.7 13.7 13.7 13.7 13.7 13.7
14071D8302 06/29/2020 26
Capacitor C=0.158 MVAR at Node 8
14071D8302 06/29/2020 27
Case 4: Optimal Capacitor for Branch 8 at Node 9
Power Flow
Node C=0.12MVAR C=0.11MVAR C=0.115MVAR C=0.114MVAR
Without Capacitor
From To P(KW) Q(KVAR) P(KW) Q(KVAR) P(KW) Q(KVAR) P(KW) Q(KVAR) P(KW) Q(KVAR)
1 2 426.2 387.6 424 278.2 424 287.3 424 282.8 424 283.7
2 3 363.9 326.9 362.2 217.7 362.2 226.9 362.2 22.3 362.2 233.2
3 4 322.3 296.6 321.2 187.6 321.1 196.7 321.1 192.1 321.1 193.1
4 5 265.9 242.1 265.5 133.3 265.4 142.5 265.4 137.9 265.4 138.1
5 6 234 212.3 234.6 103.6 234.4 112.9 234.5 108.4 234.5 109.3
6 7 214.3 197.8 215 89.4 214.9 98.5 215 93.9 214.9 94.8
7 8 162.1 146.1 162.8 37.4 162.6 46.5 162.7 41.9 162.7 42.9
8 9 118.9 104.2 119.9 -4.71 119.8 4.47 119.8 -0.117 119.8 0.8
9 10 81.4 67.6 82.4 68.5 82.4 68.4 82.4 68.5 82.4 68.4
11 12 13.5 13.5 13.7 13.7 13.6 3.6 13.7 13.7 13.7 13.7
14071D8302 06/29/2020 28
Capacitor
Capacitor C=0.114
C=0.114 MVAR
MVAR at
at Node
Node 9
9
14071D8302 06/29/2020 29
Voltage Profile after Capacitor Placement
14071D8302 06/29/2020 30
Power Flows in Congested Branches after Capacitor Placement
14071D8302 06/29/2020 31
Comparison Between Before And After Compensation
Total Reactive Power Loss 6.8KVAR 4.6 KVAR 5.2 KVAR 4.6 KVAR 4.8 KVAR
14071D8302 06/29/2020 32
With Two Capacitors
14071D8302 06/29/2020 33
Case 1: C = 0.046 MVAR for Branch 7 at Node 8
14071D8302 06/29/2020 34
Case 2: C = 0.1 MVAR for Branch 8 at Node 7
14071D8302 06/29/2020 35
Case 3: C = 0.115 MVAR for Branch 5 at Node 6
14071D8302 06/29/2020 36
Case 4: C = 0.145 MVAR for Branch 4 at Node 5
POWER
LINE LOSS
BRANCH FLOWS
FROM TO KVA AMP V(P.U)
NUMBER
KW KVAR KW KVAR
14071D8302 06/29/2020 37
Voltage Profile after Two Capacitors Placement
14071D8302 06/29/2020 38
Power Flows in Congested Branches after Two Capacitors
Placement
14071D8302 06/29/2020 39
Comparison of Consolidated Results With and Without
Capacitor
Total Reactive
6.8KVAR 4.4 KVAR 4.1 KVAR 4 KVAR 4 KVAR
Power Loss
14071D8302 06/29/2020 40
IEEE 10 Bus Radial Distribution System
14071D8302 06/29/2020 41
Line and load data
14071D8302 06/29/2020 42
Simulation Results
● Consider a IEEE 10 bus radial distribution network having one generator of 23KV,
100 MVA, 90% efficiency,0.85 P.F. Using ETAP 14 software simulation results are tabulated.
POWER
LINE LOSS
FROM TO FLOWS KVA AMP V(P.U)
KW KVAR KW KVAR
1 2 11457 4516 12315 309.1 0.9938 35.3 118.8
2 3 9604 3943 10382 262.2 0.9891 2.89 124.8
3 4 8643 3485 9319 236.5 0.9689 125.2 202.2
4 5 6837 2864 7413 192.1 0.9562 77.3 67.3
5 6 5299 1115 5415 142.2 0.9317 120.2 104.7
6 7 3782 489 3813 102.7 0.924 28.7 25
7 8 3087 370.1 3109 84.5 0.9101 44 24.9
8 9 2090 294.7 2111 58.2 0.8877 48.7 27.6
9 10 1269 164.5 1279 36.2 0.8722 21 11.9
Simulation Results
14071D8302 06/29/2020 43
REACTIVE LOADING INDEX AND ITS MAXIMUM RANGE FOR
DIFFERENT BRANCHES
Branch Lq sin L
2
V
V
L
1 sin
Difference Rank
No. max q
s
Reactive Loading Index and Its Maximum Range for Different Branches
14071D8302 06/29/2020 44
Capacitor Placement
● From the Table.3, it is observed that branches 3,5,8,4 are congested and ranked 1,2,3,4 respectively.
Here first four congested lines are considered and the congested branches in rank wise are listed
below.
a) Branch 3 (3-4) get rank 1
b)Branch 5 (5-6) get rank 2
c) Branch 8 (8-9) get rank 3
d) Branch 4(4-5) get rank 4
● From the above information the receiving end of each congested line node is considered as optimal
location or shunt capacitor and the locations are 4,6,9,5 and connecting a shunt capacitor with
random ratings is placed at these nodes individually .Which compensates maximum reactive power
in the congested line without violating the generating limits will be the optimal capacitor size.
14071D8302 06/29/2020 45
Case 1: C = 3.684 MVAR for Branch 3 at Node 4
14071D8302 06/29/2020 46
Case 2: C = 1.279 MVAR for Branch 5 at Node 6
14071D8302 06/29/2020 47
Case 3: C = 0.373 MVAR for Branch 8 at Node 9
14071D8302 06/29/2020 48
Case 4: C = 3.122 MVAR for Branch 4 at Node 5
14071D8302 06/29/2020 49
Voltage Profile after Capacitor Placement
14071D8302 06/29/2020 50
Power Flows in Congested Branches after Capacitor
Placement
14071D8302 06/29/2020 51
Comparison of Consolidated Results With and Without
Capacitor
Total Active
503.4 KW 497.3 KW 490.3 KW 498.5 KW 487.2 KW
Power Loss
Total Reactive
706.9 KVAR 670.9 KVAR 680.3 KVAR 698.8 KVAR 664.2 KVAR
Power Loss
14071D8302 06/29/2020 52
With Two Capacitors
The same analysis on the 10 bus radial distribution system
with a fixed capacitor at node 8 with 0.446 MVAR and with
different ratings of capacitor values placing at 7,6,5,4 nodes
respectively for reactive power compensation
14071D8302 06/29/2020 53
Case1: C = 0.139 MVAR for Branch 6 at Node 7
14071D8302 06/29/2020 54
Case 2: C = 0.854 MVAR for Branch 5 at Node 6
14071D8302 06/29/2020 55
Case 3: C = 2.717 MVAR for Brach 4 at Node 5
14071D8302 06/29/2020 56
Case 4: C = 3.292 MVAR for Branch 3 at Node 4
14071D8302 06/29/2020 57
Voltage Profile after Two Capacitors Placement
14071D8302 06/29/2020 58
Power Flows in Congested Branches after Two Capacitors
Placement
14071D8302 06/29/2020 59
Comparison of Consolidated Results With and Without
Capacitor
Total Reactive
706.9 KVAR 693.3 KVAR 681.3 KVAR 664.5 KVAR 669.2 KVAR
Power Loss
14071D8302 06/29/2020 60
IEEE 10 Bus Radial Distribution System
14071D8302 06/29/2020 61
The Line and Load Data For 33-Node Radial Distribution System
14071D8302 06/29/2020 62
17 17 18 0.7320 0.5740 90.00 40.00
18 2 19 0.1640 0.1565 90.00 40.00
19 19 20 1.5042 1.3554 90.00 40.00
20 20 21 0.4095 0.4784 90.00 40.00
21 21 22 0.7089 0.9373 90.00 40.00
22 3 23 0.4512 0.3083 90.00 50.00
23 23 24 0.8980 0.7091 420.00 200.00
24 24 25 0.8960 0.7011 420.00 200.00
25 6 26 0.2030 0.1034 60.00 25.00
26 26 27 0.2842 0.1447 60.00 25.00
27 27 28 1.0590 0.9337 60.00 20.00
28 28 29 0.8042 0.7006 120.00 70.00
29 29 30 0.5075 0.2585 200.00 600.00
30 30 31 0.9744 0.9630 150.00 70.00
31 31 32 0.3105 0.3619 210.00 100.00
32 32 33 0.3410 0.5302 60.00 40.00
14071D8302 06/29/2020 63
Simulation Results
POWER FLOWS LINE LOSS
BRANCH
KVA AMP V(P.U)
NUMBER KW KVAR KW KVAR
14071D8302 06/29/2020 64
Cont…
16 150.30 60.38 161.98 8.1 0.25 0.34
0.9137
17 90.05 40.04 98.55 4.9 0.05 0.04
0.9131
18 361.14 161.08 395.43 18.1 0.16 0.15
0.9965
19 270.98 120.93 296.73 13.6 0.83 0.75
0.9929
20 180.14 80.18 197.18 9.1 0.10 0.12
0.9922
21 90.04 40.06 98.55 4.5 0.04 0.06
0.9916
22 939.61 457.24 1044.96 48.5 3.18 2.17
0.9794
23 846.43 405.07 938.36 43.7 5.14 4.06
0.9727
24 421.29 201.01 466.78 21.9 1.29 1.01
0.9694
25 950.78 973.64 1360.86 65.4 2.60 1.32
0.9477
26 888.18 947.31 1298.56 62.5 3.33 1.69
0.9452
27 824.85 920.62 1236.09 59.6 11.30 9.96
0.9337
28 753.55 890.65 1166.66 57.0 7.83 6.82
0.9255
29 625.72 813.83 1026.57 50.6 3.90 1.98
0.922
30 421.82 211.84 472.03 23.3 1.59 1.57
0.9178
31 270.23 140.27 304.46 15.1 0.21 0.25
0.9169
32 60.01 40.02 72.13 210.4 0.01 0.02
0.9166
14071D8302 06/29/2020 65
REACTIVE LOADING INDEX AND ITS MAXIMUM RANGE FOR
DIFFERENT BRANCHES
Branch
Number
Lq max
sin L q
2
V
V s
L
= 1 sin
Difference Rank
14071D8302 06/29/2020 66
Cont…
13 0.796272 0.792351 0.003921 16
14 0.664834 0.66279 0.002044 22
15 0.589753 0.587994 0.001759 24
16 0.80039 0.796847 0.003544 17
17 0.617062 0.616241 0.000821 29
18 0.690371 0.689639 0.000732 30
19 0.669407 0.6646 0.004807 13
20 0.759694 0.758616 0.001078 26
21 0.797573 0.796549 0.001025 27
22 0.564166 0.560049 0.004116 15
23 0.619726 0.611283 0.008443 5
24 0.616244 0.612031 0.004213 14
25 0.453873 0.452029 0.001844 23
26 0.453724 0.451269 0.002455 21
27 0.661338 0.645329 0.016009 2
28 0.65687 0.645307 0.011563 4
29 0.453873 0.450384 0.003489 18
30 0.70286 0.696516 0.006345 12
31 0.758946 0.757432 0.001514 25
32 0.840993 0.840472 0.00052 32
14071D8302 06/29/2020 67
Capacitor Placement
● From the Table.3, it is observed that branches 5,27,2,28 are congested and ranked 1,2,3,4
respectively. Here first four congested lines are considered and the congested branches in rank
wise are listed below.
a) Branch 5 (5-6) get rank 1
b) Branch 27 (27-28) get rank 2
c) Branch 2(2-3) get rank 3
d) Branch 28(28-29) get rank 4
● From the above information the receiving end of each congested line node is considered as
optimal location or shunt capacitor and the locations are 6,28,3,29 and connecting a shunt
capacitor with random ratings is placed at these nodes individually .Which compensates
maximum reactive power in the congested line without violating the generating limits will be
the optimal capacitor size.
14071D8302 06/29/2020 68
Case 1: C = 1.658 MVAR for Branch 5 at Node 6
14071D8302 06/29/2020 69
Cont…
17 18 17 90.05 40.04 98.55 4.8 0.928 0.05 0.04
2 19 18 361.14 161.08 395.43 18.1 0.997 0.16 0.15
19 20 19 270.98 120.92 296.73 13.6 0.9934 0.83 0.75
20 21 20 180.14 80.18 197.18 9.1 0.9927 0.10 0.12
21 22 21 90.04 40.06 98.55 4.5 0.9921 0.04 0.06
3 23 22 939.55 457.20 1044.88 48.3 0.9825 3.16 2.16
23 24 23 846.39 405.04 938.31 43.6 0.9758 5.11 4.04
24 25 24 421.28 201.00 466.77 21.8 0.9725 1.28 1.00
6 26 25 949.81 972.89 1359.66 64.3 0.9621 2.52 1.28
26 27 26 887.29 946.61 1297.44 61.5 0.9596 3.22 1.64
27 28 27 824.07 919.97 1235.08 58.7 0.9483 10.95 9.65
28 29 28 753.12 890.32 1166.13 56.1 0.9402 7.59 6.61
29 30 29 625.54 813.71 1026.36 49.8 0.9367 3.77 1.92
30 31 30 421.76 211.79 471.95 23.0 0.9326 1.54 1.53
31 32 31 270.22 140.26 304.45 14.9 0.9317 0.21 0.24
32 33 32 60.01 40.02 72.13 3.5 0.9315 0.01 0.02
14071D8302 06/29/2020 70
Case 2: C = 1.013MVAR for Branch 27 at Node 28
14071D8302 06/29/2020 71
Cont…
17 18 17 90.05 40.04 98.55 4.9 0.9223 0.05 0.04
14071D8302 06/29/2020 72
Case 3: C = 2.256 MVAR for Branch at Node 3
POWER FLOWS LINE LOSS
FROM BRANCH
KVA AMP V(P.U)
NUMBER TO KW KVAR KW KVAR
14071D8302 06/29/2020 73
Cont…
17 17 18 90.05 40.041 98.55 4.89 0.05 0.04
0.9176
2 18 19 361.14 161.077 395.43 18.08 0.16 0.15
0.9972
19 19 20 270.98 120.924 296.73 13.57 0.83 0.75
0.9936
20 20 21 180.14 80.175 197.18 9.05 0.10 0.12
0.9929
21 21 22 90.04 40.058 98.55 4.53 0.04 0.06
0.9922
3 22 23 939.53 457.180 1044.86 48.27 3.15 2.16
0.9836
23 23 24 846.38 405.025 938.29 43.51 5.10 4.03
0.9769
24 24 25 421.28 200.999 466.77 21.79 1.28 1.00
0.9736
6 25 26 950.48 973.406 1360.49 65.03 2.58 1.31
0.9521
26 26 27 887.91 947.094 1298.22 62.18 3.30 1.68
0.9495
27 27 28 824.61 920.416 1235.78 59.35 11.19 9.87
0.9382
28 28 29 753.42 890.549 1166.50 56.70 7.76 6.76
0.93
29 29 30 625.66 813.791 1026.50 50.34 3.86 1.96
0.9264
30 30 31 421.80 211.826 472.00 23.23 1.58 1.56
0.9223
31 31 32 270.22 140.266 304.46 15.05 0.21 0.25
0.9214
32 32 33 60.01 40.020 72.13 3.57 0.01 0.02
0.9211
14071D8302 06/29/2020 74
Case 4: C = 0.991 MVAR for Branch 28 at Node 29
14071D8302 06/29/2020 75
Cont…
17 18 17 90.05 40.04 98.55 4.87 0.9221 0.05 0.04
14071D8302 06/29/2020 76
Voltage Profile after Capacitor Placement
14071D8302 06/29/2020 77
Power Flows in Congested Branches after Capacitor
Placement
14071D8302 06/29/2020 78
Comparison of Consolidated Results With and Without
Capacitor
WITHOUT
CAPACITOR C=1.658 C=1.013 C=2.256 C=0.991
MVAR MVAR MVAR MVAR
AT NODE 6 AT NODE 28 AT NODE 3 AT NODE 29
14071D8302 06/29/2020 79
With Two Capacitors
The same analysis on the 33 bus radial distribution
system with a fixed capacitor at node 6 with 0.774
MVAR and with different ratings of capacitor values
placing at node 3 0.1 MVAR respectively for
reactive power compensation
14071D8302 06/29/2020 80
Case 1: C=0.1 MVAR for branch 2 at Node 3
14071D8302 06/29/2020 81
Cont…
15 16 15 210.57 80.56 225.45 11.03 0.9308 0.27 0.20
14071D8302 06/29/2020 82
Voltage Profile after Two Capacitors Placement
14071D8302 06/29/2020 83
Power Flows in Congested Branches after Two Capacitors
Placement
14071D8302 06/29/2020 84
Comparison of Consolidated Results With and Without Capacitor
WITHOUT
C=1.658
CAPACITOR
MVAR
AT NODE 6
14071D8302 06/29/2020 85
PUBLICATION DETAILS:
S.NO Title of the paper Authors Journal Name, ISSN/ISB Impact National/
N no: Factor Or
Vol no, Citation International
Page No
14071D8302 06/29/2020 86
References
[1] M.H. Haque, “Efficient load flow method for distribution systems with radial or mesh
[2] Das, D., Nagi, H. S., and Kothari, D. P., ‘ Novel method for solving radial distribution
[3] T.VanCutsem: ‘A method to compute reactive power margins with respect to voltage
collapse’, IEEE Trans. on Power Systems, No. 1, 1991M. Young, The Technical Writer's
[4] H. K. Clark, ‘New challenges: Voltage stability’ IEEE Power Engg Rev, April 1990, pp. 33-
37.
[5] Sumit Banerjee, Member IEEE 1, C.K. Chanda ,S.C. Konar , SayonsomChanda ,
14071D8302 06/29/2020 87
[6] Goswami, S. K., and Basu, S. K., ‘Direct solution of distribution systems’, IEE Proc. C, 1991, 138, (1),
[7] C.K. Chanda, A. Chakraborti,S.Dey, ‘Development of global voltage security indicator(VSI) and role of
68),2004, pp.1-9.
[8] J.F. Chen, W. M. Wang, ‘Steady state stability criteria and uniqueness of load flow solutions for radial
distribution systems’, Electric Power and Energy Systems,Vol. 28, pp. 81-87, 1993.
[9] D. Das, D.P. Kothari, A. Kalam, ‘Simple and efficient method for load solution of radial distribution
networks’, Electric Power and Energy Systems,Vol. 17, pp. 335- 346, 1995.
[10] M. Chakravorty, D. Das, ‘Voltage stability analysis of radial distribution networks’, Electric Power and
14071D8302 06/29/2020 88
Thank you
14071D8302 06/29/2020 89