Professional Documents
Culture Documents
Proposed by Ziegler and Nichols in 1942. It consists of two steps:
The QDR response is very desirable for disturbance inputs, because it prevents a
large initial deviation from set point without being too oscillatory. However, it is not
so desirable for step changes in set point because it causes a 50% overshoot.
This difficulty can be easily corrected by reducing the controller gain from the value
predicted by the formulas.
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION
The Ziegler-Nichols on-line tuning method introduced before is the only one that
characterizes process by and . Most methods approximate processes to a first order
plus dead time (FOPDT) or a second order plus dead time (SOPDT) transfer function.
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION
Where and .
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION
As the controller concerns, is the process, and this is precisely what must be
approximated, if possible, as a FOPDT or SOPDT transfer function.
A FOPDT looks like:
1. With the controller on manual apply a step change in the signal . The
magnitude of this change should be large enough for the consequent change in
the transmitter signal to be measurable, but not so large that the response will
be distorted by the process nonlinearities.
2. Record the response of from the time of introduction of the step test until the
system reaches a new steady state.
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
PROCESS STEP TESTING
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
PROCESS STEP TESTING:
APPROXIMATION TO FOPDT (FIT 3)
Once open-loop step response has been performed, the FOPDT parameters can be
determined by a fit 3 procedure:
∆𝑐 3
𝑘= ,𝜏= ( 𝑡 2 − 𝑡 1 ) , 𝑡 0 =𝑡 2 − 𝜏
Δ𝑚 2
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
TUNING FOR QDR RESPONSE
In addition to on-line tuning formulas, Ziegler and Nichols developed off-line
formulas based on a FOPDT model fit to the process reaction curve.
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
TUNING FOR QDR RESPONSE
In using the formulas of Table 7-2.1, we must keep in mind that they are empirical
and apply only to a limited range of ratios of dead time to time constant. They are
most applicable for a range of of around 0.10 to 0.5.
As pointed out in the discussion of on-line tuning, the QDR formulas can be adjusted
to less oscillatory responses by reducing the proportional gain from the value given
by the tuning formula.
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
TUNING FOR MINIMUM ERROR INTEGRAL
CRITERION
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
TUNING FOR MINIMUM ERROR INTEGRAL CRITERIA
The integral of the error cannot be minimized directly, because a very large negative
error would be the minimum.
In terms of the input type, we must select either set point or disturbance input for
tuning, according to which one is expected to affect the loop more often.
Most process controllers are considered regulators, except for the slave controllers in
cascade control schemes, which are servo regulators (in this case set point changes
are the most important).
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
MINIMUM IAE FORMULAS FOR DISTURBANCE INPUTS
Lopez et al. (1967) developed tuning formulas for minimum error integral criteria.
Instead of using a pre-determined controller structure (e.g., a PID), Dahlin proposed to
obtain the controller’s transfer function that is required to obtain a desired response,
given that we know the process transfer function . The closed loop transfer function is:
From the above equation, the most suited controller’s transfer function. can be obtained:
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION: DAHLIN
SYNTHESIS TUNING FORMULAS
To fully determine the controller characteristics, a desired response must be specified.
Suppose that we want to tightly (without any delay) follow setpoint, i.e.: . Then:
This is impossible!
where is a time constant associated with the loop, and will be an adjustable tuning parameter.
Some authors use .
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION: DAHLIN
SYNTHESIS TUNING FORMULAS
This desired response requires a controller with the following structure:
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION: DAHLIN
SYNTHESIS TUNING FORMULAS
Suppose that the process can be modelled as a first order transfer function, i.e.:
And that the desired response is . Then, the controller should be:
After some algebraic manipulation, the above equation can be re-written as:
For 5% Overshoot:
TUNING A CONTROLLER FOR AN INTEGRATING PROCESS
Mass Balance:
Then:
Then:
Defining: :
TUNING A CONTROLLER FOR AN INTEGRATING PROCESS
For
a direct-action P-only controller:
Then:
Notice that:
• If , both roots will be complex with a negative real part. Thus, the loop response would be
stable with oscillations around the setpoint.
• Otherwise, if , both roots would be real and negative. Thus, the loop response would be
stable without oscillations.
TUNING: EXCERCISES:
7-15
TUNING: EXCERCISES:
7-15
TUNING: EXCERCISES:
7-15
Solution, Item b)
For , the change after the step-test was , while Also, , and . Then:
Then:
TUNING: EXCERCISES:
7-15
Solution, Item b)
For
, the change after the step-test was , while Also, , and . Then:
Then:
TUNING: EXCERCISES:
7-15
Solution, Items c) and d)
c)
Notice that
Regarding the controller action, since the gain (of ) is negative, so should the controller gain be, i.e. . Thus, the
controller will have a direct action.
The gain of the closed loop transfer function for the disturbance input will be:
For 5% Overshoot:
THE FEEDBACK CONTROL LOOP:
CLOSED LOOP TRANSFER FUNCTIONS:
A SIMPLER FORM
,
THE FEEDBACK CONTROL LOOP:
STEADY STATE DEVIATION (OFFSET) AFTER SETPOINT
AND DISTURBANCE CHANGES
Kc>0 reverse action
∆𝑐 3
𝑘= ,𝜏= ( 𝑡 2 − 𝑡 1 ) , 𝑡 0 =𝑡 2 − 𝜏
Δ𝑚 2
PROCESS CHARACTERIZATION:
ON-LINE (CLOSED LOOP) METHOD:
QUARTER DECAY RATIO (QDR) BY ULTIMATE GAIN
Once and have been determined, they are used to calculate the controller parameters
using formulas in the following table:
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
TUNING FOR QDR RESPONSE
In addition to on-line tuning formulas, Ziegler and Nichols developed off-line
formulas based on a FOPDT model fit to the process reaction curve.
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
MINIMUM IAE FORMULAS FOR DISTURBANCE INPUTS
Lopez et al. (1967) developed tuning formulas for minimum error integral criteria.